Project 1

22.03.2013

Operator Telephone Fax e-Mail

PHILIPS SGP551 T-POT A FG / Luminaire Data Sheet


Luminous emittance 1: See our luminaire catalog for an image of the luminaire.

Luminaire classification according to CIE: 100 CIE flux code: 38 75 97 100 81

Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

Page 1

Project 1
22.03.2013

Operator Telephone Fax e-Mail

PHILIPS SGP551 T-POT M GB / Luminaire Data Sheet


Luminous emittance 1: See our luminaire catalog for an image of the luminaire.

Luminaire classification according to CIE: 100 CIE flux code: 37 71 96 100 82

Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

Page 2

Project 1
22.03.2013

Operator Telephone Fax e-Mail

PHILIPS SGP551 T-POT M GB / Luminaire Data Sheet


Luminous emittance 1: See our luminaire catalog for an image of the luminaire.

Luminaire classification according to CIE: 100 CIE flux code: 37 71 96 100 85

Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

Page 3

Project 1
22.03.2013

Operator Telephone Fax e-Mail

10m Corridor - Local Urban Access (Residential) / Planning data


Street Profile Cycle Lane Carriageway Parking Bay Foot Path (Width: 2.000 m) (Width: 3.650 m, Number of lanes: 1, tarmac: R3, q0: 0.070) (Width: 2.500 m) (Width: 1.850 m)

Maintenance factor: 0.70 Luminaire Arrangements

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, bottom at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 42.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -2.196 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 4

Project 1
22.03.2013

Operator Telephone Fax e-Mail

10m Corridor - Local Urban Access (Residential) / Carriageway / Results overview

Maintenance factor: 0.70 Grid: 14 x 3 Points Accompanying Street Elements: Carriageway. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (1 Pieces): No. 1 Observer Observer 1 Position [m] (-60.000, 1.825, 1.500) Lav [cd/m] 1.17 U0 0.56 Lav [cd/m] 1.17 0.75 U0 0.56 0.40 Ul 0.57 0.50

Scale 1:344

TI [%] 12 30

SR 0.78 0.50

Ul 0.57

TI [%] 12

Page 5

Project 1
22.03.2013

Operator Telephone Fax e-Mail

10m Corridor - Local Urban Access (Residential) / Cycle Lane / Results overview

Maintenance factor: 0.70 Grid: 14 x 3 Points Accompanying Street Elements: Cycle Lane. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 11.73 10.00

Scale 1:344

Emin [lx] 6.17 3.00

Page 6

Project 1
22.03.2013

Operator Telephone Fax e-Mail

10m Corridor - Local Urban Access (Residential) / Foot Path / Results overview

Maintenance factor: 0.70 Grid: 14 x 3 Points Accompanying Street Elements: Foot Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.50 10.00

Scale 1:344

Emin [lx] 3.07 3.00

Page 7

Project 1
22.03.2013

Operator Telephone Fax e-Mail

12m Corridor - Local Urban Access (Residential) / Planning data


Street Profile Shared Use Path Roadway 1 Lay-by 1 Sidewalk 1 Maintenance factor: 0.70 Luminaire Arrangements (Width: 2.500 m) (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070) (Width: 2.200 m) (Width: 1.300 m)

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, top at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 40.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. 0.004 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 8

Project 1
22.03.2013

Operator Telephone Fax e-Mail

12m Corridor - Local Urban Access (Residential) / Valuation Field Roadway 1 /

Results overview

Maintenance factor: 0.70 Grid: 14 x 6 Points Accompanying Street Elements: Roadway 1. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (2 Pieces): No. 1 2 Observer Observer 1 Observer 3 Position [m] (-60.000, 1.500, 1.500) (-60.000, 4.500, 1.500) Lav [cd/m] 1.40 1.29 U0 0.49 0.48

Scale 1:329

(All lighting performance requirements are met.) Lav [cd/m] 1.29 1.25 U0 0.48 0.40 Ul 0.52 0.50 TI [%] 15 20 SR 0.58 0.50

Ul 0.63 0.52

TI [%] 10 15

Page 9

Project 1
22.03.2013

Operator Telephone Fax e-Mail

12m Corridor - Local Urban Access (Residential) / Valuation Field Sidewalk 1 /

Results overview

Maintenance factor: 0.70 Grid: 14 x 3 Points Accompanying Street Elements: Sidewalk 1. Selected Lighting Class: S3 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 8.18 7.50

