ABOUT US

Pirelli Cables and Systems Oy has roots back to 1912 when the
rst cable factory was founded in Finland under the name of
The Finnish Braiding Factory. This was soon changed to the
Finnish Cable Factory. The company became in the 1960s part
of the Nokia group and was renamed Nokia Cables. In the mid
1990s the Nokia sold all of its cable industry to the NKF group
and the company was renamed to NK Cables and then to NK
Energy. In 2000 the NKF group was sold and Pirelli acquired the

Pikkala factory, making it Pirelli Cables and Systems Oy. Pirelli


has made cables since 1872.
In Pikkala, less than 40 km west of Helsinki along the coast,
we make marine cables, heating cables, exible rubber cables,
low voltage cables, medium and high voltage cables. Our
customers are ship yards, installers, wholesalers, contractors,
industry and power companies

6.
11.

8.

7.

5.

9.

3.
12.

4.

10.

1.

2.

1..

Martin Pekuri

+358 10 77 55 605

7.

Vesa Riitaoja

+358 10 77 55 472

2..

Mikael Rautelin

+358 10 77 55 664

8.

Katja Sepp

+358 10 77 55 808

3.

Satu Vuorio

+358 10 77 55 604

9.

Camilla Sandstrm

+358 10 77 55 219

4.

Katrine Dawson

+358 10 77 55 606

10.

Torbjrn Theman

+358 10 77 55 608

5.

Jari Ijs

+358 10 77 55 358

11.

Matti Elovirta

+358 10 77 55 876

6.

Marcus Sippel

+358 10 77 55 610

12.

Jorma Ikheimonen

+358 10 77 55 496

E-mail: rstname.surname@pirelli.com | Fax: +358 9 298 2204


Pirelli has built in a multi-step quality assurance programme, covering the production process from cable
design and raw material purchase to nal inspection and testing documentation.
The quality system of Pirelli has been assessed and approved and is audited regularly to the ISO 9001 and
the ISO 14001 Quality System Standard by dierent (depending on the factory) quality assurance entities.

CONTENTS

General

POWER & CONTROL CABLES


LM-HF 0,6/1 (1,2) kV
Unarmoured Power and Control Cable

LSM-HF 0,6/1 (1,2) kV


Armoured Power and Control Cable

INSTRUMENTATION CABLES
LJST-HF 150/250 (300) V
Armoured Instrumentation and
Telecommunication Cable

10

LJT-HF 60 V
Screened Instrumentation and
Telecommunication Cable

11

HFX-ISOSA/Cu 60 and 250 V


Individually Screened Instrumentation and
Telecommunication Cable

12

PROFIBUS M-02Y(ST)CHX 100 V


Bus-Cable

13

FIRE RESISTANT CABLES


LM-FRHF 0,6/1 (1,2) kV
Unarmoured Fire Resistant Power and Control Cable

14

LSM-FRHF 0,6/1 (1,2) kV


Armoured Fire Resistant Power and Control Cable

16

LJST-FRHF 150/250 (300) V


Armoured Fire Resistant Instrumentation and
Telecommunication Cable

18

MEDIUM VOLTAGE CABLES


LSESM 6/10 (12) kV
Armoured Medium Voltage Power Cable

20

LSESM 12/20 (24) kV


Armoured Medium Voltage Power Cable

22

TECHNICAL INFORMATION
Installation

24

Current rating

25

Identication

25

Electrical data

26

Voltage drop

27

GENERAL

MARINE CABLES
(ship wiring cables, ship board cables)
Marine cables are for installations on board ships. They have
been type approved by a classication society and they have
a construction that follows standards for marine cables.
CONDUCTOR
Marine cable conductors are of stranded annealed copper
combining the exibility and small dimensions to provide
excellent installability and economical solutions. To minimise
the cable diameter and weight we use sector shaped
conductors for bigger cross-section.
INSUL ATION MATERIAL
XLPE (cross-linked polyethylene) is used as the main insulation
material. It withstands higher temperatures than ordinary
thermoplastic polyethylene. It is resistant against deformation
and various chemicals. It has excellent mechanical and
electrical properties. The maximum conductor temperature
stipulated by IEC 60092-351 marine cable standard is 90 C.
SHEATHING MATERIAL
The sheath (jacket) is composed of halogen free, ame
retardant thermoplastic compound. It fulls the criterion
of SHF1 according to IEC 60092-359. In case of re the
sheathing material oers advantages such as reduced
emission of smoke and corrosive toxic gasses.
QUALIT Y CONTROL
Each manufactured cable goes through a test procedure
according to the IEC 60092-300 series standards.
FIRE TESTING METHODS
Flame retardance of a single cable is tested in accordance with
IEC 60332-1. It is performed on a 60 cm cable sample with a gas
ame for 1-4 min depending on the cable diameter.
The cable has to be self-extinguishing within certain limits to
full the test. Please see gure 1.

Fire retardance is tested on bunched cables in accordance


with IEC 60332-3, simulating the re behaviour of the cables
installed in a bunch. The main category that is used is A. This
is based on an amount of 7 litres of combustible material per
metre. The bunch of cables has to be minimum 3.5 m high
when it is in a burning chamber subjected to re from
a burner directed at the cables for fourty minutes. The cable
bunch may not burn more than 2.5 m above the burner.
Please see gure 2.
Fire resistance test is aimed at verifying the behaviour
of a cable that must work even when it is burning.
There are two dierent testing methods, IEC 60331-21 and
IEC 60331-31, used for power and control cables.
Ship cable standards require the IEC 60331-21 test, where
the cable sample is subjected to a ame at 750 C for 90
minutes followed by a 15 minutes cooling period while
the rated voltage is being applied between the conductors.
No breakdown or short circuit is permitted during the test.
Please see gure 3. The optional testing method for cables
with diameter over 20 mm, is the more rigorous IEC 60331-31
test, in which a bent cable, aected by mechanical impacts,
is subjected to a 830 C ame for 120 minutes.
Smoke density is tested according to IEC61034-1 (apparatus)
and IEC61034-2 (procedure and requirements). It is done
by placing cable in a smoke cube (3x3x3 m). When the cable
is burning, the light transmittance is measured using
a photometric system. This test is aimed at simulating
visibility when cables are burning on board a ship 60 %
(70 % for a single cable) visibility is satisfactory if it is attained
throughout the test.
Halogens. To test whether a material is halogen free or not,
the tests IEC 60754-1 and 60754-2 are used. The acidity of the
gasses from burning materials is measured. Being halogen-free
means that the materials used in the cables do not contain any
halogens such as chlorine, bromine, iodine and uorine.
In order to attain the self-extinguishing eects that halogens
have in cables, ATH based materials are used instead.
This way the negative eects of halogens are avoided
(corrosivity, toxicity etc.)

APPROVALS
All above mentioned test are part of the IEC test procedures for
marine cables. As a conrmation of the successfully passed test
our products have type approval certicates from the following
classication societies:

Bunched cables being tested


for re retardance .

ABS
BV
DNV
GL
LRS
RINA
RMRS

American Bureau of Shipping


Bureau Vritas
Det Norske Veritas
Germanischer Lloyd
Lloyds Register of Shipping
Registro Italiano Navale
Russian Marine Register of Shipping

Vertical flame propagation test

30025

Cable sample

IEC 60332-1
50
120025
60025

55025

475

540

Support arm and copper


wire wrapping

50

Figure 1.

Max. length of downward


limit of charred surface

1 kW burner, 45 angle ame/sample

Vertical flame spread of bunched cables

IEC 60332-3-22 cat.A


Round Steel Rungs

1000100

Spacing
Distance

Smoke Outlet
(30030) x (1000100)

150
Metal Wire Ties
4000100
Centre Line of Burner
Air Inlet
(80020) x (40010)

6005

5005
4005

Floor

2000100

Maximum Width

Rig raised above ground level

Figure 2.

