Professional Documents
Culture Documents
APPLICATION GUIDE
Copyright 2011 ComAp s.r.o. Written by Pavel Mare Prague, Czech Republic
ComAp, spol. s r.o. Kundratka 2359/17, 180 00 Praha 8, Czech Republic Tel: +420 246 012 111, Fax: +266 31 66 47 E-mail: info@comap.cz, www.comap.cz
Table of Contents
Table of Contents ...............................................................................................................................................2 1. IGS-NT family overview .............................................................................................................................5 1.1. InteliSys-NT hardware options..........................................................................................................5 1.2. InteliGen-NT hardware options .........................................................................................................6 1.3. InteliMains-NT hardware options ......................................................................................................8 1.4. Loadsharing and Power management ..............................................................................................9 1.5. Inputs/outputs overview ..................................................................................................................10 1.6. Available extension modules overview ...........................................................................................11 1.7. Communication ports overview .......................................................................................................11 1.8. Order codes overview .....................................................................................................................11 1.8.1. InteliSys-NT ............................................................................................................................11 1.8.2. InteliSys-NTC-BB ...................................................................................................................11 1.8.3. InteliGen-NT, ..........................................................................................................................11 1.8.4. InteliGen-NT-BB .....................................................................................................................12 1.8.5. InteliMains-NT ........................................................................................................................12 1.8.6. InteliMains-NT-BB ..................................................................................................................12 1.8.7. Displays ..................................................................................................................................12 1.8.8. Common modules ..................................................................................................................12 1.8.9. I/O expansion modules...........................................................................................................12 1.8.10. Remote communication modules ...........................................................................................12 1.8.11. Communication bridges with Non-J1939 Electronic engines .................................................13 1.8.12. IGS-NT simulators ..................................................................................................................13 2. InteliGen-NT, InteliSys-NT applications overview ...................................................................................14 2.1. Applications with GCB & MCB control ............................................................................................14 2.2 Applications with GCB control and no MCB....................................................................................15 2.3 Applications with GCB control with external MCB control ..............................................................15 2.4 Generic applications........................................................................................................................16 3. Applications description ...........................................................................................................................17 3.1 GCB& MCB Control ........................................................................................................................17 3.1.1 AMF Automatic mains failure start...........................................................................................17 Specification.............................................................................................................................................17 Hardware requirements ...........................................................................................................................18 Required application type: SPtM.ant .......................................................................................................18 Required setting:......................................................................................................................................18 3.1.2. AMF + On Load Test ..............................................................................................................18 Specification.............................................................................................................................................18 Hardware requirements ...........................................................................................................................18 Required application type: SPtM.ant .......................................................................................................18 Required setting:......................................................................................................................................18 3.1.3. Single Set Parallel to Mains ...................................................................................................19 Specification.............................................................................................................................................19 Hardware requirements ...........................................................................................................................19 Required application type: SPtM.ant .......................................................................................................19 Required setting:......................................................................................................................................19 3.1.4 SPtM + On Load Test .................................................................................................................20 Specification.............................................................................................................................................20 Hardware requirements ...........................................................................................................................20 Required application System configuration/ default archive : SPtM.ant..................................................21 Required setting:......................................................................................................................................21 3.2 Applications with GCB control and no MCB....................................................................................22 3.2.1 MRS - Manual & Remote Start and stop ....................................................................................22 Specification:............................................................................................................................................22 Hardware requirements ...........................................................................................................................22 Required application System configuration/ default archive : MINT.ant..................................................22 Required setting:......................................................................................................................................22 3.2.2 Multiple sets in island..................................................................................................................23 Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF 2
Specification.............................................................................................................................................23 Description without MGCB.......................................................................................................................23 Description with MGCB............................................................................................................................24 Required application System configuration/ default archive : MINT.ant..................................................24 Hardware requirements ...........................................................................................................................24 Required setting:......................................................................................................................................24 3.2.3 SPI parallel to Mains only ........................................................................................................25 Specification.............................................................................................................................................25 Required application System configuration/ default archive : SPI.ant.....................................................25 Hardware requirements ...........................................................................................................................25 Required setting:......................................................................................................................................25 3.3 Applications with GCB control with external MCB control ..............................................................26 3.3.1 Multiple AMF ...............................................................................................................................26 Specification.............................................................................................................................................26 Description without MGCB.......................................................................................................................26 Description with MGCB............................................................................................................................27 Required application System configuration/ default archive : MINT.ant..................................................27 Hardware requirements ...........................................................................................................................27 Required setting:......................................................................................................................................28 3.3.2 SPI External MCB / Island or Parallel......................................................................................28 Specification.............................................................................................................................................28 Required application System configuration/ default archive : SPI.ant.....................................................28 Hardware requirements ...........................................................................................................................28 Required setting:......................................................................................................................................28 3.3.3 Multiple parallel to Mains, MCB control from IM-NT ...................................................................29 Specification.............................................................................................................................................29 Description without MGCB.......................................................................................................................29 Description with MGCB............................................................................................................................30 Required application System configuration/ default archive: IG/IS-MINT.ant and IM-MCB/MGCB.ant ..31 PeakShaving settings: .............................................................................................................................31 Hardware requirements ...........................................................................................................................31 3.3.4 Multiple parallel to Mains, MCB control from IM-NT ...................................................................32 Specification.............................................................................................................................................32 Description ...............................................................................................................................................33 Hardware requirements ...........................................................................................................................33 Required application System configuration/ default archive: IG/IS-MINT.ant and IM-MCB.ant ..............33 3.3.5 Multiple parallel to Mains, MCB and BTB control from IM-NT....................................................34 Specification.............................................................................................................................................34 Description without MGCB.......................................................................................................................35 Hardware requirements ...........................................................................................................................35 Required application System configuration/ default archive: IG/IS-MINT.ant and IM-MCB/BTB.ant......35 Required setting:......................................................................................................................................35 3.3.6 Multiple parallel to Mains, MCB and BTB (MGCB) control from IM-NT......................................37 Specification.............................................................................................................................................37 Description with MGCB............................................................................................................................38 Hardware requirements ...........................................................................................................................39 Required application System configuration/ default archive: IG/IS-MINT.ant and IM-MCB/BTB.ant......39 3.3.7 Multiple parallel to Mains, MCB and MGCB control from IM-NT ................................................40 Specification.............................................................................................................................................40 Description ...............................................................................................................................................41 Hardware requirements ...........................................................................................................................42 Required application System configuration/ default archive: IG/IS-MINT.ant and IM-MGCB.ant ...........42 3.3.8 Multiple parallel to Mains, MCB and BTB control from IM-NT (3Mains).....................................43 Description ...............................................................................................................................................44 Hardware requirements ...........................................................................................................................44 Required setting:......................................................................................................................................44 3.3.9 Multiple parallel to Mains, MCB and BTB control from IM-NT (2Mains).....................................46 Description ...............................................................................................................................................47 Hardware requirements ...........................................................................................................................47 Required setting:......................................................................................................................................47 3.4 Combi applications..........................................................................................................................48 3.4.1 Single applications SPI and SPTM .............................................................................................48 Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF 3
Specification.............................................................................................................................................48 Hardware requirements ...........................................................................................................................48 Required application type: Combi.ant......................................................................................................49 Required setting:......................................................................................................................................49 3.4.2 MINT application .........................................................................................................................49 Specification.............................................................................................................................................49 Hardware requirements ...........................................................................................................................50 Required application System configuration/ default archive : Combi.ant ................................................50 Required setting:......................................................................................................................................50 4. Virtual peripherals ....................................................................................................................................51 4.1 Integrated PLC ................................................................................................................................51 List of function types: ...............................................................................................................................51 Functions description ...............................................................................................................................54 Log Func I. ...............................................................................................................................................54 Log Func II. ..............................................................................................................................................55 Comp Hyst ...............................................................................................................................................55 Comp Time ..............................................................................................................................................55 Window comparator .................................................................................................................................56 Ana Switch ...............................................................................................................................................56 Math Func, Extended Math......................................................................................................................57 Mov Avg ...................................................................................................................................................57 InterpolFunc .............................................................................................................................................58 ForceHistory.............................................................................................................................................58 ForceProtect ............................................................................................................................................58 PID Ana Bias............................................................................................................................................59 PID Bin.....................................................................................................................................................59 Counter ....................................................................................................................................................60 Timer........................................................................................................................................................60 Delay........................................................................................................................................................60 RAMP.......................................................................................................................................................63 Up/Down ..................................................................................................................................................63 4.2 Internal virtual I/O periphery............................................................................................................65 4.3 Shared virtual I/O periphery ............................................................................................................65 Configuration............................................................................................................................................65 SHBOUT/SHAOUT modules ...................................................................................................................65 ShBIN/SHAIN modules............................................................................................................................66 SHBOUT + SHBIN modules ....................................................................................................................66 SHAOUT + SHAIN modules ....................................................................................................................67 5. Controller configuration tricks ..................................................................................................................69 5.1. Force value .....................................................................................................................................69
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
L1
L2
L3
L1
L2
L3
BI 1
L COM H
L COM H
B COM A
BO 1
BO 8
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
D+
+BATT GND
A COM B
BO 16
BO 9
BI 16
BI 7
BI 6
1.2.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
IG-NTC-BB
Base Box is the control unit without internal display. The control unit can be mounted into the switchboard on DIN rail. Extended functionality. The unit has three extra communication ports: (USB slave port + Ethernet and RS485(2). Also selectable AC voltage and current input ranges are available. For details, please see the Reference guide for a specific software configuration
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
1.3.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
IM-NT-BB
Base Box is the control unit without internal display. IM-NT-BB can be mounted into the switchboard on the DIN rail.
