VARIABLE FREQUENCY DRIVES

A500 Series
The A500 Series delivers outstanding performance for a wide range of applications, including machinery that requires high motor torque production without encoder feedback, even at low RPM. A broad selection of standard settings, plus 3 plug-in option ports, enable the user to tailor the product to suit application requirements.

Control Panel standard. Stores settings in non-volatile memory for copying to other drives. Low cost optional upgrade Parameter Unit, with 8 languages, back-light, 24 keys for direct numeric entry, non-volatile memory of all settings. RS-485 Multi-drop serial communication standard. Communications options: DeviceNet, Profibus DP, CC-Link, Modbus Plus

Ease of maintenance: Removable control circuit terminal block Quick fan change-out Open loop magnetic flux vector control. Closed loop fluxvector speed control, including 0 RPM holding torque, with encoder feedback option. Sink / Source selectable control logic.
POWER ALARM
MON EXT REV

CONTROL PANEL POWER ALARM


MON EXT REV HZ A V PU FWD

POWER ALARM
MON

CONTROL PANEL
HZ A V EXT REV PU FWD

CONTROL PANEL
HZ A V PU FWD

CONTROL PANEL POWER ALARM


MON EXT REV HZ A V PU FWD

Constant Torque hp Output Amps 0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 3 5 8 11 17 24 33 46 61 76 90 115 145 175 215 1.5 2.5 4 6 9 12 17 23 31 38 43 57 71 86 110

Variable Torque hp Output Amps 3-Phase 240 VAC Input / Output 1 3.6 1.5 5 3 9.6 3 12 5 18 10 28 10 37 20 54 25 68 30 80 40 104 50 130 60 154 75 185 100 248 3-Phase 480 VAC Input / Output 1 1.8 1.5 3 3 4.8 3 6.7 5 9 10 14 15 21 20 27 25 34 30 40 40 52 50 65 60 77 75 96 100 124

*
Model Number
* CE mark is available on 240V and 480V models only

FR-A520-0.4K-NA FR-A520-0.75K-NA FR-A520-1.5K-NA FR-A520-2.2K-NA FR-A520-3.7K-NA FR-A520-5.5K-NA FR-A520-7.5K-NA FR-A520-11K-NA FR-A520-15K-NA FR-A520-18.5K-NA FR-A520-22K-NA FR-A520-30K-NA FR-A520-37K-NA FR-A520-45K-NA FR-A520-55K-NA FR-A540-0.4K-NA FR-A540-0.75K-NA FR-A540-1.5K-NA FR-A540-2.2K-NA FR-A540-3.7K-NA FR-A540-5.5K-NA FR-A540-7.5K-NA FR-A540-11K-NA FR-A540-15K-NA FR-A540-18.5K-NA FR-A540-22K-NA FR-A540-30K-NA FR-A540-37K-NA FR-A540-45K-NA FR-A540-55K-NA

16

hp

Constant Torque Output Amps 144 180 216 260 325 432 547 722 866 1010 1152 1296 1440 1584 1.7 4 6.1 12 22 33 55 84 104 131 152 202 255 304 402 552 663 773 800 880 990 1100 1210

100 150 150 200 250 350 450 600 700 800 900 1000 1150 1250 1 3 5 10 20 30 50 75 100 125 150 200 250 300 400 550 650 750 800 900 1000 1100 1200

Variable Torque Light Variable Torque Output Amps hp Output Amps 3-Phase 480 VAC Input / Output 150 180 150 180 150 216 200 260 200 260 250 302 300 361 350 432 350 432 400 477 450 547 500 610 600 722 600 750 700 866 800 1010 900 1152 1000 1296 1150 1440 1250 1534 1400 1728 3-Phase 600 VAC Input / Output 1 1.8 3 4.7 5 7.3 10 14.8 25 27 40 41 60 62 100 99 100 104 150 152 215 221 250 255 300 304 400 402 500 496 650 663 750 773 800 800 900 900 1000 990 1100 1100 1200 1210 1300 1320 hp

