You are on page 1of 56

technical data

air conditioning systems


Air-cooled selection procedure

Air-cooled selection procedure

TABLE OF CONTENTS 1 Air-cooled selection procedure

Selection procedure VRVIII system based on cooling load . . . 2


Indoor unit selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Outdoor unit selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Actual performance data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selection example based on cooling load . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 2 3 3

Capacity correction ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5


VRVIII-S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 VRVIII cooling only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 VRVIII heat pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 VRVIII heat recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

3 4 5 6

Integrated heating capacity coefficient . . . . . . . . . . . . . . . . . . . . . . . . .

36

Refnet pipe systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Example of Refnet piping layouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


47

Refrigerant pipe selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48


VRVIII-S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VRVIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VRVIII heat recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Piping thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
48 49 51 54

VRV Systems Air-cooled selection procedure

Air-cooled selection procedure

1
1-1

Selection procedure VRVIII system based on cooling load


Indoor unit selection

Enter indoor unit capacity tables at given indoor and outdoor temperature. Select the unit that the capacity is the nearest to and higher than the given load.

NOTE

Individual indoor unit capacity is subject to change by the combination. Actual capacity has to be calculated according to the combination by using outdoor units capacity table.

1
1

1-2

Outdoor unit selection

Allowable combinations are indicated in indoor unit combination total capacity index table. In general, oudoor units can be selected as follows though the location of the unit, zoning and usage of the rooms should be considered. The indoor and outdoor unit combination is determined that the sum of indoor unit capacity index is nearest to and smaller than the capacity index at 100 % combination ratio of each outdoor unit. Up to 16 indoor units can be connected to one outdoor unit. It is recommended to choose a larger outdoor unit if the installation space is large enough. If the combination ratio is higher than 100 %, the indoor unit selection will have to be reviewed by using actual capacity of each indoor unit. Indoor unit combination total capacity index table Outdoor unit RXYSQ4PV / RXYSQ4PY1 RXYSQ5PV / RXYSQ5PY1 RXYSQ6PV / RXYSQ6PY1 Outdoor unit RX(Y)Q5P RX(Y)Q8P/REYQ8P RX(Y)Q10P/REYQ10P RX(Y)Q12P/REYQ12P RX(Y)Q14PA/REYQ14P RX(Y)Q16PA/REYQ16P RX(Y)Q18PA/REYQ18P RXYQ20P(A)/REYQ20P RXYQ22P(A)/REYQ22P RXYQ24P(A)/REYQ24P RXYQ26P(A)/REYQ26P RXYQ28P(A)/REYQ28P RXYQ30P(A)/REYQ30P RXYQ32P(A)/REYQ32P RXYQ34P(A)/REYQ34P RXYQ36P(A)/REYQ36P RXYQ38P(A)/REYQ38P RXYQ40P(A)/REYQ40P RXYQ42P(A)/REYQ42P RXYQ44P(A)/REYQ44P RXYQ46P(A)/REYQ46P RXYQ48P(A)/REYQ48P RXYQ50P(A) RXYQ52P(A) RXYQ54P(A)
130 % 130 162.5 182 120 % 120 150 168 110 % 110 137.5 154 100 % 100 125 140 Indoor unit combination ratio 90 % 90 112.5 126 Indoor unit combination ratio 90 % 112.5 180 225 270 315 360 405 450 495 540 585 630 675 720 765 810 855 900 945 990 1,035 1,080 1,125 1,170 1,215 80 % 80 100 112 70% 70 87.5 98 60 % 60 75 84 50 % 50 62.5 70

130 % 162.5 260 325 390 455 520 585 650 715 780 845 910 975 1,040 1,105 1,170 1,235 1,300 1,365 1,430 1,495 1,560 1,625 1,690 1,755

120 % 150 240 300 360 420 480 540 600 660 720 780 840 900 960 1,020 1,080 1,140 1,200 1,260 1,320 1,380 1,440 1,500 1,560 1,620

110 % 137.5 220 275 330 385 440 495 550 605 660 715 770 825 880 935 990 1,045 1,100 1,155 1,210 1,265 1,320 1,375 1,430 1,485

100 % 125 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1,000 1,050 1,100 1,150 1,200 1,250 1,300 1,350

80 % 100 160 200 240 280 320 360 400 440 480 520 560 600 640 680 720 760 800 840 880 920 960 1,000 1,040 1,080

70% 87.5 140 175 210 245 280 315 350 385 420 455 490 525 560 595 630 665 700 735 770 805 840 875 910 945

60 % 75 120 150 180 210 240 270 300 330 360 390 420 450 480 510 540 570 600 630 660 690 720 750 780 810

50 % 62.5 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 625 650 675

Indoor unit capacity index Model Capacity index


20 20 25 25 32 31.25 40 40 50 50 63 62.5 71 71 80 80 100 100 125 125 200 200 250 250

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

1
1-3

Selection procedure VRVIII system based on cooling load


Actual performance data

Use outdoor unit capacity tables Determine the correct table according to the outdoor unit model and combination ratio. Enter the table at given indoor and outdoor temperature and find the outdoor capacity and power input. The individual indoor unit capacity (power input) can be calculated as follows: ICA = OCA x INX TNX ICA: Individual indoor unit capacity (power input) OCA: Outdoor unit capacity (power input) INX: Individual indoor unit capacity index TNX: Total capacity index Then, correct the indoor unit capacity according to the piping length. If the corrected capacity is smaller than the load, the size of indoor unit has to be increased. Repeat the same selection procedure.

1
1

1-4
1 Given

Selection example based on cooling load

Design condition Cooling: indoor 20CWB, outdoor 33CDB Cooling load Room Load (kW)
A 2.9 B 2.7 C 2.5 D 4.3 E 4.0 F 4.0 G 3.9 H 4.2

Power supply: 3-phase 380V/50Hz Indoor unit selection

Enter indoor unit capacity table at: 20CWB indoor temperature 33CDB outdoor air temperature. Selection results are as follows: Room Load (kW) Unit size Capacity 3
A 2.9 25 3.0 B 2.7 25 3.0 C 2.5 25 3.0 D 4.3 40 4.8 E 4.0 40 4.8 F 4.0 40 4.8 G 3.9 40 4.8 H 4.2 40 4.8

Outdoor unit selection Assume that the indoor and outdoor unit combination is as follows. Outdoor unit: RXYQ10P Indoor unit: FXCQ25M8 x 3, FXCQ40M8 x 5 Indoor unit combination total capacity index 25 x 3 + 40 x 5 = 275 (110 %)

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

1
1-4
4

Selection procedure VRVIII system based on cooling load


Selection example based on cooling load
Actual performance data (50Hz) Outdoor unit cooling capacity: 30.5kW (RXYQ10P, 110 %) Individual capacity Capacity of FXCQ25M Capacity of FXCQ40M = 30.5 x = 30.5 x 25 275 40 275 = 2.77kW = 4.44kW

Actual combination capacity

1
1

Room Load (kW) Unit size Capacity

A 2.9 25 2.77

B 2.7 25 2.77

C 2.5 25 2.77

D 4.3 40 4.44

E 4.0 40 4.44

F 4.0 40 4.44

G 3.9 40 4.44

H 4.2 40 4.44

The unit size for room A has to be increased from 25 to 32 because the capacity is less than the load. For new combination, actual capacity is calculated as follows. Indoor unit combination total capacity index (25 x 2) +31.25 + (40 x5) = 281.25 (112.5 %) Outdoor unit cooling capacity: 27,610 kcal/h (direct interpolation between 110 % and 120 % in the table) Individual capacity Capacity of FXCQ25M Capacity of FXCQ32M Capacity of FXCQ40M = 30.0 x 25 = 2.7kW 281.25 = 30.0 x 32 = 3.4kW 281.25 = 30.0 x 40 = 4.3kW 281.25

Actual capacity of new combination Room Load (kW) Unit size Capacity
A 2.9 32 3.4 B 2.7 25 2.7 C 2.5 25 2.7 D 4.3 40 4.3 E 4.0 40 4.3 F 4.0 40 4.3 G 3.9 40 4.3 H 4.2 40 4.3

Then, the capacities have to be corrected for actual piping length according to the location of indoor and outdoor units and the distance between them.

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-1

Capacity correction ratio


VRVIII-S
RXYSQ4,5PV/RXYSQ4,5PY1
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

1
2
3D045710C NOTES 1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. 3. Method of calculating cooling / heating capacity (max. capacity for combination with standard indoor unit). Cooling / heating capacity = cooling / heating capacity obtained from performance characteristics table x each capacity rate of change In the case length of piping differs depending on the indoor unit, maximum capacity of each unit during simultaneous operation is: Cooling / heating capacity = cooling / heating capacity of each unit x capacity rate of change for each piping length <As for RXYSQ4,5P7V3B> 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. [Diameter of above case]

Model RXYSQ4, 5P7V3B RXYSQ4, 5P7Y1B

Gas J19.1

Liquid Not increased

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example: : RXYSQ4, 5P7V3B : RXYSQ4, 5P7Y1B
Equivalent length Equivalent length

Indoor unit Outdoor unit Size increase

Branch

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.78. Explanation of symbols Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipes]

Model RXYSQ4, 5P7V3B RXYSQ4, 5P7Y1B

Gas J15.9

Liquid J9.5

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-1

Capacity correction ratio


VRVIII-S
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

RXYSQ6PV/RXYSQ6PY1

1
2
3D045961C NOTES 1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. 3. Method of calculating cooling / heating capacity (max. capacity for combination with standard indoor unit). Cooling / heating capacity = cooling / heating capacity obtained from performance characteristics table X each capacity rate of change In the case length of piping differs depending on the indoor unit, maximum capacity of each unit during simultaneous operation is: Cooling / heating capacity = cooling / heating capacity of each unit X capacity rate of change for each piping length <As for RXYSQ6P7V3B> 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. [Diameter of above case]

Model RXYSQ6P7V3B RXYSQ6P7Y1B

Gas J22.2

Liquid Not increased

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example: : RXYSQ6P7V3B : RXYSQ6P7Y1B
Equivalent length Equivalent length

Indoor unit Outdoor unit Size increase

Branch

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.86. Explanation of symbols Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipes]

Model RXYSQ6P7V3B RXYSQ6P7Y1B

Gas J19.1

Liquid J9.5

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-2

Capacity correction ratio


VRVIII cooling only
RXQ5P
Correction ratio for cooling capacity
60 50 40 30 20 10 0 0 -10 -20 -30 -40 -50 Height difference between outdoor and farest indoor (m) 0.86 0.94 0.92 0.90 0.88 0.84 0.82 0.80 0.78 0.76 0.74

1.00

0.98

0.96

10 1.00

20 0.98 0.96

30

40

50

60

70

80

90

100

110

0.94

0.92 0.90 0.88 0.86 0.84 0.82 0.80 0.78 0.76 Equivalent piping length

3TW27302-6
NOTES

1
2

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXQ5P gas pipe 19.1 liquid pipe 9.5

When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXQ5P gas pipe 15.9 liquid pipe 9.5

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size. Correction factor Standard size Size increase 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.78

