22-1782-01

Product Data
4TCC3018A through 4TCC3060A
Single Package Convertible Cooling
13 SEER
1 - 5 Ton
R-410A

Mar. 03, 2006


2006 American Standard inc. All Rights Reserved

Pub. No. 22-1782-01

It's Hard to Stop a Trane.


Single Package Cooling System
Trane offers a complete family of cooling systems, designed to give you the
unbeatable combination of energy efficiency and lower operating costs.

Introducing the new TRANE Single Package Cooling System.


Single Package Cooling Systems are
easy and versatile to install. Because
cooling and air handlingfunctions are all
contained in a single cabinet, a Trane
package air conditioner is easy to install
and service. It can be flush mounted
beside your home at ground level or
placed on the roof for horizontal or
downflow installation. When connected to
an optional Trane thermostat control and
air distribution ducts, you have a highly
efficient, total home comfort system.

Single Package Cooling Systems


provide better performance. Our
single package air conditioners offer
cooling efficiencies that are unmatched
in the industry and provide you with a
product far superior in performance than
the competition.

Contents

Optional Equipment Listing

General Data

Heater Data

SPEK Data

Performance Cooling Data

10

Typical Wiring

13

Optional Equipment

16

Dimensional Data

21

Mechanical Specifications

25

Optional Equipment Listing


] indicates accessories included)
OPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [
Roof Curb Full Perimeter (4TCC3018-36A) 3 ................................................................... BAYCURB050A[
Roof Curb Full Perimeter (4TCC3042-60A) 3 ................................................................... BAYCURB051A[
Roof Curb Utility Extension Kit (BAYCURB050A) ................................................................. BAYUTIL101A[
Roof Curb Utility Extension Kit (BAYCURB051A) ................................................................. BAYUTIL102A[
0-25% Manual Fresh Air Damper (4TCC3018-36A) 1. ...................................................... BAYOSAH001A[
0-25% Manual Fresh Air Damper (4TCC3042-60A) 1. ...................................................... BAYOSAH002A[
Motorized Fresh Air Damper (4TCC3018-36A) 1. ............................................................ BAYDMPR101A[
Motorized Fresh Air Damper (4TCC3042-60A) 1. ............................................................. BAYDMPR102A[
16" Round Duct Adapter (2 per box) (4TCC3018-36A) 6 ................................................. BAYSQRD001A[
18" Round Duct Adapter (2 per box) (4TCC3018-60A) 6 ................................................. BAYSQRD002A[
0-100% Mod Economizer w/Baro. Relief (4TCC3018-36A) 124 .................................... BAYECON101B[
0-100% Mod. Economizer w/Baro. Relief (4TCC042-60A) 124. .................................... BAYECON102B[
0-100% Horizontal Economizer (4TCC3018-36A) 12 . .................................................... BAYECON200A[
0-100% Horizontal Economizer (4TCC3042-60A) 12 . .................................................... BAYECON201A[
Enthalpy Control for Economizer (solid state). .................................................................... BAYENTH001A[
Remote Potentiometer (All-BAYECON***A) ............................................................................ BAYSTAT023[
1"-2" Filter Frame (4TCC3018-36A) (20 x 20 filter not included) 1. .................................... BAYFLTR101A[
1"-2" Filter Frame (4TCC3042-60A) (20 x 20,20X18 filter not included) 1. ........................ BAYFLTR201A[
Evaporator Defrost Control (Low Ambient Cooling) Kit 5. ................................................. BAYLOAM011A[
Head Pressure Control (Low Ambient Cool) (208/240v) Kit 5. ......................................... BAYLOAM105A[
Quick Start Kit (4TCC3-A1) .................................................................................................. BAYKSKT301A[
Crankcase Heater Recip (4TCC3018A1)(230v) 5. ............................................................. BAYCCHT003A[
Crankcase Heater Scroll(4TCC3036,48,60A1/3)(230v) 5. ................................................. BAYCCHT202A[
Crankcase Heater (4TCC3036,48,60A4)(460v) 5. ............................................................. BAYCCHT203A[
Adapter Curb 4TCC3018-036A to BAYCURB030,38 ........................................................ BAYADAP050A[
Adapter Curb 4TCC3018-036A to BAYCURB033 ............................................................. BAYADAP051A[
Adapter Curb 4TCC3042-060A to BAYCURB030,38 ........................................................ BAYADAP052A[
Adapter Curb 4TCC3042-060A to BAYCURB033 ............................................................. BAYADAP053A[
Adapter Curb 4TCC3042-060A to BAYCURB034 ............................................................. BAYADAP054A[
12" Duct Shroud Covers Horizontal 4TCC3018-060A7. ................................................... BAYCOVR112A[
18" Duct Shroud Covers Horizontal 4TCC3018-060A 7. .................................................. BAYCOVR118A[
Extreme Condition Mounting Kit - All BAYCURB & BAYADAP ......................................... BAYEXMK001A[
Extreme Condition Mounting Kit - All BAYUTIL .................................................................. BAYEXMK002A[
Extreme Condition Mounting Kit - All Slab Mounts ............................................................. BAYEXMK003A[
Lifting Lug Kit .......................................................................................................................... BAYLlFT002B[
SUPPLEMENTARY HEATERS (1 PHASE)
3.76/5.0 KW Heater (208/240V 1PH) (4TCC3018-060A1) ................................................. BAYHTRV105A[
7.50/10.0 KW Heater (208/240V 1PH) (4TCC3024-060A1) ............................................... BAYHTRV110A[
11.27/15.00 KW Heater (208/240V 1PH) (4TCC3030-060A1) ........................................... BAYHTRV115A[
15.0/20.0 KW Heater (208/240V 1PH) (4TCC3048-060A1) ............................................... BAYHTRV120A[
SUPPLEMENTARY HEATERS (3 PHASE)
3.76/5.0 KW Heater (208/240V 3PH) (4TCC3018-060A3) ................................................. BAYHTRV305A[
7.50/10.0 KW Heater (208/240V 3PH) (4TCC3024-060A3) ............................................... BAYHTRV310A[
11.27/15.00 KW Heater (208/240V 3PH) (4TCC3030-060A3) ........................................... BAYHTRV315A[
15.00/20.0 KW Heater (208/240V 3PH) (4TCC3048-060A3) ............................................. BAYHTRV320A[
3.76/5.0 KW Heater (460V 3PH) (4TCC3018-060A4) ........................................................ BAYHTRV405A[
7.50/10.0 KW Heater (460V 3PH) (4TCC3024-060A4) ...................................................... BAYHTRV410A[
11.27/15.00 KW Heater (460V 3PH) (4TCC3030-060A4) .................................................. BAYHTRV415A[
15.00/20.0 KW Heater (460V 3PH) (4TCC3048-060A4) .................................................... BAYHTRV420A[
Single Power Entry Kit 8 . ................................................................................................... BAYSPEK060A[
Single Power Entry Kit 8 . ................................................................................................... BAYSPEK061A[
Single Power Entry Kit 8 . ................................................................................................... BAYSPEK062A[
Single Power Entry Kit 8 . ................................................................................................... BAYSPEK063A[
Single Power Entry Kit 8 . ................................................................................................... BAYSPEK064A[
Single Power Entry Kit 8 . ................................................................................................... BAYSPEK065A[
NOTES: 1
2
3
4
5
6
7
8

]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]

Must use internal filter frame when economizer or fresh air kit is used.
Dry bulb control standard with economizer.
Ships knocked down.
Downflow only.
Low Ambient cooling requires crankcase heater (BAYCCHT----A).
It is the responsibility of the installing dealer to properly size the ductwork for each specific application.
BAYCOVR112,118A will not cover BAYSQRD002A applications.
See table on page 8 for matching kit with units and heaters.