Model Number

FR-A540L-G75K-NA FR-A540L-G90K-NA FR-A540L-G110K-NA FR-A540L-G132K-NA FR-A540L-G160K-NA FR-A540L-G220K-NA FR-A540L-G280K-NA FR-A540L-375K-NA FR-A540L-450K-NA FR-A540L-530K-NA FR-A540L-600K-NA FR-A540L-670K-NA FR-A540L-750K-NA FR-A540L-800K-NA FR-A560-0.75K-NA FR-A560-2.2K-NA FR-A560-3.7K-NA FR-A560-7.5K-NA FR-A560-15K-NA FR-A560-22K-NA FR-A560-37K-NA FR-A560-55K-NA FR-A560L-75K-NA FR-A560L-90K-NA FR-A560L-110K-NA FR-A560L-132K-NA FR-A560L-185K-NA FR-A560L-220K-NA FR-A560L-280K-NA FR-A560L-375K-NA FR-A560L-450K-NA FR-A560L-530K-NA FR-A560L-600K-NA FR-A560L-670K-NA FR-A560L-750K-NA FR-A560L-800K-NA FR-A560L-900K-NA

Instruction Manuals Model Number Part Number A500 IB(NA)66790 FR-A560 IB-0600012 FR-A540L / A560L IB-T7273 FR-A500 / E500 SH(NA)3193 Tech. Manual

Mitsubishi Electric Automation

Variable Frequency Drives 17

VARIABLE FREQUENCY DRIVES

Ratings 240V Class 0.4K 55K


Model FR-A520Hp Rating *1

K-NA

0.4
0.5 1 1.1 1.3 3 3.6

0.75
1 1.5 1.9 1.9 5 5

1.5
2 3 3.1 3.7 8 9.6

2.2
3 3 4.2 4.6 11 12

3.7
5 5 6.7 7.1 17 18

5.5
7.5 10 9.2 10.7 24 28

7.5
10 10 12.6 14.1 33 37

11
15 20 17.6 20.7 46 54

15
20 25 23.3 25.9 61 68

18.5
25 30 29 30.5 76 80

22
30 40 34 39.2 90 104

30
40 50 44 49.7 115 130

37
50 60 55 58.4 145 154

45
60 75 67 70.8 175 185

55
75 100 82 94.6 215 248

Constant Torque Variable Torque

Rated Capacity Constant Torque (kVA) *2 Variable Torque Continuous Rating (A) Constant Torque Variable Torque

Constant Torque Output Overload *3 Current Rating Variable Torque Voltage *4 Regenerative Max. Value / Time Braking Torque Tolerable Work. Rate Rated Input, AC Volt., Frequency Power Tolerable AC Voltage Fluctuation Supply Tolerable Frequency Fluctuation Supply (kVA) *7 Protective Structure (JEM1030) Cooling Method Approx. Weight Height Width Depth kg lbs mm inches mm inches mm inches Self cooling 2.0 2.5 4.4 260 10.2 110 4.3 110 4.3 5.5 260 10.2 110 4.3 125 4.9 3.5 7.7 260 10.2 150 5.9 140 5.5 3.5 7.7 260 10.2 150 5.9 140 5.5 1.5 2.5 4.5 150% for 5 sec. 3%ED

150% for 60 sec., 200% for 0.5 sec. (Inverse time characteristics) 120% for 60 sec., 150% for 0.5 sec. (Inverse time characteristics) 3-Phase 200 - 220V 50Hz, 200 - 240V 60Hz 100% for 5 sec. 2%ED 170 - 242V 50Hz, 170 - 264V 60Hz 5% 5.5 9 12 17 20 28 34 41 52 66 80 100 Enclosed type (IP20) 3.5 7.7 260 10.2 150 5.9 140 5.5 6.0 13.2 260 10.2 220 8.7 170 6.7 6.0 13.2 260 10.2 220 8.7 170 6.7 8.0 Forced air cooling 13.0 13.0 28.7 400 15.8 250 9.8 190 7.5 28.7 400 15.8 250 9.8 190 7.5 13.0 28.7 400 15.8 250 9.8 190 7.5 30.0 66.1 550 21.6 340 13.4 195 7.7 Open type (IP00) 40.0 88.2 550 21.6 450 17.7 250 9.8 40.0 88.2 550 21.6 450 17.7 250 9.8 50.0 110.2 700 27.6 480 18.9 250 9.8 3-Phase 200 - 220V 50Hz, 200 - 240V 60Hz 20% *5 Continuous *5
3-Phase 200 - 220V 50Hz, 200 - 230V 60Hz 3-Phase 200 - 220V 50Hz, 200 - 230V 60Hz

170 - 242V 50Hz, 170 - 253V 60Hz

17.6 300 11.8 220 8.7 190 7.5

Notes: See page 21.