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-2

Capacity correction ratio


VRVIII cooling only
RXQ8P
Correction ratio for cooling capacity
60 Height difference between outdoor and farest indoor (m) 50 40 30 20 10 -10 -20 -30 -40 -50 1.00 20 0.98 0.96 0.94 0.92 0.90 0.88 0.86 0.84 Equivalent piping length (m) 30 40 50 60 70 80 90 100 110 0 0.75 0 10 1.00 0.98 0.96 0.94 0.92 0.90 0.88 0.86 0.84 0.82

1
2
1 2 3

3TW27302-6
NOTES

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXQ8P gas pipe 22.2 liquid pipe 12.7

When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXQ8P gas pipe 19.1 liquid pipe 9.5

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size. Correction factor Standard size Size increase 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.86

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-2

Capacity correction ratio


VRVIII cooling only
RXQ10P
Correction ratio for cooling capacity
60 0.90 0.88 0.86 0.84 0.82 0.80 50 0.92 40 0.94 30 0.96 20 0.98 10 1.00 0 0 40 60 80 100 120 140 160 20 -10 1.00 -20 0.98 -30 0.96 -40 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 -50 Equivalent piping length (m) Height difference between outdoor and farest indoor (m) 0.78

180

0.78

3TW27302-6
NOTES

1
2

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXQ10P gas pipe 25.4* liquid pipe 12.7

* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6). 5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXQ10P 6 gas pipe 22.2 liquid pipe 9.5

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size. Correction factor Standard size Size increase 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.87

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-2

Capacity correction ratio


VRVIII cooling only
RXQ12,14P
Correction ratio for cooling capacity
60 0.92 0.90 0.88 0.86 0.94 50 0.96 40 30 0.98 20 10 1.00 0 40 60 80 0 100 120 140 160 20 -10 1.00 -20 -30 0.98 -40 0.96 0.94 0.92 0.90 0.88 0.86 -50 Equivalent piping length (m) Height difference between outdoor and farest indoor (m) 0.84

180

1
2
1
NOTES

0.84

3TW27302-6

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXQ12-14P gas pipe 28.6 liquid pipe 15.9

When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXQ12-14P gas pipe 28.6 liquid pipe 12.7

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size. Correction factor Standard size Size increase 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.89

10

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-2

Capacity correction ratio


VRVIII cooling only
RXQ16P
Correction ratio for cooling capacity
60 Height difference between outdoor and farest indoor (m) 50 0.92 0.90 0.88 0.86 0.84 0.82 0.80 0.78

0.94 40 0.96 30 0.98 20 10 1.00 00 20 40 60 80 -10 1.00 -20 0.98 -30 0.96 -40 0.94 0.92 0.90 0.88 -50

100

120

140

160

180

0.86 0.84 0.82 Equivalent piping length

0.80

0.78

3TW27302-6
NOTES

1
2

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXQ5P gas pipe 31.8* liquid pipe 15.9

When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXQ5P gas pipe 28.6 liquid pipe 12.7

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size. Correction factor Standard size Size increase 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.88

VRV Systems Air cooled selection procedure

11

Air-cooled selection procedure

2
2-2

Capacity correction ratio


VRVIII cooling only
RXQ18P
Correction ratio for cooling capacity
60 0.84 0.82 0.92 0.90 0.88 0.86 50 0.94 40 0.96 30 0.98 20 10 1.00 0 20 100 0 120 140 80 40 60 -10 1.00 -20 0.98 -30 0.96 -40 0.94 0.92 0.90 0.88 0.86 0.84 0.82 -50 Equivalent piping length Height difference between outdoor and farest indoor (m) 0.80 0.78

160

180

1
2
1
NOTES

0.80

0.78

3TW27302-6

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXQ18P gas pipe 31.8* liquid pipe 19.1

* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6). 5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXQ18P 6 gas pipe 28.6 liquid pipe 15.9

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size . Correction factor Standard size Size increase 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.83

12

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
RXYQ5P
Correction ratio for cooling capacity
60 Height difference between outdoor and farest indoor (m) 50 40 30 20 10 0 -10 0 -20 -30 -40 -50 10 1.00 20 0.98 0.96 30 40 50 60 70 80 90 100 110 1.00 0.98 0.96 0.94 0.92 0.90 0.86 0.88 0.84 0.82 0.80 0.78 0.76 0.74

Height difference between outdoor and farest indoor (m)

Correction ratio for heating capacity


60 50 40 30 20 10 0 -10 -10 -20 -30 -40 -50 Equivalent piping length (m) 1.00 10 1.00 30 50 70 90 110 130 150 170 190

0.94

0.92 0.90 0.88 0.86 0.84 0.82 0.80 0.78 0.76 Equivalent piping length

3TW27232-6
NOTES

1
2

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ5P gas pipe 19.1 liquid pipe 9.5

When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ5P gas pipe 15.9 liquid pipe 9.5

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 120m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.78 heating capacity when height difference = 0 is thus approximately 1.0

VRV Systems Air cooled selection procedure

13

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
RXYQ8P
Correction ratio for cooling capacity
60 Height difference between outdoor and farest indoor (m) 50 40 30 20 10 1.00 10 1.00 0.98 0.96 0.94 0.92 0.90 0.88 Equivalent piping length 0.86 0.84 20 30 40 50 60 70 80 90 100 110 0 0.70 0 -10 -20 -30 -40 -50 0.98 0.96 0.94 0.92 0.90 0.88 0.86 0.84 0.82

Correction ratio for heating capacity


60 Height difference between outdoor and farest indoor (m) 50 40 30 20 10 0 -10 -20 -30 -40 -50 Equivalent piping length (m) 0 1.00 10 1.00 20 30 40 50 60 70 80 90 100 110

1
2
1 2 3

3TW27232-6
NOTES

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ8P gas pipe 22.2 liquid pipe 12.7

When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ8P gas pipe 19.1 liquid pipe 9.5

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.86 heating capacity when height difference = 0 is thus approximately 1.0

14

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
RXYQ10P
Correction ratio for cooling capacity
60 0.90 0.88 0.86 0.84 0.82 0.80 50 0.92 40 0.94 30 0.96 0.98 20 10 1.00 0 40 60 80 20 100 120 140 160 0 -10 1.00 -20 0.98 -30 0.96 -40 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 -50 Equivalent piping length Height difference between outdoor and farest indoor (m) 0.78

Correction ratio for heating capacity


60 Height difference between outdoor and farest indoor (m) 50 40 30 20 10 0 -10 -20 -30 -40 -50 0.98 0.96 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 Equivalent piping length (m) 0 1.00 10 1.00 20 30 40 50 60 70 80 90 100 110 0.98 0.96 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80

180

0.78

3TW27232-6
NOTES

1
2

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ10P gas pipe 25.4* liquid pipe 12.7

* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6). 5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ10P 6 gas pipe 22.2 liquid pipe 9.5

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.87 heating capacity when height difference = 0 is thus approximately 0.90

VRV Systems Air cooled selection procedure

15

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
Correction ratio for heating capacity

RXYQ12,14,24,36P
Correction ratio for cooling capacity
Heigth difference between outdoor and farest indoor (m)

Heigth difference between outdoor and farest indoor (m)

Equivalent piping length (m)

1
2

Equivalent piping length (m)

Notes 1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. 3. Method of calculating the capacity of the outdoor units The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = X Maximum capacity of outdoor units = X Capacity of outdoor units from capacity table at 100% connection ratio Correction ratio of piping to farest indoor Capacity of outdoor units from capacity table at installed connection ratio Correction ratio of piping to farest indoor

Condition: Indoor connection ratio exceeds 100%

4. When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased. For new diameters, see below.

model RXYQ12+14P RXYQ24P RXYQ36P model RXYQ12+14P RXYQ24P RXYQ36P

Gas pipe 28,6 34,9 41,3 Gas pipe 28,6 34,9 41,3
=

Liquid pipe 15,9 19,1 22,2 Liquid pipe 12,7 15,9 19,1

5. When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual).

6. Equivalent length used in the above figures is based upon the following equivalent length Equivalent piping length Equivalent length of main pipe X Correction factor Correction factor

+ Equivalent length of branch pipes X

Choose the correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size

Cooling (Gas pipe) Heating (Liquid pipe)


Example

Correction factor Standard size Size increase 1,0 0,5 1,0 0,5
Branch gas pipe size increase Branch liquid pipe size increase

Main gas pipe size increase Main liquid pipe size increase

In the above case (Cooling) Overall equivalent length = 80mx1,0 + 40mx1,0 = 120m (Heating) Overall equivalent length = 80mx0,5 + 40mx1,0 = 80m The rate of change in: Cooling capacity when heigth difference = 0 is thus approximately 0,89 Heating capacity when heigth difference = 0 is thus approximately 1,0

3TW27232-6A

16

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
RXYQ16P
Correction ratio for cooling capacity
60 0.80 0.79 0.92 0.90 0.88 0.86 0.84 0.82 50 0.94 40 0.96 30 0.98 20 10 1.00 0 20 40 60 80 100 120 140 160 180 0 -10 1.00 -20 0.98 -30 0.96 -40 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 0.79 -50 Equivalent piping length Height difference between outdoor and farest indoor (m)

Correction ratio for heating capacity


60 Height difference between outdoor and farest indoor (m) 50 40 30 20 10 0 -10 -20 -30 -40 -50 Equivalent piping length (m) 0.99 0.97 0.95 0.93 0 1.00 10 1.00 20 30 40 50 60 70 80 90 100 110 0.99 0.97 0.95 0.93

3TW27232-6
NOTES

1
2

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ16P gas pipe 31.8* liquid pipe 15.9

* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6). 5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ16P 6 gas pipe 28.6 liquid pipe 12.7

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.88 heating capacity when height difference = 0 is thus approximately 0.99

VRV Systems Air cooled selection procedure

17

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
Correction ratio for heating capacity
60 Height difference between outdoor and farest indoor (m) 50 40 30 20 10 0 -10 -20 -30 -40 -50 Equivalent piping length (m) 0 1.00 10 1.00 20 30 40 50 60 70 80 90 100 110

RXYQ18,26,28,30,38,40,42,44P
Correction ratio for cooling capacity
60 0.80 0.79 0.92 0.90 0.88 0.86 0.84 0.82 50 0.94 40 0.96 30 0.98 20 1.00 10 0 40 60 80 100 120 140 160 180 0 20 -10 1.00 -20 0.98 -30 0.96 -40 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 0.79 -50 Equivalent piping length Height difference between outdoor and farest indoor (m)

1
2
1
NOTES

3TW27232-6

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ18P RXYQ26-30P RXYQ38-44P gas pipe 31.8* 38.1* 41.3 liquid pipe 19.1 22.2 22.2

* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6). 5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ18P RXYQ26-30P RXYQ38-44P 6 gas pipe 28.6 34.9 41.3 liquid pipe 15.9 19.1 19.1

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.83 heating capacity when height difference = 0 is thus approximately 1.0

18

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
RXYQ20,32,34P
Correction ratio for cooling capacity
60 0.80 0.78 50 0.92 0.90 0.88 0.86 0.84 0.82 40 0.94 30 0.96 20 0.98 10 1.00 0 20 40 60 80 100 120 140 160 180 0 -10 1.00 -20 0.98 -30 0.96 -40 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 0.78 -50 Equivalent piping length Height difference between outdoor and farest indoor (m)

Correction ratio for heating capacity


60 Height difference between outdoor and farest indoor (m) 50 40 30 20 10 0 -10 -20 -30 -40 -50 Equivalent piping length (m) 0 1.00 10 1.00 20 30 40 50 60 70 80 90 100 110

