Station Identifier: 132KV Switchyard BAY: 132kV BUSBAR II Relay Identifier: F11 Device: DRS-C2BB Nominal system frequency: Current Transformer Ratio: 132KV Side CT Ratio: Label 1
1.01 1.02 1.03 1.04 1.05 1.06

NFREQ=50Hz CT Prim,=1600 CT Sec,=1 Protection Philosophy


Mask for Zone 1_Busbar II Feeder.

Setting Range Value Busbar Differential Protection Elements (87BB), Function liabrary: MC321
Zone 1 Feeder Zone 2 Feeder Zone 3 Feeder Checkzone Feeder Maint. Feeder Maintenance Selection From Feeder 1 to Feeder 10 Selection From Feeder 1 to Feeder 10 Selection From Feeder 1 to Feeder 10 Selection From Feeder 1 to Feeder 10 Selection From Feeder 1 to Feeder 10 static/ dynamic Feeder 1, 2, 3, 4 None None Feeder 1, 2, 3, 4 None static

Mask for Checkzone Feeder. Mask for Maintenance. Maintenance: static - all feeder defined in maintenance mask work with zero current. dynamic - the maintenance status is defined via digital inputs. Mask for 'Enable I> Interlock'. Overcurrent in one or more feeders is one of the conditions for busbar tripping. Depending on this parameter overcurrent in this feeder starts the operation of the busbar protection. This feature is often justed for weak feeders. Mask for 'I> Trip Release'. If selected, the trip command to the ciruit breaker of this feeder is enabled only if the fault current is greater than the 'I> Interlock' value.

1.07

Enable I> Interlock

Selection From Feeder 1 to Feeder 10 Feeder 1, 2, 3, 4

1.08 1.09 1.09.1 1.09.2 1.09.3 1.09.4 1.09.5 1.09.6

I> Trip Release Zone Parameters Bias Operate Value Stage1 Operate Value Stage2 Time Delay Stage 2 Operate Val.Alarmst. Time Delay Alarmst.

Selection From Feeder 1 to Feeder 10 None

50% - 80% 0.2 - 10.00 A 0.2 - 10.00 A 0.10 - 10.00 S 0.1 - 1.00 A 0.02 - 10.00 S

50% 0.40 10 10 0.10 5.00

As disable or off feature has not been shown so highest values has been selected.

1.10 1.10.1 1.10.2 1.10.3 1.10.4 1.11 1.12 1.13 1.14 1.15

Checkzone Param. Bias Operate Value Stage1 Operate Value Stage2 Time Delay Stage 2 t> Discrepancy 1 Save Isol. 1 Status t> Discrepancy 2 Save Isol. 2 Status Block If Alarm Stage

50% - 80% 0.2 - 10.00 A 0.2 - 10.00 A 0.10 - 10.00 S 0.01- 20.00 S no/ yes 0.01- 20.00 S no/ yes no/ yes

40% 0.40 10 10 20 no 20 no yes Blocking of busbar protection stage 1 and 2 at alarm stage pick-up. Blocking of busbar protection stage 1 and 2 at isolator discrepancy. Select activation of checkzone. Dwell time setting for function output. 11AEA01 Feeder_Q03 As disable or off feature has not been shown so highest values has been selected.

1.16 1.17 1.18 1.19 1.19.1 1.19.2 1.19.3 1.20 1.20.1 1.20.2 1.20.3 1.21 1.21.1 1.21.2 1.21.3

Block If Discrepancy Release By Checkzone Dwell Time Feeder 1 parameter I>Interlock Current Direction Primary CT Ratio Feeder 2 parameter I>Interlock Current Direction Primary CT Ratio Feeder 3 parameter I>Interlock Current Direction Primary CT Ratio

no/ yes no/ yes 0.050 - 5.000 S

no yes 0.500

0.08A - 10.00A Direction 1, Direction 2 0.050 - 1.000

0.20A Direction 2 1.000

If feeder is selected Enable I> Interlock, Overcurrent interlock setting value should be given out. Selection of current direction. Ratio of feeder CT compared to highest rated CT. 11AEA02 Feeder_Q03

0.08A - 10.00A Direction 1, Direction 2 0.050 - 1.000

0.20A Direction 2 1.000

If feeder is selected Enable I> Interlock, Overcurrent interlock setting value should be given out. Selection of current direction. Ratio of feeder CT compared to highest rated CT. 11AEA03 Feeder_Q03

0.08A - 10.00A Direction 1, Direction 2 0.050 - 1.000

0.20A Direction 2 1.000

If feeder is selected Enable I> Interlock, Overcurrent interlock setting value should be given out. Selection of current direction. Ratio of feeder CT compared to highest rated CT.