Ratings 480V Class 0.4K 55K


Model FR-A540Hp Rating *1

K-NA

0.4
0.5 1 1.1 1.3 1.5 1.8

0.75
1 1.5 1.9 2.3 2.5 3

1.5
2 3 3.1 3.6 4 4.8

2.2
3 3 4.2 5.1 6 6.7

3.7
5 5 6.9 6.9 9 9

5.5
7.5 10 9.1 10.6 12 14

7.5
10 15 13 16.0 17 21

11
15 20 17.5 20.5 23 27

15
20 25 23.6 25.9 31 34

18.5
25 30 29 30.5 38 40

22
30 40 32.8 39.7 43 52

30
40 50 43.4 49.5 57 65

37
50 60 54 58.6 71 77

45
60 75 65 72.6 86 96

55
75 100 84 94.7 110 124

Constant Torque Variable Torque

Rated Capacity Constant Torque (kVA) *2 Variable Torque Continuous Rating (A) Constant Torque Variable Torque Constant Torque

Output Overload *3 Current Rating Variable Torque Voltage *4

150% for 60 sec., 200% for 0.5 sec. (Inverse time characteristics) 120% for 60 sec., 150% for 0.5 sec. (Inverse time characteristics) 3-Phase 380 - 480V 50Hz / 60Hz 100% for 5 sec. 2% ED 3-Phase 380 - 480V 50Hz / 60Hz 323 - 528V 50Hz, / 60Hz 5% 1.5 2.5 4.5 5.5 9 12 17 20 28 34 41 52 66 80 100 Enclosed type (IP20) Self cooling 3.5 7.7 260 10.2 150 5.9 140 5.5 3.5 7.7 260 10.2 150 5.9 140 5.5 3.5 7.7 260 10.2 150 5.9 140 5.5 3.5 7.7 260 10.2 150 5.9 140 5.5 3.5 7.7 260 10.2 150 5.9 140 5.5 6.0 13.2 260 10.2 220 8.7 170 6.7 6.0 13.2 260 10.2 220 8.7 170 6.7 Forced air cooling 13.0 28.7 400 15.8 250 9.8 190 7.5 13.0 28.7 400 15.8 250 9.8 190 7.5 13.0 28.7 400 15.8 250 9.8 190 7.5 13.0 28.7 400 15.8 250 9.8 190 7.5 24.0 53.0 550 21.6 340 13.9 195 7.7 35.0 77.3 550 21.6 450 17.7 250 9.8 35.0 77.3 550 21.6 450 17.7 250 9.8 36.0 79.5 550 21.6 450 17.7 250 9.8 Open type (IP00) 20% *5 Continuous *5

Regenerative Max. Value / Time Braking Torque Tolerable Work. Rate Rated Input, AC Volt., Frequency Power Tolerable AC Voltage Fluctuation Supply Tolerable Frequency Fluctuation Supply (kVA) *7 Protective Structure (JEM1030) Cooling Method Approx. Weight Height Width Depth kg lbs mm inches mm inches mm inches

Notes: See page 21.