Fire resistance test

IEC 60331-21

Clamp

Cable Sample
Support Arm

7010

Figure 3.

Temperature 750C
Flow Rates (1 bar, 20C):
Air 805 Propane 50,25

45

Unarmoured Power and Control Cable

LM-HF 0,6/1 (1,2) kV


(TEMA)

DESIGN
Conductor

Insulation
Sheath

STANDARDS
Annealed stranded plain copper
- round 1,5 to 16 mm2
- round compacted 25 to 300 mm2
- sector shaped in 3-4 cores 25 to 300 mm2

Construction

IEC 60092-353 and IEC 60092-350

Materials

IEC 60228 Class 2 (conductor), IEC 60092-351


(insulation) and -359 (sheath)

Flame Retardance

IEC 60332-3-22 (cat A) and IEC 60332-1

Extruded XLPE
- See page 25 for core identification colours

Halogen Free Properties

IEC 60754-1 and -2

Low Smoke Emission

IEC 61034-1 and -2

Extruded black halogen free polyolefine, SHF1

Tests

IEC 60092-353

Choice and Installation

IEC 60092-352

Installation information and electrical data on pages 24-27.

Size
(n x mm2)
POWER CABLES
1x16
1x25
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
2x1,5
2x2,5
2x4

Conductor
Diameter
approx.
(mm)

Insulation
Thickness
nominal
(mm)

Diameter
approx.
(mm)

Cable
Weight
approx.
(kg/km)

Bending
Radius
min.
(mm)

5,0
5,8
6,8
7,9
9,6
11,3
12,7
14,1
15,7
18,1
20,2
1,6
2,0
2,6

0,7
0,9
0,9
1,0
1,1
1,1
1,2
1,4
1,6
1,7
1,8
0,7
0,7
0,7

8,8
10,2
11,2
12,7
14,8
16,5
18,3
20,4
22,4
25,2
28,3
8,4
9,5
10,4

200
290
385
510
720
970
1210
1490
1840
2390
2990
80
110
150

40
45
45
55
60
70
75
85
90
155
170
35
40
45

Conductor
Size

Diameter/Height
approx.
(n x mm2)
(mm)
3x1
1,3
3x1,5
1,6
3x2,5
2,0
3x4
2,6
3x6
3,1
3x10
4,0
3x16
5,0
3x25
4,8
3x35
5,6
3x50
6,5
3x70
7,9
3x95
9,3
3x120
10,5
3x150
11,6
4x1,5
1,6
4x2,5
2,0
4x4
2,6
4x6
3,1
4x10
4,0
4x16
5,0
4x25
5,8
4x35
6,2
4x50
7,2
4x70
8,6
4x95
10,2
4x120
11,5
5G1,5
1,6
5G2,5
2,0
5G4
2,6
5G6
3,1
5G10
4,0
5G16
5,0
5G25
5,8
CONTROL CABLES
5x1,5
1,6
7x1,5
1,6
12x1,5
1,6
19x1,5
1,6
27x1,5
1,6
37x1,5
1,6
5x2,5
2,0
7x2,5
2,0
12x2,5
2,0
19x2,5
2,0
27x2,5
2,0
37x2,5
2,0

Insulation

Cable

Bending

Width
approx.
(mm)

7,8
9,2
10,7
12,8
15,1
17,0
18,9

8,6
9,9
12,0
14,1
15,8

Thickness
nominal
(mm)
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,9
0,9
1,0
1,1
1,1
1,2
1,4
0,7
0,7
0,7
0,7
0,7
0,7
0,9
0,9
1,0
1,1
1,1
1,2
0,7
0,7
0,7
0,7
0,7
0,7
0,9

Diameter
approx.
(mm)
8,5
8,9
10,1
11,1
12,4
14,4
16,8
17,8
19,9
22,9
26,4
29,8
33,2
36,7
9,9
11,0
12,3
13,6
16,0
18,6
21,7
22,6
26,1
30,0
33,9
37,5
10,8
12,0
13,4
15,0
17,5
20,5
24,1

Weight
approx.
(kg/km)
97
100
140
210
280
420
620
860
1150
1540
2150
2910
3660
4500
130
175
265
350
540
800
1180
1510
2020
2830
3860
4820
155
215
325
435
660
980
1460

Radius
min.
(mm)
35
40
45
45
50
60
70
145
160
185
215
240
270
295
40
45
50
55
65
75
90
185
210
245
275
305
45
50
55
65
75
85
100

0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7

10,5
12,7
15,3
18,1
21,8
24,5
11,7
14,2
17,2
20,3
24,8
27,9

155
215
325
480
670
890
215
305
460
690
980
1300

85
105
125
145
175
200
95
115
140
165
200
225

Armoured Power and Control Cable

LSM-HF 0,6/1 (1,2) kV


(TEMA-A)

DESIGN
Conductor

STANDARDS
Annealed stranded plain copper
- round 1,5 to 16 mm2
- round compacted 25 to 300 mm2
- sector shaped in 3-4 cores 25 to 300 mm2
Extruded XLPE
- See page 25 for core identification colours

Construction

IEC 60092-353 and IEC 60092-350

Materials

IEC 60228 Class 2 (conductor), IEC 60092-351


(insulation) and -359 (sheath)

Flame Retardance

IEC 60332-3-22 (cat A) and IEC 60332-1

Halogen Free Properties

IEC 60754-1 and -2

Armour

Braid of copper wires designed to act as collective screen

Low Smoke Emission

IEC 61034-1 and -2

Sheath

Extruded black halogen free polyolefine, SHF1

Tests

IEC 60092-353

Choice and Installation

IEC 60092-352

Insulation

Installation information and electrical data on pages 24-27.

Size
(n x mm2)
POWER CABLES
1x16
1x25
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
2x1,5
2x2,5
2x4

Conductor
Diameter/Height
approx.
(mm)

Insulation
Thickness
nominal
(mm)

Diameter
over Braid
approx.
(mm)

Diameter
approx.
(mm)

Cable

5,0
5,8
6,8
7,9
9,6
11,3
12,7
14,1
15,7
18,1
20,2
1,6
2,0
2,6

0,7
0,9
0,9
1,0
1,1
1,1
1,2
1,4
1,6
1,7
1,8
0,7
0,7
0,7

8,1
9,4
10,3
12,0
14,0
15,7
17,5
19,4
21,4
24,0
26,3
7,7
8,6
9,7

10,7
12,2
13,1
15,0
17,2
18,9
21,0
23,0
25,0
27,8
30,4
10,1
10,9
12,2

Weight
approx.
(kg/km)
270
375
470
640
870
1130
1400
1690
2070
2630
3240
135
165
225

Bending
Radius
min.
(mm)
65
75
80
95
105
115
130
140
155
170
185
65
70
75

Conductor
Size

Diameter

Cable

Bending

Diameter/Height

Width

Thickness

over Braid

Diameter

Weight

Radius

approx.

approx.

nominal

approx.

approx.

approx.

min.