General Data
4TCC3018A1000A
208-230/1/60
18000
RATINGS (COOLING) 1
Indoor Airflow (CFM)
675
Power Input (KW)
1.64
EER/SEER (BTU/Watt-Hr)6
11/13
Sound Rating No. 2
74
208-230/1/60
POWER CONN.V/Ph/Hz
Min. Brch. Cir. Ampacity 3
10.1
Fuse SizeMax. /Recmd.(Amps)
15/15
COMPRESSOR
Volts/Ph/Hz
200-230/1/60
R.L. AmpsL.R. Amps
6.41/38.6
SPINE FIN
OUTDOOR COILTYPE
Rows/F.P.I.
2/24
Face Area (sq.ft.)
10.06
Tube Size (in.)
3/8
PLATE FIN
INDOOR COILTYPE
Rows/F.P.I.
3/15
Face Area (sq.ft.)
3.54
Tube Size (in.)
3/8
Refrigerant Control
EXPANSION VALVE
Drain Conn. Size (in.)
3/4 FEMALE NPT
PROPELLER
OUTDOOR FAN TYPE
No. Used/Dia. (in.)
1/23
Type Drive/No. Speeds
DIRECT/1
MotorHP / R.P.M.
1/12/810
Volts/Ph/Hz
230/1/60
F.L. AmpsL.R. Amps
0.54/0.95
CENTRIFUGAL
INDOOR FANTYPE
Dia x Width (in.)
11 x 10
Drive / No. Speeds
DIRECT/2
MotorHP / R.P.M.
1/8/825
Volts/Ph/Hz
200-230/1/60
F.L. AmpsL.R. Amps
1/1.5
NO
FILTER / FURNISHED?
Type Recommended
THROWAWAY
Min. Face Area 7 (sq. ft.)
2.0
(R-410A)
REFRIGERANT
Charge (lbs.)
5.94
H X W X D
DIMENSIONS
Crated (in.)
45.86X44.5X52.03
WEIGHT
444/348
Shipping (lbs.) / Net (lbs.)
MODEL
RATED Volts/Ph/Hz

4TCC3024A1000A
208-230/1/60
23000
725
2.09
11/13
76
208-230/1/60
13.6
20/20

4TCC3030A1000A
208-230/1/60
28000
1000
2.67
11/13
75
208-230/1/60
21.7
35/35

4TCC3036A1000A
208-230/1/60
35000
1200
3.29
11/13
76
208-230/1/60
23.2
35/35

4TCC3036A3000A
208-230/3/60
35000
1200
3.18
11/13
76
208-230/3/60
18.2
30/30

200-230/1/60
8.3/57.8
SPINE FIN
2/24
10.06
3/8
PLATE FIN
3/15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
1/23
DIRECT/1
1/12/810
230/1/60
0.54/0.95
CENTRIFUGAL
11 x 10
DIRECT/2
1/4/825
200-230/1/60
1.4/2.8
NO
THROWAWAY
2.67
(R-410A)
5.8
H X W X D
45.86X44.5X52.03

208-230/1/60
14.7/72.5
SPINE-FIN
2/24
10.06
3/8
PLATE FIN
3/15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
1/23
DIRECT/1
1/5/830
230/1/60
1.1/1.9
CENTRIFUGAL
11 x 10
DIRECT/3
1/2/1080
200-230/1/60
2/4.4
NO
THROWAWAY
3.33
(R-410A)
6.3
H X W X D
45.86X44.5X52.03

208-230/1/60
15.4/83
SPINE FIN
2/24
10.06
3/8
PLATE FIN
4/15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
1/23
DIRECT/1
0.2/830
230/1/60
1.1/1.9
CENTRIFUGAL
11 x 10
DIRECT/3
1/2/1075
200-230/1/60
2.9/5.8
NO
THROWAWAY
4.0
(R-410A)
7.7
H X W X D
5.86X44.5X52.03

208-230/3/60
11.5/77
SPINE FIN
2/24
10.06
3/8
PLATE FIN
4/15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
1/23
DIRECT/1
1/5/830
230/1/60
1.1/1.9
CENTRIFUGAL
10 x 10
DIRECT/3
1/2/1075
200-230/1/60
2.9/5.8
NO
THROWAWAY
4.0
(R-410A)
7.7
H X W X D
45.86X44.5X52.03

444/348

445/349

460/364

450/354

1Rated in accordance with

2 All models are UL Listed. Rat-

A.R.I. Standard 210/240.


Noise tested in accordance
with A.R.I. Standard 270.
A.R.I. standard rating conditions are: 80 D.B. 67 W.B.
entering air to indoor coil. 95
D.B. entering air to outdoor
coil.

ings shown are for elevations


up to 2000 ft. For higher elevations reduce ratings at a
rate of 4% per 1000 ft. elevation.

3 Convertible to LPG.
4 This value is approximate. For
more precise value, see Unit
Nameplate.

5 Based on U.S. Government


Standard Tests.

6 Filters must be installed in


return air stream. Square footages listed are based on 300
f.p.m. face velocity. If permanent filters are used size per
manufacturer's recommendation with a clean resistance of
0.05" W.C.

7 Unit is shipped on high input,


unit is convertible to low input
with a Low Fire accessory kit.