18

Ratings 480V Class 75K 280K


Model FR-A540L-G
Horsepower Rating *1

K-NA
Constant Torque Variable Torque *6 Light Variable Torque Constant Torque

75
100 150 150 144 180 180

90
150 150 200 180 216 260

110
150 200 250 216 260 302

132
200 300 350 260 361 432

160
250 350 400 325 432 477

220
350 450 500 432 547 610

280
450 600 600 547 722 750

Rated Current (A) Output Overload Current Rating *3 Voltage *4

Variable Torque *6 Light Variable Torque Constant Torque Variable Torque *6 Light Variable Torque

150% 60 sec., 200% 0.5 sec @50C. (Inverse time characteristics) 120% 60 sec., 150% 0.5 sec. @50C. (Inverse time characteristics) 110% 60 sec., 150% 0.5 sec. @40C. (Inverse time characteristics) 3-Phase 380 - 480V 50Hz/ 60Hz 3-Phase 380 - 480V 50Hz/ 60Hz 323 - 528V 50Hz/ 60Hz 5% 110 137 137 165 165 198 198 275 Open type (IP00) Forced air cooling 76 (167) 86 (189) 740 (29.1) 480 (18.9) 360 (14.2) 405 (15.9) 175 (6.9) 190 (7.5) 88 (194) 740 (29.1) 480 (18.9) 360 (14.2) 405 (15.9) 175 (6.9) 195 (7.7) 149 (328) 1010 (39.8) 498 (19.6) 380 (15.0) 408 (16.1) 175 (6.9) 230 (9.1) 156 (343) 1010 (39.8) 498 (19.6) 380 (15.0) 443 (17.4) 190 (7.5) 230 (9.1) 268 (590) 1010 (39.8) 680 (26.8) 380 (15.0) 500 (19.7) 210 (8.3) 260 (10.2) 292 (642) 1330 (52.4) 790 (31.1) 440 (17.3) 500 (19.7) 220 (8.7) 255 (10.0) 248 329 329 417 417 550

Rated Input, AC Voltage, Frequency Power Supply Tolerable Frequency Fluctuation Constant Torque Supply (kVA) *7 Variable Torque *6 Protective Structure (JEM1030) Cooling Method Approximate Weight (kg (lbs)) Drive Height Drive Width Drive Depth DC Reactor Height DC Reactor Width DC Reactor Depth mm (in) mm (in) mm (in) mm (in) mm (in) mm (in) 740 (29.1) 480 (18.9) 360 (14.2) 342 (13.5) 150 (5.9) 185 (7.3) Tolerable AC Voltage Fluctuation

Notes: See page 21.

Ratings 480V Class 375K 800K


Model FR-A540LHorsepower Rating *1 Rated Capacity (kVA) *2 Rated Current (A) Output Overload Capacity *3 Variable Torque *6 Voltage *4 Rated Input, AC Voltage, Frequency Tolerable AC Voltage Fluctuation Power Tolerable Frequency Fluctuation Supply Supply (kVA) *7 Protective Structure (JEM1030) Cooling Method Approximate Weight Drive Height Drive Width Drive Depth Reactor Height Reactor Width Reactor Depth kg lbs mm (in) mm (in) mm (in) mm (in) mm (in) mm (in) 490 1078 500 1100 1900 (74.8) 1100 (43.3) 500 (19.7) 330 (13.0) 240 (9.5) 460 (18.4) 1060 2332 Constant Torque Variable Torque *6 550 660 660 770 770 878

K-NA
Constant Torque Variable Torque *6 Constant Torque Variable Torque *6 Constant Torque Variable Torque *6 Constant Torque

375 600 700 550 660 722 866

450 700 800 660 770 866 1010

530 800 900 770 878 1010 1152

600 900 1000 878 988 1152 1296

670 1000 1150 988 1097 1296 1440

750 1150 1250 1097 1169 1440 1534

800 1250 1400 1169 1317 1584 1728

150% 60 sec. , 200% 0.5 sec (Inverse time characteristics) 120% 60 sec. , 150% 0.5 sec. (Inverse time characteristics)

150% 60 sec. (Inverse time characteristics) 120% 60 sec. (Inverse time characteristics) 3-Phase 380 - 480V 50Hz/ 60Hz 3-Phase 380 - 480V 50Hz/ 60Hz 323 - 528V 50Hz/ 60Hz 5% 878 988 Forced air cooling 1060 2332 1100 2420 2900 (114.2) 2300 (90.6) 800 (31.5) Internally mounted and wired in cabinet 1100 2420 1200 2640 988 1097 Enclosed type (IP20) 1097 1210 1210 1320

Open type (IP00)

Notes: See page 21.