3TW27232-6
NOTES

1
2

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ20P RXYQ32-34P gas pipe 31.8* 38.1* liquid pipe 19.1 22.2

* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6). 5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ20P RXYQ32-34P 6 gas pipe 28.6 34.9 liquid pipe 15.9 19.1

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.88 heating capacity when height difference = 0 is thus approximately 1.0

VRV Systems Air cooled selection procedure

19

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
RXYQ22P
Correction ratio for cooling capacity
60 0.80 0.92 0.90 0.88 0.86 0.84 0.82 50 0.94 40 0.96 30 0.98 20 1.00 10 0 0.70 20 40 60 80 100 120 140 160 0 -10 -20 1.00 -30 0.98 -40 0.96 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 -50 Equivalent piping length Height difference between outdoor and farest indoor (m) 0.78

Correction ratio for heating capacity


60 50 40 30 20 10 0 0 -10 -20 -30 -40 -50 Height difference between outdoor and farest indoor (m)

1.00 10 1.00 20 30 40 50 60 70 80 90 100 110

180

1
2
1
NOTES

Equivalent piping length (m)

3TW27232-6

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ22P gas pipe 31.8* liquid pipe 19.1

* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6). 5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ22P 6 gas pipe 28.6 liquid pipe 15.9

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.88 heating capacity when height difference = 0 is thus approximately 1.0

20

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
RXYQ46P
Correction ratio for cooling capacity
60 0.90 0.88 0.86 0.84 0.82 0.80 0.78 50 0.92 40 0.94 30 0.96 0.98 20 10 1.00 0 40 60 80 100 120 140 160 180 0 20 -10 1.00 -20 0.98 -30 0.96 -40 0.78 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 -50 Equivalent piping length Height difference between outdoor and farest indoor (m)

Correction ratio for heating capacity


60 50 40 30 20 10 0 0 -10 -20 -30 -40 -50 Height difference between outdoor and farest indoor (m) 0.99 0.97 0.95

1.00 10 1.00 20 30 40 50 60 70 80 90 100 110

Equivalent piping length (m)

0.99 0.97 0.95

3TW27232-6
NOTES

1
2

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ46P gas pipe 41.3 liquid pipe 22.2

When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ46P gas pipe 41.3 liquid pipe 19.1

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.83 heating capacity when height difference = 0 is thus approximately 1.0

VRV Systems Air cooled selection procedure

21

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
RXYQ48P
Correction ratio for cooling capacity
60 0.90 0.88 0.86 0.84 0.82 0.80 0.78 50 0.92 40 0.94 30 0.96 0.98 20 10 1.00 0 40 60 80 100 120 140 160 180 0 20 -10 1.00 -20 0.98 -30 0.96 -40 0.78 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 -50 Equivalent piping length Height difference between outdoor and farest indoor (m)

Correction ratio for heating capacity


60 50 40 30 20 10 0 0 -10 -20 -30 -40 -50 Height difference between outdoor and farest indoor (m) 0.99 0.97 0.95 0.93 0.91 0.89

1.00 10 1.00 20 30 40 50 60 70 80 90 100 110

1
2
1
NOTES

Equivalent piping length (m)

0.99 0.97 0.95 0.93 0.91 0.89

3TW27232-6

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ48P gas pipe 41.3 liquid pipe 22.2

When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ48P gas pipe 41.3 liquid pipe 19.1

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.83 heating capacity when height difference = 0 is thus approximately 0.97

22

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
RXYQ50P
Correction ratio for cooling capacity
60 0.90 0.88 0.86 0.84 0.82 0.80 0.78 50 0.92 40 0.94 30 0.96 0.98 20 10 1.00 0 0.70 40 60 80 100 120 140 160 180 0 20 -10 1.00 -20 0.98 -30 0.96 -40 0.78 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 -50 Equivalent piping length Height difference between outdoor and farest indoor (m)

Correction ratio for heating capacity


60 50 40 30 20 10 0 0 -10 -20 -30 -40 -50 Height difference between outdoor and farest indoor (m) 0.99 0.97 0.95 0.93 0.91 0.89 0.87 0.85

1.00 10 1.00 20 30 40 50 60 70 80 90 100 110

0.99 0.97 0.95 0.93 0.91 0.89 0.87 0.85 Equivalent piping length (m)

3TW27232-6
NOTES

1
2

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ50P gas pipe 41.3 liquid pipe 22.2

When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ50P gas pipe 41.3 liquid pipe 19.1

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.83 heating capacity when height difference = 0 is thus approximately 0.92

VRV Systems Air cooled selection procedure

23

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
RXYQ52P
Correction ratio for cooling capacity
60 0.90 0.88 0.86 0.84 0.82 0.80 0.78 0.92 50 40 0.94 0.96 30 20 0.98 1.00 10 0 0.70 40 60 80 100 120 140 160 180 0 20 -10 1.00 -20 0.98 -30 0.96 -40 0.78 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 -50 Equivalent piping length Height difference between outdoor and farest indoor (m)

Correction ratio for heating capacity


60 50 40 30 20 10 0 0 -10 -20 -30 -40 -50 Height difference between outdoor and farest indoor (m) 0.98 0.00 0.04 0.02 0.00 0.00 0.00 0.04 0.02 0.00 0.99

1.00 10 1.00 20 30 40 50 60 70 80 90 100 110

1
2
1
NOTES

0.99 0.980.00 0.04 0.02 0.00 0.00 0.00 0.04 0.02 0.00 Equivalent piping length (m)

3TW27232-6

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ52P gas pipe 41.3 liquid pipe 22.2

When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ52P gas pipe 41.3 liquid pipe 19.1

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.83 heating capacity when height difference = 0 is thus approximately 0.88

24

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-3

Capacity correction ratio


VRVIII heat pump
RXYQ54P
Correction ratio for cooling capacity
Height difference between outdoor and farest indoor (m) 60 0.92 0.90 0.88 0.86 0.84 50 0.94 40 0.96 30 0.98 20 10 1.00 0 40 60 80 100 20 -100 1.00 -20 0.98 -30 -40 -50 0.96 0.94 0.92 0.90 0.88 0.86 0.84 0.82 Equivalent piping length 0.80 0.78 0.82 0.80 0.78

Correction ratio for heating capacity


60 50 40 30 20 10 0 0 -10 -20 -30 -40 -50 Height difference between outdoor and farest indoor (m) 0.95 0.93 0.91 0.89 0.89 0.85 0.83 0.81 0.79 0.77 0.75

0.99 1.00

0.97

120

140

160

180

10

20

30

40

50

60

70

80

90

100

110

1.00

0.99

0.97 0.95 0.93 0.91 0.89 0.89 0.85 0.83 0.81 0.79 0.77 0.75 Equivalent piping length (m)

3TW27232-6
NOTES

1
2

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures. With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out. Method of calculating the capacity of the outdoor units: The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller. Condition: Indoor connection ratio does not exceed 100% Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio x correction ratio of piping to farest indoor Condition: Indoor connection ratio exceeds 100% Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio x correction ratio of piping to farest indoor

2 3

When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased.. For new diameters see below. Model RXYQ54P gas pipe 41.3 liquid pipe 22.2

When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual). Diameter of main pipes (standard size) Model RXYQ54P gas pipe 41.3 liquid pipe 19.1

Equivalent length used in the above figures is based upon the following equivalent length. Equivalent piping length = Equivalent length of main pipe x Correction factor + Equivalent length of branch pipes x Correction factor Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size. Correction factor Standard size Size increase 1.0 0.5 1.0 0.5
Branch gas pipe size increase Branch liquid pipe size increase 40 m

Cooling (gas pipe) Heating (liquid pipe) 7 Example

Main gas pipe size increase Main liquid pipe size increase 80 m

In the above case (Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m (Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m The rate of change in: cooling capacity when height difference = 0 is thus approximately 0.83 heating capacity when height difference = 0 is thus approximately 0.83

VRV Systems Air cooled selection procedure

25

Air-cooled selection procedure

2
2-4

Capacity correction ratio


VRVIII heat recovery
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

REYQ8,22P

1
2

3D057931A NOTES
1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. 3. Method of calculating A/C (cooling/heating) capacity: The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristic table or the maximum A/C capacity of outdoor units as mentioned bellow, whichever smaller. Calculating A/C capacity of outdoor units Condition: Indoor unit combination ratio does not exceed 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination X Capacity change rate due to piping length to the farthest indoor unit Condition: Indoor unit combination ratio exceeds 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination X Capacity change rate due to piping length to the farthest indoor unit 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. When level difference is 50m or more, the diameter of the main liquid pipe (outdoor unit-branch sections) must be increased. [Diameter of above case]

Model REYQ8PY1 REYQ22PY1

Liquid J12.7 J19.1

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only) Overall equivalent length = Equivalent length to main pipe x Correction factor + Equivalent length after branching [Choose a correction factor from the following table]

Model REYQ8PY1 REYQ22PY1

Correction factor 0.2 0.4


Equivalent length Equivalent length

(Example) In case of REYQ22PY1

Indoor unit Outdoor unit Liquid pipe: Size increase Branch BS unit

In the above case (Heating) Overall equivalent length = 80m x 0.4 + 40m = 72m The correction factor in capacity when Hp=0m is thus approximately 1.0. 6. In the combination which does not include cooling only indoor unit, Calculate the equivalent length pipe by the following when you calculate cooling capacity. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Branch BS unit

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.88.

Explanation of symbols
Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipe (standard size)]

Model REYQ8PY1 REYQ22PY1

Liquid J9.5 J15.9

26

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-4

Capacity correction ratio


VRVIII heat recovery
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

REYQ10P

3D058181 NOTES 1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. 3. Method of calculating A/C (cooling/heating) capacity: The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristic table or the maximum A/C capacity of outdoor units as mentioned bellow, whichever smaller. Calculating A/C capacity of outdoor units Condition: Indoor unit combination ratio does not exceed 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination X Capacity change rate due to piping length to the farthest indoor unit Condition: Indoor unit combination ratio exceeds 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination X Capacity change rate due to piping length to the farthest indoor unit 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. When level difference is 50m or more, the diameter of the main liquid pipe (outdoor unit-branch sections) must be increased. [Diameter of above case]

1
2

Model REYQ10PY1

Liquid J12.7

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only) Overall equivalent length = Equivalent length to main pipe x 0.2 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Liquid pipe: Size increase Branch BS unit

In the above case (Heating) Overall equivalent length = 80m x 0.2 + 40m = 56m The correction factor in capacity when Hp=0m is thus approximately 1.0. 6. In the combination which does not include cooling only indoor unit, Calculate the equivalent length pipe by the following when you calculate cooling capacity. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Branch BS unit

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.88. Explanation of symbols Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipe (standard size)]

Model REYQ10PY1

Liquid J9.5

VRV Systems Air cooled selection procedure

27

Air-cooled selection procedure

2
2-4

Capacity correction ratio


VRVIII heat recovery
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

REYQ12,18,20,28,30,38,40,42,44P

3D057935A

1
2

NOTES
1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. 3. Method of calculating A/C (cooling/heating) capacity: The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristic table or the maximum A/C capacity of outdoor units as mentioned bellow, whichever smaller. Calculating A/C capacity of outdoor units Condition: Indoor unit combination ratio does not exceed 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination X Capacity change rate due to piping length to the farthest indoor unit Condition: Indoor unit combination ratio exceeds 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination X Capacity change rate due to piping length to the farthest indoor unit 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. When level difference is 50m or more, the diameter of the main liquid pipe (outdoor unit-branch sections) must be increased. [Diameter of above case]
Model REYQ12PY1 REYQ18PY1 REYQ26PY1 REYQ28PY1 Liquid J15.9 J19.1 J22.2 Model REYQ30PY1 REYQ38PY1 REYQ40PY1 REYQ42PY1 Liquid J22.2 Model REYQ44PY1 Liquid J22.2

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only) Overall equivalent length = Equivalent length to main pipe x Correction factor + Equivalent length after branching [Choose a correction factor from the following table]
Model REYQ12PY1 REYQ18PY1 REYQ26PY1 REYQ28PY1 REYQ30PY1
Equivalent length

Correction factor 0.3 0.4

Model REYQ38PY1 REYQ40PY1 REYQ42PY1 REYQ44PY1

Correction factor 0.4

(Example) In case of REYQ18PY1


Equivalent length

Indoor unit Outdoor unit Liquid pipe: Size increase Branch BS unit

In the above case (Heating) Overall equivalent length = 80m x 0.4 + 40m = 72m The correction factor in capacity when Hp=0m is thus approximately 1.0. 6. In the combination which does not include cooling only indoor unit, Calculate the equivalent length pipe by the following when you calculate cooling capacity. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Branch BS unit

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.88.