General Data
MODEL
RATED Volts/Ph/Hz

4TCC3036A4000A
460/3/60
35000
RATINGS (COOLING) 1
Indoor Airflow (CFM)
1200
Power Input (KW)
3.29
EER/SEER (BTU/Watt-Hr)6
11/13
Sound Rating No. 2
76
460/3/60
POWER CONN.V/Ph/Hz
Min. Brch. Cir. Ampacity 3
8.7
Fuse SizeMax. /Recmd.(Amps)
15/15
COMPRESSOR
Volts/Ph/Hz
460/3/60
R.L. AmpsL.R. Amps
5.13/35
SPINE FIN
OUTDOOR COILTYPE
Rows/F.P.I.
2/24
Face Area (sq.ft.)
10.06
Tube Size (in.)
3/8
PLATE FIN
INDOOR COILTYPE
Rows/F.P.I.
4/15
Face Area (sq.ft.)
3.54
Tube Size (in.)
3/8
Refrigerant Control
EXPANSION VALVE
Drain Conn. Size (in.)
3/4 FEMALE NPT
PROPELLER
OUTDOOR FAN TYPE
No. Used/Dia. (in.)
1/23
Type Drive/No. Speeds
DIRECT/1
MotorHP / R.P.M.
1/5/830
Volts/Ph/Hz
230/1/60
F.L. AmpsL.R. Amps
0.6/1.3
CENTRIFUGAL
INDOOR FANTYPE
Dia x Width (in.)
10 x 10
Drive / No. Speeds
DIRECT/2
MotorHP / R.P.M.
1/2/ 1075
Volts/Ph/Hz
460/1/60
F.L. AmpsL.R. Amps
1.7/3.12
NO
FILTER / FURNISHED?
Type Recommended
THROWAWAY
Min. Face Area 7 (sq. ft.)
4.0
(R-410A)
REFRIGERANT
Charge (lbs.)
7.7
H X W X D
DIMENSIONS
Crated (in.)
45.86X44.5X52.03
WEIGHT
Shipping (lbs.) / Net (lbs.)
450/354

4TCC3042A1000A
208-230/1/60
40000
1450
3.95
11/13
78
208-230/1/60
27.9
45/45

4TCC3048A1000A
208-230/1/60
46500
1600
4.23
11/13
80
208-230/1/60
31.1
50/50

4TCC3048A3000A
208-230/3/60
46500
1600
4.23
11/13
80
208-230/3/60
23.6
35/35

4TCC3048A4000A
460/3/60
46500
1600
4.23
11/13
80
460/3/60
11.7
15/15

208-230/1/60
19.2/104
SPINE FIN
2/24
13.40
3/8
PLATE FIN
3/15
5
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
1/27.6
DIRECT/1
1/4/825
230/1/60
1.4/3.5
CENTRIFUGAL
10 x 10
DIRECT/3
1/2/ 1075
200-230/1/60
2.5/3.2
NO
THROWAWAY
4.67
(R-410A)
8.1
H X W X D
47.86X47.4X61.75

208-230/1/60
20.5/109
SPINE FIN
2/24
13.4
3/8
PLATE FIN
3/15
5
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
1/27.6
DIRECT/1
1/4/825
230/1/60
1.4/3.5
CENTRIFUGAL
10 x 10
DIRECT/3
3/4/ 1080
200-230/1/60
4/8.4
NO
THROWAWAY
5.33
(R-410A)
8.2
H X W X D
47.86X47.4X61.75

208-230/3/60
14.6/91
SPINE FIN
2/24
13.4
3/8
PLATE FIN
3/15
5
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
1/27.6
DIRECT/1
1/4/825
230/1/60
1.4/3.5
CENTRIFUGAL
10 x 10
DIRECT/3
3/4/1080
200-230/1/60
4/8.4
NO
THROWAWAY
5.33
(R-410A)
8.2
H X W X D
47.86X47.4X61.75

460/3/60
7.05/46
SPINE FIN
2/24
13.4
3/8
PLATE FIN
3/15
5
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
1/27.6
DIRECT/1
1/4/825
460/1/60
0.74/1.6
CENTRIFUGAL
10 x 10
DIRECT/2
3/4/1080
460/1/60
2.2/4.36
NO
THROWAWAY
5.33
(R-410)
8.2
H X W X D
47.86X47.4X61.75

523/395

607/479

607/479

607/479

1Rated in accordance with

2 All models are UL Listed. Rat-

A.R.I. Standard 210/240.


Noise tested in accordance
with A.R.I. Standard 270.
A.R.I. standard rating conditions are: 80 D.B. 67 W.B.
entering air to indoor coil. 95
D.B. entering air to outdoor
coil.

ings shown are for elevations


up to 2000 ft. For higher elevations reduce ratings at a
rate of 4% per 1000 ft. elevation.

3 Convertible to LPG.
4 This value is approximate. For
more precise value, see Unit
Nameplate.

5 Based on U.S. Government


Standard Tests.

6 Filters must be installed in


return air stream. Square footages listed are based on 300
f.p.m. face velocity. If permanent filters are used size per
manufacturer's recommendation with a clean resistance of
0.05" W.C.

7 Unit is shipped on high input,


unit is convertible to low input
with a Low Fire accessory kit.

General Data
4TCC3060A1000A
208-230/1/60
58000
RATINGS (COOLING) 1
Indoor Airflow (CFM)
1800
Power Input (KW)
5.27
EER/SEER (BTU/Watt-Hr)6
11/13
Sound Rating No. 2
79
208-230/1/60
POWER CONN.V/Ph/Hz
Min. Brch. Cir. Ampacity 3
43.5
Fuse SizeMax. /Recmd.(Amps)
60/60
COMPRESSOR
Volts/Ph/Hz
208-230/1/60
R.L. AmpsL.R. Amps
27.6/158
SPINE FIN
OUTDOOR COILTYPE
Rows/F.P.I.
2/24
Face Area (sq.ft.)
13.84
Tube Size (in.)
3/8
PLATE FIN
INDOOR COILTYPE
Rows/F.P.I.
4/15
Face Area (sq.ft.)
5
Tube Size (in.)
3/8
Refrigerant Control
EXPANSION VALVE
Drain Conn. Size (in.)
3/4 FEMALE NPT
PROPELLER
OUTDOOR FAN TYPE
No. Used/Dia. (in.)
1/27.6
Type Drive/No. Speeds
DIRECT/1
MotorHP / R.P.M.
1/4/825
Volts/Ph/Hz
230/1/60
F.L. AmpsL.R. Amps
1.4/3.5
CENTRIFUGAL
INDOOR FANTYPE
Dia x Width (in.)
11 x 10
Drive / No. Speeds
DIRECT/3
MotorHP / R.P.M.
1/1075
Volts/Ph/Hz
208-230/1/60
F.L. AmpsL.R. Amps
7.6/7.6
NO
FILTER / FURNISHED?
Type Recommended
THROWAWAY
Min. Face Area 7 (sq. ft.)
6.67
(R-410A)
REFRIGERANT
Charge (lbs.)
10
H X W X D
DIMENSIONS
Crated (in.)
49.86X47.4X61.75
WEIGHT
Shipping (lbs.) / Net (lbs.)
610/482
MODEL
RATED Volts/Ph/Hz

4TCC3060A3000A
208-230/3/60
58000
1800
5.27
11/ 13.0
79
208-230/3/60
31.7
50/50

4TCC3060A4000A
460/3/60
58000
1800
5.27
11 / 13.0
79
460/3/60
19.5
25/25

208-230/3/60
18.1/137
SPINE FIN
2 / 24
13.84
3/8
PLATE FIN
4 / 15
5
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
1 / 27.6
DIRECT / 1
1/4 / 825
230/1/60
1.4 /3.5
CENTRIFUGAL
11 X 10
DIRECT/3
1 / 1075
208-230/1/60
7.6/7.6
NO
THROWAWAY
6.67
(R-410A)
10
H X W X D
49.86 X 47.4 X 61.75

460/3/60
8.97/62
SPINE FIN
2 / 24
13.84
3/8
PLATE FIN
4/ 15
5
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
1 / 27.6
DIRECT / 1
1/4 / 825
460/1/60
0.74 /1.6
CENTRIFUGAL
11 X 10
DIRECT/3
1 / 1075
208-230/1/60
7.6/7.6
NO
THROWAWAY
6.67
(R-410A)
10
H X W X D
49.86 X 47.4 X 61.75

610 / 482

610 / 482

1Rated in accordance with

2 All models are UL Listed. Rat-

A.R.I. Standard 210/240.