(mm)
1,3
1,6
2,0
2,6
3,1
4,0
5,0
4,8
5,6
6,5
7,9
9,3
10,5
11,6
1,6
2,0
2,6
3,1
4,0
5,0
5,8
6,2
7,2
8,6
10,2
11,5
1,6
2,0
2,6
3,1
4,0
5,0
5,8

(mm)

7,8
9,2
10,7
12,8
15,1
17,0
18,9

8,6
9,9
12,0
14,1
15,8

(mm)
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,9
0,9
1,0
1,1
1,1
1,2
1,4
0,7
0,7
0,7
0,7
0,7
0,7
0,9
0,9
1,0
1,1
1,1
1,2
0,7
0,7
0,7
0,7
0,7
0,7
0,9

(mm)
7,8
8,1
9,0
10,3
11,4
13,8
16,1
16,6
18,5
21,0
24,3
27,8
31,2
34,5
8,8
10,0
11,3
13,0
15,4
17,9
20,6
21,0
24,1
28,0
31,9
35,3
9,8
10,9
12,9
14,2
17,0
19,8
23,0

(mm)
10,0
10,5
11,4
12,9
13,9
16,5
19,0
20,1
22,2
25,1
28,6
32,4
36,1
39,7
11,2
12,5
13,8
15,7
18,4
21,1
23,9
24,8
28,4
32,5
36,9
40,5
12,3
13,5
15,7
17,0
20,0
22,9
26,5

(kg/km)
135
160
200
275
335
530
740
1020
1340
1760
2400
3200
4080
4930
190
250
325
465
670
940
1330
1730
2270
3120
4280
5290
225
290
435
550
800
1140
1630

(mm)
65
65
70
80
85
100
115
165
180
205
230
260
290
320
70
80
85
95
115
130
145
200
230
265
300
325
75
85
95
105
125
140
160

0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7

9,6
12,0
14,7
17,2
20,8
23,3
10,8
13,5
16,5
19,5
23,5
26,4

12,2
14,8
17,6
20,3
24,1
26,8
13,3
16,2
19,5
22,6
27,1
30,2

220
330
455
630
850
1100
285
435
600
870
1180
1540

75
90
110
125
145
165
80
100
120
140
165
185

(n x mm )
3x1
3x1,5
3x2,5
3x4
3x6
3x10
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150
4x1,5
4x2,5
4x4
4x6
4x10
4x16
4x25
4x35
4x50
4x70
4x95
4x120
5G1,5
5G2,5
5G4
5G6
5G10
5G16
5G25
CONTROL CABLES
5x1,5
7x1,5
12x1,5
19x1,5
27x1,5
37x1,5
5x2,5
7x2,5
12x2,5
19x2,5
27x2,5
37x2,5
2

Insulation

1,6
1,6
1,6
1,6
1,6
1,6
2,0
2,0
2,0
2,0
2,0
2,0

Armoured Instrumentation and


Telecommunication Cable
(TEMA-TA)

DESIGN

STANDARDS

Conductor

Stranded annealed plain copper conductor 0,75 mm

Construction

IEC 60092-376 and IEC 60092-350

Insulation

Extruded XLPE
- See page 25 for core identification colours

Materials

IEC 60228 Class 2 (conductor), IEC 60092-351


(insulation) and -359 (sheath)

Armour
(common
screen)

Combined electrical and mechanical protection


Braid of copper wires
- Filling factor > 0.6 (optical coverage min. 84%)
- Drain conductor

Flame Retardance

IEC 60332-3-22 (cat A) and IEC 60332-1

Halogen Free Properties

IEC 60754-1 and -2

Low Smoke Emission

IEC 61034-1 and -2

Extruded orange halogen free polyolefine, SHF1

Tests

IEC 60092-376

Sheath

Size
(n x 2 x 0,75 mm)
1x2x0,75
2x2x0,75 (quad)
4x2x0,75
7x2x0,75
12x2x0,75
19x2x0,75
24x2x0,75
37x2x0,75

Conductor
Diameter
approx.
(mm)
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1

Core
Diameter
approx.
(mm)
2,2
2,2
2,2
2,2
2,2
2,2
2,2
2,2

Screen
Diameter
approx.
(mm)
6,2
7,2
11,5
11,5
17,5
21,4
24,0
29,1

Cable
Diameter
approx.
(mm)
8,4
9,4
14,2
16,0
20,6
24,6
27,7
33,0

Weight
approx.
(kg/km)
95
135
240
325
550
780
960
1340

Bending
Radius
min.
(mm)
50
55
85
95
125
150
165
200

(quad) construction used in two pair cables:

Electrical data (according to IEC 60092-376)


n x 2 x A mm2
n x 2 x 0,75

Characteristic properties (approximate values)

Conductor resistance at
20 C max /km

Insulation resistance
min M/km

26,0

1200

Variable
Working capacitance

single pair
multi pair

Loop inductance

10

Value
60 nF/km
50 nF/km
0, 8 mH/km

Screened Instrumentation and


Telecommunication Cable

LJT-HF 60 V
(TEMA-TO)

DESIGN

STANDARDS

Conductor

Stranded annealed plain copper conductor 0,5 mm

Construction

IEC 60092-375, -376 and IEC 92-3

Insulation

Extruded XLPE
- See page 25 for core identification colours

Materials

IEC 60228 Class 2 (conductor), IEC 60092-351


(insulation) and -359 (sheath)

Common screen Plastic laminated aluminum tape


- Tinned copper drain wire
- 100 % coverage

Flame Retardance

IEC 60332-3-22 (cat A) and IEC 60332-1

Halogen Free Properties

IEC 60754-1 and -2

Low Smoke Emission

IEC 61034-1 and -2

Sheath

Tests

IEC 60092-375

Extruded orange halogen free polyolefine, SHF1

Conductor
Diameter
approx.
(mm)
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9

Size
(n x 2 x 0,5 mm)
1x2x0,5
2x2x0,5 (quad)
4x2x0,5
7x2x0,5
12x2x0,5
19x2x0,5
24x2x0,5
37x2x0,5

Core
Diameter
approx.
(mm)
2,1
2,1
2,1
2,1
2,1
2,1
2,1
2,1

Screen
Diameter
approx.
(mm)
4,6
5,5
9,1
10,6
13,8
17,0
19,2
23,5

Cable
Diameter
approx.
(mm)
6,6
7,5
11,3
13,0
16,6
20,0
22,4
26,9

Weight
approx.
(kg/km)
50
70
125
180
290
420
520
760

Bending
Radius
min.
(mm)
55
60
90
105
135
160
180
215

(quad) construction used in two pair cables:

Electrical data (according to IEC 60092-375)


n x 2 x A mm2
n x 2 x 0,5

Characteristic properties (approximate values)

Conductor resistance at
20 C max /km

Insulation resistance
min M/km

40,4

1200

Variable
Working capacitance

Value
single pair
multi pair

Loop inductance

60 nF/km
45nF/km
0,8 mH/km

11

Individually Screened Instrumentation and


Telecommunication Cable

HFX-ISOSA/Cu 60 and 250 V


(TEMA-TIOA)

DESIGN

STANDARDS

Conductor

Stranded annealed plain copper conductor

Construction

IEC 60092-375, -376 and 92-3

Insulation

Extruded XLPE
- Number identification of black and blue cores

Materials

IEC 60228 Class 2 (conductor), IEC 60092-351


(insulation) and -359 (sheath)

Sreen

Individual and collective screen of plastic


laminated aluminium tape
- tinned copper drain wires

Flame Retardance

IEC 60332-3-22 (cat A) and IEC 60332-1

Halogen Free Properties

IEC 60754-1 and -2

Armour

Braid of plain copper wires

Low Smoke Emission

IEC 61034-1 and -2

Sheath

Extruded orange halogen free polyolefine, SHF1

Tests

IEC 60092-375, -376

Size
(n x 2 x n mm)

Conductor
Resistance
Diameter
max.
approx.
(/km)
(mm)

Insulation
Thickness
nominal
(mm)

Core
Diameter
approx.
(mm)

Diameter
max.
(mm)

Weight
approx.
(kg/km)

Bending
Radius
min.
(mm)