GEN VOLT L1 L2 L3 N MAINS VOLT L1 L2 L3 BI 1 BI 6 BI 12 N
L COM H
B COM A
L COM H
CAN1
CAN2 AI 3 AI 2 AI 1 AI COM
IMNTBB
BI 7
+BATT GND
BO 12
BO 9
BO 1
BO 8
Mains current
1.4.
Dongle for load sharing, power management and additional PLC functions should be installed from the rear side of the controller under the rubber plug. The dongle label should remain visible as shown on the picture.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
D+
L1
L2
L3
L1
L2
L3
B COM A
L COM H
L COM H
BI 7 BI 8 BI 9 BI 10 BI 11 BI 12
1.5.
Inputs/outputs overview
Binary Inputs 12 16 6 12 Binary Analogue Analogue SpeedGov Outputs Inputs Outputs control 9 12 3 16 6 12 4 0 3 1 0 1 9 AVR control 9 9 -
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
D+
+BATT GND
BO 9 BO 10 BO 11 BO 12
BI 1 BI 2 BI 3 BI 4 BI 5 BI 6
RS232 (1)
10
1.6.
The table shows maximum number of particular modules that can be connected to IG/IS-NT controller. The total number of connected modules is limited by IG/IS-NT extension capacity: - 12 groups of binary inputs - 12 groups of binary outputs - 10 groups of analog inputs - 4 groups of analog outputs 1 group has 8 inputs/outputs. IGS-PTM 4 IS-BIN16/8 6 IS-AIN8 10 IS-AIN8TC 10 I-AOUT8 4 IGL-RA15 4
1.7.
CAN2** 9 9 9 9 9
9
9 9 9 9 9
9
9 9
9 9
9 9
9
9
*CAN1 - communication bus for external modules and ECU (J1939) **CAN2 - communication bus for intercontroller and monitoring communication ***External display interface (RS485(1)) - communication with display (see appropriate reference guide).
1.8.
1.8.1. InteliSys-NT
InteliSys Base Box IS-NT-BB Local/Remote display for InteliSys IS-Display*, InteliVision 8, InteliVision 5 Complete unit (IS-NT-BB+IS-Display) IS-NT Low temperature version of IS-Display IS-Display LT * * - GC feature included by default in all InteliVision 8 and IS-Display modules
1.8.2. InteliSys-NTC-BB
New InteliSys BaseBox unit IS-NTC-BB
1.8.3. InteliGen-NT,
Controller basic type IG-NT Extended functionality IG-NTC Low temperature version IG-NT LT Extended functionality and low temperature IG-NTC LT * - GC feature included by default in all internal displays from 2010. Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF 11
A common name for any of the above controllers is IGS-NT. This name is used for description of functions or features common to all IG-NT, IG-NT-BB and IS-NT, IS-NTC-BB controllers.
1.8.4. InteliGen-NT-BB
Controller basic type Extended functionality IG-NT-BB IG-NTC-BB
1.8.5. InteliMains-NT
Controller basic type Full controller version IM-NT GC IM-NT GC LT
1.8.6. InteliMains-NT-BB
Controller basic type IM-NT-BB
1.8.7. Displays
5,7 Colour display* InteliVision 5 8 Colour display * InteliVision 8 Monochromatic display for IS-NT-BB IS-Display Remote Display for InteliGen IG-Display GC Low temperature version of Remote Display IG-Display GC LT for InteliGen Low temperature version of Remote Display IG-Display GC LT for InteliGen * - Display can be connected to IS-NT-BB, IS-NTC-BB, IG-NT-BB, IG-NTC-BB, IM-NT-BB, IG-NT, IG-NTC controllers
I-CB/CAT Gas
I-CB-MTU
IS-NTC-MULTIKIT
HS-MULTIKIT
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
13
Generic
Appl. type:COX
2.1.
G
Typical applications: AMF (SSB): Automatic mains failure start AMF with no break return Single set in Parallel to Mains with AMF (SPtM) Combined heat and power (CHP) Peak shaving Import/Export power control
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
14
2.2
G
Typical applications: MRS (SPM): Manual or remote start/stop of a single engine
Load
G G
Typical applications: Multiple sets running in island-parallel
Load
G
Typical applications: CHP with no island operation (no backup)
2.3
G G
G G
Typical applications: AMF with multiple sets running in island-parallel. MCB controlled by a simple mains protection relay or InteliMains AMF with no break return (multiple sets). MCB controlled by InteliMains-NT. Parallel to Mains with AMF for multiple sets (CHP) MCB controlled by InteliMains-NT. Load
G
Typical applications: CHP with external MCB control. Normally the load is higher than gen-set capacity and nonpreferential load must be switched off before gen-set can be switched to island operation.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
15
2.4
Generic applications
Controller performs individual steps like: Gen-set start GCB dead bus closing Synchronizing Load control mode Reverse synchronizing Gen-set stop Steps are driven by commands from an external device, e.g. PLC. This device is responsible for all sequencing (steps order). Typical applications: Complex systems with several buses where PLC controls each step of the gen-set. Complex CHP applications controlled from a central PLC
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
16
3. Applications description
3.1 GCB& MCB Control
3.1.1 AMF Automatic mains failure start Specification
Automatic gen-set start when the mains fails GCB & MCB full control or ATS control Break transfer on mains failure Break return on mains return (Load reclosing) Test mode (set running and waiting for mains failure)
MCB is automatically opened when Mains fails. GCB is closed when all required parameters are within the limits (Voltage and frequency). When Mains recovers GCB is opened and MCB is reclosed. Two separate breakers GCB and MCB
LOAD
T
3x
MCB
3x 3x
GCB
3x MCB
GCB
3xU M
3xU G
K4
K3
MCB
GCB CLOSE/OPEN MCB CLOSE/OPEN
GCB
BO
IGS-NT
BI
3x T
ATS
3x 3x 3x
3xIG
3xU M
3xU G
K3
GCB
GCB CLOSE/OPEN
IGS-NT
MCB CLOSE/OPEN BO BI
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
3xIG
17
Hardware requirements
1x IGS-NT
LOAD T
3x
MCB
3x 3x
GCB
3x
3xU M
3xUG
K4
K3
MCB
GCB
BO
IGS-NT
BI
MCB MCB
FEEDBACK
Hardware requirements
1x IGS-NT
3xI G
Specification
AMF with no break return Automatic gen-set start when the mains fails GCB & MCB full control Break transfer on mains failure No break return on mains return with soft load transfer Test mode (set running and waiting for mains failure with GCB opened) Short time parallel (normally mains protection not required by mains authority) Power control Voltage matching Reverse power protection Long time Parallel to Mains Continuous parallel to mains operation Generator Base load and PF control Mains protections (Vector shift, voltage, frequency protections) No break transfer on mains failure(if the set was running before the mains failure and was capable to cover the load)
LOAD T
3x
MCB
3x 3x
GCB
3x
3xUM
3xUG
K4
K3
MCB
GCB CLOSE/OPEN MCB CLOSE/OPEN
GCB
BO
3xIG
AVRi
iG-AVRi
AVR
IGS-NT
BI Vout SPEED GOVERNOR
Hardware requirements
1x 1x 1x IGS-NT IG-AVRi IG-AVRi-TRANS/LV (when volt matching and PF control is required) (when IG-AVRi is used)
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
19
Synchro enable BOTH (In case of AMF with no break return where On load test is not used, this setpoint may be set to REVERSE only) MFStart enable YES
MCB
3x 3x
GCB
3x
3xUM
1x I M
3xU G
K4
K3
MCB
GCB CLOSE / OPEN MCB CLOSE / OPEN
GCB
BO
3xIG
AVRi
iG- AVRi
AVR
IGS-NT
BI Vout SPEED GOVERNOR
REMOTE TEST ON LOAD TEST REQUIRED PARALL. TO MAINS REQUIRED MCB GCB FEEDBACK GCB TEST ON LOAD REM START / STOP MCB FEEDBACK
Hardware requirements
1x 1x 1x IGS-NT IG-AVRi IG-AVRi-TRANS/LV (when volt matching and PF control is required) (when IG-AVRi is used)
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
20
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
21
3.2
LOAD
GCB
3x 3x
G
3xUG 3xIG
IGS-NT
SYS START/STOP GCB FEEDBACK GCB
Hardware requirements
1x IGS-NT
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
22
GCB1
3x
G 1
3xUG
3xUB
3xIG
CAN
CAN2
AVRi
iG-AVRi
AVR
IGS-NT
Vout SYS START/STOP SPEED GOVERNOR
GCB2
3x
G 2
3xUB
3xUG
3xIG
CAN
CAN2
AVRi
iG-AVRi
AVR
IGS-NT
Vout SYS START/STOP START/STOP SPEED GOVERNOR
When BI Sys start/stop closes, sets are starting with a delay SysAMFstrtDel. The first set with a correct voltage and frequency closes the GCB to the dead bus, others are synchronized. When the relay BI Sys start/stop is opened, all GCBs are opened at the same time with a delay SysAMFstopDel.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
23
GCB1
3x
G 1
3xUB
3xUG
3xIG
MGCB
CAN
CAN2
AVRi
iG-AVRi
AVR
IGS-NT
Vout SYS START/STOP LOAD RES 2 MGCB 3x SPEED GOVERNOR
GCB2
3x
G 2
3xUG 3xIG
3xUB
CAN
CAN2
AVRi
iG-AVRi
AVR
IGS-NT
Vout SYS START/STOP START/STOP LOAD RES 2 SPEED GOVERNOR
When BI Sys start/stop closes, sets are starting with a delay SysAMFstrtDel. The first set with a correct voltage and frequency closes the GCB to the dead bus, others are synchronized. BI Load res 2 is controlled by MGCB to differentiate the load reserve necessary before closing of MGCB (setpoints LoadRes Strt 2 and LoadRes Stp 2), and operational load reserve while the system is loaded (setpoints LoadRes Strt 1 and LoadRes Stp 1).Typically before MGCB closing the higher reserve is needed to absorb the full load. Once loaded, the load reserve can be reduced to e.g. level of the biggest single consumer. MGCB is closed by BO Syst res 1 OK of any running genset and then held by MGCB feedback. When the relay BI Sys start/stop is opened, all GCBs are opened at the same time with a delay SysAMFstopDel. Loss of voltage at the bus opens MGCB.