Scale 1:329

Emin [lx] 5.74 1.50

Page 10

Project 1
22.03.2013

Operator Telephone Fax e-Mail

12m Corridor - Local Urban Access (Residential) / Shared Use Path / Results

overview

Maintenance factor: 0.70 Grid: 14 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 11.03 10.00

Scale 1:329

Emin [lx] 3.38 3.00

Page 11

Project 1
22.03.2013

Operator Telephone Fax e-Mail

16m Corridor - Local Urban Access (Residential) / Planning data


Street Profile Shared Use Path Parking Bay Roadway 1 Parking Bay Shared Use Path Maintenance factor: 0.70 Luminaire Arrangements (Width: 2.500 m) (Width: 2.500 m) (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070) (Width: 2.500 m) (Width: 2.500 m)

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, top at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 58.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -2.196 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 12

Project 1
22.03.2013

Operator Telephone Fax e-Mail

16m Corridor - Local Urban Access (Residential) / Planning data


Luminaire Arrangements

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, bottom at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 58.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -2.196 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 13

Project 1
22.03.2013

Operator Telephone Fax e-Mail

16m Corridor - Local Urban Access (Residential) / Valuation Field Roadway 1 /

Results overview

Maintenance factor: 0.70 Grid: 3 x 3 Points Accompanying Street Elements: Roadway 1. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (2 Pieces): No. 1 2 Observer Observer 1 Observer 3 Position [m] (-60.000, 1.500, 1.500) (-60.000, 4.500, 1.500) Lav [cd/m] 1.41 1.43 U0 0.66 0.69

Scale 1:458

(All lighting performance requirements are met.) Lav [cd/m] 1.41 1.25 U0 0.66 0.40 Ul 0.62 0.50 TI [%] 13 20 SR 0.69 0.50

Ul 0.65 0.62

TI [%] 9 13

Page 14

Project 1
22.03.2013

Operator Telephone Fax e-Mail

16m Corridor - Local Urban Access (Residential) / Shared Use Path / Results

overview

Maintenance factor: 0.70 Grid: 20 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.10 10.00

Scale 1:458

Emin [lx] 3.49 3.00

Page 15

Project 1
22.03.2013

Operator Telephone Fax e-Mail

20m Corridor - Local Urban Access (Residential) / Planning data


Street Profile Shared Use Path Parking Bay Roadway 1 Parking Bay Shared Use Path Maintenance factor: 0.70 Luminaire Arrangements (Width: 4.500 m) (Width: 2.500 m) (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070) (Width: 2.500 m) (Width: 4.500 m)

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, top at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 50.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -2.496 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 16

Project 1
22.03.2013

Operator Telephone Fax e-Mail

20m Corridor - Local Urban Access (Residential) / Planning data


Luminaire Arrangements

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, bottom at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 50.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -2.496 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 17

Project 1
22.03.2013

Operator Telephone Fax e-Mail

20m Corridor - Local Urban Access (Residential) / Valuation Field Roadway 1 /

Results overview

Maintenance factor: 0.70 Grid: 3 x 3 Points Accompanying Street Elements: Roadway 1. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (2 Pieces): No. 1 2 Observer Observer 1 Observer 3 Position [m] (-60.000, 1.500, 1.500) (-60.000, 4.500, 1.500) Lav [cd/m] 1.51 1.53 U0 0.73 0.82

Scale 1:401

(All lighting performance requirements are met.) Lav [cd/m] 1.51 1.25 U0 0.73 0.40 Ul 0.66 0.50 TI [%] 12 20 SR 0.74 0.50

Ul 0.66 0.71

TI [%] 9 12

Page 18

Project 1
22.03.2013

Operator Telephone Fax e-Mail

20m Corridor - Local Urban Access (Residential) / Shared Use Path / Results

overview

Maintenance factor: 0.70 Grid: 17 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.15 10.00

Scale 1:401

Emin [lx] 3.20 3.00

Page 19

Project 1
22.03.2013

Operator Telephone Fax e-Mail

20m Corridor - Local Urban Access (Residential) / Shared Use Path / Results

overview

Maintenance factor: 0.70 Grid: 17 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.13 10.00