Cable

60 V
2 x 2 x 0,5
4 x 2 x 0,5
7 x 2 x 0,5
10 x 2 x 0,5
14 x 2 x 0,5
19 x 2 x 0,5
24 x 2 x 0,5
30 x 2 x 0,5

40,4
40,4
40,4
40,4
40,4
40,4
40,4
40,4

0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9

0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4

1,9
1,9
1,9
1,9
1,9
1,9
1,9
1,9

12,2
14,4
17,2
21,1
22,9
25,4
28,7
30,5

165
220
355
475
600
760
930
1100

98
115
138
169
183
203
230
244

2 x 2 x 0,75
4 x 2 x 0,75
7 x 2 x 0,75
10 x 2 x 0,75
14 x 2 x 0,75
19 x 2 x 0,75
24 x 2 x 0,75
30 x 2 x 0,75

26,0
26,0
26,0
26,0
26,0
26,0
26,0
26,0

1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1

0,5
0,5
0,5
0,5
0,5
0,5
0,5
0,5

2,2
2,2
2,2
2,2
2,2
2,2
2,2
2,2

13,6
17,0
20,1
24,9
27,1
30,1
34,1
36,2

170
300
420
630
760
1000
1190
1460

109
136
161
199
217
241
273
290

250 V

12

Bus-Cable

PROFIBUS M-02Y(ST)CHX 100V


(TEMA-PROFIBUS)

DESIGN

STANDARDS

Conductor

Bare copper, round stranded R-Cu 58


according to DIN 40500 Part 4, 0,35 mm

Ozone

DIN VDE 0472 Part 805, Test B

Insulation

Polyethylene foam (cellular HDPE)

Fire retandance

DIN VDE 0472 Part 805, Test C


(based on IEC 60332-3)

Multilayered
shield

Laminated aluminium foil, overlapped


Braided screen of tinned copper wires

Corrosivity of
combuction gasses

DIN VDE 0472 Part 813


(corresponds to IEC 60754-2)

Inner Sheath

Halogen-free polymer HM4 acc. to DIN VDE 0207 Part 24

Smoke density

Outer Sheath

SHF1 compound according to IEC 60092-359

Resistance to chemicals:

DIN VDE 0472 Part 816


(corresponds to IEC 61034)
diesel fuel to din 51601
ASTM oil number 2 to DIN 53521
Nato code oils 0-278, BW-TL 9150-0031/2
to VG 95214 Part 4
Hydraulic fluids, NATO code H-515,
BW-TL 9150-0031/2 to VG 95214 Part 4
Solvent cleansing agents, Bw-TL 6850-0017
to 95214 Part4
DE-ionozed water to VG 95214 Part4
DE-ionized waterwith 3,5 % NaCl

Identication Number of cores:


- a core red
- b core green
- 2 dummy cores

Test to VG 95218 Part 2


TRANSMISSION CHARACTERISTICS
Voltage

100 V

Conductor resisitance 1 km loop at 20 C


max. 110 /km
Charasterristic at 3 to 20 MHz
impedance
at 38,4 kHz
at 9,6 kHz

150 15
185 18,5
250 25

Wave
attenuation

max. 45 dB/km
max. 22 dB/km
max. 5 dB/km
max. 3 dB/km

at 16 MHz
at 4 MHz
at 38,4 MHz
at 9,6 MHz

Mutual capacitance at 800 Hz

max. 30 nF/km

Insulation resistance at 20 C
min. 1600 Mkm
Outer seath surface resistance min 10

OTHER PROPERTIES
Ambient temperatures
During operations as bus cable fixed intallation 40 to 80 C
During installation
10 to 50 C
Conductor temperature in operation
max. 80 C
Tensile load during installation

max. 100 N

Bending radius
Single bending
Flexing

(D = overall diameter )
min 10 x D
min 20 x D

Weight

appr. 109 kg/1000 m

13

Unarmoured Fire Resistant Power and Control Cable

LM-FRHF 0.6/1 (1,2) kV


(TEMA-FR)

STANDARDS

DESIGN
Conductor

Insulation

Sheath

Annealed stranded plain copper


- round 1,5 to 16 mm2
- round compacted 25 to 300 mm2
- sector shaped in 3-4 cores 25 to 300 mm2

Construction

IEC 60092-353 and IEC 60092-350

Materials

IEC 60228 Class 2 (conductor), IEC 60092-351


(insulation) and -359 (sheath)

Fire Resistance

IEC 60331

Mica tape with overlap as fire resistant layer


Extruded XLPE
- see page 25 for core identification colours

Flame Retardance

IEC 60332-3-21 (cat A) and IEC 60332-1

Halogen Free Properties

IEC 60754-1 and -2

Low Smoke Emission

IEC 61034-1 and -2

Extruded green halogen free polyolefine, SHF1

Tests

IEC 60092-353

Choice and Installation

IEC 60092-352

Installation information and electrical data on pages 24-27.

Size
(n x mm2)
POWER CABLES
1x16
1x25
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300

14

Conductor
Diameter
approx.
(mm)
5,0
5,8
6,8
7,9
9,6
11,3
12,7
14,1
15,7
18,1
20,2

Insulation
Thickness
nominal
(mm)
0,7
0,9
0,9
1,0
1,1
1,1
1,2
1,4
1,6
1,7
1,8

Cable
Diameter
approx.
(mm)
10,3
11,8
12,8
13,9
16,0
17,7
19,6
21,6
23,8
26,6
28,9

Weight
approx.
(kg/km)
215
310
410
530
740
990
1240
1520
1890
2450
3020

Bending
Radius
min.
(mm)
45
50
55
60
65
75
80
90
100
160
175

Conductor
Size

Diameter/Height
approx.
(n x mm2)
(mm)
2x1,5
1,6
2x2,5
2,0
3x1,5
1,6
3x2,5
2,0
3x4
2,6
3x6
3,1
3x10
4,0
3x16
5,0
3x25
4,8
3x35
5,6
3x50
6,5
3x70
7,9
3x95
9,3
3x120
10,5
3x150
11,6
4x1,5
1,6
4x2,5
2,0
4x4
2,6
4x6
3,1
4x10
4,0
4x16
5,0
4x25
5,8
4x35
6,2
4x50
7,2
4x70
8,6
4x95
10,2
4x120
11,5
CONTROL CABLES
5x1,5
1,6
7x1,5
1,6
12x1,5
1,6
19x1,5
1,6
27x1,5
1,6
37x1,5
1,6
5x2,5
2,0
7x2,5
2,0
12x2,5
2,0
19x2,5
2,0
27x2,5
2,0
37x2,5
2,0

Insulation

Cable

Bending

Width
approx.
(mm)

7,8
9,2
10,7
12,8
15,1
17,0
18,9

8,6
9,9
12,0
14,1
15,8

Thickness
nominal
(mm)
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,9
0,9
1,0
1,1
1,1
1,2
1,4
0,7
0,7
0,7
0,7
0,7
0,7
0,9
0,9
1,0
1,1
1,1
1,2

Diameter
approx.
(mm)
10,0
11,0
10,4
11,5
12,6
13,8
15,9
18,1
19,6
21,7
24,3
27,8
31,4
34,5
38,3
11,4
12,4
13,8
15,0
17,4
20,1
27,2
24,7
27,7
31,9
35,7
39,5

Weight
approx.
(kg/km)
95
125
120
160
235
300
450
650
930
1230
1600
2230
3010
3750
4620
145
195
290
375
570
800
1640
1620
2100
2940
3970
4960

Radius
min.
(mm)
45
45
45
50
55
60
65
75
160
175
195
225
255
280
310
50
50
60
65
70
85
95
200
225
260
290
320

0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7

12,0
14,5
17,7
20,8
25,1
28,1
13,5
16,1
19,8
23,2
28,0
31,5

175
250
370
550
770
1010
245
340
520
770
1090
1440

50
60
75
85
155
170
55
65
80
95
170
190

15

Armoured Fire Resistant Power and Control Cable

LSM-FRHF 0,6/1 (1,2) kV


(TEMA-AFR)

DESIGN
Conductor

STANDARDS
Annealed stranded plain copper
- round 1,5 to 16 mm2
- round compacted 25 to 300 mm2
- sector shaped in 3-4 cores 25 to 300 mm2

Construction

IEC 60092-353 and IEC 60092-350

Materials

IEC 60228 Class 2 (conductor), IEC 60092-351


(insulation) and -359 (sheath)

Fire Resistance

IEC 60331

Flame Retardance

IEC 60332-3-21 (cat A) and IEC 60332-1

Insulation

Mica tape with overlap as fire resistant layer


Extruded XLPE
- See page 25 for core identification colours

Halogen Free Properties

IEC 60754-1 and -2

Armour

Braid of copper wires designed to act as collective screen

Low Smoke Emission

IEC 61034-1 and -2

Sheath

Extruded green halogen free polyolefine, SHF1

Tests

IEC 60092-353

Choice and Installation

IEC 60092-352

Installation information and electrical data on pages 24-27.