Explanation of symbols
Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipe (standard size)]
Model REYQ12PY1 REYQ18PY1 REYQ26PY1 REYQ28PY1 REYQ30PY1 Liquid J12.7 J15.9 J19.1 Model REYQ38PY1 REYQ40PY1 REYQ42PY1 REYQ44PY1 Liquid J19.1

28

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-4
2-4-1

Capacity correction ratio


VRVIII heat recovery
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

REYQ14P

3D058182 NOTES 1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. 3. Method of calculating A/C (cooling/heating) capacity: The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristic table or the maximum A/C capacity of outdoor units as mentioned bellow, whichever smaller. Calculating A/C capacity of outdoor units Condition: Indoor unit combination ratio does not exceed 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination X Capacity change rate due to piping length to the farthest indoor unit Condition: Indoor unit combination ratio exceeds 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination X Capacity change rate due to piping length to the farthest indoor unit 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. When level difference is 50m or more, the diameter of the main liquid pipe (outdoor unit-branch sections) must be increased. [Diameter of above case]

1
2

Model REYQ14PY1

Liquid J15.9

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only) Overall equivalent length = Equivalent length to main pipe x 0.3 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Liquid pipe: Size increase Branch BS unit

In the above case (Heating) Overall equivalent length = 80m x 0.3 + 40m = 64m The correction factor in capacity when Hp=0m is thus approximately 1.0. 6. In the combination which does not include cooling only indoor unit, Calculate the equivalent length pipe by the following when you calculate cooling capacity. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Branch BS unit

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.96. Explanation of symbols Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipe (standard size)]

Model REYQ14PY1

Liquid J12.7

VRV Systems Air cooled selection procedure

29

Air-cooled selection procedure

2
2-4

Capacity correction ratio


VRVIII heat recovery
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

REYQ16P

1
2
NOTES 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.

3D058183

1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 3. Method of calculating A/C (cooling/heating) capacity: The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristic table or the maximum A/C capacity of outdoor units as mentioned bellow, whichever smaller. Calculating A/C capacity of outdoor units Condition: Indoor unit combination ratio does not exceed 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination X Capacity change rate due to piping length to the farthest indoor unit Condition: Indoor unit combination ratio exceeds 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination X Capacity change rate due to piping length to the farthest indoor unit 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. When level difference is 50m or more, the diameter of the main liquid pipe (outdoor unit-branch sections) must be increased. [Diameter of above case]

Model REYQ16PY1

Liquid J15.9

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only) Overall equivalent length = Equivalent length to main pipe x 0.3 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Liquid pipe: Size increase Branch BS unit

In the above case (Heating) Overall equivalent length = 80m x 0.3 + 40m = 64m The correction factor in capacity when Hp=0m is thus approximately 1.0. 6. In the combination which does not include cooling only indoor unit, Calculate the equivalent length pipe by the following when you calculate cooling capacity. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Branch BS unit

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.93. Explanation of symbols Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipe (standard size)]

Model REYQ16PY1

Liquid J12.7

30

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-4

Capacity correction ratio


VRVIII heat recovery
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

REYQ20,32,34P

3D057933 NOTES 1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. 3. Method of calculating A/C (cooling/heating) capacity: The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristic table or the maximum A/C capacity of outdoor units as mentioned bellow, whichever smaller. Calculating A/C capacity of outdoor units Condition: Indoor unit combination ratio does not exceed 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination X Capacity change rate due to piping length to the farthest indoor unit Condition: Indoor unit combination ratio exceeds 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination X Capacity change rate due to piping length to the farthest indoor unit 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. When level difference is 50m or more, the diameter of the main liquid pipe (outdoor unit-branch sections) must be increased. [Diameter of above case]

1
2

Model REYQ20PY1 REYQ32PY1 REYQ34PY1

Liquid J19.1 J22.2

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only) Overall equivalent length = Equivalent length to main pipe x 0.4 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Liquid pipe: Size increase Branch BS unit

In the above case (Heating) Overall equivalent length = 80m x 0.4 + 40m = 72m The correction factor in capacity when Hp=0m is thus approximately 1.0. 6. In the combination which does not include cooling only indoor unit, Calculate the equivalent length pipe by the following when you calculate cooling capacity. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Branch BS unit

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.88. Explanation of symbols Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipe (standard size)]

Model REYQ20PY1 REYQ32PY1 REYQ34PY1

Liquid J15.9 J19.1

VRV Systems Air cooled selection procedure

31

Air-cooled selection procedure

2
2-4

Capacity correction ratio


VRVIII heat recovery
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

REYQ24P

1
2
NOTES 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.

3D057932

1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 3. Method of calculating A/C (cooling/heating) capacity: The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristic table or the maximum A/C capacity of outdoor units as mentioned bellow, whichever smaller. Calculating A/C capacity of outdoor units Condition: Indoor unit combination ratio does not exceed 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination X Capacity change rate due to piping length to the farthest indoor unit Condition: Indoor unit combination ratio exceeds 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination X Capacity change rate due to piping length to the farthest indoor unit 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. When level difference is 50m or more, the diameter of the main liquid pipe (outdoor unit-branch sections) must be increased. [Diameter of above case]

Model REYQ24PY1

Liquid J19.1

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only) Overall equivalent length = Equivalent length to main pipe x 0.4 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Liquid pipe: Size increase Branch BS unit

In the above case (Heating) Overall equivalent length = 80m x 0.4 + 40m = 72m The correction factor in capacity when Hp=0m is thus approximately 1.0. 6. In the combination which does not include cooling only indoor unit, Calculate the equivalent length pipe by the following when you calculate cooling capacity. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Branch BS unit

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.91. Explanation of symbols Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipe (standard size)]

Model REYQ24PY1

Liquid J15.9

32

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-4

Capacity correction ratio


VRVIII heat recovery
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

REYQ36P

3D057934 NOTES 1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. 3. Method of calculating A/C (cooling/heating) capacity: The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristic table or the maximum A/C capacity of outdoor units as mentioned bellow, whichever smaller. Calculating A/C capacity of outdoor units Condition: Indoor unit combination ratio does not exceed 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination X Capacity change rate due to piping length to the farthest indoor unit Condition: Indoor unit combination ratio exceeds 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination X Capacity change rate due to piping length to the farthest indoor unit 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. When level difference is 50m or more, the diameter of the main liquid pipe (outdoor unit-branch sections) must be increased. [Diameter of above case]

1
2

Model REYQ36PY1

Liquid J22.2

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only) Overall equivalent length = Equivalent length to main pipe x 0.4 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Liquid pipe: Size increase Branch BS unit

In the above case (Heating) Overall equivalent length = 80m x 0.4 + 40m = 72m The correction factor in capacity when Hp=0m is thus approximately 1.0. 6. In the combination which does not include cooling only indoor unit, Calculate the equivalent length pipe by the following when you calculate cooling capacity. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Branch BS unit

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.92. Explanation of symbols Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipe (standard size)]

Model REYQ36PY1

Liquid J19.1

VRV Systems Air cooled selection procedure

33

Air-cooled selection procedure

2
2-4

Capacity correction ratio


VRVIII heat recovery
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

REYQ46P

1
2

3D057936 NOTES 1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. 3. Method of calculating A/C (cooling/heating) capacity: The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristic table or the maximum A/C capacity of outdoor units as mentioned bellow, whichever smaller. Calculating A/C capacity of outdoor units Condition: Indoor unit combination ratio does not exceed 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination X Capacity change rate due to piping length to the farthest indoor unit Condition: Indoor unit combination ratio exceeds 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination X Capacity change rate due to piping length to the farthest indoor unit 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. When level difference is 50m or more, the diameter of the main liquid pipe (outdoor unit-branch sections) must be increased. [Diameter of above case]

Model REYQ46PY1

Liquid J22.2

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only) Overall equivalent length = Equivalent length to main pipe x 0.4 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Liquid pipe: Size increase Branch BS unit

In the above case (Heating) Overall equivalent length = 80m x 0.4 + 40m = 72m The correction factor in capacity when Hp=0m is thus approximately 1.0. 6. In the combination which does not include cooling only indoor unit, Calculate the equivalent length pipe by the following when you calculate cooling capacity. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Branch BS unit

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.88. Explanation of symbols Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipe (standard size)]

Model REYQ46PY1

Liquid J19.1

34

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

2
2-4

Capacity correction ratio


VRVIII heat recovery
1. Rate of change in cooling capacity 2. Rate of change in heating capacity

REYQ48P

3D057937 NOTES 1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. 3. Method of calculating A/C (cooling/heating) capacity: The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristic table or the maximum A/C capacity of outdoor units as mentioned bellow, whichever smaller. Calculating A/C capacity of outdoor units Condition: Indoor unit combination ratio does not exceed 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination X Capacity change rate due to piping length to the farthest indoor unit Condition: Indoor unit combination ratio exceeds 100%. Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination X Capacity change rate due to piping length to the farthest indoor unit 4. When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased. When level difference is 50m or more, the diameter of the main liquid pipe (outdoor unit-branch sections) must be increased. [Diameter of above case]

1
2

Model REYQ48PY1

Liquid J22.2

5. When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only) Overall equivalent length = Equivalent length to main pipe x 0.4 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Liquid pipe: Size increase Branch BS unit

In the above case (Heating) Overall equivalent length = 80m x 0.4 + 40m = 72m The correction factor in capacity when Hp=0m is thus approximately 1.0. 6. In the combination which does not include cooling only indoor unit, Calculate the equivalent length pipe by the following when you calculate cooling capacity. Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching Example:
Equivalent length Equivalent length

Indoor unit Outdoor unit Branch BS unit

In the above case (Cooling) Overall equivalent length = 80m x 0.5 + 40m = 80m The correction factor in capacity when Hp=0m is thus approximately 0.88. Explanation of symbols Hp : Level difference (m) between indoor and outdoor units where indoor in inferior position. HM : Level difference (m) between indoor and outdoor units where indoor in superior position. L : Equivalent pipe length (m) : Capacity correction factor [Diameter of pipe (standard size)]

Model REYQ48PY1

Liquid J19.1

VRV Systems Air cooled selection procedure

35

Air-cooled selection procedure

Integrated heating capacity coefficient


The tables do not take account of the reduction in capacity when frost has accumulated or while the defrosting operation is in progress. The capacity values which take these factors into account, in other words the integrated heating capacity values, can be calculated as follows: Formula: Integrated heating capacity = A Value given in table of capacity characteristics = B Integrating correction factor for frost accumulation (kW) = C A=BxC Correction factor for finding integrated heating capacity

Inlet port temperature of heat exchanger (C/RH 85%) REYQ8,10,12PY1 Integrating correction factor for frost accumulation REYQ14,16PY1 REYQ18~32PY1 REYQ34~48PY1
Defrosting operation Defrosting operation

-7 0.97 0.96 0.99 0.98

-5 0.95 0.94 0.97 0.96

-3 0.90 0.89 0.92 0.91

0 0.86 0.85 0.88 0.87

3 0.87 0.86 0.89 0.88

5 0.92 0.91 0.94 0.93

7 1.00 1.00 1.00 1.00

1
3
Heating capacity

NOTE

Time

1 cycle
(V0368)

It will be seen on the figure on the left that the integrated heating capacity expresses the integrated heating capacity for a single cycle (from defrost operation to defrost operation) in terms of time.