Scale 1:401

Emin [lx] 3.24 3.00

Page 20

Project 1
22.03.2013

Operator Telephone Fax e-Mail

20m Corridor - Local Urban Access (Commercial) / Planning data


Street Profile Shared Use Path Buffer Parking Bay Carriageway Parking Bay Buffer Shared Use Path Maintenance factor: 0.70 Luminaire Arrangements (Width: 3.500 m) (Width: 0.700 m) (Width: 2.500 m) (Width: 6.600 m, Number of lanes: 2, tarmac: R3, q0: 0.070) (Width: 2.500 m) (Width: 0.700 m) (Width: 3.500 m)

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, top at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 46.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -2.696 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 21

Project 1
22.03.2013

Operator Telephone Fax e-Mail

20m Corridor - Local Urban Access (Commercial) / Planning data


Luminaire Arrangements

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, bottom at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 46.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -2.696 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 22

Project 1
22.03.2013

Operator Telephone Fax e-Mail

20m Corridor - Local Urban Access (Commercial) / Carriageway / Results overview

Maintenance factor: 0.70 Grid: 3 x 3 Points Accompanying Street Elements: Carriageway. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (2 Pieces): No. 1 2 Observer Observer 1 Observer 3 Position [m] (-60.000, 1.650, 1.500) (-60.000, 4.950, 1.500) Lav [cd/m] 1.50 1.51 U0 0.77 0.83 Lav [cd/m] 1.50 1.25 U0 0.77 0.40 Ul 0.70 0.50

Scale 1:372

TI [%] 12 20

SR 0.75 0.50

Ul 0.70 0.70

TI [%] 9 12

Page 23

Project 1
22.03.2013

Operator Telephone Fax e-Mail

20m Corridor - Local Urban Access (Commercial) / Shared Use Path / Results

overview

Maintenance factor: 0.70 Grid: 16 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.31 10.00

Scale 1:372

Emin [lx] 3.33 3.00

Page 24

Project 1
22.03.2013

Operator Telephone Fax e-Mail

20m Corridor - Local Urban Access (Commercial) / Shared Use Path / Results

overview

Maintenance factor: 0.70 Grid: 16 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.31 10.00

Scale 1:372

Emin [lx] 3.33 3.00

Page 25

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Residential) / Planning

data
Street Profile Shared Use Path Buffer Parking Bay Carriageway Parking Bay Buffer Shared Use Path Maintenance factor: 0.70 Luminaire Arrangements (Width: 4.000 m) (Width: 2.500 m) (Width: 2.500 m) (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070) (Width: 2.500 m) (Width: 2.500 m) (Width: 4.000 m)

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, top at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 38.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -3.796 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 26

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Residential) / Planning

data
Luminaire Arrangements

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, bottom at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 38.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -3.796 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 27

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Residential) / Carriageway / Results overview

Maintenance factor: 0.70 Grid: 3 x 3 Points Accompanying Street Elements: Carriageway. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (2 Pieces): No. 1 2 Observer Observer 1 Observer 3 Position [m] (-60.000, 1.500, 1.500) (-60.000, 4.500, 1.500) Lav [cd/m] 1.52 1.53 U0 0.81 0.81 Lav [cd/m] 1.52 1.25 U0 0.81 0.40 Ul 0.75 0.50

Scale 1:315

TI [%] 10 20

SR 0.95 0.50

Ul 0.75 0.89

TI [%] 9 10

Page 28

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Residential) / Shared Use Path / Results overview

Maintenance factor: 0.70 Grid: 13 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.14 10.00

Scale 1:315

Emin [lx] 3.47 3.00

Page 29

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Residential) / Shared Use Path / Results overview

Maintenance factor: 0.70 Grid: 13 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.11 10.00

Scale 1:315

Emin [lx] 3.44 3.00

Page 30

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Planning

data
Street Profile Footpath Buffer Cycle Track Grass Strip 1 Parking Bay Roadway 1 Parking Bay Grass Strip 2 Cycle Track Buffer Footpath (Width: 2.350 m) (Width: 0.850 m) (Width: 1.500 m) (Width: 1.500 m) (Width: 2.500 m) (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070) (Width: 2.500 m) (Width: 1.500 m) (Width: 1.500 m) (Width: 0.850 m) (Width: 2.350 m)