Mitsubishi Electric Automation

Variable Frequency Drives 19

VARIABLE FREQUENCY DRIVES

Ratings 600V Class 0.75K 55K


Model FR-A560Horsepower Rating *1 Rated Capacity (kVA) *2 Continuous Rating (A) Output Overload Current Rating *3 Voltage *4 Regenerative Braking Torque Max. Value / Time 100% 5 sec 2% ED 3-Phase 575V 60Hz 490 - 632V 60Hz 5% 2.5 5.5 9 17 28 41 66 100 Enclosed type (IP20) Forced air cooling 7 (15) mm Height Width Depth inches mm inches mm inches 260 10.2 220 8.7 170 6.7 7 (15) 260 10.2 220 8.7 170 6.7 7 (15) 260 10.2 220 8.7 170 6.7 7 (15) 260 10.2 220 8.7 170 6.7 15 (32) 400 15.7 250 9.8 190 7.5 15 (32) 400 15.7 250 9.8 190 7.5 55 (120) 807.5 31.8 450 17.7 250 9.8 55 (120) 807.5 31.8 450 17.7 250 9.8 Tolerable Work. Rate Rated Input, AC Voltage, Frequency Power Tolerable AC Voltage Fluctuation Supply Tolerable Frequency Fluctuation Supply (kVA) *7 Protective Structure (JEM1030) Cooling Method Approximate Weight (kg (lbs))

K-NA
Constant Torque Variable Torque *6 Constant Torque Variable Torque Constant Torque Variable Torque *6 Constant Torque Variable Torque *6

0.75
1 1 1.7 1.8 1.7 1.8

2.2
3 3 4 4.7 4 4.7

3.7
5 5 6.1 7.3 6.1 7.3

7.5
10 10 12 14.8 12 14.8

15
20 25 22 27 22 27

22
30 40 33 41 33 41

37
50 60 55 62 55 62

55
75 100 84 99 84 99

150% 60 sec., 200% 0.5 sec. (Inverse time characteristics) 120% 60 sec., 150% 0.5 sec. (Inverse time characteristics) 3-Phase 600V 60Hz 20% *5 Continuous *5

Notes: See page 21.

Ratings 600V Class 75K 280K


Model FR-A560LHorsepower Rating *1 Rated Capacity (kVA) *2 Rated Current (A) Output Overload Current Rating *3 Voltage *4 Rated Input, AC Voltage, Frequency Tolerable AC Voltage Fluctuation Power Supply Tolerable Frequency Fluctuation Constant Torque Supply (kVA) *7 Variable Torque *6 Protective Structure (JEM1030) Cooling Method Approx. Weight (kg (lbs)) Drive Height Drive Width Drive Depth DC Reactor Height DC Reactor Width DC Reactor Depth mm inches mm inches mm inches mm inches mm inches mm inches 61 (135) 740 29.2 480 18.9 360 14.2 320 12.6 140 5.5 170 6.7 93 (205) 740 29.2 480 18.9 360 14.2 337 13.3 150 5.9 180 7.1 94 (207) 740 29.2 480 18.9 360 14.2 400 15.8 175 6.9 200 7.8

K-NA
Constant Torque Variable Torque *6 Constant Torque Variable Torque *6 Constant Torque Variable Torque *6 Constant Torque Variable Torque *6

75
100 100 75 75 104 104

90
125 150 90 110 131 152

110
150 215 110 160 152 202

132
200 250 132 185 202 255

185
250 300 185 220 255 304

220
300 400 220 280 304 402

280
400 500 280 375 402 496

150% 60 sec., 200% 0.5 sec. (Inverse time characteristics) 120% 60 sec., 150% 0.5 sec. (Inverse time characteristics) 3-Phase 600V 60Hz 3-Phase 600V 50Hz/ 60Hz 488 - 632V 50Hz/ 60Hz 5% 104 104 130 151 151 220 201 254 Open type (IP00) Forced air cooling 149 (328) 1010 39.8 498 19.6 380 15.0 400 15.8 175 6.9 215 8.5 155 (341) 1010 39.8 498 19.6 380 15.0 438 17.3 190 7.5 220 8.7 266 (586) 1010 39.8 680 26.8 380 15.0 495 19.5 210 8.3 235 9.3 290 (638) 1330 52.4 790 31.1 440 17.3 495 19.5 220 8.7 265 10.4 254 303 303 400 400 494

Notes: See page 21.