Noise tested in accordance
with A.R.I. Standard 270.
A.R.I. standard rating conditions are: 80 D.B. 67 W.B.
entering air to indoor coil. 95
D.B. entering air to outdoor
coil.

ings shown are for elevations


up to 2000 ft. For higher elevations reduce ratings at a
rate of 4% per 1000 ft. elevation.

3 Convertible to LPG.
4 This value is approximate. For
more precise value, see Unit
Nameplate.

5 Based on U.S. Government


Standard Tests.

6 Filters must be installed in


return air stream. Square footages listed are based on 300
f.p.m. face velocity. If permanent filters are used size per
manufacturer's recommendation with a clean resistance of
0.05" W.C.

7 Unit is shipped on high input,


unit is convertible to low input
with a Low Fire accessory kit.

Heater Data
4TCC3018A to 4TCC3060A Heater Data
UNIT
MODEL

^W/TC*3018A1
^W/TC*3024A1
^W/TC*3030A1
^W/TC*3036A1
^W/TC*3042A1

^W/TC*3048A1
^W/TC*3060A1

^W/TC*3036A3

^W/TC*3048A3
^W/TC*3060A3

^W/TC*3036A4

^W/TC*3048A4
^W/TC*3060A4

ELECTRIC
HEATER
MODEL

HEATER CAPACITY
RATED
PHASE AMPS
VOLTAGE
KW

NO. OF
STAGES

BTUH

KW / STAGE
MCA (2)
1

MAX.
CANADA
FUSE
ONLY MAX.
OR HQCR
CKT BKR
CKT BKR
SIZE (5)
SIZE (4)

BAYHTRV105A

208/240

18/21

3.76/5.0

12800/17100

3.76/5.0

23/26

25/30

25/30

BAYHTRV105A

208/240

18/21

3.76/5.0

12800/17100

3.76/5.0

23/26

25/30

25/30

BAYHTRV110A

208/240

36/42

7.50/10.0

25600/34100

7.50/10.0

45/52

45/60

45/60

BAYHTRV105A

208/240

18/21

3.76/5.0

12800/17100

3.76/5.0

23/26

25/30

25/30
45/60

BAYHTRV110A

208/240

36/42

7.50/10.0

25600/34100

7.50/10.0

BAYHTRV115A#

208/240

54/63

11.27/15.0

38500/51200

7.50/10.0

BAYHTRV105A

208/240

18/21

3.76/5.0

12800/17100

3.76/5.0

3.76/5.0

45/52

45/60

68/78

70/80

70/80

23/26

25/30

25/30
45/60

BAYHTRV110A

208/240

36/42

7.50/10.0

25600/34100

7.50/10.0

45/52

45/60

BAYHTRV115A#

208/240

54/63

11.27/15.0

38500/51200

7.50/10.0

3.76/5.0

68/78

70/80

70/80

BAYHTRV120A#

208/240

72/83

15.00/20.0

51200/68300

7.50/10.0

7.50/10.0

90/104

90/110

90/110

BAYHTRV305A

208/240

10/12

3.76/5.0

12800/17100

3.76/5.0

13/15

15/15

15/15

BAYHTRV310A

208/240

21/24

7.50/10.0

25600/34100

7.50/10.0

26/30

30/30

30/30

BAYHTRV315A

208/240

31/36

11.27/15.0

38500/51200

7.50/10.0

39/45

40/45

40/45

BAYHTRV305A

208/240

10/12

3.76/5.0

12800/17100

3.76/5.0

13/15

15/15

15/15

BAYHTRV310A

208/240

21/24

7.50/10.0

25600/34100

7.50/10.0

26/30

30/30

30/30

BAYHTRV315A

208/240

31/36

11.27/15.0

38500/51200

7.50/10.0

3.76/5.0

39/45

40/45

40/45

BAYHTRV320A

208/240

42/48

15.00/20.0

51200/68300

7.50/10.0

7.50/10.0

52/60

60/60

60/60

BAYHTRV405A

480

17100

15

15

BAYHTRV410A

480

12

10

34100

10

15

15

15

BAYHTRV415A

480

18

15

51200

10

23

25

25

BAYHTRV405A

480

17100

15

15

BAYHTRV410A

480

12

10

34100

10

15

15

15

BAYHTRV415A

480

18

15

51200

10

23

25

25

BAYHTRV420A

480

24

20

68300

10

10

30

30

30

3.76/5.0

NOTES:
1. Any power supply and circuits must be wired and protected in accordance with local electrical codes.
(2) The MCA values listed are for electric heater only.
3. Field wire must be rated at least 75C
(4) The HACR circuit breaker is for U.S.A. installations only.
(5) For Canada installation reference only.
* Heater uses fuses.

Single Power Entry Kit Data


SPEK 4TCC3018A to 4TCC3060A
SINGLE CIRCUIT POWER AMPACITY AND OVER CURRENT PROTECTION
SINGLE
POWER
ENTRY
KIT

HEATER
MODEL

UNIT
MODEL

MIN
CKT
AMP

MAX
OVERCURRENT
DEVICE

4TC*3018A1

27

30

4TC*3024A1

28

30

4TC*3030A1

29

35

4TC*3036A1

30

35

4TC*3042A1

29

4TC*3048A1

SINGLE
POWER
ENTRY
KIT

MIN
CKT
AMP

MAX
OVERCURRENT
DEVICE

4TC*3030A1

81

90

4TC*3036A1

82

90

4TC*3042A1

81

90

4TC*3048A1

83

90

45

4TC*3060A1

88

90

31

50

4TC*3048A1

109

110

4TC*3024A1

54

60

4TC*3060A1

114

125

4TC*3030A1

55

60

4TC*3048A3

65

70

4TC*3036A1

56

60

4TC*3060A3

70

70

4TC*3042A1

55

60

HEATER
MODEL

BAYHTRV115A

UNIT
MODEL

BAYHTRV105A

BAYSPEK060

BAYSPEK063A #

BAYHTRV120A

BAYSPEK064A #
BAYHTRV110A

BAYHTRV305A

BAYHTRV310A

BAYHTRV315A

BAYSPEK061A
BAYHTRV405A

BAYHTRV410A

BAYHTRV415A

4TC*3048A1

57

60

4TC*3036A3

18

30

4TC*3048A3

24

35

4TC*3060A3

32

45
35

4TC*3036A3

33

4TC*3048A3

35

35

4TC*3060A3

40

45

4TC*3036A3

48

50

4TC*3048A3

50

50

4TC*3060A3

55

60

4TC*3036A4

10

15

4TC*3048A4

12

15

4TC*3060A4

20

25

4TC*3036A4

17

20

4TC*3048A4

18

20

4TC*3060A4

25

25

4TC*3036A4

25

25

4TC*3048A4

25

25

4TC*3060A4

32

35

4TC*3048A4

33

35

BAYHTRV320A

BAYHTRV420A
4TC*3060A4

40

40

BAYHTRV105A

4TC*3060A1

44

70

BAYHTRV110A

4TC*3060A1

62

70

BAYSPEK062A #
# Single Circuit Power fuses are supplied if required for unit and/or heater.