Size
(n x mm2)
POWER CABLES
1x16
1x25
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300

16

Conductor
Diameter/Height
approx.
(mm)

Insulation
Thickness
nominal
(mm)

Diameter
over Braid
approx.
(mm)

Diameter
approx.
(mm)

Cable

5,0
5,8
6,8
7,9
9,6
11,3
12,7
14,1
15,7
18,1
20,2

0,7
0,9
0,9
1,0
1,1
1,1
1,2
1,4
1,6
1,7
1,8

8,9
10,3
11,2
12,7
14,6
16,3
17,9
19,8
21,8
24,4
26,7

11,4
13,0
13,9
15,6
17,7
19,4
21,2
23,3
25,3
28,1
30,6

Weight
approx.
(kg/km)
270
380
475
640
870
1140
1400
1700
2070
2650
3250

Bending
Radius
min.
(mm)
70
80
85
95
110
120
130
140
155
170
185

Conductor
Size
(n x mm2)
2x1,5
2x2,5
2x4
3x1,5
3x2,5
3x4
3x6
3x10
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150
4x1,5
4x2,5
4x4
4x6
4x10
4x16
4x25
4x35
4x50
4x70
4x95
4x120
CONTROL CABLES
5x1,5
7x1,5
12x1,5
19x1,5
27x1,5
37x1,5
5x2,5
7x2,5
12x2,5
19x2,5
27x2,5
37x2,5

Diameter/Height
approx.
(mm)
1,6
2,0
2,6
1,6
2,0
2,6
3,1
4,0
5,0
4,8
5,6
6,5
7,9
9,3
10,5
11,6
1,6
2,0
2,6
3,1
4,0
5,0
5,8
6,2
7,2
8,6
10,2
11,5
1,6
1,6
1,6
1,6
1,6
1,6
2,0
2,0
2,0
2,0
2,0
2,0

Width
approx.
(mm)

7,8
9,2
10,7
12,8
15,1
17,0
18,9

8,6
9,9
12,0
14,1
15,8

Insulation

Diameter

Cable

Bending

Thickness
nominal
(mm)
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,9
0,9
1,0
1,1
1,1
1,2
1,4
0,7
0,7
0,7
0,7
0,7
0,7
0,9
0,9
1,0
1,1
1,1
1,2

over Braid
approx.
(mm)
8,4
9,5
10,4
8,9
9,9
11,1
12,9
14,9
17,1
17,9
19,8
22,2
25,4
29,2
32,0
35,4
9,8
10,9
12,9
14,1
16,4
18,9
21,9
22,6
25,4
29,1
33,2
36,6

Diameter
approx.
(mm)
10,8
12,0
13,0
11,2
12,5
13,6
15,6
17,8
20,0
21,6
23,7
26,3
29,8
33,9
37,0
40,8
12,4
13,4
15,7
16,9
19,3
22,0
25,3
26,7
29,8
33,9
38,2
42,0

Weight
approx.
(kg/km)
140
180
240
170
220
280
380
560
770
1100
1420
1810
2450
3360
4120
5030
210
265
380
465
690
960
1380
1830
2340
3210
4360
5390

Radius
min.
(mm)
65
75
80
70
80
85
95
110
125
175
190
215
240
275
300
330
75
85
95
105
120
135
155
215
240
275
310
340

0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7

11,3
14,0
16,4
19,3
23,3
26,2
13,0
15,3
18,3
21,6
26,1
29,3

13,8
16,7
19,4
22,5
26,8
29,9
15,8
18,3
21,5
24,9
29,8
33,3

255
385
500
710
960
1230
375
490
670
950
1300
1680

85
105
120
140
165
180
95
110
130
150
180
200

17

Armoured Fire Resistant Instrumentation and


Telecommunication Cable

LJST-FRHF 150/250 (300) V


(TEMA-TAFR)

DESIGN

STANDARDS

Conductor

Stranded annealed plain copper conductor 0,75 mm

Construction

IEC 60092 -376

Insulation

Mica tape with overlap as fire resistant layer


Extruded XLPE, nominal thickness 0,5 mm
- See page 25 for core identification colours

Materials
Fire Resistance

IEC 60228 Class 2 (conductor), IEC 60092-351


(insulation) and -359 (sheath)
IEC 60331-21

Armour
(common
screen)

Braid of copper wires


- lling factor > 0.6 (optical coverage min. 84%)
- drain conductor

Flame Retardance

IEC 60332-3-22 (cat A) and IEC 60332-1

Halogen Free Properties

IEC 60754-1 and -2

Low Smoke Emission

IEC 61034-1 and -2

Sheath

Extruded green halogen free polyolefine, SHF1

Tests

IEC 60092-376

Conductor
Diameter
approx.
(mm)
1,1
1,1
1,1
1,1
1,1
1,1
1,1
1,1

Size
(n x 2 x 0,5 mm)
1x2x0,75
2x2x0,75 (quad)
4x2x0,75
7x2x0,75
12x2x0,75
19x2x0,75
24x2x0,75
37x2x0,75

Core
Diameter
approx.
(mm)
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6

Screen
Diameter
approx.
(mm)
6,7
8,1
13,0
15,5
19,8
24,2
27,1
33,0

Cable
Diameter
approx.
(mm)
9,1
10,5
15,7
18,4
23,1
27,9
31,0
37,3

Weight
approx.
(kg/km)
105
155
270
420
640
910
1100
1570

Bending
Radius
min.
(mm)
55
65
95
110
140
165
185
225

(quad) construction used in two pair cables:

Electrical data (according to IEC 60092-376)


n x 2 x A mm

n x 2 x 0,75

Characteristic properties (approximate values)

Conductor resistance at
20 C max /km

Insulation resistance
min M/km

26,0

1200

Variable
Working capacitance
Loop inductance

18

Value
single pair

60 nF/km

multi pair

50 nF/km
0, 8 mH/km

Courtesy of Aker Finnyards

Courtesy of Kvaerner
Philad

Courtesy of

elphia Shipyard, Inc.

rds
Aker Finnya

Courtesy of Aker Finnyard


s

Courtesy of Admiralty Shipyards

e-mail: akernnyards@akeryards.com

19

Armoured Medium Voltage Power Cable

LSESM 6/10 (12) kV


(TEMA-A)

DESIGN

STANDARDS

Conductor

Annealed stranded and compressed copper conductor

Construction

IEC 60092-354 and IEC 60092-350

Insulation

Extruded o-white EPR-rubber, nominal thickness 3,4 mm

Materials

IEC 60228 Class 2 (conductor), IEC 60092-351


(insulation) and -359 (sheath)