Maintenance factor: 0.70

Page 31

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Planning

data
Luminaire Arrangements

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, bottom at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 45.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -3.921 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, top at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 45.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -3.921 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 32

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Valuation Field Roadway 1 / Results overview

Maintenance factor: 0.70 Grid: 15 x 6 Points Accompanying Street Elements: Roadway 1. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (2 Pieces): No. 1 2 Observer Observer 1 Observer 4 Position [m] (-60.000, 1.500, 1.500) (-60.000, 4.500, 1.500) Lav [cd/m] 1.26 1.26 U0 0.76 0.78

Scale 1:365

(All lighting performance requirements are met.) Lav [cd/m] 1.26 1.25 U0 0.76 0.40 Ul 0.70 0.50 TI [%] 11 20 SR 0.97 0.50

Ul 0.70 0.70

TI [%] 10 11

Page 33

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Footpath /

Results overview

Maintenance factor: 0.70 Grid: 15 x 3 Points Accompanying Street Elements: Footpath. Selected Lighting Class: S3 Calculated values: Required values according to class: Fulfilled/Not fulfilled:

Scale 1:365

(All lighting performance requirements are met.) Eav [lx] 7.91 7.50 Emin [lx] 2.21 1.50

Page 34

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Footpath /

Results overview

Maintenance factor: 0.70 Grid: 15 x 3 Points Accompanying Street Elements: Footpath. Selected Lighting Class: S3 Calculated values: Required values according to class: Fulfilled/Not fulfilled:

Scale 1:365

(All lighting performance requirements are met.) Eav [lx] 7.90 7.50 Emin [lx] 2.16 1.50

Page 35

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Cycle Track / Results overview

Maintenance factor: 0.70 Grid: 15 x 3 Points Accompanying Street Elements: Cycle Track. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 12.25 10.00

Scale 1:365

Emin [lx] 5.02 3.00

Page 36

Project 1
22.03.2013

Operator Telephone Fax e-Mail

24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Cycle Track / Results overview

Maintenance factor: 0.70 Grid: 15 x 3 Points Accompanying Street Elements: Cycle Track. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 12.23 10.00

Scale 1:365

Emin [lx] 5.04 3.00

Page 37

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Minor Urban Collector (Residential) / Planning data


Street Profile Shared Use Path Buffer Parking Bay & Hard Strip Carriageway Hatched Median Carriageway Parking Bay & Hard Strip Buffer Shared Use Path Maintenance factor: 0.70 (Width: 4.500 m) (Width: 3.500 m) (Width: 3.000 m) (Width: 3.000 m, Number of lanes: 1, tarmac: R3, q0: 0.070) (Width: 4.000 m, Height: 0.000 m) (Width: 3.000 m, Number of lanes: 1, tarmac: R3, q0: 0.070) (Width: 3.000 m) (Width: 3.500 m) (Width: 4.500 m)

Page 38

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Minor Urban Collector (Residential) / Planning data


Luminaire Arrangements

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 27015 lm Maximum luminous intensities 33200 lm at 70: 457 cd/klm 519.0 W at 80: 127 cd/klm Double row, with offset at 90: 3.74 cd/klm Any direction forming the specified angle from the downward vertical, with 53.000 m the luminaire installed for use. 10.000 m 9.955 m Arrangement complies with luminous intensity class -4.996 m G2. 5.0 Arrangement complies with glare index class D.6. 1.000 m

Page 39

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Minor Urban Collector (Residential) / Carriageway / Results overview

Maintenance factor: 0.70 Grid: 18 x 3 Points Accompanying Street Elements: Carriageway. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (1 Pieces): No. 1 Observer Observer 1 Position [m] (-60.000, 1.500, 1.500) Lav [cd/m] 1.38 U0 0.71 Lav [cd/m] 1.38 1.25 U0 0.71 0.40 Ul 0.67 0.50

Scale 1:422

TI [%] 14 20

SR 0.96 0.50

Ul 0.67

TI [%] 14

Page 40

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Minor Urban Collector (Residential) / Shared Use Path / Results

overview

Maintenance factor: 0.70 Grid: 18 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.82 10.00