From Dwg. 21C932254 P01&2

Performance Data Cooling


4TCC3018A AT 600 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)
O.D.
D.B.
85

95

105

115

I.D.
W.B.
59
63
67
71

TOTAL
CAP.
17.5
18.2
19.7
21.2

SENS. CAP. AT ENTERING D.B. TEMP.


72
75
78
80
11.6
14.0
16.3
17.5
10.7
12.8
14.9
16.3
9.2
11.1
12.9
14.1
7.6
9.2
10.7
11.7

COMPR.
KW
1.43
1.44
1.46
1.47

59
63
67
71

15.9
16.6
17.8
19.3

11.0
10.1
8.7
7.2

13.2
12.1
10.5
8.7

15.4
14.2
12.2
10.1

15.9
15.5
13.3
11.1

1.57
1.58
1.60
1.62

59
63
67
71

14.3
14.9
16.0
17.3

10.3
9.4
8.2
6.8

12.4
11.4
9.8
8.1

14.3
13.2
11.4
9.5

14.3
14.5
12.5
10.4

1.71
1.72
1.75
1.76

59
63
67
71

12.6
13.2
14.2
15.3

9.5
8.7
7.5
6.2

11.4
10.5
9.0
7.5

12.6
12.2
10.5
8.7

12.6
13.2
11.5
9.5

1.85
1.86
1.89
1.91

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)


LOW
HIGH

AIRFLOW

TOTAL CAPACITY

SENSIBLE CAPACITY

525
675

0.98
1.02

0.97
1.03

VALUES AT ARI RATING CONDITIONS


TOTAL NET CAPACITY = 18000 BTUH
AIRFLOW = 675 CFM
COMPRESSOR POWER = 1183 WATTS
I.D. FAN POWER = 236 WATTS
O.D. FAN POWER = 217 WATTS
S.E.E.R. = 13.00 BTUH/WATT
E.E.R = 11.00 BTUH/WATT
ALL TEMPERATURES IN DEGREES F.

4TCC3024A AT 800 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)
O.D.
D.B.
85

95

105

115

I.D.
W.B.
59
63
67
71

TOTAL
CAP.
22.5
23.5
25.3
27.3

SENS. CAP. AT ENTERING D.B. TEMP.


72
75
78
80
14.7
17.7
20.6
22.5
13.5
16.2
18.9
20.7
11.6
14.0
16.3
17.8
9.7
11.6
13.5
14.8

COMPR.
KW
1.91
1.92
1.95
1.97

59
63
67
71

20.6
21.5
23.2
25.0

13.8
12.6
10.9
9.1

16.6
15.2
13.1
10.9

19.3
17.7
15.3
12.7

20.6
19.4
16.7
13.9

2.07
2.08
2.12
2.14

59
63
67
71

18.8
19.6
21.1
22.8

12.8
11.7
10.1
8.4

15.4
14.1
12.2
10.1

17.9
16.4
14.2
11.8

18.8
18.0
15.5
12.9

2.23
2.25
2.28
2.31

59
63
67
71

16.9
17.6
19.0
20.5

11.7
10.8
9.3
7.7

14.1
13.0
11.2
9.3

16.5
15.1
13.0
10.8

16.9
16.5
14.2
11.8

2.39
2.41
2.45
2.47

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)


LOW
HIGH

AIRFLOW

TOTAL CAPACITY

SENSIBLE CAPACITY

700
900

0.98
1.02

0.97
1.03

VALUES AT ARI RATING CONDITIONS


TOTAL NET CAPACITY = 23000 BTUH
AIRFLOW = 725 CFM
COMPRESSOR POWER = 1698 WATTS
I.D. FAN POWER = 191 WATTS
O.D. FAN POWER = 202 WATTS
S.E.E.R. = 13.00 BTUH/WATT
E.E.R = 11.00 BTUH/WATT
ALL TEMPERATURES IN DEGREES F.

4TCC3030A AT 1000 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)
O.D.
D.B.
85

95

105

115

I.D.
W.B.
59
63
67
71

TOTAL
CAP.
26.8
28.0
30.2
32.6

SENS. CAP. AT ENTERING D.B. TEMP.


72
75
78
80
18.3
22.0
25.6
26.8
16.8
20.1
23.5
25.7
14.5
17.4
20.3
22.1
12.0
14.4
16.8
18.4

COMPR.
KW
2.24
2.26
2.29
2.32

59
63
67
71

24.9
26.0
28.0
30.2

17.3
15.9
13.7
11.4

20.8
19.1
16.5
13.7

24.3
22.3
19.2
15.9

24.9
24.3
21.0
17.4

2.49
2.50
2.55
2.57

59
63
67
71

23.0
24.0
25.9
27.9

16.3
15.0
12.9
10.7

19.6
18.0
15.5
12.9

22.9
21.0
18.1
15.0

23.0
22.9
19.8
16.4

2.73
2.75
2.80
2.82

59
63
67
71

21.1
22.0
23.7
25.6

15.3
14.0
12.1
10.0

18.3
16.8
14.5
12.1

21.1
19.6
16.9
14.0

21.1
21.4
18.5
15.4

2.98
3.00
3.05
3.08

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)


LOW
HIGH

AIRFLOW

TOTAL CAPACITY

SENSIBLE CAPACITY

875
1125

0.98
1.02

0.97
1.03

VALUES AT ARI RATING CONDITIONS


TOTAL NET CAPACITY = 28000 BTUH
AIRFLOW = 1000 CFM
COMPRESSOR POWER = 1922 WATTS
I.D. FAN POWER = 315 WATTS
O.D. FAN POWER = 308 WATTS
S.E.E.R. = 13.00 BTUH/WATT
E.E.R = 11.00 BTUH/WATT
ALL TEMPERATURES IN DEGREES F.

10

Performance Data Cooling


4TCC3036A AT 1200 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)
O.D.
D.B.
85

95

105

115

I.D.
W.B.
59
63
67
71

TOTAL
CAP.
33.6
35.0
37.8
40.8

SENS. CAP. AT ENTERING D.B. TEMP.