Inner Covering Extruded halogen free EPDM compound

Flame Retardance

IEC 60332-3-22 (cat A) and IEC 60332-1

Armour

Halogen Free Properties

IEC 60754-1 and -2

Low Smoke Emission

IEC 61034-1 and -2

Metallic Screen Braid of copper wires


Braid of copper wires

Sheath

Extruded red halogen free compound, SHF1

Size
(n x mm2)
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
3x35
3x50
3x70
3x95
3x120

20

Conductor
Diameter
approx.
(mm)
7,3
8,8
10,3
12,1
13,6
15,0
16,8
19,1
21,4
7,3
8,8
10,3
12,1
13,6

Core
Diameter
approx.
(mm)
18,5
19,9
21,1
23,1
24,6
26,9
28,2
31,1
33,8
18,4
19,8
21,0
23,0
24,5

Tests

IEC 60092-354

Choice and Installation

IEC 60092-352

Inner Cover
Thickness
approx.
(mm)
1,2
1,2
1,2
1,2
1,2
1,4
1,4
1,4
1,4
1,6
1,6
1,6
1,8
1,8

Braid
Diameter
approx.
(mm)
22,5
23,9
25,0
27,0
28,6
31,3
32,6
35,8
38,6
44,9
48,0
50,5
55,1
58,5

Cable
Diameter
approx.
(mm)
26,4
27,8
29,2
31,2
33,0
35,9
37,2
40,6
43,6
50,6
54,0
56,8
61,6
65,4

Weight
approx.
(kg/km)
1290
1480
1740
2080
2410
2850
3250
4110
4750
4370
5040
5950
7190
8390

Size

Cross
Section

(n x mm2)

(mm)

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
3x35
3x50
3x70
3x95
3x120

Current
rating at +45 C
ambient
(A)

35
50
70
95
120
150
185
240
300
35
50
70
95
120

145
180
225
275
320
365
415
490
560
102
126
158
193
224

Size

Reactance

(n x mm2)

(/km)

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
3x35
3x50
3x70
3x95
3x120

Conductor Resistance
RDC

Inductance

Capacitance

(/km)

(mH/km)

(H/km)

at +20 C

at +45 C

at +85 C

0,529
0,391
0,270
0,195
0,154
0,126
0,100
0,0762
0,0607
0,529
0,391
0,270
0,195
0,154

0,581
0,429
0,297
0,214
0,169
0,138
0,110
0,084
0,067
0,581
0,429
0,297
0,214
0,169

0,664
0,491
0,339
0,245
0,193
0,158
0,126
0,096
0,076
0,664
0,491
0,339
0,245
0,193

0,457
0,438
0,411
0,392
0,379
0,375
0,360
0,350
0,363
0,385
0,370
0,345
0,331
0,320

0,280
0,320
0,360
0,400
0,440
0,480
0,450
0,580
0,630
0,280
0,320
0,360
0,400
0,440

at 50 Hz
X50

at 60 Hz
X60

DC

0,144
0,138
0,129
0,123
0,119
0,118
0,113
0,110
0,114
0,121
0,116
0,108
0,104
0,101

0,172
0,165
0,155
0,148
0,143
0,142
0,136
0,132
0,137
0,145
0,140
0,130
0,125
0,121

1,328
0,982
0,678
0,490
0,387
0,316
0,251
0,191
0,152
1,328
0,982
0,678
0,490
0,387

Voltage Drop at +85 C


cos=0,8
(mV/Am)
at 50 Hz
1-phase
3-phase
1,235
1,070
0,951
0,823
0,697
0,604
0,539
0,467
0,452
0,392
0,395
0,342
0,337
0,292
0,285
0,247
0,259
0,224
1,208
1,046
0,925
0,801
0,672
0,582
0,516
0,447
0,430
0,372

at 60 Hz
1-phase
1,270
0,984
0,728
0,569
0,481
0,423
0,364
0,311
0,286
1,237
0,953
0,699
0,541
0,454

3-phase
1,099
0,852
0,631
0,493
0,417
0,366
0,315
0,270
0,248
1,071
0,825
0,605
0,469
0,393

21

Armoured Medium Voltage Power Cable

LSESM 12/20 (24) kV


(TEMA-A)

DESIGN

STANDARDS

Conductor

Annealed stranded and compressed copper conductor

Insulation

Extruded o-white EPR-rubber, nominal thickness 5,5 mm

Metallic Screen Braid of copper wires


Inner Covering Extruded halogen free EPDM compound
Armour

Braid of copper wires

Sheath

Extruded red halogen free compound, SHF1

Size
(n x mm2)
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
3x35
3x50
3x70
3x95

22

Conductor
Diameter
approx.
(mm)
7,3
8,8
10,3
12,1
13,6
15,0
16,8
19,1
7,3
8,8
10,3
12,1

Core
Diameter
approx.
(mm)
23,1
24,5
25,9
27,9
29,4
31,5
32,8
35,5
23,0
24,4
25,8
27,8

Construction
Materials
Flame Retardance

IEC 60092-354 and IEC 60092-350


IEC 60228 Class 2 (conductor), IEC 60092-351
(insulation) and -359 (sheath)
IEC 60332-3-22 (cat A) and IEC 60332-1

Halogen Free Properties

IEC 60754-1 and -2

Low Smoke Emission

IEC 61034-1 and -2

Tests

IEC 60092-354

Choice and Installation

IEC 60092-352

Inner Cover
Thickness
approx.
(mm)
1,2
1,2
1,2
1,2
1,2
1,2
1,2
1,2
1,4
1,6
1,6
1,6

Braid
Diameter
approx.
(mm)
27,1
28,5
29,9
32,2
34,2
36,3
37,6
40,2
55,3
58,3
61,3
65,5

Cable
Diameter
approx.
(mm)
31,3
32,9
34,3
36,8
39,0
41,1
42,6
45,5
61,8
65,0
68,4
72,9

Weight
approx.
(kg/km)
1640
1860
2160
2560
3010
3430
3860
4630
5850
6690
7740
9080

Size

Cross
Section

(n x mm2)

(mm)

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
3x35
3x50
3x70
3x95

35
50
70
95
120
150
185
240
35
50
70
95

Size

145
180
225
275
320
365
415
490
102
126
158
193

at 60 Hz
X60
0,185
0,178
0,167
0,160
0,156
0,152
0,146
0,141
0,162
0,155
0,146
0,139

Inductance

Capacitance

(/km)

(mH/km)

(H/km)

at +45 C

at +85 C

0,529
0,391
0,270
0,195
0,154
0,126
0,100
0,0762
0,529
0,391
0,270
0,195

0,581
0,429
0,297
0,214
0,169
0,138
0,110
0,084
0,581
0,429
0,297
0,214

0,664
0,491
0,339
0,245
0,193
0,158
0,126
0,096
0,664
0,491
0,339
0,245

0,492
0,472
0,443
0,425
0,413
0,402
0,387
0,373
0,430
0,412
0,386
0,368

0,200
0,220
0,250
0,280
0,300
0,320
0,300
0,380
0,200
0,220
0,250
0,280

(/km)
at 50 Hz
X50
0,154
0,148
0,139
0,133
0,130
0,126
0,122
0,117
0,135
0,129
0,121
0,116

Conductor Resistance
RDC

at +20 C

Reactance

(n x mm2)

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
3x35
3x50
3x70
3x95

Current
rating at +45 C
ambient
(A)

DC
1,328
0,982
0,678
0,490
0,387
0,316
0,251
0,191
1,328
0,982
0,678
0,490

Voltage Drop at +85 C


cos=0,8
(mV/Am)
at 50 Hz
1-phase
3-phase
1,248
1,081
0,963
0,834
0,709
0,614
0,552
0,478
0,465
0,403
0,405
0,351
0,347
0,300
0,294
0,254
1,225
1,061
0,941
0,815
0,688
0,596
0,531
0,460

at 60 Hz
1-phase
1,285
0,999
0,743
0,584
0,496
0,435
0,376
0,322
1,257
0,972
0,717
0,558

3-phase
1,113
0,865
0,643
0,506
0,430
0,377
0,326
0,279
1,089
0,842
0,621
0,484

23

TECHNICAL INFORMATION
GENERAL
The rated voltage of a cable must not be lower than the nominal
voltage of the circuit in which it is used. The ambient temperature
during operation should be at least 10 C lower than the maximum
conductor temperature allowed to the insulation material.