Required setting:
Set SysAMFstrtDel and SysAMFstopDel setpoints at 1s for fast response on BI Sys start/stop Input MCB FEEDBACK should not be configured
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
24
LOAD T
3x
3x 3x
GCB
3x
3xU M
3xU G
K 3
GCB
BO GCB CLOSE / OPEN
1xI M
3xI G
AVRi
iG- AVRi
AVR
IGS-NT
BI Vout SPEED GOVERNOR
Required setting:
Setpoints group: ProcessControl Island enable: NO ParallelEnable YES Synchro enable FORWARD
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
25
3.3
U,f
MCB
3x 3x
GCB1
3x
G1
3xU B 3xU G CA N
MCB
MCB
AVRi
iG-AVRi
AVR
IGS-NT
Vout SYS START/STOP SPEED GOVERNOR
GCB2
3 x
G2
3xU G 3xU B 3xIG CA N
AVRi
iG-AVRi
AVR
IGS-NT
Vout SYS START/STOP U,f SPEED GOVERNOR
The Uf relay opens MCB after the mains fails. At the same time the Uf relay closes BI Sys start/stop and the sets are starting with a delay SysAMFstrtDel. It is similar to setpoint EmergStart del in SPtM application. The first set with a correct voltage and frequency closes the GCB to the dead bus, others are synchronized. When the mains returns, Uf relay opens BI Sys start/stop and all GCBs are opened at the same time with SysAMFstopDel delay. It is similar to setpoint Mains Ret del in SPtM application. Bus 3 phase voltage relay detects no voltage and with its time delay closes MCB
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
26
U,f
MCB
3x
3x
MGCB
3x
GCB1
3x
G1
RES.OK.(1)
U,f MGCB
RES.OK.(2)
3xUB
3xUG
MGCB
MCB
MCB
3xIG
MGCB
CAN
AVRi
iG-AVRi
AVR
IGS-NT
Vout SYS START/STOP LOAD RESERVE 2 3x MGCB SPEED GOVERNOR
GCB2
3 x
G2
3xUG
3xUB
3xI G
CAN
AVRi
iG-AVRi
AVR
IGS-NT
Vout SYS START/STOP U,f LOAD RESERVE 2 SPEED GOVERNOR
Hint: Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint EmergStart del in Single Stand-by. Setpoint SysAMFstp del is used for GCB opening after the mains returns. Single Stand-by.
The Uf relay opens MCB after the mains fails. At the same time the Uf relay closes BI Sys start/stop and the sets are starting with a delay SysAMFstrtDel. It is similar to setpoint EmergStart del in SPtM application. The first set with a correct voltage and frequency closes the GCB to the dead bus, others are synchronized. BI Load res 2 is controlled by MGCB to differentiate the load reserve necessary before closing of MGCB (setpoints LoadRes Strt 2 and LoadRes Stp 2), and operational load reserve while the system is loaded (setpoints LoadRes Strt 1 and LoadRes Stp 1).Typically before MGCB closing the higher reserve is needed to absorb the full load. Once loaded, the load reserve can be reduced to e.g. level of the biggest single consumer. MGCB is closed by BO Syst res 1 OK of any running genset and then held by MGCB feedback. When the mains returns, Uf relay opens BI Sys start/stop and all GCBs are opened at the same time with SysAMFstopDel delay. It is similar to setpoint Mains Ret del in SPtM application. Loss of voltage at the bus opens MGCB. Bus 3 phase voltage relay detects no voltage and with its time delay closes MCB
Required setting:
Input MCB FEEDBACK should not be configured.
LOAD T
3x
MCB
3x 3x
GCB
3x
3xUM 1xI M
K3
MCB
External MCB control
GCB
GCB CLOSE/OPEN BO
3xUG 3xIG
AVRi
iG-AVRi
AVR
IGS-NT
BI Vout SPEED GOVERNOR
Required setting:
Setpoints group: ProcessControl Island enable: YES ParallelEnable YES Synchro enable FORWARD
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
28
+24V
Ko1 Ko2
IM-NT
LOAD
3xUM 3xU B 3xIM CAN CAN
MCB
3x
3x
3x
GCB1
G1
iG- AVRi TRANS
3xU B 3xUG 3xIG CAN
Ko1
iG-AVRi
AVR
MCB
AVRi
AVRi OUT
IG/IS-NT
Vout
SPEED GOVERNOR
GCB2
3x
G2
iG- AVRi TRANS
3xUG 3xIG CAN
3xUB
iG- AVRi
AVRi AVRi OUT
AVR
IG/IS-NT
Vout
Ko2
SPEED GOVERNOR
MCB
The IM-NT controller opens MCB after the mains fails or after the gen-sets are running according to setpoint AMF settings:MCB opens on. The IM-NT controller closes binary output Sys start/stop which is connected to Sys start/stop inputs of the gen-set controllers if: a) If IM-NT binary input Rem start/stop gets active (AUT mode only). b) If AMF condition is sensed in IM-NT and the gen-set group should be started as stand-by power source (AUT mode only). c) If PeakShaving function senses that it is suitable to start the gen-set group in order to lower the mains import (AUT mode only). d) If Start button is pressed on IM-NT front panel or remotely (MAN mode only). The signal can be deactivated by pressing the Stop button. If the controller is switched from AUT to MAN mode, the internal status of the flip-flop circuit created by Start-Stop buttons is set to follow the previous state in AUT mode. E.g. if the gen-set group has run in an AMF situation in AUT mode, switching to MAN will not stop it (= Sys start/stop output stays active).
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
29
After binary input Sys start/stop closes the gen-sets are starting with a delay SysAMFstrtDel. It is similar to setpoint EmergStart del in SPtM application. The first set with a correct voltage and frequency closes the GCB to the dead bus, others are synchronized. When the mains returns, IM-NT synchronizes gen-sets to the mains with limitations given by setpoints ProcessControl:ParallelEnable and Synchro enable (see Table on p.9 in IM-NT-MCBMGCB-X.X.pdf).