72
75
78
80
22.6
27.2
31.7
33.6
20.8
25.0
29.1
31.8
17.9
21.5
25.1
27.5
14.9
17.9
20.8
22.8

COMPR.
KW
2.80
2.82
2.86
2.89

59
63
67
71

31.2
32.5
35.0
37.8

21.6
19.9
17.1
14.2

26.0
23.9
20.6
17.1

30.3
27.8
24.0
19.9

31.2
30.4
26.3
21.8

3.11
3.13
3.18
3.21

59
63
67
71

28.7
29.9
32.2
34.8

20.5
18.9
16.3
13.5

24.7
22.7
19.6
16.2

28.7
26.4
22.8
18.9

28.7
28.9
24.9
20.7

3.42
3.44
3.50
3.53

59
63
67
71

26.2
27.3
29.5
31.8

19.3
17.8
15.3
12.7

23.3
21.3
18.4
15.3

26.2
24.9
21.5
17.8

26.2
27.2
23.5
19.5

3.74
3.76
3.82
3.86

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)


LOW
HIGH

AIRFLOW

TOTAL CAPACITY

SENSIBLE CAPACITY

1050
1350

0.98
1.02

0.97
1.03

VALUES AT ARI RATING CONDITIONS


TOTAL NET CAPACITY = 35000 BTUH
AIRFLOW = 1200 CFM
COMPRESSOR POWER = 2556 WATTS
I.D. FAN POWER = 420 WATTS
O.D. FAN POWER = 206 WATTS
S.E.E.R. = 13.00 BTUH/WATT
E.E.R = 11.00 BTUH/WATT
ALL TEMPERATURES IN DEGREES F.

4TCC3042A AT 1400 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)
O.D.
D.B.
85

95

105

115

I.D.
W.B.
59
63
67
71

TOTAL
CAP.
38.1
39.8
42.9
46.3

SENS. CAP. AT ENTERING D.B. TEMP.


72
75
78
80
25.6
30.7
35.8
38.1
23.5
28.2
32.9
35.9
20.2
24.3
28.4
31.0
16.8
20.2
23.5
25.7

COMPR.
KW
3.17
3.19
3.24
3.27

59
63
67
71

35.5
37.0
39.9
43.1

24.6
22.5
19.4
16.1

29.5
27.1
23.4
19.4

34.4
31.6
27.2
22.6

35.5
34.5
29.8
24.7

3.53
3.55
3.61
3.65

59
63
67
71

32.9
34.3
36.9
39.9

23.4
21.5
18.6
15.4

28.2
25.8
22.3
18.5

32.8
30.1
26
21.6

32.9
32.9
28.4
23.6

3.89
3.92
3.98
4.02

59
63
67
71

30.2
31.5
33.9
36.6

22.2
20.4
17.6
14.6

26.7
24.5
21.1
17.5

30.2
28.5
24.6
20.4

30.2
31.2
26.9
22.3

4.26
4.28
4.35
4.40

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)


LOW
HIGH

AIRFLOW
1225
1575

TOTAL CAPACITY
0.98
1.02

SENSIBLE CAPACITY
0.97
1.03

VALUES AT ARI RATING CONDITIONS


TOTAL NET CAPACITY = 40000 BTUH
AIRFLOW = 1450 CFM
COMPRESSOR POWER = 3009 WATTS
I.D. FAN POWER = 518 WATTS
O.D. FAN POWER = 109 WATTS
S.E.E.R. = 13.00 BTUH/WATT
E.E.R = 11.00 BTUH/WATT
ALL TEMPERATURES IN DEGREES F.

4TCC3048A AT 1600 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)
O.D.
D.B.
85

95

105

115

I.D.
W.B.
59
63
67
71

TOTAL
CAP.
43.8
45.6
49.2
53.1

SENS. CAP. AT ENTERING D.B. TEMP.


72
75
78
80
29.8
35.8
41.7
43.8
27.3
32.9
38.3
41.9
23.6
28.3
33
36.1
19.6
23.5
27.4
30.0

COMPR.
KW
3.74
3.76
3.82
3.86

59
63
67
71

41.4
43.2
46.5
50.2

28.8
26.4
22.8
18.9

34.6
31.7
27.4
22.7

40.3
37.0
31.9
26.5

41.4
40.4
34.9
28.9

4.13
4.16
4.23
4.27

59
63
67
71

39.0
40.7
43.8
47.3

27.7
25.4
21.9
18.2

33.3
30.5
26.3
21.9

38.8
35.6
30.7
25.5

39.0
38.9
33.6
27.8

4.53
4.55
4.63
4.67

59
63
67
71

36.6
38.2
41.2
44.5

26.5
24.3
21.0
17.4

31.9
29.2
25.2
20.9

36.6
34.1
29.4
24.4

36.6
37.3
32.1
26.7

4.92
4.95
5.03
5.08

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)


LOW
HIGH

AIRFLOW

TOTAL CAPACITY

SENSIBLE CAPACITY

1400
1800

0.98
1.02

0.97
1.03

VALUES AT ARI RATING CONDITIONS


TOTAL NET CAPACITY = 46500 BTUH
AIRFLOW = 1600 CFM
COMPRESSOR POWER = 3330 WATTS
I.D. FAN POWER = 583 WATTS
O.D. FAN POWER = 314 WATTS
S.E.E.R. = 13.00 BTUH/WATT
E.E.R = 11.00 BTUH/WATT
ALL TEMPERATURES IN DEGREES F.

11

Performance Data Cooling


4TCC3060A AT 2000 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)
O.D.
D.B.
85

95

105

115

I.D.
W.B.
59
63
67
71

TOTAL
CAP.
56.0
58.4
62.9
67.9

SENS. CAP. AT ENTERING D.B. TEMP.


72
75
78
80
35.7
42.9
50.0
54.6
32.7
39.4
45.9
50.1
28.3
34.0
39.6
43.3
23.4
28.2
32.8
35.9

COMPR.
KW
4.72
4.75
4.82
4.87

59
63
67
71

52.1
54.3
58.5
63.2

34.3
31.5
27.2
22.5

41.2
37.8
32.7
27.1

48.1
44.1
38.1
31.6

52.1
48.2
41.6
34.5

5.24
5.27
5.36
5.41

59
63
67
71

48.2
50.2
54.1
58.4

32.8
30.1
25.9
21.5

39.4
36.1
31.2
25.9

45.9
42.1
36.3
30.2

48.2
46.0
39.7
33.0

5.77
5.80
5.90
5.95

59
63
67
71

44.3
46.2
49.7
53.7

31.0
28.5
24.6
20.4

37.3
34.2
29.6
24.5

43.5
39.9
34.4
28.6

44.3
43.6
37.7
31.2

6.29
6.33
6.44
6.50

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)


LOW
HIGH

AIRFLOW

TOTAL CAPACITY

SENSIBLE CAPACITY

1750
2250

0.98
1.02

0.97
1.03

VALUES AT ARI RATING CONDITIONS


TOTAL NET CAPACITY = 58000 BTUH
AIRFLOW = 1800 CFM
COMPRESSOR POWER = 4391 WATTS
I.D. FAN POWER = 595 WATTS
O.D. FAN POWER = 287 WATTS
S.E.E.R. = 13.00 BTUH/WATT
E.E.R = 11.00 BTUH/WATT
ALL TEMPERATURES IN DEGREES F.

