Functions and technicaldata

Quick PRD surge arrester

Withdrawable "LV" surge arresters type 2 or 3


Withdrawable Quick PRD surge arresters allow damaged cartridges to be replaced quickly. They offer remote reporting of the "cartridge must be changed" message.
They protect electrical and electronic equipment against lightning-induced surges. Quick PRD surge arresters are prewired, incorporating their end-of-life disconnector. Each surge arrester in the range has a specific use: b incoming protection (type 2): v Quick PRD 40r is recommended for a high risk level v Quick PRD 20r is recommended for a moderate risk level b close protection (type 2 or 3): v Quick PRD 8r provides close protection for the loads to be protected and is cascade-mounted with the incoming surge arresters. This surge arrester is required as close as possible to the loads to be protected when they are located more than 30 metres away from the incoming surge arrester.

General technical data


Operating voltage Quick PRD 8r, 1P+N. Disconnector short-circuit withstand Operating frequency Constant operating current Ic Response time Protection class Type of connection End of life indication 230/400 V CA Isc = 25 kA (50 Hz) 50/60 Hz < 1 mA < 25 ns IP40 on the front panel IK05 Tunnel terminals, 2.5 to 35 mm By the cartridges White Red Operational At end of life

By control lever in OFF position and red mechanical indicator lamp By the NO/NC remote indication contact 250 V AC / 2 A Operating temperature Quick PRD 40r, 3P+N. Storage temperature Standards Certifications Weight (g) -25C to +60C -40C to +70C IEC 61643-1 T2 and EN 61643-11 Type 2 NF, KEMA KEUR (Quick PRD 8r, 20r) 1P+N: 435 (Quick PRD 40r: 445) 3P: 665 (Quick PRD 40r: 700) 3P+N: 810 (Quick PRD 40r: 850)

Diagrams
14

1P+N / 3P+N.

3P.

version: 1.5

90277E.indd

Functions and technicaldata

Quick PRD surge arrester

Withdrawable "LV" surge arresters type 2 or 3


Technical data
Name of surge arrester No. of Width in Imax (kA) poles 9 mm Maximum modules discharge current In (kA) Up (MCB+SPD) Earthing Nominal (kV) (1) system discharge Protection level current CM DM
L/t Quick PRD 40r Quick PRD 40r Quick PRD 40r Quick PRD 20r Quick PRD 20r Quick PRD 20r Quick PRD 8r Quick PRD 8r Quick PRD 8r N/t 1.5 1.5 1.5 1.5 L/N 2.5 2.5 1.5 1.5 TT and TN-S 230 TN-C and IT 230 V 230/400 TT and TN-S TT and TN-S 230 TN-C and IT 230 V 230/400 TT and TN-S 20 1.5 2 1.5 1.5 1.5 1.5

Un (V) Nominal mains voltage

Uc (V) Cat. Maximum no. steady state voltage CM DM


L/t 350 350 N/t 264 264 264 264 264 264 L/N 350 350 350 350 350 350 16292 16293 16294 16295 16296 16297 16298 16299 16300

Quick PRD 40r

1P+N 3P 3P+N 1P+N 3P 3P+N 1P+N 3P 3P+N

8 13 15 8 13 15 8 13 15

40

Quick PRD 20r

20

Quick PRD 8r (2)

Type 2 / Type 3

1.5/1.4 1.5/1.5 1.2/1.4 TT and TN-S 230 1.2/1.4 TN-C and IT 230 V 230/400 1.5/1.4 1.5/1.5 1.2/1.4 TT and TN-S

350

CM: common mode (between phase/earth and neutral/earth). DM: differential mode (between phase and neutral). (1) Up (MCB + SPD): total value measured between Modular Circuit Breaker (MCB) terminal block and PE surge arrester device terminal block (SPD). (2) Uoc: open-circuit voltage in combined wave: 10 kV.

Replacement cartridges
Type C 40-350 C 20-350 C 8-350 C neutral-350 Replacement cartridges. Replacement cartridges for Quick PRD 40r Quick PRD 20r Quick PRD 8r All products Up (Cartridge) (kV) 1.4 1.2 1.1 1.5 Cat. no. 16310 16311 16312 16313

Accessories
Earth terminal block support
Type Support kit L = 4 blocks Batch of 1 Cat. no. PRA90053

25 mm2 terminal block kit

L = 1 block

Batch of 5

PRA90046

Pragma: the earth terminal block needs 1 support kit and 1terminal block kit.