+24V
Ko1
MCB CLOSE/ OPEN
Ko2
MGCB CLOSE/ OPEN
Ko3
SYS START / STOP
IM-NT
LOAD
3xUM 3xUB 3xIM
CA N CAN
REM START/STOP
MGCB FEEDBACK
MCB FEEDBACK
MCB
3x
3x
MGCB
3x
GCB1
G1
3xUB 3xUG 3xIG
CAN
+24V
Ko1 Ko2
MCB
MGCB
AVRi
AVRi OUT
IG/IS-NT
Vou t
SPEED GOVERNOR
GCB2
3x
G2
3xIG
CAN
3xUG
3xUB
AVRi
IG/IS-NT
Vout
Ko3
SPEED GOVERNOR
MCB MGCB
The IM-NT controller opens MCB after the mains fails or after the gen-sets are running according to setpoint AMF settings:MCB opens on. The IM-NT controller closes binary output Sys start/stop which is connected to Sys start/stop inputs of the gen-set controllers if: a) If IM-NT binary input Rem start/stop gets active (AUT mode only). Before the output Sys start/stop is activated, the MGCB close command is issued (if ProcessControl:MGCBparalClose = YES). b) If AMF condition is sensed in IM-NT and the gen-set group should be started as stand-by power source (AUT mode only). MGCB is not closed before the GCBs but only after a reasonable amount of gen-sets have synchronized to the bus (load reserve achived). c) If PeakShaving function senses that it is suitable to start the gen-set group in order to lower the mains import (AUT mode only). Before the output Sys start/stop is activated, the MGCB close command is issued (if ProcessControl:MGCBparalClose = YES). d) If Start button is pressed on IM-NT front panel or remotely (MAN mode only). The signal can be deactivated by pressing the Stop button. If the controller is switched from AUT to MAN mode, the internal status of the flip-flop circuit created by Start-Stop buttons is set to follow the previous state in AUT mode. E.g. if the gen-set group has run in an AMF situation in AUT mode, switching to MAN will not stop it (= Sys start/stop output stays active). After binary input Sys start/stop closes the gen-sets are starting with a delay SysAMFstrtDel. It is similar to setpoint EmergStart del in SPtM application. The first set with a correct voltage and frequency closes the GCB to the dead bus, others are synchronized.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
30
When the mains returns, IM-NT synchronizes gen-sets to the mains with limitations given by setpoints ProcessControl:ParallelEnable and Synchro enable (see Table on p.9 in IM-NT-MCBMGCB-X.X.pdf).
Hint: It is possible to use virtual shared inputs/outputs to connect for example Sys start/stop output from IM-NT to corresponding binary input of all controllers instead of hardwiring it. See chapter Shared virtual I/O periphery.
PeakShaving settings:
PeakLevelStart: PeakLevelStop: PeakAutS/S del: PeakLevelStop to 32000 kW 0 to PeakLevelStart kW 1-3200 s. Function is active only for PeakAutS/S del <> OFF.
If PeakLevelStart is reached for PeakAutS/S del time then the IM-NT controller closes binary output Sys start/stop which is connected to Sys start/stop inputs of the gen-set. Sys start/stop is deactivated after PeakLevelStop is reached for PeakAutS/S del. Hint: The Peak start/stop function activates the common output signal Sys start/stop in IM-NT. The signal is intended to be directly connected to Sys start/stop inputs of all gen-set controllers in the system, e.g. using SHBIN/SHBOUT peripherals.
Hardware requirements
1x nx nx nx nx 1x IM-NT IG/IS-NT IGS-NT-LSM+PMS IG-AVRi IG-AVRi-TRANS/LV I-LB+ or IG-IB
(when volt matching and VAR sharing is required) (when IG-AVRi is used) (Optional Refer to IGS-NT-Communication guide)
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
31
+24V
Ko1
MCB1 CLOSE/ OPEN
Ko2
SYS START / STOP
IM-NT ( MCB)
LOAD
CAN CAN
MCB1
3x 3x
3x
GCB1
G1
iG- AVRi TRANS
CAN
Ko1
iG- AVRi
AVR
MCB1
AVRi
AVRi OUT
IG/IS-NT
Vout
Ko2
SPEED GOVERNOR
InMainsParal
0V
+24V
Ko3
MCB2 CLOSE/ OPEN
Ko4
SYS START / STOP
IM-NT ( MCB)
CAN
MCB2
3x
GCB2
3x
G2
iG- AVRi TRANS
CAN
3x
Ko3
iG- AVRi
MCB2
LOAD
AVRi
AVRi OUT
AVR
IG/IS-NT
Vout
Ko4
SPEED GOVERNOR
InMainsParal
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
32
Description
The IM-NT (MCB) controller opens MCB after the mains fails or after the gen-sets are running according to setpoint AMF settings:MCB opens on. The IM-NT controller closes binary output Sys start/stop which is connected to Sys start/stop inputs of the gen-set controllers in the corresponding group if: - If IM-NT (MCB) binary input Rem start/stop gets active (AUT mode only). - If AMF condition is sensed in IM-NT (MCB) and the gen-set group should be started as stand-by power source (AUT mode only). - If PeakShaving function senses that it is suitable to start the gen-set group in order to lower the mains import (AUT mode only). - If Start button is pressed on IM-NT front panel or remotely (MAN mode only). The signal can be deactivated by pressing the Stop button. If the controller is switched from AUT to MAN mode, the internal status of the flip-flop circuit created by Start-Stop buttons is set to follow the previous state in AUT mode. E.g. if the gen-set group has run in an AMF situation in AUT mode, switching to MAN will not stop it (= Sys start/stop output stays active). After binary input Sys start/stop closes the gen-sets are starting with a delay SysAMFstrtDel. It is similar to setpoint EmergStart del in SPtM application. The first set with a correct voltage and frequency closes the GCB to the dead bus, others are synchronized. When the mains returns, IM-NT (MCB) synchronizes gen-sets to the mains with limitations given by setpoints ProcessControl:ParallelEnable and Synchro enable (see Table on p.9 in IM-NT-MCBMGCB-X.X.pdf). The gen-set controllers know whether they are connected to the Mains from binary input MCB feedback that can be configured on binary output InMainsParal (using VPIO for instance). This binary output is distributed over the CAN bus and indicates which MCBs are closed and connected to the Mains. Based on this information the gen-set controllers are controlled by one or another IMNT (MCB) controller.
Hardware requirements
2x nx nx nx nx 1x IM-NT IG/IS-NT IGS-NT-LSM+PMS IG-AVRi IG-AVRi-TRANS/LV I-LB+ or IG-IB
(when volt matching and VAR sharing is required) (when IG-AVRi is used) (Optional Refer to IGS-NT-Communication guide)
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
33
3.3.5 Multiple parallel to Mains, MCB and BTB control from IM-NT Specification
Automatic gen-set start when the mains fails (BI Sys start/stop is closed) MCB controlled by IM-NT Break transfer on mains failure MCB synchronizing after mains return BTB and MGCB synchronizing Pwr management (load dependent start and stop) Sets priority can be defined manually or automatically based on running hours equalization or load demand (most efficient combination) Load sharing and VAR sharing Gen-sets soft loading and unloading Voltage matching Reverse power protection MGCB support
REM START/STOP MCB1 FEEDBACK
3xUM
3xUB
3xIM
3xUB
3xUG 3xUG
0V
BTB
REM START/STOP
MCB2 FEEDBACK
3xUM
3xUB
3xIM
+24V
Ko5
Ko5
3xUB
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
3xIG
3xIG
34
Hardware requirements
3x nx nx nx nx 1x IM-NT IG/IS-NT IGS-NT-LSM+PMS IG-AVRi IG-AVRi-TRANS/LV I-LB+ or IG-IB
(when volt matching and VAR sharing is required) (when IG-AVRi is used) (Optional Refer to IGS-NT-Communication guide)
Required application System configuration/ default archive: IG/IS-MINT.ant and IM-MCB/BTB.ant Required setting:
example related to the first scheme above: IM-NT (MCB1) Control group = 1 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IGS-NT (GCB1) Control group = 1 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IM-BTB GroupLinkLeft = 2 GroupLinkRight = 1 IM-NT (MCB2) Control group = 2 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IGS-NT (GCB2) Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF 35
Control group = 2 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important)
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
36
3.3.6 Multiple parallel to Mains, MCB and BTB (MGCB) control from IM-NT Specification
Automatic gen-set start when the mains fails (BI Sys start/stop is closed) MCB controlled by IM-NT Break transfer on mains failure MCB synchronizing after mains return BTB synchronizing Pwr management (load dependent start and stop) Sets priority can be defined manually or automatically based on running hours equalization or load demand (most efficient combination) Load sharing and VAR sharing Gen-sets soft loading and unloading Voltage matching Reverse power protection
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
37
REM START/STOP
MCB1 FEEDBACK
3xUM
3xUB
3xIM
MGCB1
FEEDBACK
3xIBL
3xUBL
3xUBR
3xUB
3xUG 3xUG
0V
BTB
REM START/STOP
MCB2 FEEDBACK
+24V
Ko5
3xUM
3xUB
3xIM
MGCB2
FEEDBACK
3xUBL
Ko5
3xUBR
3xIBL
3xUB
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
3xIG
3xIG
38
When the mains returns, IM-NT (MCB) synchronizes gen-sets to the mains with limitations given by setpoints ProcessControl:ParallelEnable and Synchro enable (see Table on p.9 in IM-NT-MCBMGCB-X.X.pdf). The gen-set controllers know whether they are connected to the Mains from binary input MCB feedback that can be configured on binary output InMainsParal (using VPIO for instance). This binary output is distributed over the CAN bus and indicates which BTBs are closed and so which logical groups are interconnected and connected to the Mains. Based on this information the gen-set controllers are controlled by one or another IM-NT (MCB) controller.