Please note that when there is an accumulation of snow against the outside surface of the outdoor unit heat exchanger, there will always be a temporary reduction in capacity although this will, of course, vary in degree in accordance with a number of other factors such as the outdoor temperature (CDB), relative humidity (RH) and the amount of frosting which occurs.

36

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

Refnet pipe systems


Liquid side junction Discharge gas side junction Suction gas side junction
I.D. J28.60 I.D. J25.40

KHRP22M64T8

I.D. J15.90

I.D. J12.70

I.D. J12.70 I.D. J15.90 I.D. J19.10

I.D. J10 I.D. J38.10 I.D. J15.90 I.D. J9.52 I.D. J12.70 I.D. J31.80

I.D. J31.80 I.D. J15.90 I.D. J19.10 I.D. J25.40

I.D. J25.40

KHRP22M75T8

I.D. J31.80 I.D. J15.90 I.D. J19.10 I.D. J15.90 I.D. J19.10 I.D. J12.70 I.D. J38.10

I.D. J38.10 I.D. J22.20 I.D. J19.10 I.D. J15.90 I.D. J12.70 I.D. J44.50 I.D. J31.80 I.D. J25.40

KHRQ22M20TA8

I.D. J09.52

I.D. J6.35 I.D. J15.90

I.D. J15.90 I.D. J19.10

I.D. J12.70

I.D. J12.70

I.D. J9.52 I.D. J9.52 I.D. J6.35

I.D. J19.10

I.D. J22.20 I.D. J15.90

KHRQ22M29T9

I.D. J9.52

I.D. J6.35

I.D. J19.10

I.D. J15.90 I.D. J19.10

I.D. J12.70

I.D. J12.70

I.D. J9.52 I.D. J9.52 I.D. J6.35

I.D. J25.40

I.D. J22.20

1
4

I.D. J15.90

I.D. J9.52 I.D. J12.70

KHRQ22M64T8

I.D. J12.70

I.D. J9.52

I.D. J25.40

I.D. J29.10

I.D. J15.90

I.D. J15.90 I.D. J12.70 I.D. J15.90 I.D. J12.70 I.D. J6.35 I.D. J9.52 I.D. J31.80 I.D. J28.60

I.D. J25.40 I.D. J12.70 I.D. J12.70

I.D. J19.10

KHRQ22M75T8

I.D. J28.60 I.D. J19.10 I.D. J15.90 I.D. J19.10 I.D. J22.20 I.D. J15.90 I.D. J12.70 I.D. J31.80 I.D. J19.10 I.D. J15.90 I.D. J12.70 I.D. J38.10 I.D. J31.80 I.D. J25.40

I.D. J25.40

I.D. J15.90 I.D. J19.10

KHRP23M33T8

I.D. J12.70 I.D. J15.90 I.D. J15.90 I.D. J12.70

I.D. J9.52

I.D. J15.90 I.D. J19.10 I.D. J15.90 I.D. J19.10

I.D. J12.70

I.D. J25.40

I.D. J19.10

I.D. J15.90

I.D. J12.70

I.D. J25.40 I.D. J31.80 I.D. J22.20 I.D. J15.90 I.D. J12.70 I.D. J15.90 I.D. J28.60 I.D. J19.10 I.D. J12.70 I.D. J15.90

I.D. J6.35 I.D. J9.52

KHRP23M64T8

I.D. J15.90

I.D. J12.70

I.D. J25.40

I.D. J19.10

I.D. J28.60

I.D. J25.40

I.D. J12.70 I.D. J15.90

I.D. J19.10 I.D. J19.10 I.D. J15.90 I.D. J9.52 I.D. J12.70

I.D. J31.80

I.D. J25.40 I.D. J28.60 I.D. J19.10 I.D. J12.70 I.D. J15.90 I.D. J38.10 I.D. J31.80

I.D. J31.80 I.D. J15.90 I.D. J19.10 I.D. J25.40

I.D. J25.40

KHRP23M75T8

I.D. J15.90 I.D. J19.10 I.D. J15.90 I.D. J19.10

I.D. J12.70

I.D. J25.40

I.D. J19.10

I.D. J15.90

I.D. J31.80 I.D. J38.10 I.D. J38.10

I.D. J25.40 I.D. J22.20 I.D. J19.10 I.D. J15.90 I.D. J12.70 I.D. J31.80 I.D. J28.60 I.D. J19.10 I.D. J12.70 I.D. J15.90 I.D. J44.50

I.D. J31.80

I.D. J25.40

KHRQ23M20T8

I.D. J9.52

I.D. J6.35

I.D. J12.70 I.D. J15.90 I.D. J15.90 I.D. J12.70

I.D. J9.52 I.D. J15.90

I.D. J15.90 I.D. J19.10 I.D. J19.10 I.D. J22.20 I.D. J15.90

I.D. J12.70

I.D. J12.70

I.D. J9.52 I.D. J9.52 I.D. J6.35

I.D. J12.70

I.D. J6.35 I.D. J9.52

KHRQ23M29T9

I.D. J9.52

I.D. J6.35

I.D. J15.90 I.D. J12.70 I.D. J12.70 I.D. J19.10 I.D. J19.10 I.D. J15.90 I.D. J9.52 I.D. J12.70 I.D. J25.40 I.D. J22.20 I.D. J19.10 I.D. J15.90 I.D. J19.10

I.D. J12.70

I.D. J12.70

I.D. J9.52 I.D. J9.52 I.D. J6.35 I.D. J9.52

I.D. J15.90

I.D. J15.90

I.D. J9.52 I.D. J12.70 I.D. J15.90

KHRQ23M64T8

I.D. J12.70 I.D. J15.90

I.D. J19.10

I.D. J15.90 I.D. J19.10

I.D. J12.70

I.D. J25.40

I.D. J19.10

I.D. J12.70

I.D. J15.90

I.D. J25.40 I.D. J12.70 I.D. J6.35 I.D. J9.52

I.D. J22.20

I.D. J31.80 I.D. J9.52 I.D. J12.70

I.D. J28.60

I.D. J25.40 I.D. J12.70 I.D. J15.90

I.D. J15.90

I.D. J19.10

KHRQ23M75T8

I.D. J15.90 I.D. J19.10 I.D. J15.90 I.D. J19.10

I.D. J12.70

I.D. J25.40

I.D. J19.10

I.D. J15.90

I.D. J28.60

I.D. J25.40

I.D. J22.20

I.D. J19.10 I.D. J15.90 I.D. J12.70

I.D. J31.80

I.D. J25.40 I.D. J28.60 I.D. J19.10 I.D. J12.70 I.D. J15.90 I.D. J38.10 I.D. J31.80

I.D. J31.80 I.D. J15.90 I.D. J19.10

I.D. J25.40

KHRQ58T7

I.D. J9.52

I.D. J6.35 I.D. J15.90

I.D. J15.90 I.D. J19.10

O.D. J12.70

I.D. J12.70

I.D. J9.52 I.D. J9.52 I.D. J6.35 I.D. J15.90

Closed pipes

O.D. J6.35

O.D. J9.52

O.D. J12.70

O.D. J15.90

O.D. J19.10

1TW25799-4C

VRV Systems Air cooled selection procedure

37

Air-cooled selection procedure

4
KHRQ22M29H8

Refnet pipe systems


Liquid side header
I.D. J6.35 (2x) I.D. J15.90 I.D. J6.35 (6x) I.D. J9.52 (6x) I.D. J15.90 I.D. J15.90

Discharge gas side header

Suction gas side header


I.D. J12.70 I.D. J19.10 I.D. J19.10 I.D. J22.20 I.D. J19.10 (3x) I.D. J12.70 (3x) I.D. J15.90 (3x) I.D. J12.70 (3x) I.D. J15.90 (3x) I.D. J12.70 (2x) I.D. J15.90 I.D. J12.70 (2x) I.D. J15.90 (2x) I.D. J12.70 (5x)

KHRQ22M64H8

I.D. J6.35 (6x) I.D. J15.90

I.D. J6.35 (6x) I.D. J9.52 (6x) I.D. J15.90

I.D. J25.40 I.D. J28.60

I.D. J31.80

KHRQ22M75H8

I.D. J9.52 (8x) I.D. J31.80 I.D. J19.10

I.D. J15.90 (6x)

I.D. J19.10 (6x)

I.D. J15.90 (2x)

I.D. J19.10 I.D. J38.10 I.D. J9.52 (3x) I.D. J9.52 (3x) I.D. J12.70 (3x) I.D. J9.52 (2x) I.D. J19.10 I.D. J19.10 I.D. J15.90 I.D. J9.52 (3x) I.D. J9.52 (3x) I.D. J12.70 (3x) I.D. J9.52 (2x) I.D. J25.40 I.D. J28.60 I.D. J19.10 (3x) I.D. J22 I.D. J12.70 (3x) I.D. J15.90 (3x) I.D. J12.70 (3x) I.D. J15.90 (3x) I.D. J12.70 (2x) I.D. J12.70 I.D. J15.90 I.D. J12.70 (2x) I.D. J15.90 (2x) I.D. J12.70 (5x)

KHRQ23M29H8

1
4

I.D. J6.35 (2x) I.D. J15.90

I.D. J6.35 (6x) I.D. J9.52 (6x) I.D. J15.90

I.D. J12.70 (3x) I.D. J15.90 (3x) I.D. J25.40 I.D. J22.20 I.D. J19.10

KHRQ23M64H8

I.D. J6.35 (2x) I.D. J15.90

I.D. J6.35 (6x) I.D. J9.52 (6x) I.D. J15.90

I.D. J12.70 (3x) I.D. J15.90 (3x) I.D. J25.40 I.D. J22.20 I.D. J19.10 I.D. J12.70 (3x) I.D. J15.90 (3x)

I.D. J31.80 I.D. J12.70 (3x) I.D. J15.90 (3x) I.D. J12.70 (2x)