SPECIAL PRECAUTIONS FOR


SINGLE CORE CABLE A.C. WIRING
Whenever possible, a.c. wiring should be carried out with
multicore cables. When it is necessary to use single core cables,
they should either be unarmoured or armoured with
a non-magnetic material.

RATED VOLTAGE
The rated voltages of cables are expressed as Uo/U(Um) where

When several multi or single core cables are connected


in parallel per phase, they should be of the same type
and equal length.

Uo
U
Um

the rated voltage between the conductor and earth,


or between the conductor and the metal screen for
which the cable is designed.
the rated voltage between the conductors for which
the cable is designed.
the highest system voltage for which the cables
may be used

All cables pertaining to the same phase should be alternated


with those of the other phases to avoid unequal division
of the current. In the case of two cables per phase,
for example, the correct dispositions to conform with
IEC 92-352 (phases 1, 2 and 3) are:

INSTALL ATION TEMPERATURE


The minimum installation temperature for thermoplastic
sheathed cables is 15 C. If, however, the cables are warmed up
prior to installation, they can be installed at lower temperatures.

2 3 3 2 1

or
EARTHING OF BRAIDS
Earthing of braids is to be carried out in accordance with
the regulations of the classication society.
BENDING RADIUS
The minimum bending radii according to IEC 60092-352
in the nal xed assembly:
Insulation

Outer covering
Unarmoured or
unbraided

Metal braid screened or


armoured
Thermoplastic or
thermosetting
Metal wire armoured
with shaped
Metal tape armoured or
copper conductors
metalsheathed

Overall diameter Minimum internal


of cable (D)
radius of bend
25 mm

4D

25 mm

6D

Any

6D

Any

6D

Composite polyester/
metal laminate screened
units or collective tape
screening

Any

8D

Thermoplastic or
thermosetting with
shaped copper
conductors

Any

Any

Medium voltage
cable, Thermosetting with circular
copper conductors

Metal braid screened or


armoured

1 3

3 1

2 3

2 1

SOME OTHER INSTALLATION EX AMPLES OF


SINGLE CORE CABLES (PHASES 1, 2 AND 3)
Four cables per phase

3 1

3 1

2 3

2 1

3 2 1

or

Six cables per phase

3 1

3 1

3 1

or
8D

2 3

2 1

3 2 1

2 3

3 2 1

single core: 13D


Any
multicore: 9D

During installation the recommended radius is 1.5 times


the value given in the table.
Maximun pulling tension P= 50 N x total conductor cross
section mm2 value of the cable.

24

or

Ten cables per phase on the same cable tray

3 1

3 1

3 1

3 1

3 1

Current rating for continuous service.


Conductor temperature max. +85C, ambient max +45C.
According to IEC 60092-352, chapter 6 for 0,6/1 kV cables.
Up to 6 cables bunched together.

Conductor
cross
section

Short time duty and intermittent service load correction factors


(according to IEC 60092-352)

Cores

12

19

27

37

Reduction

1,00

0,85

0,70

0,70

0,58

0,52

0,44

0,37

0,33

0,30

(mm)

(A)

(A)

(A)

(A)

(A)

(A)

(A)

(A)

(A)

(A)

16

14

11

11

1,5

20

17

14

14

12

10

2,5

28

24

20

20

16

15

12

10

38

32

27

27

22

20

17

14

13

48

41

34

34

28

25

21

18

10

67

57

47

47

39

35

29

25

Cable diameter Time constant

Critical duration (rest time


between service periods)

Service time
correction
factor

Intermittent
service correction factor

D (mm)

T (min)

3xT (min)

30
min

60
min

4 min load
+ 6 min rest

2,2

6,5

1,058

1,058

1,083

11

2,8

8,3

1,058

1,058

1,127

16

14

3,4

10

1,058

1,058

1,170

22

20

4,1

12

1,059

1,058

1,208

16

90

77

63

63

53

47

39

34

30

27

4,8

14

1,059

1,058

1,242

25

120

102

84

84

70

63

52

45

40

36

10

5,5

16

1,061

1,058

1,273

35

145

123

102

102

85

76

63

54

48

44

15

9,5

28

1,081

1,059

1,376

50

180

153

126

126

20

14

42

1,126

1,066

1,433

70

225

191

158

158

25

19

57

1,186

1,081

1,468

95

275

234

193

193

30

24

73

1,255

1,105

1,490

120

320

272

224

224

35

30

89

1,328

1,137

1,506

150

365

310

256

256

40

36

107

1,403

1,173

1,518

185

415

353

291

291

45

42

125

1,479

1,212

1,527

240

490

417

343

343

50

48

145

1,554

1,254

1,534

300

560

476

392

392

60

62

185

1,705

1,341

1,544

70

76

228

1,852

1,432

1,551

80

91

273

1,996

1,522

1,556

Ambient temperature correction factors according to IEC 60092-352


Temperature (C)

35

40

45

50

55

60

65

70

75

90

107

320

2,136

1,613

1,559

Correction factor

1,12

1,06

1,00

0,94

0,87

0,79

0,71

0,61

0,50

100

123

368

2,273

1,702

1,562

IDENTIFICATION COLOURS
POWER AND CONTROL CABLE CORES
Cable with earth core
Type

2X

Blue

3X
4X
537X

Cable without earth core


Line

PE

3G

G Y

Blue

Brown

Grey

4G

G Y

Brown

Black

Grey

Grey

5G

G Y

Blue

Brown

Black

Grey

Brown
Brown

Blue

Type

Brown

Black
Black

White insulation with black numbers

737G

Line

White insulation with black numbers + last core green and yellow

INSTRUMENTATION AND TELECOMMUNICATION CABLE CORES


Pair

Core a
White insulation +
black number

Core b
Blue insulation +
black number

1
2
N

1
3
2*N-1

2
4
2*N

25

Cable Type
LM-HF, LSM-HF,
LM-FRHF, LSM-FRHF
(n x mm2)

Cross
Section

Conductor Resistance
R (IEC 60228)

Inductance

(mm2)

(/km)

(mH/km)

at +20 C
0,5 mm loop
0,75 mm loop
1,0 mm loop
1,5 mm loop
2,5 mm loop
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
2 x 1,5
2 x 2,5
3 x 1,5
3 x 2,5
3x4
3x6
3 x 10
3 x 16
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
4 x 1,5
4 x 2,5
4x4
4x6
4 x 10
4 x 16
4 x 25
4 x 35
4 x 50
4 x 70
4 x 95
4 x 120
4 x 150
4 x 185
4 x 240
4 x 300

26

0,5
0,75
1
1,5
2,5
35
50
70
95
120
150
185
240
300
1,5
2,5
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

36,0
24,5
18,1
12,1
7,41
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
12,1
7,41
12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
12,1
7,410
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601

at +45 C

at +85 C

39,537
26,907
19,878
13,289
8,138
0,575
0,425
0,294
0,212
0,168
0,136
0,109
0,083
0,066
13,289
8,138
13,289
8,138
5,063
3,383
2,010
1,263
0,798
0,575
0,425
0,294
0,212
0,168
0,136
0,109
0,083
0,066
13,289
8,138
5,063
3,383
2,010
1,263
0,798
0,575
0,425
0,294
0,212
0,168
0,136
0,109
0,083
0,066