Hint: It is possible to use virtual shared inputs/outputs to connect for example Sys start/stop output from IM-NT to corresponding binary input of all controllers instead of hardwiring it. See chapter Shared virtual I/O periphery. For BTB controllers the BI BTB Feedback should be configured as Group link input as well.
Hardware requirements
5x nx nx nx nx 1x IM-NT IG/IS-NT IGS-NT-LSM+PMS IG-AVRi IG-AVRi-TRANS/LV I-LB+ or IG-IB
(when volt matching and VAR sharing is required) (when IG-AVRi is used) (Optional Refer to IGS-NT-Communication guide)
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
39
3.3.7 Multiple parallel to Mains, MCB and MGCB control from IM-NT Specification
Automatic gen-set start when the mains fails (BI Sys start/stop is closed) MCB controlled by IM-NT Break transfer on mains failure MCB synchronizing after mains return MGCB synchronizing Pwr management (load dependent start and stop) Sets priority can be defined manually or automatically based on running hours equalization or load demand (most efficient combination) Load sharing and VAR sharing Gen-sets soft loading and unloading Voltage matching Reverse power protection MGCB support
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
40
+24V
Ko1
MCB1 CLOSE/ OPEN
Ko2
SYS START / STOP
IM-NT ( MGCB )
3xUM 3xUB 3xIM CAN
LOAD
CAN
MCB1
3x 3x
3x
MGCB1
GCB1
G1
iG- AVRi TRANS
3xUB 3xUG 3xIG CAN
Ko1
Ko6
iG- AVRi
AVR
MCB1
MGCB1
AVRi
AVRi OUT
IG/IS-NT
Vout
Ko2
SPEED GOVERNOR
InMainsParal
+24V
Ko3
MCB2 CLOSE/ OPEN
Ko4
SYS START / STOP
IM-NT (MGCB)
3xUM 3xUB 3xIM CAN
MCB2
3x
MGCB2
GCB2
3x
G2
iG- AVRi TRANS
3xUG 3xIG CAN
3x
Ko3
Ko7
3xUB
iG- AVRi
MCB2
LOAD
MGCB2
AVRi
AVRi OUT
AVR
IG/IS-NT
Vout
Ko4
SPEED GOVERNOR
InMainsParal
Description
The IM-NT controller opens MCB after the mains fails or after the gen-sets are running according to setpoint AMF settings:MCB opens on. The IM-NT controller closes binary output Sys start/stop which is connected to Sys start/stop inputs of the gen-set controllers in the corresponding group if: - If IM-NT (MCB) binary input Rem start/stop gets active (AUT mode only). - If Start button is pressed on IM-NT front panel or remotely (MAN mode only). The signal can be deactivated by pressing the Stop button. If the controller is switched from AUT to MAN mode, the internal status of the flip-flop circuit created by Start-Stop buttons is set to follow the previous state in 41
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
AUT mode. E.g. if the gen-set group has run in an AMF situation in AUT mode, switching to MAN will not stop it (= Sys start/stop output stays active). - If IM-NT binary input Rem start/stop gets active (AUT mode only). Before the output Sys start/stop is activated, the MGCB close command is issued (if ProcessControl:MGCBparalClose = YES). - If AMF condition is sensed in IM-NT and the gen-set group should be started as stand-by power source (AUT mode only). MGCB is not closed before the GCBs but only after a reasonable amount of gen-sets have synchronized to the bus (load reserve achived). - If PeakShaving function senses that it is suitable to start the gen-set group in order to lower the mains import (AUT mode only). Before the output Sys start/stop is activated, the MGCB close command is issued (if ProcessControl:MGCBparalClose = YES). After binary input Sys start/stop closes the gen-sets are starting with a delay SysAMFstrtDel. It is similar to setpoint EmergStart del in SPtM application. The first set with a correct voltage and frequency closes the GCB to the dead bus, others are synchronized. When the mains returns, IM-NT (MCB) synchronizes gen-sets to the mains with limitations given by setpoints ProcessControl:ParallelEnable and Synchro enable (see Table on p.9 in IM-NT-MCBMGCB-X.X.pdf). The gen-set controllers know whether they are connected to the Mains from binary input MCB feedback that can be configured on binary output InMainsParal (using VPIO for instance). This binary output is distributed over the CAN bus and indicates which BTBs are closed and so which logical groups are interconnected and connected to the Mains. Based on this information the gen-set controllers are controlled by one or another IM-NT (MCB) controller.
Hardware requirements
2x IM-NT nx IG/IS-NT nx IGS-NT-LSM+PMS nx IG-AVRi (when volt matching and VAR sharing is required) nx IG-AVRi-TRANS/LV (when IG-AVRi is used) 1x I-LB+ or IG-IB (Optional Refer to IGS-NT-Communication guide) Hint: Without IG-AVRi Droop VAR sharing must be used.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
42
3.3.8 Multiple parallel to Mains, MCB and BTB control from IM-NT (3Mains)
0V REM START/STOP MCB1 FEEDBACK
+ 24V
Ko1
MCB1 CLOSE/ OPEN
Ko2
SYS START/ STOP
IM- NT ( MCB)
Group1
3xUM 3xUB 3xIM CAN
LOAD
CAN
MCB1
3x 3x
3x
GCB1
G1
iG- AVRi TRANS
3xUB 3xUG 3xIG CAN
Ko1
iG- AVRi
AVR
MCB1
AVRi
AVRi OUT
IG/IS- NT
BTB 1
Group1
Ko2 SYS START / STOP MCB FEEDBACK InMainsParal
Vout
3xUBR
SPEED GOVERNOR
BTB FEEDBACK
IM- NT ( BTB)
BTB CLOSE / OPEN
3xU BL 3xI BL
BTB 1
Ko5
+ 24V
Ko3 Ko4
SYS START/ STOP
IM- NT ( MCB)
Group2
3xUM 3xUB CAN 3xIM
+24V
Ko5
LOAD
MCB2
3x 3x
Ko3
MCB2
GCB2
3x
G2
iG- AVRi TRANS
3xUG 3xIG CAN
3xUB
iG- AVRi
AVRi AVRi OUT
AVR
IG/IS- NT
Group2
Ko4 SYS START / STOP MCB FEEDBACK
Vout
SPEED GOVERNOR
3xUBR
0V REM START/STOP MCB2 FEEDBACK
+ 24V
0V
BTB FEEDBACK
IM-NT ( BTB)
3xU BL 3xI BL
BTB 2
InMainsParal
Ko7
MCB2 CLOSE/ OPEN
BTB 2
Ko6
Ko8
SYS START/ STOP
Group3
3xUM 3xUB 3xIM CAN
+24V
MCB2
3x
2 GCB3
3x
Ko6
IM- NT ( MCB)
G3
iG- AVRi TRANS
3xUG 3xIG CAN
3x
Ko7
3xUB
iG- AVRi
MCB2
LOAD
AVRi
AVRi
OUT
AVR
IG/IS- NT
Group3
Ko8 SYS START / STOP MCB FEEDBACK InMainsParal
Vout
SPEED GOVERNOR
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
43
Description
The IM-NT (MCB) controller opens MCB after the mains fails or after the gen-sets are running according to setpoint AMF settings:MCB opens on. The IM-NT controller closes binary output Sys start/stop which is connected to Sys start/stop inputs of the gen-set controllers in the corresponding group if: - If IM-NT (MCB) binary input Rem start/stop gets active (AUT mode only). - If AMF condition is sensed in IM-NT (MCB) and the gen-set group should be started as standby power source (AUT mode only). - If PeakShaving function senses that it is suitable to start the gen-set group in order to lower the mains import (AUT mode only). - If Start button is pressed on IM-NT (BTB) front panel or remotely (MAN mode only). The signal can be deactivated by pressing the Stop button. If the controller is switched from AUT to MAN mode, the internal status of the flip-flop circuit created by Start-Stop buttons is set to follow the previous state in AUT mode. E.g. if the gen-set group has run in an AMF situation in AUT mode, switching to MAN will not stop it (= Sys start/stop output stays active). After binary input Sys start/stop closes the gen-sets are starting with a delay SysAMFstrtDel. It is similar to setpoint EmergStart del in SPtM application. The first set with a correct voltage and frequency closes the GCB to the dead bus, others are synchronized. When the mains returns, IM-NT (MCB) synchronizes gen-sets to the mains with limitations given by setpoints ProcessControl:ParallelEnable and Synchro enable (see Table on p.9 in IM-NT-MCBMGCB-X.X.pdf). The gen-set controllers know whether they are connected to the Mains from binary input MCB feedback that can be configured on binary output InMainsParal (using VPIO for instance). This binary output is distributed over the CAN bus and indicates which BTBs are closed and so which logical groups are interconnected and connected to the Mains. Based on this information the gen-set controllers are controlled by one or another IM-NT (MCB) controller.