I.D. J19.10 (3x)

KHRQ23M75H8

I.D. J15.90 (6x)

I.D. J9.52 (8x)

I.D. J19.10 (6x)

I.D. J25.40 I.D. J28.60 I.D. J19.10

I.D. J15.90 (2x)

I.D. J31.80

I.D. J19.10

I.D. J31.80 I.D. J38.10

I.D. J9.52

I.D. J12.70 I.D. J15.90

I.D. J12.70 (2x) I.D. J15.90 (2x) I.D. J9.52 (3x) I.D. J6.35 (3x) I.D. J19.10 (2x) I.D. J28.60 I.D. J19.10 I.D. J25.40

I.D. J12.70

KHRQ250H8

I.D. J15.90

I.D. J9.52

I.D. J12.70

I.D. J12.70 (2x) I.D. J15.90 (2x) I.D. J9.52 (3x) I.D. J6.35 (3x) I.D. J19.10 (2x) I.D. J28.60 I.D. J19.10 I.D. J25.40

I.D. J12.70

KHRP127HB8

I.D. J15.90

I.D. J15.90

I.D. J9.52

I.D. J12.70 I.D. J19.10 I.D. J15.90 I.D. J12.70

I.D. J9.52 (3x) I.D. J12.70 (3x)

KHRQ127H8

I.D. J15.90

I.D. J9.52 (3x) I.D. J6.35 (3x)

I.D. J9.52

I.D. J12.70 I.D. J15.90 I.D. J9.52 (3x) I.D. J6.35 (3x)

I.D. J12.70 (3x)

KHRQ58H7

I.D. J15.90

O.D. J15.90

I.D. J12.70

I.D. J9.52

O.D. J19.10

I.D. J22.20

O.D. J19.10

I.D. J22.20

I.D. J25.40

O.D. J25.40 I.D. J28.60

O.D. J25.40

I.D. J28.60 I.D. J31.80

O.D. J31.80

I.D. J38.10

O.D. J9.52

I.D. J6.35 O.D. J12.70

I.D. J9.52

O.D. J12.70

I.D. J9.52

I.D. J6.35

Reducers - Expanders

O.D. J15.90

I.D. J12.70

O.D. J19.10

I.D. J15.90

I.D. J12.70

O.D. J25.4

I.D. J19.10

I.D. J15.90 I.D. J12.70

O.D. J15.90

I.D. J19.10

O.D. J31.80

I.D. J34.95

I.D. J41.28 O.D. J38.10

I.D. J41.28

O.D. J9.52

I.D. J12.70

O.D. J22.20

I.D. J28.60 O.D. J12.70 I.D. J15.90

O.D. J6.35

I.D. J9.52

O.D. J9.52

I.D. J12.70

O.D. J12.70

I.D. J19.10

1TW25799-4C

38

VRV Systems Air cooled selection procedure

Gas-side junction for gas pipe for liquid pipe

Liquid-side junction

Reducers

Insulation tube for gas pipe for liquid pipe

ID 19.1 ID 19.1 ID 15.9 ID 9.5 ID 34.9 ID 12.7 ID 12.7 ID 9.5 ID 22.2 ID 25.4 ID 28.6 OD 15.9 OD 15.9 ID 22.2 ID 15.9 ID 28.6 OD 38.1 OD 25.4 ID 12.7 ID 9.5 OD 31.8 OD 31.8 OD 12.7 OD 31.8 ID 25.4

ID 38.1 ID 41.3

ID 31.8 ID 28.6

ID 25.4

Refnet pipe systems

BHFQ22P1007
OD 25.4 ID 41.3 ID 31.8 ID 34.9 ID 15.9 ID 15.9 ID 19.1 ID 19.1 ID 22.2 ID 25.4 ID 28.6 OD 28.6 OD 31.8 (2x) ID 22.2 ID 41.3 ID 9.5 ID 12.7 ID 25.4 (2x) ID 28.6 ID 31.8 OD 31.8 OD 12.7 ID 9.5 ID 12.7 ID 15.9 OD 12.7 OD 38.1 ID 28.6 ID 22.2 ID 15.9 ID 19.1 ID 25.4 ID 28.6 ID 19.1 ID 15.9 OD 25.4 ID 15.9 OD 31.8 ID 12.7 ID 9.5 OD 28.6 (2x) OD 19.1 (2x) (2x) (2x) OD 25.4 OD 25.4 OD 38.1 OD 15.9 OD 15.9 OD 19.1

ID 22.2 ID 19.1

ID 28.6 ID 25.4

ID 15.9 ID 19.1 ID 22.2

ID 38.1 ID 31.8

ID 25.4

ID 28.6 ID 31.8

ID 19.1 ID 22.2

Air-cooled selection procedure

BHFQ22P1517

ID 25.4

ID 28.6 ID 31.8

ID 15.9 ID 19.1

VRV Systems Air cooled selection procedure

ID 28.6 ID 25.4 ID 22.2 ID 19.1

(2x)

2TW27239-1

1
4

39

40

Refnet pipe systems

SUCTION GAS SIDE JUNCTION FOR SUCTION GAS PIPE FOR DISCHARGE GAS PIPE FOR LIQUID PIPE

DISCHARGE GAS SIDE JUNCTION

LIQUID SIDE JUNCTION

REDUCERS / EXPANDERS JOINT FOR OIL PIPE

1
4
Air-cooled selection procedure

VRV Systems Air cooled selection procedure

2TW25799-6

Reducers Liquid side junction For gas pipe For discharge gas pipe For liquid pipe For gas pipe
I.D. J19.1 I.D. J19.1 I.D. J22.2 I.D. J25.4 I.D. J25.4 I.D. J15.9 I.D. J28.6 I.D. J28.6 I.D. J9.5 I.D. J22.2 I.D. J15.9 I.D. J19.1 I.D. J22.2 O.D. J15.9 I.D. J34.9 O.D. J12.7 O.D. J9.5 O.D. J25.4 O.D. J25.4 I.D. J12.7 O.D. J25.4 I.D. J25.4 I.D. J19.1 I.D. J25.4 I.D. J22.2

Gas side junction Joint for pressure equalization pipe For liquid pipe

Discharge gas side junction

Insulation tube For pressure equalization pipe

I.D. J25.4

BHFQ23P907

I.D. J28.6 I.D. J31.8

I.D. J28.6

I.D. J28.6

I.D. J28.6 I.D. J25.4 I.D. J22.2 I.D. J19.1

I.D. J25.4

I.D. J25.4

I.D. J22.2 O.D. J25.4

I.D. J22.2 I.D. J19.1

O.D. J31.8

Refnet pipe systems

I.D. J38.1 I.D. J31.8 I.D. J28.6 I.D. J25.4 I.D. J15.9 I.D. J25.4 I.D. J31.8 I.D. J25.4 I.D. J19.1 I.D. J22.2 I.D. J28.6 O.D. J25.4 O.D. J31.8 I.D. J9.5 I.D. J25.4 I.D. J12.7 O.D. J25.4 I.D. J15.9 I.D. J19.1 I.D. J22.2 I.D. J28.6 I.D. J19.1

I.D. J22.2

I.D. J25.4

BHFQ23P1357

Air-cooled selection procedure

I.D. J28.6 I.D. J31.8

I.D. J28.6

I.D. J31.8

I.D. J28.6 I.D. J25.4 I.D. J22.2 I.D. J19.1

I.D. J19.1 I.D. J22.2 I.D. J25.4 I.D. J15.9 I.D. J28.6 O.D. J31.8 I.D. J25.4 I.D. J19.1 I.D. J22.2

I.D. J34.9

O.D. J25.4 O.D. J15.9

VRV Systems Air cooled selection procedure


I.D. J19.1 I.D. J19.1 I.D. J19.1 I.D. J15.9 I.D. J19.1 I.D. J41.3 I.D. J12.7 I.D. J9.5 O.D. J25.4 O.D. J25.4 O.D. J38.1

I.D. J25.4

I.D. J28.6

I.D. J31.8

I.D. J28.6 I.D. J25.4 I.D. J22.2

I.D. J28.6

I.D. J28.6

I.D. J19.1

I.D. J25.4

I.D. J25.4

I.D. J22.2

I.D. J22.2 I.D. J19.1

2TW29119-1

1
4

41

Air-cooled selection procedure

4
KHRQM22M20T8

Refnet pipe systems


Liquid side junction
I.D. J10 I.D. J6 I.D. J16 I.D. J12 I.D. J10 I.D. J10 I.D. J6 I.D. J20 I.D. J20 I.D. J22 I.D. J16

Discharge gas side junction

Suction gas side junction


I.D. J16

I.D. J12

KHRQM22M29T8

I.D. J10

I.D. J6

I.D. J20

I.D. J16 I.D. J20

I.D. J12

I.D. J12

I.D. J10 I.D. J10 I.D. J6

I.D. J26

I.D. J22

I.D. J16

I.D. J12

I.D. J10

KHRQM22M64T8

I.D. J12

I.D. J10

I.D. J26

I.D. J20

I.D. J16

1
4

I.D. J16 I.D. J12 I.D. J16 I.D. J12 I.D. J6 I.D. J10 I.D. J32 I.D. J28

I.D. J26 I.D. J12 I.D. J20 I.D. J16

KHRQM22M75T8

I.D. J28 I.D. J20 I.D. J16 I.D. J20 I.D. J22 I.D. J16 I.D. J12 I.D. J32 I.D. J20 I.D. J16 I.D. J12 I.D. J38 I.D. J32 I.D. J26

I.D. J26

I.D. J16 I.D. J20

KHRQM23M20T8

I.D. J10

I.D. J6

I.D. J12 I.D. J16 I.D. J16 I.D. J12

I.D. J10 I.D. J16

I.D. J16 I.D. J20 I.D. J20 I.D. J22 I.D. J16

I.D. J12

I.D. J12

I.D. J10 I.D. J10 I.D. J6

I.D. J12

I.D. J6 I.D. J10

KHRQM23M29T8

I.D. J10

I.D. J6

I.D. J16

I.D. J12

I.D. J20

I.D. J16 I.D. J20

I.D. J12

I.D. J12

I.D. J10 I.D. J10 I.D. J6

I.D. J12 I.D. J16

I.D. J20 I.D. J20 I.D. J16 I.D. J10 I.D. J12 I.D. J26 I.D. J22

I.D. J16

I.D. J12

I.D. J10

KHRQM23M64T8

I.D. J12 I.D. J16 I.D. J16 I.D. J12

I.D. J10 I.D. J20 I.D. J16 I.D. J20

I.D. J12

I.D. J26

I.D. J20

I.D. J16

I.D. J12

I.D. J26 I.D. J6 I.D. J10

I.D. J22

I.D. J32 I.D. J12 I.D. J10

I.D. J28

I.D. J26 I.D. J12 I.D. J16

I.D. J16

I.D. J20

KHRQM23M75T8

I.D. J20

I.D. J16

I.D. J12

I.D. J26

I.D. J20

I.D. J16

I.D. J28

I.D. J26

I.D. J16 I.D. J20

I.D. J20 I.D. J22 I.D. J16 I.D. J12

I.D. J32

I.D. J26 I.D. J28 I.D. J20 I.D. J12 I.D. J16 I.D. J38 I.D. J32

I.D. J32 I.D. J16 I.D. J20

I.D. J26

KHRQM58T7

I.D. J10

I.D. J6 I.D. J16

I.D. J16 I.D. J20

I.D. J12

I.D. J12

I.D. J10 I.D. J10 I.D. J6 I.D. J16

Closed pipes
O.D. J6 I.D. J10 O.D. J12

O.D. J16

O.D. J20

1TW29479-1

42

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

4
KHRQM23M75H8 KHRQM23M64H8 KHRQM23M29H8 KHRQM22M75H8 KHRQM22M64H8 KHRQM22M29H8

Refnet pipe systems


Liquid side header
I.D. J6 (2x) I.D. J16 I.D. J6 (6x) I.D. J10 (6x) I.D. J16 I.D. J16