Scale 1:422

Emin [lx] 3.10 3.00

Page 41

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Minor Urban Collector (Residential) / Shared Use Path / Results

overview

Maintenance factor: 0.70 Grid: 18 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.82 10.00

Scale 1:422

Emin [lx] 3.10 3.00

Page 42

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Minor Urban Collector (Residential) / Carriageway / Results overview

Maintenance factor: 0.70 Grid: 18 x 3 Points Accompanying Street Elements: Carriageway. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (1 Pieces): No. 1 Observer Observer 4 Position [m] (-60.000, 8.500, 1.500) Lav [cd/m] 1.38 U0 0.71 Lav [cd/m] 1.38 1.25 U0 0.71 0.40 Ul 0.67 0.50

Scale 1:422

TI [%] 14 20

SR 0.96 0.50

Ul 0.67

TI [%] 14

Page 43

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Major Urban Collector (Commercial) / Planning data


Street Profile Shared Use Path Buffer Parking Bay & Hard Strip Carriageway Median with hardstrips Carriageway Parking Bay & Hard Strip Buffer Shared Use Path Maintenance factor: 0.70 (Width: 3.500 m) (Width: 1.400 m) (Width: 3.000 m) (Width: 6.600 m, Number of lanes: 2, tarmac: R3, q0: 0.070) (Width: 3.000 m, Height: 0.000 m) (Width: 6.600 m, Number of lanes: 2, tarmac: R3, q0: 0.070) (Width: 3.000 m) (Width: 1.400 m) (Width: 3.500 m)

Page 44

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Major Urban Collector (Commercial) / Planning data


Luminaire Arrangements

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 27015 lm Maximum luminous intensities 33200 lm at 70: 457 cd/klm 519.0 W at 80: 127 cd/klm on Median at 90: 3.74 cd/klm Any direction forming the specified angle from the downward vertical, with the luminaire 44.000 m installed for use. 10.000 m 9.955 m Arrangement complies with luminous intensity class G2. 0.504 m Arrangement complies with glare index class D.6. 5.0 2.000 m

Page 45

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Major Urban Collector (Commercial) / Carriageway / Results

overview

Maintenance factor: 0.70 Grid: 15 x 6 Points Accompanying Street Elements: Carriageway. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (2 Pieces): No. 1 2 Observer Observer 1 Position [m] (-60.000, 1.650, 1.500) (-60.000, 4.950, 1.500) Lav [cd/m] 2.28 2.09 U0 0.59 0.57 Lav [cd/m] 2.09 2.00 U0 0.57 0.40 Ul 0.70 0.70

Scale 1:358

TI [%] 13 20

SR 0.80 0.50

Ul 0.70 0.73

TI [%] 11 13

Page 46

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Major Urban Collector (Commercial) / Shared Use Path / Results

overview

Maintenance factor: 0.70 Grid: 15 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.56 10.00

Scale 1:358

Emin [lx] 6.37 3.00

Page 47

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Major Urban Collector (Commercial) / Shared Use Path / Results

overview

Maintenance factor: 0.70 Grid: 15 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 10.56 10.00

Scale 1:358

Emin [lx] 6.37 3.00

Page 48

Project 1
22.03.2013

Operator Telephone Fax e-Mail

32m Corridor - Major Urban Collector (Commercial) / Carriageway / Results

overview

Maintenance factor: 0.70 Grid: 15 x 6 Points Accompanying Street Elements: Carriageway. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (2 Pieces): No. 1 2 Observer Observer 4 Position [m] (-60.000, 11.250, 1.500) (-60.000, 14.550, 1.500) Lav [cd/m] 2.09 2.28 U0 0.57 0.59 Lav [cd/m] 2.09 2.00 U0 0.57 0.40 Ul 0.70 0.70