Hardware requirements
5x nx nx nx nx 1x IM-NT IG/IS-NT IGS-NT-LSM+PMS IG-AVRi IG-AVRi-TRANS/LV I-LB+ or IG-IB
(when volt matching and VAR sharing is required) (when IG-AVRi is used) (Optional Refer to IGS-NT-Communication guide)
Required setting:
System without MGCB (example related to the first scheme above): IM-NT (MCB1) Control group = 1 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IGS-NT (GCB1) Control group = 1 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IM-BTB 1 GroupLinkLeft = 2 GroupLinkRight = 1 IM-NT (MCB2) Control group = 2 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IGS-NT (GCB2) Control group = 2 GroupLinkLeft = COMMON (setting not important) Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF 44
GroupLinkRight = COMMON (setting not important) IM-BTB 2 GroupLinkLeft = 3 GroupLinkRight = 2 IM-NT (MCB3) Control group = 3 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IGS-NT (GCB3) Control group = 3 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important)
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
45
3.3.9 Multiple parallel to Mains, MCB and BTB control from IM-NT (2Mains)
0V REM START/STOP MCB1 FEEDBACK 0V FEEDBACK
+ 24V
MGCB1
V 24 +
Ko1
MCB1 CLOSE/ OPEN
Ko6
Ko2
SYS START/ STOP
IM- NT ( MCB)
Group1
3xUM 3xUB 3xIM CAN
LOAD
IM- NT ( BTB)
3xUBR
CAN 3xUBL
3xIBL
MCB1
3x 3x
3x
MGCB1
GCB1
G1
iG - AVRi TRANS
3xUB 3xUG 3xIG CAN
Ko1
Ko6
iG - AVRi
MCB1
MGCB1
AVRi
AVRi OUT
IG/IS- NT
Group2
SYS START / STOP MCB FEEDBACK
Vout
SPEED GOVERNOR
GCB2
G2
iG - AVRi TRANS
3xUB 3xUG 3xIG CAN
iG - AVRi
AVRi AVRi OUT
3xUBR
IG/IS- NT
Group2
Vout
BTB FEEDBACK 0V
IM- NT ( BTB)
BTB CLOSE / OPEN
SPEED GOVERNOR
BTB
InMainsParal Ko5
BTB
Ko5
+24V
0V FEEDBACK
+ 24V
Ko4
SYS START/ STOP
IM-NT ( MCB)
Group3
3xUM 3xUB CAN 3xIM CAN
MGCB2
Ko3
V 24 +
Ko7
IM- NT ( BTB)
3xUBL
3xUBR
3x
3xIBL
MCB2
GCB 3
3x
MGCB2
3x
G3
iG- AVRi TRANS
3xUG 3xIG CAN
Ko3
Ko7
3xUB
iG- AVRi
MCB2
LOAD
MGCB2
AVRi
AVRi OUT
AVR
IG/IS- NT
Group4
SYS START / STOP MCB FEEDBACK
Vout
SPEED GOVERNOR
GCB 4
3x
G4
iG - AVRi TRANS
3xUG 3xIG CAN
3xUB
iG- AVRi
AVRi AVRi OUT
AVR
IG/IS- NT
Group4
Ko4 SYS START / STOP MCB FEEDBACK InMainsParal
Vout
SPEED GOVERNOR
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
46
Description
The system with this topology has to be separated into 4 logical groups by 3 IM-NT (BTB) controllers. It is not possible to use IM-NT MGCB application for this purpose. The IM-NT (MCB) controller opens MCB after the mains fails or after the gen-sets are running according to setpoint AMF settings:MCB opens on. IM-NT (BTB) controller closes automatically BTB/MGCB if - bus voltages are within the limits (Sync ctrl:Phase window, Voltage window) - there is voltage on one of the buses and closing to dead bus is enabled by ProcessControl:DeadBusClosing - binary input BTB disable is not closed - it is enabled by setting of ProcessControl:Synchro enable, Mains coupling setpoints After binary input Sys start/stop closes the gen-sets are starting with a delay SysAMFstrtDel. It is similar to setpoint EmergStart del in SPtM application. The first set with a correct voltage and frequency closes the GCB to the dead bus, others are synchronized. When the mains returns, IM-NT (MCB) synchronizes gen-sets to the mains with limitations given by setpoints ProcessControl:ParallelEnable and Synchro enable (see Table on p.9 in IM-NT-MCBMGCB-X.X.pdf). The gen-set controllers know whether they are connected to the Mains from binary input MCB feedback that can be configured on binary output InMainsParal (using VPIO for instance). This binary output is distributed over the CAN bus and indicates which BTBs are closed and so which logical groups are interconnected and connected to the Mains. Based on this information the gen-set controllers are controlled by one or another IM-NT (MCB) controller.
Hint: It is possible to use virtual shared inputs/outputs to connect for example Sys start/stop output from IM-NT to corresponding binary input of all controllers instead of hardwiring it. See chapter Shared virtual I/O periphery. For BTB controllers the BI BTB Feedback should be configured as Group link input as well.
Hardware requirements
5x nx nx nx nx 1x IM-NT IG/IS-NT IGS-NT-LSM+PMS IG-AVRi IG-AVRi-TRANS/LV I-LB+ or IG-IB
(when volt matching and VAR sharing is required) (when IG-AVRi is used) (Optional Refer to IGS-NT-Communication guide)
Required setting:
System with MGCBs (example related to the second scheme above): IM-NT (MCB1) Control group = 1 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IGS-NT (GCB1) Control group = 2 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IGS-NT (GCB2) Control group = 2 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IM-NT (MGCB1) BTB appl. used GroupLinkLeft = 1 GroupLinkRight = 2 IM-NT (BTB) GroupLinkLeft = 3 GroupLinkRight = 1 IM-NT (MGCB2) BTB appl. used Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF 47
GroupLinkLeft = 3 GroupLinkRight = 4 IM-NT (MCB2) Control group = 3 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IGS-NT (GCB3) Control group = 4 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important) IGS-NT (GCB4) Control group = 4 GroupLinkLeft = COMMON (setting not important) GroupLinkRight = COMMON (setting not important)
3.4
Combi applications
LOAD
MCB
3x
3x 3x
GCB
3x
3xUM
3xUG
K4
K3
MCB
GCB CLOSE / OPEN MCB CLOSE / OPEN
GCB
BO
3xIG
AVRi
iG- AVRi
AVR
IGS-NT
BI Vout SPEED GOVERNOR SYS START/STOP SPI ENABLE BASELOAD UP
Hardware requirements
1x 1x 1x IGS-NT IG-AVRi IG-AVRi-TRANS/LV (when volt matching and PF control is required) (when IG-AVRi is used) 48
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
Sync timeout timeout = NO Hint: For ManualFuseSync and Sync timeout setpoints, you can additionally use the Force value feature, so you can switch between std. sync and manual fuce sync using binary input.
3xUB 3xUB
3xUG 3xUG
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
3xIG
3xIG
49
Hardware requirements
nx nx nx nx 1x IGS-NT IGS-NT-LSM+PMS IG-AVRi IG-AVRi-TRANS/LV I-LB+ or IG-IB (when volt matching and VAR sharing is required) (when IG-AVRi is used) (Optional Refer to IGS-NT-Communication guide)
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
50
4. Virtual peripherals
4.1 Integrated PLC
The NT family controllers contain a virtual PLC module that can be connected to the system. The activation of the PLC is done in the Modules card in GenConfig. Depending on the controller HW type, a different number of functions and function types is available. See the table below for complete overview. The internal PLC can simplify or even avoid the external logic in a switchboard, bringing another level of control system integration. The PLC has analog and binary inputs and outputs that can be interfaced to any suitable controller analog value, physical or logical binary input and output.
Log Func I.
32
200
32
200
Comp Hyst
16
Comp Time
Analog input One limit + delay Binary output Window comparator Analog input, two limits, analog output. Binary output is active when input is within limits.
Comp.Win.
16
Math Func
16
ADD, SUB, ABS, AVG, MAX, MIN Two analog inputs Analog output
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
51
Math functions with expandable number of inputs up to 8. Selectable: ADD, AVG, MAX, MIN 8 analog inputs, 1 analog output.
InterpolFunc
Linear interpolation Analog input Analog output PID - Analog output jumps to adjustable Bias value when Gate input is active (instead zero as before) and starts from Bias.
PID Ana B
PID Bin
Ramp
Up/Down
Ramp - Analog input, analog output. Two setpoints for Ramp-up and down speed (in number of units per second). Enable-Up, Enable-Down: Ena/Disables the ramp. Analog output changing within 2 limits (by defined rate of change - ramp) when Up/Down input is active.