Discharge gas side header

Suction gas side header


I.D. J20 I.D. J20 I.D. J22 I.D. J20 (3x) I.D. J12 (3x) I.D. J16 (3x) I.D. J12 (3x) I.D. J16 (3x) I.D. J12 (2x) I.D. J12 I.D. J16 I.D. J12 (2x) I.D. J16 (2x) I.D. J12 (5x)

I.D. J6 (2x) I.D. J16

I.D. J6 (6x) I.D. J10 (6x) I.D. J16

I.D. J28

I.D. J26

I.D. J32

I.D. J10 (8x) I.D. J32 I.D. J20 I.D. J20 I.D. J10 (3x) I.D. J6 (2x) I.D. J16 I.D. J6 (6x) I.D. J10 (6x) I.D. J16 I.D. J12 (3x) I.D. J16 (3x) I.D. J26 I.D. J22 I.D. J20 I.D. J10 (3x) I.D. J6 (2x) I.D. J16 I.D. J6 (6x) I.D. J10 (6x) I.D. J16 I.D. J12 (3x) I.D. J16 (3x) I.D. J26 I.D. J22 I.D. J20 I.D. J20 (3x) I.D. J10 (8x) I.D. J26 I.D. J28 I.D. J20 I.D. J32 I.D. J38 I.D. J12 (3x) I.D. J16 (3x) I.D. J12 (3x) I.D. J16 (3x) I.D. J12 (2x) I.D. J32 I.D. J10 (3x) I.D. J12 (3x) I.D. J10 (2x) I.D. J26 I.D. J28 I.D. J10 (3x) I.D. J12 (3x) I.D. J10 (2x) I.D. J20 I.D. J20 I.D. J16

I.D. J16 (6x)

I.D. J20 (6x)

I.D. J16 (2x)

I.D. J38 I.D. J12 I.D. J16 I.D. J12 (2x) I.D. J16 (2x)

I.D. J12 (5x)

1
4

I.D. J22 I.D. J20 (3x) I.D. J12 (3x) I.D. J16 (3x) I.D. J12 (3x) I.D. J16 (3x) I.D. J12 (2x)

I.D. J32

I.D. J16 (6x)

I.D. J20 (6x)

I.D. J16 (2x)

I.D. J20

KHRQM250H8

I.D. J10

I.D. J12 I.D. J16

I.D. J12 (2x) I.D. J16 (2x) I.D. J10 (3x) I.D. J6 (3x) I.D. J20 (2x) I.D. J26

I.D. J12

I.D. J16

I.D. J10

I.D. J12 I.D. J16 I.D. J20 I.D. J16 I.D. J12

I.D. J10 (3x) I.D. J12 (3x)

KHRQM127H8

I.D. J10 (3x) I.D. J6 (3x)

I.D. J10

I.D. J12 I.D. J16 I.D. J16 I.D. J10 (3x) I.D. J6 (3x)

KHRQM58H7

I.D. J12 (3x)

O.D. J16

I.D. J12

I.D. J10

I.D. J20

I.D. J22

O.D. J20

I.D. J22

I.D. J26

O.D. J26

I.D. J28

I.D. J26

I.D. J28

I.D. J32

O.D. J32

I.D. J38

O.D. J10

I.D. J6

I.D. J12

I.D. J10

O.D. J12

I.D. J10

I.D. J6

Reducers - Expanders

O.D. J16

I.D. J12

I.D. J20

I.D. J16

I.D. J12

O.D. J26

I.D. J20

I.D. J16

I.D. J12

O.D. J16

I.D. J20

I.D. J32

I.D. J35

I.D. J42

O.D. J10

I.D. J12

O.D. J22

I.D. J28

I.D. J12

I.D. J16

O.D. J6

I.D. J10

O.D. J12

I.D. J20

1TW29479-1

VRV Systems Air cooled selection procedure

43

BHFQM22P1007A

BHFQM22P1517A

44

1
4

Gas-side junction For gas pipe


I.D. J20 O.D. J19.1 I.D. J20 I.D. J22 I.D. J26 I.D. J16 O.D. J22.2 O.D. J12.7 O.D. J16 O.D. J26 I.D. J12 I.D. J10 O.D. J32 O.D. J32 O.D. J12 I.D. J28 O.D. J28.6 O.D. J26 I.D. J16 O.D. J15.9 O.D. J32 O.D. J16 I.D. J28 I.D. J28 I.D. J22 I.D. J12 I.D. J26 I.D. J12 I.D. J35 I.D. J12 I.D. J22 I.D. J10 I.D. J10 I.D. J16 I.D. J38 I.D. J20 I.D. J42 O.D. J9.5 I.D. J10

Liquid side junction For liquid pipe

Reducers

Insulation tube Gas Liquid

I.D. J32

I.D. J28

I.D. J26

I.D. J22 I.D. J20

I.D. J28 I.D. J26

I.D. J16 I.D. J20 I.D. J22

I.D. J42 I.D. J32 I.D. J35 I.D. J20 O.D. J19.1 I.D. J20 I.D. J22 I.D. J26 I.D. J26 I.D. J28 O.D. J28 O.D. J32 O.D. J26 I.D. J26 I.D. J16 I.D. J28 O.D. J32 O.D. J26 O.D. J28 O.D. J38 O.D. J20 I.D. J12 I.D. J10 O.D. J28.6 I.D. J42 I.D. J28 I.D. J22 O.D. J22.2 O.D. J32 I.D. J10 I.D. J12 O.D. J32 I.D. J22 I.D. J32 I.D. J16 I.D. J20 O.D. J28 I.D. J22 I.D. J20 I.D. J28 I.D. J16 I.D. J38

I.D. J20

I.D. J16 I.D. J10 O.D. J9.5

Refnet pipe systems

I.D. J38 I.D. J32 I.D. J16

I.D. J26

I.D. J28 I.D. J32

I.D. J20 I.D. J22

I.D. J12 O.D. J12 O.D. J12 O.D. J12.7

I.D. J10 I.D. J12

I.D. J16 I.D. J16

Air-cooled selection procedure

I.D. J26

O.D. J15.9 O.D. J16 O.D. J16 O.D. J20

VRV Systems Air cooled selection procedure

I.D. J28 I.D. J32

I.D. J28 I.D. J26 I.D. J22 I.D. J20

I.D. J16 I.D. J20

2TW29659-1

Suction gas side junction For suction gas pipe


I.D. J15.90 I.D. J19.10 I.D. J22.20 O.D. J25.40 I.D. J15.90 I.D. J19.10 I.D. J25.40 I.D. J22.20 I.D. J28.60 I.D. J10 I.D. J12 O.D. J25.40 I.D. J16 O.D. J15.90 I.D. J20 I.D. J22 I.D. J22 I.D. J20 I.D. J16 I.D. J10 I.D. J12 I.D. J35 O.D. J32 I.D. J22 I.D. J20 I.D. J16 I.D. J22 I.D. J20 I.D. J16 I.D. J22.20 I.D. J19.10 I.D. J15.90

Discharge gas side junction For liquid pipe

Liquid side junction

Reducers - Expanders For discharge gas pipe Parts for oil pipe

I.D. J25.40

I.D. J25.40

I.D. J20

I.D. J32

BHFQM23M907A

I.D. J22

I.D. J28

I.D. J28 I.D. J26 I.D. J22 I.D. J20 I.D. J16 I.D. J19.10 I.D. J25.40 O.D. J25.40 I.D. J22.20 I.D. J28.60 I.D. J15.90 I.D. J19.10 I.D. J22.20 O.D. J25.40

I.D. J22 I.D. J26 I.D. J28

I.D. J25.40 I.D. J15.90

I.D. J25.40

Joint

I.D. J32 I.D. J22 I.D. J26 I.D. J28 I.D. J22 I.D. J20 I.D. J20 I.D. J16

I.D. J32 I.D. J28 I.D. J35 O.D. J32 I.D. J22.20 I.D. J19.10

Refnet pipe systems

I.D. J32 I.D. J28

I.D. J38

I.D. J10 I.D. J12

I.D. J25.40 I.D. J15.90 I.D. J22 I.D. J20

O.D. J15.90

BHFQM23M1357A

I.D. J25.40

Reducer
I.D. J6

I.D. J20 I.D. J20 I.D. J16 I.D. J10 I.D. J12 I.D. J42 O.D. J38

I.D. J32

I.D. J22 I.D. J20 I.D. J22

I.D. J28

Air-cooled selection procedure

I.D. J22 I.D. J26 I.D. J28

VRV Systems Air cooled selection procedure


I.D. J22 I.D. J20 I.D. J22 I.D. J20

O.D. J6.35

I.D. J28 I.D. J26

2TW29679-1

1
4

45

46

1
4
INSULATION TUBE

Refnet pipe systems

GAS SIDE JUNCTION FOR GAS PIPE FOR LIQUID PIPE FOR DISCHARGE GAS PIPE MM-INCH REDUCERS

DISCHARGE GAS SIDE JUNCTION

LIQUID SIDE JUNCTION

REDUCERS

JOINT FOR PRESSURE FOR GAS PIPE FOR PRESSURE FOR LIQUID PIPE EQUALIZATION PIPE EQUALIZATION PIPE

Air-cooled selection procedure

VRV Systems Air cooled selection procedure

1TW29119-2

Air-cooled selection procedure

5
Type of fitting

Example of Refnet piping layouts


Sample systems

Outdoor unit

Outdoor unit

Outdoor unit

Outdoor unit

REFNET joint

REFNET joint

Simultaneous control of cooling/heating

REFNET joint

REFNET joint

Indoor unit
Distribution by REFNET joints

Indoor unit

Cooling only

Indoor unit

Indoor unit

Cooling only

1
5

Cooling only

Cooling only

Simultaneous control of cooling/heating

Cooling only

Outdoor unit REFNET header (8 branch fitting)

Outdoor unit

REFNET header (8 branch fitting)

Distribution by REFNET header

Indoor unit

Simultaneous control of cooling/heating

Can be added

Indoor unit

Cooling only Can be added

REFNET header (8 branch fitting)

Can be added

Indoor unit

Cooling only

Outdoor unit
Distribution by REFNET joints and headers

Outdoor unit

REFNET joint

Simultaneous control of cooling/heating

Indoor unit REFNET header (8 branch fitting) Indoor unit REFNET header (8 branch fitting) Can be added