Scale 1:358

TI [%] 13 20

SR 0.80 0.50

Ul 0.73 0.70

TI [%] 13 11

Page 49

Project 1
22.03.2013

Operator Telephone Fax e-Mail

64m Corridor - Major Urban Arterial(Carriageway) / Planning data


Street Profile Median with Hard Strip Carriageway Landscape with hardstrip Cycle Track Buffer Service Road Parking Bay Buffer Footway Maintenance factor: 0.70 (Width: 8.000 m) (Width: 10.950 m, Number of lanes: 3, tarmac: R3, q0: 0.070) (Width: 2.500 m) (Width: 2.000 m) (Width: 1.550 m) (Width: 4.000 m) (Width: 2.500 m) (Width: 1.500 m) (Width: 3.000 m)

Page 50

Project 1
22.03.2013

Operator Telephone Fax e-Mail

64m Corridor - Major Urban Arterial(Carriageway) / Planning data


Luminaire Arrangements

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT A FG 45526 lm Maximum luminous intensities at 70: 286 cd/klm 56500 lm 831.0 W at 80: 54 cd/klm Single row, top at 90: 1.14 cd/klm Any direction forming the specified angle from the downward vertical, with the 40.000 m luminaire installed for use. 12.000 m 12.000 m Arrangement complies with luminous intensity class G3. -1.496 m Arrangement complies with glare index class D.6. 5.0 2.500 m

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, bottom at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 40.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -15.846 m Arrangement complies with glare index class D.6. 5.0 1.000 m
Page 51

Project 1
22.03.2013

Operator Telephone Fax e-Mail

64m Corridor - Major Urban Arterial(Carriageway) / Footway / Results overview

Maintenance factor: 0.70 Grid: 14 x 3 Points Accompanying Street Elements: Footway. Selected Lighting Class: S1 Calculated values: Required values according to class: Fulfilled/Not fulfilled:

Scale 1:334

(All lighting performance requirements are met.) Eav [lx] 17.09 15.00 Emin [lx] 6.80 5.00

Page 52

Project 1
22.03.2013

Operator Telephone Fax e-Mail

64m Corridor - Major Urban Arterial(Carriageway) / Cycle Track / Results overview

Maintenance factor: 0.70 Grid: 14 x 3 Points Accompanying Street Elements: Cycle Track. Selected Lighting Class: S1 Additional EV Lighting Class: EV5 Calculated values: Required values according to class: Fulfilled/Not fulfilled:

Scale 1:334

(All lighting performance requirements are met.) (Not all lighting performance requirements are met.) Eav [lx] 17.54 15.00 Emin [lx] 14.87 5.00 Emin (vertical) [lx] 5.85 5.00

Page 53

Project 1
22.03.2013

Operator Telephone Fax e-Mail

64m Corridor - Major Urban Arterial(Carriageway) / Carriageway / Results overview

Maintenance factor: 0.70 Grid: 14 x 9 Points Accompanying Street Elements: Carriageway. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (3 Pieces): No. 1 2 3 Observer Observer 1 Observer 2 Position [m] (-60.000, 1.825, 1.500) (-60.000, 5.475, 1.500) (-60.000, 9.125, 1.500) Lav [cd/m] 2.57 2.39 2.20 U0 0.43 0.45 0.48 Lav [cd/m] 2.20 2.00 U0 0.43 0.40 Ul 0.85 0.70

Scale 1:334

TI [%] 10 20

SR 0.78 0.50

Ul 0.91 0.87 0.85

TI [%] 5 8 10

Page 54

Project 1
22.03.2013

Operator Telephone Fax e-Mail

64m Corridor - Major Urban Arterial(Service Road) / Planning data


Street Profile Median with Hard Strip Carriageway Landscape with hardstrip Cycle Track Buffer Service Road Parking Bay Buffer Footway Maintenance factor: 0.70 (Width: 8.000 m) (Width: 10.950 m) (Width: 2.500 m) (Width: 2.000 m) (Width: 1.550 m) (Width: 4.000 m, Number of lanes: 1, tarmac: R3, q0: 0.070) (Width: 2.500 m) (Width: 1.500 m) (Width: 3.000 m)

Page 55

Project 1
22.03.2013

Operator Telephone Fax e-Mail

64m Corridor - Major Urban Arterial(Service Road) / Planning data


Luminaire Arrangements

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT A FG 45526 lm Maximum luminous intensities at 70: 286 cd/klm 56500 lm 831.0 W at 80: 54 cd/klm Single row, top at 90: 1.14 cd/klm Any direction forming the specified angle from the downward vertical, with the 40.000 m luminaire installed for use. 12.000 m 12.000 m Arrangement complies with luminous intensity class G3. -18.500 m Arrangement complies with glare index class D.6. 5.0 2.500 m