Analog output (internal register) can be Increased / Decreased by one with rising edge of binary input Inc / Dec in range from 0 to adjustable limit (max 65535). Register is Inc / Decreased over zero when "Cycle" option is ticked. Register stops on 0 even other Dec pulses come (or on Max for Inc pulses) when "Cycle" option is not ticked. Example of "Cycle" when Max = 5: 1-2-3-4-5-0-1-... or ...4-3-2-1-05-4- ... Example of "No-Cycle" when Max = 5: 1-2-3-4-5-5-5-... or ...4-3-2-10-0-0- ... Binary input "Reset" switch the Analog output to adjustable Default value. 52
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
Mov Avg
Analog input, Analog output Performs averaging (filtering) of the input value with selectable weight and period
Timer
Delay
24
Ana Switch
16
ForceHistory
ForceProtect
Jump
Multiplex constant
Binary input Enabled / Disabled jump over the selected number of the next following PLC blocks. Jumps to the last one when number of blocks is higher than existing. Jump size is fix, adjustable during the configuration procedure only. The block works as a multiple constant selected by an analog value. The output value is set to the constant with index equal to the input value
Counter
Edges counter One limit Binary output Selected part of Analog input can be decomposed (decoded) to four binary outputs.
Decomposer
Converts any "Short" and "Long" analog value format to (signed) Integer format compatible with all PLC analog inputs. The invalid Analog output is indicated (####) when Analog input value is out of Integer range. Note: For information on PLC module configuration, see GenConfig manual or context help. (press F1 button in GenConfig). Convert
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
53
Table of PLC blocks differences between IGS-NT ver. 2.5 and 2.6 (changes are in bold) Group Logical function Comparators PLC Block OR/AND XOR/RS Comp Hyst Comp Time Comp Win Math Fc Ext math Fc Interpol Fc PID Ana B PID Bin Ramp Up/Down Inc/Dec Mov Avg Timer Delay Ana Switch Force Hist Force Prot Jump Mux Const. Counter Decomp Convert IS-NT ver. 2.5 64 16 16 8 16 16 8 2 4 4 4 4 2 2 4 24 16 4 4 4 4 4 4 8 IS-NT ver. 2.6 200 200 16 8 16 16 8 2 4 4 4 4 2 2 4 24 16 4 4 4 4 4 4 8 IG-NT ver. 2.5 16 4 4 4 IG-NT ver. 2.6 32 32 4 4 4 3 2 1 IG-NT-mCHP ver. 2.5 32 32 4 4 4 3 2 1 2 2 2 2 2 1 1 8 2 4 4 4 4 1 4 4
Math operations
2 2 2 1 1 8 2 4 4 4 4 1 4 4
Functions description
IMPORTANT All analog inputs representing time are entered into PLC with one decimal in the range 0,0 3276,7 sec, i.e. if there is 100 seconds measured / converted at an analog input and the measurement is without decimal point, it is interpreted for PLC function as 10.0 seconds. For example in CMPT, Timer, Delay functions.
Log Func I.
Logical functions: AND, OR. Two to eight inputs AND, OR functions are available. Maximal number of functions: 32 OR, AND logic Input No.1 0 0 1 1 I/O Input No. 1 Input No. 2 ..
Input No.2 0 1 0 1
OR 0 1 1 1
AND 0 0 0 1 Note
I1 I2
I8 Binary input 8 Input No. 8 Output Function type OR or AND To add/remove input click on + or button. It is possible to invert any input or output. Maximum number of inputs is 8. Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF 54
Comp Hyst
Comparator with hysteresis. Maximal number of functions: 8 I/O Note Input 1 Analog input Input On ON limit Input Off OFF limit Output Binary output ON and OFF limit can be configured as - constant limit (fix): just write requested value into the field (-32000 to +32000) - setpoint limit (customer adjustable): click on field and select one from PLC setpoint list - any value (e.g. from Analog input): click on field and select one from controller or PLC values list Output signal depends on limits order.
Input ON < Input OFF Input OFF
Input ON
Output
Comp Time
Comparator with limit and delay. Maximal number of functions: 8. I/O Note Input 1 Analog input Input 2 ON/OFF limit Delay Delay [0,1s] in the range: 0,0 to 3276,7 sec. Output Binary output ON/OFF limit can be configured as - constant limit (fix): just write requested value into the field (-32000 to +32000) - setpoint limit (customer adjustable): click on field and select one from PLC setpoint list - any value (e.g. from Analog input): click on field and select one from controller or PLC values list Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF 55
Input 2
Input 1
delay
delay
delay
Output
Window comparator
Comparator indicating the value is within the two limits. Maximal number of functions: 8. I/O Note Input 1 Analog input Input ON ON limit Input OFF OFF limit Output Binary output ON/OFF limits can be configured as - constant limit (fix): just write requested value into the field (-32000 to +32000) - setpoint limit (customer adjustable): click on field and select one from PLC setpoint list - any value (e.g. from Analog input): click on field and select one from controller or PLC values list
Input ON < Input OFF Input OFF
Input ON
Output
Window
Ana Switch
Analog switch. Binary input selects which analog input is connected to analog output. Maximal number of functions: 4 I/O Note Input 1 Analog input 1 Input 2 Analog input 2 Input Sw Input selection. Output = Input1 when Input sw is opened. Output Analog output
Switch Input 1 Output Input 2
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
56
Input 1 Input 2
Output
Mov Avg
Moving average with adjustable weight and period. Maximal number of functions: 2 I/O Note Input Analog input Exp.weigh 1 to 5 Period 100 to 5000 ms Output Analog output Output value format follows the input format.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
57
InterpolFunc
Linear interpolation based on two points line. Analog output corresponds to linear characteristic specified by two points. Max number of functions: 2 I/O Note X1 The first point X Y1 The first point Y X2 The second point X Y2 The second point Y Input Analog input Output Analog output Analog output format follows analog input.
Output Y2
Y1 X1 X2
Input
ForceHistory
History record is activated when binary input value is changed from 0 to 1. Maximal number of functions: 4 I/O Input Binary input Note
ForceProtect
Force programmable state. Function activates selected programmable state. Max number of functions: 4 I/O Note Protection type Select type from the list. Lvl1 Level 1 protection: Warning Lvl2 Level 2 protection: Shut down, Cool down Fls Sensor fail Connect selected levels to binary input from the list. Selected protection level is activated when corresponding binary input is closed (active).
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
58
PID Bin
PID control loop with binary outputs. Maximal number of functions: 2 I/O Note Input Analog input Requested value Configure as constant, PLC setpoint or value. Input GAIN PID proportional factor Input INT PID integral factor Input DER PID derivative factor Active binary input GATE blocks PID calculation and set both Input GATE outputs to zero. Output Up Binary output UP. Output Down Binary output DOWN. Period Period of PID calculation: 100 to 5000 msec. Actuator Period of PLC calculation: 100 to 5000 msec. PID analog input can be configured to any analog value (physical input) Requested value and PID setting can be configured as constant or setpoint or analog value (physical input) from the object list. Active binary input GATE blocks PID calculation - binary outputs are inactive. Example: Adjust 5 sec when time from open to close valve is 5 sec. Sensor fail on measured (or requested) value blocks PID calculation. Hint: Constants should be set 10 times higher then in IS-CU for the same behavior
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
59
Counter
Impulse counter. Maximal number of functions: 2 I/O Note Input cnt Counter binary input. Input clr Counter clear (reset) binary input. Input lim Analog limit level input (max 65535). Output Binary output over limit indication. Counter can counts rising or falling edge. The result is stored in volatile memory and it is lost when controller is switched off. Binary output is activated when counter is over limit. Output stays closed even if counter overflow over maximum 65535. Counter contains binary Reset input (level sensitive) that set counter to zero, resets binary output and blocks counting when active. Maximal counter value is 65535 (16 bites wide) and continues to zero. The minimal pulse period is 0,2 sec (max 5 Hz) - in this case the counter overflow after 218 minutes.
Timer
Periodic signal generator. Maximal number of functions: 2 I/O Note Input reload val Analog value specifies period of Binary output change [ 0,1s]. Input reload Closed binary input Reload reloads timer period when closed. Input run Binary input must be closed to activate Timer. Output Binary output. Binary output changes state with period given by analog Input reload val [ 0,1s ] when Binary input Run is closed and Binary input Reload is opened. Timer starts with low state period when selection Firs down is ticked. E.g. Output changes state each 10 sec when input value is 100. Timer reloads (accepts period change) in the end of period or when binary input Reload is closed. Reload function can be useful when very long time period is running.