1.22 1.22.1 1.22.2 1.22.3

Feeder 4 parameter I>Interlock Current Direction Primary CT Ratio 0.08A - 10.00A Direction 1, Direction 2 0.050 - 1.000 0.20A Direction 2 1.000

11AEA04 Feeder_Q03 If feeder is selected Enable I> Interlock, Overcurrent interlock setting value should be given out. Selection of current direction. Ratio of feeder CT compared to highest rated CT.

2 3

Busbar Differential Alarming and Monitoring Element (87BB Alarms), Function liabrary: MC326
No any settings

Latched Alarm Stage for Alarming and Resetting, Function liabrary: MB111
Time Delay Active edge 0.00 - 180.00 S Rising, Trailing 0.00 Rising No time delaying 87BB Alarming signal latched from rising trigger, it's reset by IN03

11AEA01_Q03_50BF Trip Zone, Function liabrary: MB111


Time Delay Active edge 0.00 - 180.00 S Rising, Trailing 0.00 - 180.00 S Rising, Trailing 0.00 Rising 0.00 Rising No time delaying 50BF Trip bus zone from IN01_rising trigger No time delaying 50BF Trip bus zone from IN02_rising trigger

11AEA02_Q03_50BF Trip Zone, Function liabrary: MB111


Time Delay Active edge

11AEA03_Q03_50BF Trip Zone, Function liabrary: MB111


Time Delay Active edge 0.00 - 180.00 S Rising, Trailing 0.00 Rising No time delaying 50BF Trip bus zone from IN04_rising trigger

11AEA04_Q03_50BF Trip Zone, Function liabrary: MB111


Time Delay Active edge 0.00 - 180.00 S Rising, Trailing 0.00 Rising No time delaying 50BF Trip bus zone from IN05_rising trigger

8
IN01 IN02 IN03 IN04

Relay Inputs (Alarming and Tripping Scheme)


50BF INITIATE DRSC2BB=11AEA01GS100-Q03 50BF INITIATE DRSC2BB=11AEA02GS100-Q03 RESET ALARMSTAGE 50BF INITIATE DRSC2BB=11AEA03GS100-Q03

To be approved
Local feeder_50BF initiates tripping bus zone Local feeder_50BF initiates tripping bus zone Reset 87BB Alarming signal Local feeder_50BF initiates tripping bus zone

IN05 IN06 IN07 IN08

50BF INITIATE DRSC2BB=11AEA04GS100-Q03 SPARE SPARE SPARE

Local feeder_50BF initiates tripping bus zone

9
OUT01 OUT02 OUT03 OUT04 OUT05 OUT06 OUT07 OUT08 OUT09 OUT10 OUT11 OUT12 OUT13 OUT14 OUT15 OUT16 OUT17 OUT18 OUT19 OUT20 OUT21 OUT22 OUT23 OUT24 OUT31 OUT32

Relay outputs (Alarming and Tripping Scheme)

To be approved
87BB Feeder 1+ 50BF Q03 F1

87BB Feeder 2+ 50BF Q03 F2

TRIP BUSII BREAKER


87BB Feeder 3+ 50BF Q03 F3

87BB Feeder 4+ 50BF Q03 F4 87BB Feeder 1+ 50BF Q03 F1

BLOCK LINE AUTO RECLOSE

87BB Feeder 2+ 50BF Q03 F2 87BB Feeder 3+ 50BF Q03 F3 87BB Feeder 4+ 50BF Q03 F4 87BB Feeder 1

BFP START

87BB Feeder 2 87BB Feeder 3 87BB Feeder 4

TRIP=11AEA01GS100-Q03 C1 TRIP=11AEA01GS100-Q03 C2 TRIP=11AEA02GS100-Q03 C1 TRIP=11AEA02GS100-Q03 C2 TRIP=11AEA03GS100-Q03 C1 TRIP=11AEA03GS100-Q03 C2 TRIP=11AEA04GS100-Q03 C1 TRIP=11AEA04GS100-Q03 C2 BLOCK LINE 1 AUTO RECLOSE BLOCK LINE 2 AUTO RECLOSE BLOCK LINE 3 AUTO RECLOSE BLOCK LINE 4 AUTO RECLOSE BFP START TO = 11AEA01GS100-Q03 BFP START TO = 11AEA02GS100-Q03 BFP START TO = 11AEA03GS100-Q03 BFP START TO = 11AEA04GS100-Q03 BUSBAR TRIP Lockout Trip_11AEA01GS100-Q03 Lockout Trip_11AEA02GS100-Q03 Lockout Trip_11AEA03GS100-Q03 Lockout Trip_11AEA04GS100-Q03 SPARE SPARE SPARE PROTECTION FAULT PROTECTION STOP

Signal To CSCS

87BB General Trip+(F1F4_50BF Trip) 87BB Feeder 1+ 50BF Q03 F1

LOCKOUT Trip

87BB Feeder 2+ 50BF Q03 F2 87BB Feeder 3+ 50BF Q03 F3 87BB Feeder 4+ 50BF Q03 F4