20

Ratings 600V Class 375K 900K


Model FR-A560LHorsepower Rating *1 Rated Capacity (kVA) *2 Rated Current (A) Output Overload Capacity *3 Variable Torque *6 Voltage *4 Rated Input, AC Voltage, Frequency Power Supply Tolerable AC Voltage Fluctuation Tolerable Frequency Fluctuation Supply (kVA) *7 Protective Structure (JEM1030) Cooling Method Approximate Drive Weight (kg (lbs)) Drive Height Drive Width Drive Depth Reactor Height Reactor Width Reactor Depth mm (inches) mm (inches) mm (inches) mm (inches) mm (inches) mm (inches) 490 (1078) 500 (1100) 1900 (74.8) 1100 (43.3) 500 (19.7) 330 (13.0) 240 (9.5) 460 (18.4) 1060 (2332) Constant Torque Variable Torque *6 550 660 660 770 770 797 797 896

K-NA
Constant Torque Variable Torque *6 Constant Torque Variable Torque *6 Constant Torque Variable Torque *6 Constant Torque

375 550 650 375 450 552 663

450 650 750 450 530 663 773

530 750 800 530 600 773 800

600 800 900 600 670 800 900

670 900 1000 670 750 880 990

750 1000 1100 750 800 990 1100

800 1100 1200 800 900 1100 1210

900 1200 1300 900 950 1210 1320

150% 60 sec. , 200% 0.5 sec. (Inverse time characteristics) 120% 60 sec. , 150% 0.5 sec. (Inverse time characteristics)

150% 60 sec. (Inverse time characteristics) 120% 60 sec. (Inverse time characteristics) 3-Phase 600V 60H 3-Phase 600V 50Hz / 60Hz 488 - 632V 50Hz / 60Hz 5% 896 986 986 1095 1095 1205 1205 1315

Open type (IP00)

Enclosed type (IP20) Forced air cooling 1060 1100 (2332) (2420) 1100 (2420) 2900 (114.2) 2300 (90.6) 800 (31.5) Internally mounted and wired in cabinet 1200 (2640) 1200 (2640)

Notes: 1. The applicable motor capacity indicated is the maximum capacity applicable when Mitsubishi 4-pole standard motor is used. 2. The rated output capacity indicated is based on the National Electric Code, 220V for 200V class, 440V for 400V class, 575V for 600V class. 3. The overload capacity indicated in % is the ratio of the overload current to the inverters rated current. For repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100% load. 4. The maximum output voltage cannot exceed the power supply voltage. The maximum output voltage may be set as desired below the power supply voltage. 5. The torque indicated is the average value for deceleration from 60Hz to a stop and varies with motor loss. 6. For use in Variable torque mode, refer to Pr. 570. 7. The power supply capacity changes with the values of the power supply side inverter impedance (including those of the input reactor and cables).