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, bottom at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 40.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -5.796 m Arrangement complies with glare index class D.6. 5.0 1.000 m
Page 56

Project 1
22.03.2013

Operator Telephone Fax e-Mail

64m Corridor - Major Urban Arterial(Service Road) / Valuation Field Service Road /

Results overview

Maintenance factor: 0.70 Grid: 14 x 3 Points Accompanying Street Elements: Service Road. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (1 Pieces): No. 1 Observer Observer 3 Position [m] (-60.000, 2.000, 1.500) Lav [cd/m] 0.86 U0 0.81 Lav [cd/m] 0.86 0.75 U0 0.81 0.40 Ul 0.74 0.50

Scale 1:334

TI [%] 9 30

SR 1.14 0.50

Ul 0.74

TI [%] 9

Page 57

Project 1
22.03.2013

Operator Telephone Fax e-Mail

40m Corridor - Major Urban Collector (Residential & Commercial) / Planning data
Street Profile Median and hardstrip Carriageway Median 1 Service Road Parking Bay Shared Use Path Maintenance factor: 0.70 Luminaire Arrangements (Width: 4.000 m) (Width: 7.300 m, Number of lanes: 2, tarmac: R3, q0: 0.070) (Width: 1.500 m, Height: 0.000 m) (Width: 3.500 m, Number of lanes: 1, tarmac: R3, q0: 0.070) (Width: 2.500 m) (Width: 3.500 m)

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT A FG 45526 lm Maximum luminous intensities 56500 lm at 70: 286 cd/klm 831.0 W at 80: 54 cd/klm Single row, top at 90: 1.14 cd/klm Any direction forming the specified angle from the downward vertical, with the 49.000 m luminaire installed for use. 12.000 m 12.000 m Arrangement complies with luminous intensity class G3. 0.500 m Arrangement complies with glare index class D.6. 5.0 2.500 m

Page 58

Project 1
22.03.2013

Operator Telephone Fax e-Mail

40m Corridor - Major Urban Collector (Residential & Commercial) / Shared Use Path /

Results overview

Maintenance factor: 0.70 Grid: 17 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 11.20 10.00

Scale 1:394

Emin [lx] 7.48 3.00

Page 59

Project 1
22.03.2013

Operator Telephone Fax e-Mail

40m Corridor - Major Urban Collector (Residential & Commercial) / Service Road /

Results overview

Maintenance factor: 0.70 Grid: 17 x 3 Points Accompanying Street Elements: Service Road. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (1 Pieces): No. 1 Observer Observer 1 Position [m] (-60.000, 1.750, 1.500) Lav [cd/m] 1.20 U0 0.76 Lav [cd/m] 1.20 0.75 U0 0.76 0.40 Ul 0.84 0.50

Scale 1:394

TI [%] 9 30

SR 1.01 0.50

Ul 0.84

TI [%] 9

Page 60

Project 1
22.03.2013

Operator Telephone Fax e-Mail

40m Corridor - Major Urban Collector (Residential & Commercial) / Carriageway /

Results overview

Maintenance factor: 0.70 Grid: 17 x 6 Points Accompanying Street Elements: Carriageway. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (2 Pieces): No. 1 2 Observer Observer 3 Observer 4 Position [m] (-60.000, 6.825, 1.500) (-60.000, 10.475, 1.500) Lav [cd/m] 2.61 2.42 U0 0.60 0.60 Lav [cd/m] 2.42 2.00 U0 0.60 0.40 Ul 0.70 0.70

Scale 1:394

TI [%] 10 20

SR 0.84 0.50

Ul 0.70 0.70

TI [%] 8 10

Page 61

Project 1
22.03.2013

Operator Telephone Fax e-Mail

50m Corridor - Major Urban Collector (Residential) / Planning data


Street Profile Median and hardstrip Carriageway Median 1 Service Road Parking Bay Shared Use Path Maintenance factor: 0.70 Luminaire Arrangements (Width: 8.000 m) (Width: 7.300 m, Number of lanes: 2, tarmac: R3, q0: 0.070) (Width: 4.150 m, Height: 0.000 m) (Width: 3.400 m, Number of lanes: 1, tarmac: R3, q0: 0.070) (Width: 2.500 m) (Width: 3.650 m)