12

Typical Field Wiring

UNIT HEATER AREA

UNIT CONTROL BOX

POLARIZED
PLUG
ELECTRIC
HEATER
CONTROL
BOX

B
G
Y
W1
W2
O
T
R

COMMON
FAN
COMPRSSOR
1ST STAGE ELECTRIC HEAT
2ND STAGE ELECTRIC HEAT
SWITCHOVER VALVE
DEFROST CONTROL 'T' SIGNAL
24 VOLTS

UNIT LOW VOLTAGE AREA


GROUND
WIRE
1 PH
1 PH
POWER POWER
TYPICAL THERMOSTAT
3 PH
3 PH
POWER POWER
UNIT
HEATER
NOTE 1,8

FIG. 2

SINGLE POWER ENTRY ACCESSORY CONNECTIONS

FIG. 1

UNIT CONTROL
BOX

TO ECONOMIZER
FACTORY PROVIDED
FIELD INSTALLED WIRES
NOTE 9

UNIT HEATER AREA

FACTORY PROVIDED
FIELD CONNECTED
WIRES
TO COMPR.
CONTACTOR

ECONOMIZER ACCESSORY
CONNECTIONS

ELECTRIC
HEATER
CONTROL
BOX

(NOT APPLICABLE TO THE


WCM---F MODELS)

(BL)

(BL) B
(YL)
(GR)

(GR) G

(PR)
UNIT
FUSES

(YL)

HEATER
FUSES

(OR)

UNIT LOW
VOLTAGE AREA

(RD) R

TYPICAL 2-STAGE
THERMOSTAT

SINGLE POWR ENTRY

FIG. 3

OUTDOOR THERMOSTAT ACCESSORY CONNECTIONS

UNIT LOW
VOLTAGE
AREA

(BR) T
UNIT LOW
VOLTAGE AREA

SEE SPEK INSTALLER'S GUIDE


FOR ALL OTHER EXAMPLES

3 PH
POWER

(OR)

(OR)

GROUND
WIRE
1 PH
POWER

(WH) W1
(WH) W2

SPE
ACCESSORY
KIT

HEATER SECOND STAGE AMBIENT


TEMPERATURE LOCKOUT
NOTE 7,8

UNIT LOW
VOLTAGE
AREA

(WH) W1
(WH) W2

HEATER AMBIENT
TEMPERATURE LOCKOUT
NOTE 7,8
(WH) W1
(WH) W2

OUTDOOR
THERMOSTAT
ACCESSORY
BAYSTAT033A
NOTE 10

OUTDOOR
THERMOSTAT
ACCESSORY
BAYSTAT033A
NOTE 10
TYPICAL THERMOSTAT

TYPICAL THERMOSTAT

13

Typical Wiring

14

Typical Wiring

From Dwg. 21D757165 P02

15

Optional Equipment
BAYECON101,102A Down Discharge Economizer and Rain Hood
(Mounts Over Horizontal Return Air Opening)
HVAC Unit
A
Economizer
rain hood
Outside air
dampers
Return
air
dampers

Required filter
kit, order
separately

Mist
eliminator
Relief
damper
Roofcurb

Economizer

Unit ApplicationM odels

BAYECON101A

2/4YC,WC3018-036A
4TC*3018-036A

20.125"

BAYECON102A

2/4YC,WC3042-060A
4TC*3042-060A

24.375"

Return
Duct

BAYCON200,201A Horizontal Economizer and Rain Hood

Economizer

B
C
Gaskets (2)
Rain Hood

Duct

Economizer

Unit Application Models

BAYECON200AA

2/4YC,WC3018-036A
4TC*3018-036A

22.00"

20.00"

16.87"

BAYECON201AA

2/4YC,WC3042-060A
4TC*3042-060A

24.00"

22.65"

19.00"

16

Optional Equipment
BAYOSAH001,002A, 25% Outside Air Damper
(Replaces Filter/Coil Access Panel)

FULLY
OPEN
2/3
1/3

FULLY
CLOSED

Manual Fresh
Air Model

Unit Application
Models

BAYOSAH001

2/4YC,WC3018-036A
4TC*3018-036A

22 7/16"

20 11/16"

12 3/8"

9 3/16"

BAYOSAH002

2/4YC,WC3042-060A
4TC*3042-060A

25 3/16"

20 11/16"

12 3/8"

9 3/16"

BAYDMPR101,102A, 25% Motorized Outside Air Damper


(Mounts Over Horizontal Return AIr Opening)

Unit Application
Models

BAYDMPR101A

2/4YC,WC3018-036A
15 13/16"
4TC3018-036A

BAYDMPR102A

2/4YC,WC3042-060A
4TC3042-060A

18 3/16"

17

11 13/16"

10 1/4"

11 1/2"

12 1/4"

15 1/8"

10 1/4"

11 1/2"

12 1/4"

Optional Equipment
BAYCURB050A FULL PERIMETER ROOF MOUNTING CURB FOR *****018-036A

38.86
46.39

15
1.50
SUPPLY
19.50

14

RETURN

.812

1.50
19.50
1.50
1.50
38.86

1.50

D
A
WOOD NAILER

SUPPLY
AIR

RETURN
AIR

CHANNEL END
B

CHANNEL
SIDE

HOLE IN ROOF
SERVICE CLEARANCE DIMENSIONS
A

42"

36"

12"*

42"

*42 WITH ECONOMIZER


WITH 25% FRESH AIR ACCESSORY

43.39
22

BAYCURB050A

18

Optional Equipment
BAYCURB051A Full Perimeter Roof Mounting Curb for *****042-060A

41.861
56.111

20
1.50
SUPPLY
19.50
RETURN
1.50

.812

14

19.50
1.50
1.50
38.86

1.50

D
A
SUPPLY
AIR

WOOD NAILER

RETURN
AIR
C
B
CHANNEL
SIDE

CHANNEL END

HOLE IN ROOF
SERVICE CLEARANCE DIMENSIONS
A

42"

36"

12"*

42"

*42 WITH ECONOMIZER


WITH 25% FRESH AIR ACCESSORY

53.11
22

BAYCURB051A
19

Optional Equipment

BAYFLTR101, 201A, 1" - 2" Filter Rack


(Mounts in Filter/Coil Section)

Filter

20

Dimensional Data and Weights

RETURN

Figure 1. TCC3018A through TCC3036A (1 of 2)


21

SUPPLY

Dimensional Data and Weights

SUPPLY

903.29
[35-9/16]

RETURN

36 [79]
36 [79]

57 [125]

40 [88]

25 [56]

158 [348]

635 [25.0]

508 [20.0]

57 [125]

40 [88]

36 [79]

57 [125]

