Premier SX Fire Alarm Control Panel

LPROVED 2 APPN 54 Pt
to E :1998 &4

CB

The Premier SX Control Panel range is available in 1,2,4,6 and 8 zones, housed in a light grey flame retardant ULV0 enclosure, designed to meet modern architectural surroundings, with a removable hinged door. The Premier SX has been designed with ease of installation in mind, in addition to the robust electronic design expected from GLT Exports Ltd.

ELECTRICAL SPECIFICATION
Model Part No Detection Zones Mains Voltage System Voltage Zone Voltage Sounder Alarm O/P Fault Relay Output Fire Relay Output Zone Capacity Remote Sounder Activation Sounder Activation Delay Zone End of Line Sounder End of Line Charger Voltage Charger Size Zone Short Circuit Protection Charger Short Circuit Protection Enclosure Size Weight NPSX1 NPSX2 NPSX4 NPSX6 NPSX8 37-050 37-051 37-052 37-053 37-054 1 2 4 6 8 230 VAC +10%/-15% @ 50/60Hz 24 VDC (Nominal) 21 VDC (Nominal) 2 x 400 mA @ 24V DC (Nominal) 1 x Relay SELV (1 Amp maximum) 1 x Relay SELV (1 Amp maximum) 32 Devices per zone Via N/O contact (class change) 0-9 minutes in 1 minute increments IN4002 Diode (Cathode stripe to +) 10K Resistor 28.4V @ 20 C (with battery disconnected) 1.1 Amp 100mA Battery voltage less than 20 V 355 L x 275 H x 100 D (mm) 3.25kg (Excluding Batteries)

Complies fully to EN54 Pt 2 & Pt 4 Microprocessor based Built in detector removal line integrity (no need for active E.O.L.) Space for up to 2 x 7AH 12V SLA Batteries Battery charger short circuit protection Zone short circuit protection Fire change over relay output Fault change over relay output Class Change Top, Bottom & Rear Cable Entries Zone isolate facility One man test Facility Front Panel Short circuit indication Programmable External Sounder delay (0-9 minutes in 1 minute increments) Earth fault indication Front panel delay override facility Suitable for surface & semi-flush installation CE Marked Meets the latest European low voltage directive Battery overcharge thermal protection IP 43
Zone +
1N4002 End of Line Diode

-+IN +OUT +IN +OUT +IN +OUT

++
Call Point

Zone -

If manual call points will be mixed with detectors,diode bases must be used (to allow power to call point if a head is removed)

1N4002 End of Line Diode

Zone +

-++
Call Point

+IN -

+OUT

+IN -

+OUT

+IN -

+OUT

Zone -

If ALL manual call points are at the start of the zone, or no call points are fitted to that zone, either standard bases or common bases can be used

355mm 12 x 19mm grommet cable entries


20 mm 60 mm

73mm

Flush/Wall Mount

ZONE 1 + -

ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 + + + + + + + -

SND 1 + -

SND 2 CLASS CHANGE + -

FIRE RELAY FAULT RELAY NO CM NC NO CM NC

20 LIVE
MAINS FUSE 1A HRC CERAMIC

EARTH NEUTRAL

1 2 3 4 5 6 7 8 910 11
CONN 27

12 13

18
CONN1

CONN5

EARTH

FS4
SND1 400mA

FS5
SND2 400mA

17
456

275mm
14 15 16
FS3 FS2
+ AC AC + BATTERY En54 pt4 24V SLA FROM TRANSFORMER
SECONDARY

2 x 19mm knock-out cable entries

90 1
78
23
FS1
CHARGER En54 SUP BATTERY 1.6A 1.6A 1.6A

LIVE NEUT- EARTH RAL

19

SUPPLY (OPTIONAL)

MAINS TO TRANSFORMER PRIMARY

SEALED LEAD ACID BATTERY 12V / 6 Ah

SEALED LEAD ACID BATTERY 12V / 6 Ah

ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 SND 1 + + - + - + - + - + - + - + + -

SND 2 + -

CLASS CHANGE

FIRE RELAY FAULT RELAY NO CM NC NO CM NC