Delay
Delay module adjustable delay for rising/falling or the both edges of an output pulse. Maximal number of functions: 24 I/O Input Input time up Input time down Input reset Output Note Binary input. (IN) Delay of rising edge in 0,1s (Tup) Delay of falling edge in 0,1s (Tdown) Binary input to reset output. (RESET) Binary output. (OUT)
This module allows to create own output pulse, which is derived from an input pulse by a delay of its rising/falling or the both edges. With using of delay block, a condition Tup < Tdown + TIN has to be fulfilled. Note: output pulse is not generated if condition Tup < Tdown + TIN is not fulfilled. The function can be used as a noise filter it does not accept an input pulse shorter than 100 ms.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
60
Tdown
IN RESET
OUT
Note:
IN RESET
OUT
IN RESET
OUT
Tdown = 0
> 100 ms
Tdown Noise filter does not accept input pulse shorter than 100 ms. Linup - a gap between rising edges of previous IN pulses
RESET
OUT
Tup
IN
T rstup
> 100 ms
RESET
Tup
OUT
Pulse on edge Function depends on selection Pulse on edge in a delay block. The function generates a pulse on rising edge when Input time up (Tup) is configured or pulse on falling edge when Input time down (Tdown) is configured. A step for time adjustment is 100ms.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
61
IN RESET
Two pulses when both Time up and Time down setpoints are configured I
Tup Tdown
OUT
T down
IN RESET
OU
Tup
Tup is reset with falling
IN RESET
OUT
TIN
IN RESET OUT OUT
Tdown
Puls on edge
a) Single pulse when Tdown is not configured and Tup < TIN. b) Single pulse when Tdown is not configured and Tup > TIN. Tup is reset with falling edge of an input pulse a pulse generated by a rising edge is shorter. c) One Long pulse is generated up when Tup > TIN and Tdown is configured. The both pulses are merged. d) Two separate pulses when Time up and Time 62
Tup ;Tdown =0 Tup Tup > TIN Tdown Tup < TIN
Tdown =0
a) b) c) d)
OUT
OUT
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
down are configures The pulse is generated at each a rising and a falling edge of an input pulse. It is not possible to choose which from pulses will be generated. Only one Timer is used for Tup and Tdown timing. It means when rising/falling edge comes, Timer is set to Tup/down value, even if previous timing has not finished yet a previous timing is reset. Condition Tup < TIN + Tdown has to be fulfill.
Tdown
Tup
Timing Tup was reset with Tdown when falling edge of an input pulse came a pulse generated by rising edge is shorter.
OUT
RAMP
The analog output changes state in constant speed adjustable to different values Up and Down. Maximal number of functions: 4 I/O Note Input Analog input. Input time up Units per second Input time down Units per second Output Analog output. Option: tick EnableUp and EnableDown in PLC RAMP configuration window. The output follows input when corresponding Enable Up/Dn is not selected.
Input
Output
p pU Ram
Up/Down
The analog output is rising/falling according to binary inputs Up and Down activation. Maximal number of functions: 4 I/O Note Limit1 Analog input to limit the output. Limit2 Analog input to limit the output. Reset Binary input to reset the output to Default output value. Analog input to adjust rising speed (or falling speed when Speed up negative). Analog input to adjust falling speed (or rising speed when Speed down negative). Up Binary input to activate output rising. Down Binary input to activate output falling. Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF 63
The output switches to this value after start-up or reset or when both Up and Down inputs are activated. Analog output.
UP/Down block can be used as a Holding register. Required settings for holding register with analog input, binary input and one analog output: Up/Down Reset Default output value Output Note Binary input Analog input Analog output.
Analog output follows analog input if Reset is active if it is not active analog output is frozen and stays at the last known value. Example: The regulation PID module with binary output is used to maintain required heating temperature through the UpDn module by change of valve position. Before the engine is ready to take, the load the logical binary output LBO: Ready to Load is inactive and the valve position is given by the Default output setpoint. When the engine is ready to take the load the LBO: Ready to Load is active and PID module changes the heating temperature by series of pulses and accordingly the UpDn module reaches the required temperature (Req.temp. setpoint) by the change of valve position. The characteristic of the PID regulation loop is given by the PLC setpoints: GAIN, INT and DER. The changing speed (per second) of the valve position is limited by the Speed up and Speed down setpoints. The AO: Valve position can be changed in the limits given by the Limit1 and Limit2 setpoints.
LBO: Ready to Load PID Bin Sensor characteristic AI: Temperature sensor Req. temp. GAIN INT DER Period: 200 ms Actuator time: 100 ms OR Valve Up Valve Down Limit1 Limit2 Speed up Speed down Default out. UpDn Reset Up Dn
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
4.2
The controller features many logical outputs, i.e. outputs that could be configured to physical outputs (terminals of the controller itself or of expansion modules). But sometimes it is necessary to bring the output signal back to the input, if a special behaviour is required. E.g. logical binary output Batt volt is linked with only a Warning type alarm, and from some reason it is required that the engine be stopped in this case (at certain site). You can achieve this by bringing the signal to physical output and then connect it to a physical input. Then this input can be configured with a Shutdown type protection. The disadvantage of the above solution is that you are losing one input and one output of the controller / expansion module, which is costly. The virtual periphery simulates this within the controller, bringing a group of physical outputs, linked with a group of physical inputs. So you can configure a logical output of the controller to this module, and then configure a protection (or a link to logical input) to the physical input part of the module, as you would do with real inputs. The same can be done with PLC I/O, so e.g. a complex evaluation of a protection in PLC can be brought directly to an input configured for this protection type.
LOGICAL OUTPUTS
LOGICAL INPUTS
4.3
It is often required that certain signals be brought to all controllers in the group. For example MCB feedback, System Start/Stop, Common Shutdown signal etc. These are all binary signals. Sometimes analog signals are required as well, like engine room temperature signal, where too high temperature can cause the nominal power of all gen-sets in the room to be reduced (power derating function). IG/IS-NT controllers have a provision to make it easier when designing such an application. These controllers have a sophisticated system of shared virtual modules, where one controller is a signal server and the other controllers are recipients of this signal. The signals are distributed via the CAN bus which typically interconnects all the controllers on one site.
Configuration
These virtual modules can be added / removed like any other HW module in GenConfig / card Modules. Then they appear in the list of inputs or outputs in the card I/O.
SHBOUT/SHAOUT modules
They behave like standard output modules, but the signals assigned to them dont appear on any physical output, instead of that are distributed via the CAN bus to other controllers. Each module has 8 outputs.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
VIRTUAL BO
VIRTUAL BI
65
ShBIN/SHAIN modules
They behave like standard input modules, i.e. you can assign any logical input signal that is available in the controller to them, or configure a protection based on their activity. Each module has 8 inputs.
SOURCE (SHBOUT)
Intercontroller CAN bus
TARGET (SHBIN)
TARGET (SHBIN)
TARGET (SHBIN)
Hint: If more controllers are selected to be the source for one channel, only the controller with the lowest CAN address is taken into account, and all controllers report a SHBinCfgErr message in Alarmlist.
The picture below shows the principle of the SHBOUT module. It can distribute the forwarded states of physical binary inputs, or some signals created inside the controllers FW or PLC:
LOGICAL OUTPUTS PHYSICAL BINARY INPUTS
SYSTEM START
LOGICAL INPUTS
SHBOUT
In this particular example, the SYSTEM START signal which should command the start / stop for all the controllers on the site, is transferred from the terminal (physical binary input) to the SHBOUT module. All other controllers on the site should be configured in the way that the signal is picked up in the same position (1-8) where it has been assigned to in SHBOUT module. The signal is then picked up from the module and can be used by the controllers FW or PLC like any other physical binary input:
PHYSICAL BINARY INPUTS LOGICAL OUTPUTS
LOGICAL INPUTS
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
SHBIN
66
SOURCE (SHAOUT)
Intercontroller CAN bus
TARGET (SHAIN)
TARGET (SHAIN)
TARGET (SHAIN)
Hint: If more controllers are selected to be the source for the analog channel, only the controller with the lowest CAN address is taken into account, and all controllers report a SHAinCfgErr message in Alarmlist.
The picture below shows the principle of the SHAOUT module. It can distribute the forwarded values of externally measured (physical) analog inputs, as well as the values measured or computed inside the controllers FW or PLC:
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
67
LOGICAL INPUTS
MEASURED VALUES
SHAOUT
In this particular example, the value of externally requested System Baseload value (MLC:AnExSysBld) should be distributed to all controllers on the site. It is transferred from the terminal (physical analog input) to the SHAOUT module. All other controllers on the site should be configured in the way that the value is picked up in the same position (1-8) where it has been assigned to in SHAOUT module. The value is then picked up from the module and can be used by the controllers FW or PLC like any other physical analog input:
PHYSICAL ANALOG INPUTS MEASURED VALUES
SHAIN
LOGICAL INPUTS
Controller Functions
CAN2
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
Controller Functions
Controller Functions
68
Or between (FV) setpoint and Analog input (or in general any value):
Nominal power 100 kW Analog input (given by the curve converted output)
Hint: If Force value is active, it is not possible to change setpoint value (e.g. from InteliMonitor). Force value has to be deactivated first. Active force Value is displayed on the screen of the appropriate setpoint with the mark. See reference manual for InveliVision 5, InteliVision 8 and InteliMonitor to see more details. Configure Force value in GenConfig.
Inteli NT Application Guide, SW Version 2.6, ComAp November 2011 IGS-NT-2.6-Application Guide.PDF
69