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT A FG 45526 lm Maximum luminous intensities 56500 lm at 70: 286 cd/klm 831.0 W at 80: 54 cd/klm Single row, top at 90: 1.14 cd/klm Any direction forming the specified angle from the downward vertical, with the 48.000 m luminaire installed for use. 12.000 m 12.000 m Arrangement complies with luminous intensity class G3. -1.500 m Arrangement complies with glare index class D.6. 5.0 2.500 m

Page 62

Project 1
22.03.2013

Operator Telephone Fax e-Mail

50m Corridor - Major Urban Collector (Residential) / Planning data


Luminaire Arrangements

Luminaire: Luminous flux (Luminaire): Luminous flux (Lamps): Luminaire Wattage: Arrangement: Pole Distance: Mounting Height (1): Height: Overhang (2): Boom Angle (3): Boom Length (4):

PHILIPS SGP551 T-POT M GB 14787 lm Maximum luminous intensities 17500 lm at 70: 453 cd/klm 319.0 W at 80: 115 cd/klm Single row, bottom at 90: 3.00 cd/klm Any direction forming the specified angle from the downward vertical, with the 48.000 m luminaire installed for use. 8.000 m 7.955 m Arrangement complies with luminous intensity class G2. -2.196 m Arrangement complies with glare index class D.6. 5.0 1.000 m

Page 63

Project 1
22.03.2013

Operator Telephone Fax e-Mail

50m Corridor - Major Urban Collector (Residential) / Shared Use Path / Results

overview

Maintenance factor: 0.70 Grid: 16 x 3 Points Accompanying Street Elements: Shared Use Path. Selected Lighting Class: S2 (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Eav [lx] 13.54 10.00

Scale 1:387

Emin [lx] 5.92 3.00

Page 64

Project 1
22.03.2013

Operator Telephone Fax e-Mail

50m Corridor - Major Urban Collector (Residential) / Service Road / Results

overview

Maintenance factor: 0.70 Grid: 16 x 3 Points Accompanying Street Elements: Service Road. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (1 Pieces): No. 1 Observer Observer 1 Position [m] (-60.000, 1.700, 1.500) Lav [cd/m] 1.69 U0 0.75 Lav [cd/m] 1.69 0.75 U0 0.75 0.40 Ul 0.59 0.50

Scale 1:387

TI [%] 11 30

SR 0.91 0.50

Ul 0.59

TI [%] 11

Page 65

Project 1
22.03.2013

Operator Telephone Fax e-Mail

50m Corridor - Major Urban Collector (Residential) / Service Road / Observer 1 /

Isolines (L)

Values in Candela/m, Scale 1 : 387 Grid: 16 x 3 Points Observer Position: (-60.000 m, 1.700 m, 1.500 m) tarmac: R3, q0: 0.070 Calculated values: Required values according to class ME4a: Fulfilled/Not fulfilled: Lav [cd/m] 1.69 0.75 U0 0.75 0.40 Ul 0.59 0.50 TI [%] 11 30

Page 66

Project 1
22.03.2013

Operator Telephone Fax e-Mail

50m Corridor - Major Urban Collector (Residential) / Carriageway / Results overview

Maintenance factor: 0.70 Grid: 16 x 6 Points Accompanying Street Elements: Carriageway. tarmac: R3, q0: 0.070 Selected Lighting Class: ME4a (All lighting performance requirements are met.) Calculated values: Required values according to class: Fulfilled/Not fulfilled: Assigned Observer (2 Pieces): No. 1 2 Observer Observer 3 Observer 4 Position [m] (-60.000, 9.375, 1.500) (-60.000, 13.025, 1.500) Lav [cd/m] 2.52 2.32 U0 0.62 0.64 Lav [cd/m] 2.32 2.00 U0 0.62 0.40 Ul 0.70 0.70

Scale 1:387

TI [%] 10 20

SR 0.86 0.50

Ul 0.76 0.70

TI [%] 7 10

Page 67