Mitsubishi Electric Automation

Variable Frequency Drives 21

VARIABLE FREQUENCY DRIVES

General Specifications
Control Method Carrier Frequency Control Specifications 0.4K~55K, 230 & 480V 0.75~55K, 600V Soft-PWM control, high-carrier frequency PWM control (V/F control, advanced flux vector control selection) 700Hz to 14.5K Hz. Maximum 5KHz for Soft PWM. 700Hz to 14.5K Hz. Maximum 8KHz for variable torque rating. Maximum 5Hz for Soft PWM. 700Hz, 1K Hz, 2.5K Hz. Maximum 1KHz for Soft PWM. 2.5KHz setting permissible only with optional sine wave filter. 0.2 to 400 Hz 0.015 Hz (Terminal No. 2 input: 12 bit/0 to 10V, 11 bit/0 to 5V; Terminal No. 1 input: 12 bit/-10 to +10V, 11 bit/-5 to +5V) 0.01 Hz Within 0.2% of max. output frequency 25C 10C / (59F to 95F) during analog input: within 0.01% of set output frequency during digital input Any base frequency setting possible between 0 and 400 Hz; constant torque or variable torque pattern selection possible. 150% at 0.5 Hz (advanced flux vector control) Manual torque boost 0 to 3600 sec. (individual setting for acceleration/deceleration possible), linear or S-curve mode Operation frequency (0 to 120 Hz), operation time (0 to 10 sec.), operation voltage (0 to 30%) variable Operation current level setting possible (0 to 200% variable), enable/disable selection DC 0 to 5V, 0 to 10V, 4 to 20mA Input from control panel, parameter unit; BCD 3-digit or 12-digit binary (using option FR-A5AX) Individual selection of forward run, reverse run; starting signal self-hold input (3-wire input) selective Up to 15 set speeds (each speed can be set between 0 and 400 Hz; speed can be changed via control panel or parameter unit during operation) 0 to 3600 sec. (max. of three individual accelerations/decelerations can be set) JOG operation mode selection terminal provided (*1) Select input of frequency setting signal 4 to 20 mA DC (terminal No. 4) Instant cutoff of inverter output (frequency, voltage) Reset of protection operation hold state Upper/lower limit frequency setting, frequency jump operation, external thermal input selection, reverse polarity operation, instantaneous power failure restart operation, commercial power supply inverter switch-over function, forward run/reverse run prevention, slip compensation, operation mode selection, off-line auto tuning function, online auto tuning function, PID control, programmed operation, computer link operation (RS-485) Five types can be selected from: inverter running, frequency reached, instantaneous power failure (undervoltage), frequency detection, 2nd frequency detection, 3rd frequency detection, in program mode operation, in PU operation, overload warning, regenerative brake pre-alarm, electronic thermal relay pre-alarm, zero current detection, output current detection, PID lower limit, PID upper limit, PID forward run, PID reverse run, commercial power supply-inverter switchover MC 1, 2, 3, operation ready, brake release request, fan trouble, and fin overheat pre-alarm. Open collector output. Relay output - contact rated (230 VAC, 0.3A / 30 VDC, 0.3A); open collector - alarm code (4-bit) output One type can be selected from: output frequency, motor current (constant or peak value), output voltage, frequency setting value, operation speed, motor torque, converter output voltage (constant or peak value), regenerative brake duty (*2), electronic thermal relay load rate, input power, output power, load meter and motor excitation current. Pulse train output (1,440 pulse/sec./full scale) or analog output (0 to 10 VDC). Operation Status Error Details Operation Status Error Details Interactive Select from output frequency, motor current (constant or peak value), output voltage, frequency setting value, operation speed, motor torque, overload, converter output voltage (constant or peak value), electronic thermal relay load rate, input power, output power, load meter, motor excitation current, cumulative power ON time, actual operation time, cumulative power, regenerative brake duty and motor load rate. Details of errors are displayed when the protective function activates. Details of up to eight errors are saved. (Only four errors are displayed on the control panel.) Input terminal signal status, output terminal signal status, option mounting status, terminal assignment status. Output voltage, current, frequency and cumulative power ON time before protective function activates Operation guide and troubleshooting with help function Overcurrent cutoff (during acceleration, deceleration, constant speed), regenerative overvoltage cutoff, undervoltage, instantaneous power failure, overload cutoff (electronic thermal relay), brake transistor error (*2), ground fault overcurrent, output short circuit (*4), stall prevention, overload warning, brake resistor overheating (*2), fin overheating, fan trouble (*4), option error, parameter error, PU disconnected number of retries exceeded, output phase loss, CPU error, 24 VDC power output short circuit, control panel power short circuit, main circuit fault (*5). -10C (+14F) to +50C (+122F), no frost or condensation. -10C (+14F) to +40C (+104F) when either the variable torque rating or the FR-A5CV dirt protection attachment is used. -10C (+14F) to +30C (+86F) when both the variable torque rating and the FR-A5CV are used in combination. -10C (+14F) to +40C (+104F), no frost or condensation. -10C (+14F) to +30C (+86F) when the the FR-A5CV dirt protection attachment is used. -10C (+14F) to +50C (+122F), no frost or condensation.