45,196
30,759
22,724
15,191
9,303
0,658
0,486
0,336
0,242
0,192
0,156
0,124
0,095
0,075
15,191
9,303
15,191
9,303
5,788
3,867
2,297
1,444
0,913
0,658
0,486
0,336
0,242
0,192
0,156
0,124
0,095
0,075
15,191
9,303
5,788
3,867
2,297
1,444
0,913
0,658
0,486
0,336
0,242
0,192
0,156
0,124
0,095
0,075

0,773
0,764
0,707
0,673
0,627
0,316
0,315
0,303
0,292
0,284
0,286
0,281
0,276
0,288
0,336
0,313
0,336
0,313
0,293
0,281
0,266
0,254
0,211
0,202
0,200
0,197
0,190
0,189
0,191
0,193
0,190
0,188
0,359
0,336
0,317
0,304
0,289
0,278
0,267
0,258
0,217
0,213
0,206
0,205
0,209
0,209
0,206
0,204

Cable Type
LM-HF, LSM-HF,
LM-FRHF, LSM-FRHF
(n x mm2)

0,5 mm loop
0,75 mm loop
1,0 mm loop
1,5 mm loop
2,5 mm loop
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
2 x 1,5
2 x 2,5
3 x 1,5
3 x 2,5
3x4
3x6
3 x 10
3 x 16
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
4 x 1,5
4 x 2,5
4x4
4x6
4 x 10
4 x 16
4 x 25
4 x 35
4 x 50
4 x 70
4 x 95
4 x 120
4 x 150
4 x 185
4 x 240
4 x 300

Reactance
(/km)
at 50 Hz
X50
0,243
0,240
0,222
0,211
0,197
0,099
0,099
0,095
0,092
0,089
0,090
0,088
0,087
0,090
0,106
0,098
0,106
0,098
0,092
0,088
0,083
0,080
0,066
0,064
0,063
0,062
0,060
0,059
0,060
0,061
0,060
0,059
0,113
0,106
0,099
0,096
0,091
0,087
0,084
0,081
0,068
0,067
0,065
0,064
0,066
0,066
0,065
0,064

at 60 Hz
X60
0,291
0,288
0,267
0,254
0,236
0,119
0,119
0,114
0,110
0,107
0,108
0,106
0,104
0,108
0,127
0,118
0,127
0,118
0,111
0,106
0,100
0,096
0,080
0,076
0,075
0,074
0,072
0,071
0,072
0,073
0,072
0,071
0,136
0,127
0,119
0,115
0,109
0,105
0,101
0,097
0,082
0,080
0,078
0,077
0,079
0,079
0,078
0,077

DC
90,392
61,517
45,447
30,382
18,606
1,316
0,972
0,673
0,485
0,384
0,311
0,249
0,189
0,151
30,382
18,606
30,382
18,606
11,575
7,734
4,595
2,888
1,825
1,316
0,972
0,673
0,485
0,384
0,311
0,249
0,189
0,151
30,382
18,606
11,575
7,734
4,595
2,888
1,825
1,316
0,972
0,673
0,485
0,384
0,311
0,249
0,189
0,151

1-phase
72,605
49,502
36,625
24,559
15,121
1,172
0,896
0,653
0,498
0,415
0,357
0,305
0,255
0,229
24,432
15,003
24,432
15,003
9,371
6,293
3,776
2,406
1,540
1,129
0,853
0,612
0,459
0,379
0,321
0,272
0,223
0,192
24,441
15,011
9,380
6,302
3,785
2,415
1,561
1,150
0,859
0,619
0,465
0,385
0,328
0,278
0,229
0,198

Voltage Drop at +85 C


os=0,8
(mV/Am)
at 50 Hz
3-phase
62,878
42,870
31,718
21,269
13,095
1,015
0,776
0,565
0,431
0,359
0,309
0,264
0,221
0,198
21,159
12,993
21,159
12,993
8,115
5,450
3,270
2,084
1,334
0,978
0,738
0,530
0,398
0,328
0,278
0,235
0,193
0,166
21,167
13,000
8,123
5,457
3,278
2,091
1,352
0,996
0,744
0,536
0,403
0,333
0,284
0,241
0,198
0,171

at 60 Hz
1-phase
72,664
49,559
36,678
24,610
15,168
1,195
0,920
0,675
0,520
0,436
0,379
0,326
0,276
0,251
24,458
15,026
24,458
15,026
9,393
6,314
3,796
2,425
1,556
1,144
0,868
0,627
0,474
0,393
0,335
0,286
0,237
0,206
24,468
15,037
9,403
6,324
3,807
2,436
1,581
1,169
0,875
0,635
0,481
0,400
0,343
0,294
0,245
0,213

3-phase
62,929
42,920
31,764
21,313
13,136
1,035
0,796
0,585
0,450
0,378
0,328
0,282
0,239
0,217
21,181
13,013
21,181
13,013
8,135
5,468
3,288
2,100
1,347
0,991
0,751
0,543
0,410
0,340
0,291
0,248
0,206
0,178
21,190
13,022
8,144
5,477
3,297
2,109
1,369
1,013
0,758
0,550
0,417
0,346
0,297
0,254
0,212
0,184

27

GERMANY
Pirelli Kabel und System GmbH & Co KG
Anwendungstechnik und Export
D-96465 Neustadt bei Coburg, Germany
Tel. +49 9568 93 2902
Fax +49 9568 93 2058
THE NETHERLANDS
Pirelli Cables & Systems N.V.
Schieweng 9 - P.O. Box 495
2600 AL Delft, The Netherlands
Tel. +31 15 260 5260
Fax +31 15 261 3808
SOUTH AMERICA
Pirelli Cabos S.A.
Av. Alexandre de Gusmao 145
09110-900 - Santo - SP, Brazil
Tel. +55 11 49984000
Fax + 55 11 49984811

MARINE CABLES FINLAND


Pirelli Cables & Systems Oy
Kaapelitie 68, Pikkala
P.O. BOX 13, FI-02401 Kirkkonummi, Finland
Tel. +358 10 77551,
Fax +358 9 298 2204

SWEDEN
Pirelli Kablar och System AB
PB 14147, Gustavlundsvgen 141
S-167 14 Bromma, Sweden
Tel. +46 8 260 416
Tel. +46 8 260 417
Fax +46 8 260 413

NORWAY
Pirelli Kabler og Systemer AS
Anolitveien 4
NO-1400 Ski, Norway
Tel. +47 64 915 713
Fax +47 64 915 714

FRANCE
Cble Pirelli s.a.
19, avenue de la Paix - Paron
B.P.712-89107 Sens Cedex, France
Tel. +33 3 8695 5664
Fax +33 3 8695 5698
ITALY
Pirelli Cavi e Sistemi S.p.A.
Via Sarca 222, 20126 Milan, Italy
Tel. +39 02 64421
Fax +39 02 6442303

SPAIN
Pirelli Cables y Sistemas S.A.
Fercable, Avda. Torrelles, 15-23,
Barcelona, Spain
Tel. +34 93 6569050
Fax +34 93 6569051
USA
Pirelli Cables and Systems NA
246 Stoneridge Drive
Columbia SC 29210, USA
Tel. +1 (803) 951-1130
Fax +1 (803) 951-1092

STURMAN OY

www.pirelli.fi
www.ship-technology.com

HEAD OFFICE
Pirelli Cavi e Sistemi S.p.A.
Via Sarca 222,
20126 Milan, Italy
Tel. +39 02 64421
Fax +39 02 6442303

You might also like