40 [88]

25 [56]
25 [56]

158 [348]
158 [349]

635 [25.0]
635 [25.0]

508 [20.0]

36 [78]
36 [78]
36 [80]

56 [124]
56 [124]
58 [127]

41 [89]
41 [89]

26 [56]
26 [56]

161 [354]

635 [25.0]

508 [20.0]

635 [25.0]

515.6 [20.3]

42 [92]

37 [81]

58 [128]

41 [91]

26 [58]
26 [57]

158 [348]
162 [357]
162 [358]

635 [25.0]
635 [25.0]

515.6 [20.3]
508 [20.0]

38 [84]

61 [134]

43 [94]

27 [60]

169 [372]

635 [25.0]

508 [20.0]

Figure 2. TCC3018A through TCC3036A (2 of 2)

22

508 [20.0]

Dimensional Data and Weights

RETURN

Figure 3. TCC3042A through TCC3060A (1 of 2)


23

SUPPLY

Dimensional Data and Weights

SUPPLY

41 [90]

62 [137]

46 [102]

76 [168]

58 [127]

30 [67]
36 [79]

1004.90 [39-9/16]

47 [105]
46 [102]

78 [172]
63 [138]

59 [130]
46 [102]

35 [77]
31 [69]

954.10 [37-9/16]

42 [92]
44 [98]

66 [146]
69 [152]

49 [109]
52 [115]

33 [73]
31 [68]

80 [177]
79 [175]

61 [134]
60 [132]

36 [79]
36 [76]

954.10 [37-9/16]

1055.70 [41-9/16]
1004.90 [39-9/16]

41 [90]
48 [105]
47 [104]

179 [395]

673.1 [26.5] 629.92 [24.8]


685.8 [27.0]
635 [25.0]
698.5
[27.5]
635
[25.0]
219 [482]
182 [401] 668.02 [26.3] 629.92 [24.8]
193 [425] 668.02 [26.3] 629.92 [24.8]
217 [479]

193 [425]

698.5 [27.5]

635 [25.0]

225 [495]
222 [490]

698.5 [27.5]
698.5 [27.5]

635 [25.0]
635 [25.0]

Figure 4. TCC3042A through TCC3060A (2 of 2)


24

RETURN

Mechanical Specifications
General
The units shall be horizontal airflow as
shipped and convertible to downflow. All
units shall be factory assembled, piped,
internally wired and fully charged with R-22.
Units shall be UL listed and carry a UL
label. All units shall be factory run tested to
check cooling operation, fan and blower
rotation and control sequence. Units shall
be designed to operate at ambient temperatures between 115F and 55F in cooling as manufactured. Cooling performance
shall be rated in accordance with ARI standards.
Unit Casing
All panels shall be heavy gauge steel,
gasketed and insulated. Foil-faced fiber
insulation shall be in the heater section.
Foil-faced fiber nsulation shall be in the
evaporator section. Base pan shall be
heavy gauge steel. WEATHERGUARD
exterior corrosion resistant screws shall be
used for added resistance to rust and corrosion.
Compressor
The compressor shall be a hermetically
sealed, high efficiency Climatuff compressor. Internal overcurrent and over temperature protection, internal pressure relief shall be standard. Other features include, roto lock suction and discharge refrigerant connections, centrifugal oil pump
and low vibration and noise.
Refrigeration System
All units shall have refrigerant control. Service pressure tap ports, and a refrigerant
line filter shall be standard.
Evaporator Coil Internally enhanced
3/8-inch OD seamless copper tubing
mechanically bonded to aluminum fins,
factory pressure and leak tested at 250 to
300 psig. All units have TXV to control
refrigerant flow.

Condenser Coil
The Spine Fincondenser coil shall be
continuously wrapped, corrosion resistant
all aluminum with minimum brazed joints.
This coil is 3/8 inch O.D. seamless
aluminum tubing glued to a continuous
aluminum fin. Coils are lab tested to
withstand 2,000 pounds of pressure per
square inch. The outdoor coil provides low
airflow resistance and efficient heat
transfer. The coil is protected on all four
sides by louvered panels.
Indoor Air Fan
Direct-drive, forward-curved, centrifugal
wheel in a Composite Vortica Blower
housing. Motor shall have thermal
overload protection. Permanently
lubricated motor bearings. Motor/blower
assembly isolated from unit with rubber
mounts.
Outdoor Fan
One, direct-drive, statically and dynamically balanced propeller fan shall be used
in a drawthrough vertical discharge configuration. Permanently lubricated weather
proof motor shall have built-in thermal overload protection.
System Controls
System controls include condenser fan,
evaporator fan and compressor contactors.
Accessories Roof Curb
The roof curb shall be designed to mate
with the unit and provide support and complete weathertight installation when properly installed. Adhesive back polyurethane
sealing strips shall be provided to ensure
an airtight seal between supply and return
openings of the curb and unit. The roof
curb design allows field fabricated ductwork
to be connected directly to the curb. Curb
ships knocked down for field assembly,
and includes factory-installed wood nailer
strips.
Electric Heaters
Each heater assembly shall include power
supply fusing if over 48 amps, automatic
resetting limit switches and heat limiters
for thermal protection. Heaters shall be
provided with polarized plugs for quick
connection to unit low voltage wiring. Electric heat modules shall be UL listed.

Single Source Power Entry


This accessory when used with electric
heat accessory shall allow single source
power connection to unit and heater combination. Single source power entry kits
shall have specific matching heater(s). Kit
shall include high voltage terminal blocks,
fuse blocks and fuses, cut-to-length interconnecting wiring, and junction box (if
required) to provide power sources with
fuse protection as required for both the
unit and accessory heater. Kit components shall install within the heater cabinet in the heater access section. Single
source branch power circuit shall be protected and wired in accordance with local
codes.
Fully Modulating Economizer
This accessory shall be field installed and
be composed of the following items:
0-100% fresh air damper, damper drive
motor, fixed dry bulb enthalpy control, and
low voltage pigtails for electrical connections. Solid state enthalpy or differential
enthalpy control is optional. Economizer
operations shall be controlled by the preset position of the enthalpy control. A
barometic relief damper shall be standard
with the downflow economizer and provide a pressure operated damper that
shall be gravity closing and prohibit entrance of outside air on equipment off
cycle.
Manual Outside Air Dampers
Rain hood and screen shall be field installed. Suitable for up to 25% outside air.
Start Kit - Extra compressor starting capacity for single phase equipment.
Control Options Standard Indoor Thermostats - Two stage heating/cooling or
one stage heating/cooling thermostats
shall be available in either manual or
automatic changeover.
Programmable Electronic Night Setback Thermostat - Programmable electronic thermostat shall provide heating
setback and cooling setup with 7-day,
programming capability. 1 H/1 C or 2H/2C
models available.

Trane
6200 Troup Highway
Tyler, TX 75707-9010
An American Standard Company

American Standard has a policy of continuous product and product data improvement and it reserves the right
to change design and specifications without notice.

25