75K~280K, 480 & 600V Output Frequency Range Analog Input Frequency Control Resolution Digital Input Frequency Precision Voltage / Frequency Characteristics Starting Torque Torque Boost Acceleration / Deceleration Time Setting DC Braking Stall Prevention Operation Level Analog Input Frequency Setting Signal Digital Input Starting Signal Multi-Speed Selection 2nd, 3rd Accel. / Decel. Time JOG Operation Selection Current Input Selection Output Stop Error Reset Operation Functions Input Signal Output Signal

Operation Specifications

Operation Status

Error (Inverter Trip) For Meter

Display

Displayed on FR-DU04 Control Panel or FR-PU04 Parameter Unit Additional Displays Only on FR-PU04 Parameter Unit

Protective and Warning Functions

0.4K~55K, 240V & 480V Environment Ambient Temperature 0.75K~55K, 600 V 75K~280K, 480 & 600V

375K~900K, 480 & 600V -10C (+14F) to +40C (+104F), no frost or condensation. Ambient Humidity 90% RH or less (no condensation) Storage Temperature *3 -20C to 65C / -4 to 149F Atmosphere Indoors (no corrosive gases, flammable gases, oil mist or dust) Altitude 1000m above sea level. Contact factory for higher altitude deratings. Vibration 5.9 m/s 2 (0.6G max.) based on JIS C 0911

Notes: 1. JOG operation is possible with the control panel and parameter unit. 2. Not provided for models FR-A520-11K and larger, or models FR-A540-11K and larger, which have no brake circuits. 3. Temperatures to which the units can be exposed for a short time, such as during transportation. 4. Only on ratings 55K and smaller. 5. Only on ratings 75K and larger.

22

A500 Series Terminal Connection Diagram


NFB 3 phase AC power supply MC R S T R1 S1 PC P Forward run start Reverse run start Start self-hold selection Multi-speed selection (Max. 15 speeds)
High speed Med. speed Low speed

Motor U PU connector (RS-485) V W Jumper *3 P1 IM

Grounding *8 DC reactor (Standard for ratings 75K and larger.)

Short bar 24 VDC power supply and external transistor common *10

STF STR STOP RH *5 RM *5 RL *5 JOG *5 RT *5 MRS RES AU *5 CS *5 SD contact


input common

R PX
*1

Jumper *2 R

External brake resistor

PR
*1

N A B C

JOG mode Second accel./decel. time selection Output stop Reset Current input selection Instantaneous power failure restart selection

Error output (Relay output)

RUN SU IPF OL FU SE

Running Frequency reached Instantaneous power failure Overload Frequency detection Open collector output common Scale calibration resistor 1/2W *7 Display meters (frequency meters, etc.) (Moving coil type 1mA full scale) (+) (Analog signal output) (-) (DC 0-10V) Grounding *8

Open Collector Output *4 *10

Control input signal (not for voltage input) *10 10E (+10V) Frequency potentiometer 1/2W1K *9 3 2 1 10 (+5V) 2 DC 0 - 5V or *6 DC 0 - 10V 5 (Analog common)

FM SD AM 5

Common Auxiliary input Current input

1 DC 0 - 5V or DC 0 - 10V
4 (DC4 - 20mA)

Frequency setting signal (analog)

Main circuit terminal Input terminal for control circuit Output terminal for control circuit

Notes: 1. Terminals PR, PX, and the internal braking circuit are provided only on models FR-A520 - 0.4K through 7.5K, FR-A540 - 0.4K through 7.5K and FR-A560-0.75K through 7.5K. FR-A560-7.5K does not include the resistor. 2. Remove this jumper when using the FR-ABR external brake resistor. 3. This jumper is provided only on models 55K and below. It must be removed when a DC reactor is installed. 4. These output terminals can output error alarm codes, or 26 types of function can be individually assigned with Pr. 190 through 195. 5. This input terminal can be individually assigned 23 types of function with Pr. 180 through 186. 6. The input signal can be changed with Pr. 73. 7. Not required when the meter is calibrated with the control panel. 8. Always ground the VFD, motor and DC reactor, if used. 9. 2W1K is recommended when setting is changed often. 10. Connections shown using sink logic; source logic connection is also supported.