Simultaneous control of cooling/heating

Can be added

Cooling only

VRV Systems Air cooled selection procedure

47

Air-cooled selection procedure

6
6-1

Refrigerant pipe selection


VRVIII-S

1
6

4PW35338-1

48

VRV Systems Air cooled selection procedure

Air-cooled selection procedure

6
6-2

Refrigerant pipe selection


VRVIII

1
6

4PW35768A

VRV Systems Air cooled selection procedure

49

Air-cooled selection procedure

6
6-2

Refrigerant pipe selection


VRVIII

1
6

4PW35768A

50

VRV Systems Air cooled selection procedure

6-3

Branch with REFNET joint Outdoor unit


REFNET joint (A, B) REFNET header REFNET joint (A~G) a A a m b c r s B1 k i 4 5 6 k 8 n 7 8 d f h 8 B2 B3 e B5 B6 m g j o B5 n p B o h B4 d f b B1 B2 B3 e c g 6 7 1 2 3 REFNET header a b d c e

Branch with REFNET joint and header Outdoor unit Outdoor unit

Example of connection (Connection of 8 indoor units)

Branch with REFNET header

Outdoor unit side

BS Unit

Indoor unit side

H1

H1

f B1 F g j m o q G 1 2 3 4 5 6 7 i B2 k n p B3 B4

1 Piping from outdoor unit to BS unit Suction gas pipe (Bold):3 pipes HP/LP gas pipe Liquid pipe
A B C D E

Single outdoor system REYQ 8~16


H2
1 2 3 i B4 j 4 5

VRVIII heat recovery


H1

2 Piping from BS unit to indoor unit or indoor unit used as cooling only Piping from Refrigerant branch kit to (Suction) gas pipe (Thin):2 pipes Liquid pipe
H2
B1 ~ B4 : BS Unit : Indoor unit (Cool/Heat selection possible) 1~6 7, 8 : Indoor unit (Cooling only)

(*1)
H3 H3

Indicate the Outdoor unit multi connection piping kit. First outdoor unit multi connection piping kit Outdoor unit Outdoor unit
REFNET joint (A, B) r s REFNET header m A b B5 n B o 6 7 c r m d f 1 2 3 5 h 6 7 2 3 4 5 o q S B1 k B2 B3 e g p REFNET joint (A~G) a a b d c e t s t r u r u a s

: BS Unit B1 ~ B5 1 ~ 4 , 7 , 8 : Indoor unit (Cool/Heat selection possible) 5, 6 : Indoor unit (Cooling only) Outdoor unit

B1 ~ B4 : BS Unit : Indoor unit (Cool/Heat selection possible) 1~6 : Indoor unit (Cooling only) 7, 8

(*2) In case of multi outdoor system, re-read outdoor unit to the first Outdoor unit multi connection piping kit as seen from the indoor unit.

t REFNET header

H3

H2

Refrigerant pipe selection

H1

H1

Air-cooled selection procedure

f i F g 1 G i B4 j 4 k n p

H1

A C D

Multi outdoor system REYQ 18~48

d b B1 B2 e c

h B4 f B3 g i 1 2 3 4

j B5 k 5 B6 m n o

H2

7 B1 ~ B4 : BS Unit : Indoor unit (Cool/Heat selection possible) 1~6 7, 8 : Indoor unit (Cooling only)

H2

VRV Systems Air cooled selection procedure


8 B1 ~ B4 : BS Unit : Indoor unit (Cool/Heat selection possible) 1~6 7, 8 : Indoor unit (Cooling only)

: BS Unit B1 ~ B5 1 ~ 4 , 7 , 8 : Indoor unit (Cool/Heat selection possible) : Indoor unit (Cooling only) 5, 6

Between outdoor unit (*2) and indoor unit

Actual pipe length Equivalent length Total extention length Actual and Between first outdoor unit multi connection piping kit and outdoor unit Equivalent (in case of multi system) pipe length Difference in height Allowable Between outdoor and indoor units height Between indoor and indoor units Difference in height difference Between outdoor and outdoor units Difference in height Actual pipe Allowable length after the branch length

Pipe length between outdoor unit (*2) and indoor unit 165m Example 6 : a + b + 165m, 8 : a + m + n + p 165m Example 8 : a + o 165m Example 8 : a + b + c + d + e + s 165m Equvalent pipe length between outdoor unit (*2) and indoor unit 190m (Note 1) (Assume eqivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, that of BSVQ100, 160 to be 4m, that of BSVQ250 to be 6m for calculation purposes) Total piping length from outdoor unit (*2) to all indoor unit 1000m Actual pipe length from first outdoor unit multi connection piping kit to outdoor unit 10m Outdoor unit r 10m Equivalent pipe length from first outdoor unit multi connection piping kit to outdoor unit 13m

Difference in height between outdoor unit and indoor unit (H1) 50m (Max 40m if the outdoor unit is below) s (Equivalent length 13m) r t u + t 10m Difference in height between adjacent indoor units (H2) 15m u (Equivalent length 13m) Difference in height between adjacent outdoor units (H3) 5m Actual pipe length from first refrigerant branch kit (either REFNET joint or REFNET header) to indoor unit 40m (Note 2) Example 8 : o 40m Example 6 : b + 40m, 8: m + n + p 40m Example 8 : b + c + d + e + s 40m

(Equivalent length 13m) u + s 10m

H2

3P201178-3B

1
6

51

52

1
6
6-3

Outdoor unit multi connection piping kit and Refrigerant branch kit selection

Refrigerant branch kits can only be used with R410A. When multi outdoor system are installed, be sure to use the special separately sold Outdoor unit multi connection piping kit. (BHFP26P90 136). (For how to select the proper kit, follow the table at right.) Never use BHFP26M90 135, BHFP22M90 135P for M type of this series or T joint (field supplied).

How to select the REFNET joint When using REFNET joint at the first branch counted from the outdoor unit side, choose from the following table in accordance with the outdoor unit capacity type. (Example : REFNET joint A) Outdoor unit capacity type Refrigerant branch kit name KHRQ23M29T 8,10HP type KHRQ23M64T 12~22HP type 24HP type ~ KHRQ23M75T Choose the REFNET joints other than the first branch from the following table in accordance with the total capacity index of all the indoor units connected below the REFNET joint. Refrigerant branch kit name Indoor unit total capacity index 3 pipes 2 pipes x < 200 KHRQ22M20T KHRQ23M20T 200 x < 290 KHRQ22M29T KHRQ23M29T 290 x < 640 KHRQ23M64T KHRQ22M64T 640 x KHRQ23M75T How to select the REFNET header Choose from the following table in accordance with the total capacity index of all the indoor units connected below the REFNET header. 250 type indoor unit can not be connected below the REFNET header. Refrigerant branch kit name Indoor unit total capacity index 3 pipes 2 pipes x < 200 KHRQ22M29H KHRQ23M29H 200 x < 290 KHRQ22M29H 290 x < 640 KHRQ23M64H KHRQ22M64K 640 x KHRQ22M75H KHRQ23M75H How to select the outdoor unit multi connection piping kit (This is required when the system is multi outdoor unit system.) Choose from the following table in accordance with the number of outdoor units. Number of outdoor unit Connecting piping kit name BHFQ23P907 2 units 3 units BHFQ23P1357 Example REFNET joint C : Indoor units 5 + 6 + 7 + 8

Example for indoor units connected downstream

VRVIII heat recovery

Pipe size selection

Refrigerant pipe selection

The thickness of the pipes in the table shows the requirements of Japanease High Pressure Gas Controll low. (As of Jan. 2003)The thickness and material shall be selected in accordance with local code.

Air-cooled selection procedure

<In case of single outdoor unit system> Outdoor unit

VRV Systems Air cooled selection procedure


Equalizer pipe (part D) (multi outdoor unit system only) Piping size (O. D.) Temper grade and wall thickness for pipes (Temper grade, O type and 1/2H type indicate the material type specified in JIS H 3300.) 6.4 0.80 0.80 0.80 9.5 12.7 15.9 19.1 22.2 25.4 28.6 31.8 34.9 38.1 41.3 O type 1/2H type 0.99 0.80 0.80 0.88 0.99 1.10 1.21 1.32 1.43 Copper tube O. D. Temper grade Wall thickness (Min. requirement)

Piping between outdoor unit and refrigerant branch kit (part A)

<In case of multi outdoor unit system> Independent Independent Independent unit 1 unit 2 unit 3

Example REFNET header : Example REFNET joint B : Indoor units 7 + 8 Example REFNET header : Indoor units 1 + 2 + 3 + 4 + 5 + 6 Indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8 Piping between outdoor unit (*2) and refrigerant branch kit (part A) Piping between refrigerant branch kits Choose from the following table in accordance with the outdoor unit system capacity type. Piping between refrigerant branch kit and BS unit Piping between outdoor unit multi connection piping kits (part B) Piping between BS unit and refrigerant branch kit Choose from the following table in accordance with the total capacity of all Choose from the following table in accordance with the total capacity type of all the the outdoor units connected upstream. (unit : mm) indoor units connected downstream. Piping size (O. D.) Outdoor unit *1 Connection piping must not exceed the refrigerant Piping size between outdoor HP/LP gas pipe Liquid pipe capacity type Suction gas pipe unit and refrigerant branch kit (part A). 15.9 19.1 8HP type *2 When selecting 2 pipes line (gas pipe and liquid pipe), use Suction gas pipe 9.5 22.2 10HP type 19.1 column for gas pipe and Liquid pipe column for liquid pipe. (unit : mm) 12HP type 12.7 Piping size (O. D.) 14,16HP type Indoor capacity index 28.6 22.2 Suction gas pipe HP/LP gas pipe Liquid pipe 18HP type 15.9 12.7 x < 150 15.9 20,22HP type 19.1 15.9 9.5 150 x < 200 24HP type 34.9 28.6 22.2 200 x < 290 26~34HP type 19.1 290 x < 420 12.7 19.1 36HP type 28.6 41.3 420 x < 640 15.9 34.9 38~48HP type 640 x < 920 34.9 28.6 19.1 920 x 41.3 Piping between outdoor unit multi connection piping kit and outdoor unit (part C) Choose from the following table in accordance with the capacity type of Piping between refrigerant branch kit, BS unit and indoor unit the outdoor unit connected. (unit : mm) (unit : mm) Match to the size of the connection piping on the indoor unit. Piping size (O. D.) Outdoor unit Piping size (O. D.) HP/LP gas pipe Liquid pipe capacity type Suction gas pipe Indoor unit capacity type gas pipe Liquid pipe 9.5 0.8 22.2 8,10HP type 19.1 12.7 6.4 20 25 32 40 50 type 12HP type 28.6 12.7 15.9 63 80 100 125 type 22.2 14,16HP type 19.1 9.5 200 type 250 type 22.2 (unit : mm) 19.1

Equalizer pipe (part D) Piping between outdoor unit multi connection piping kit and outdoor unit (part C) Piping between outdoor unit multi connection piping kits (part B)

Piping between outdoor unit and refrigerant branch kit (part A)

3P201178-3B

6-3

How to calculate the additional refrigerant to be charged


R=
Total length(m) of liquid piping size at 22.2

0.37 1.02

Total length(m) of liquid piping size at 19.1

0.26

Additional refrigerant to be charged : R(kg) R should be rounded off in units of 0.1 kg.
Total length(m) of liquid piping size at 15.9

0.18

Total length(m) of liquid piping size at 12.7

0.26

REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACITY OF INDOOR UNIT MODEL NAME INDOOR CONNECTION REYQ8 REYQ34 ~ ~ CAPACITY 32PY1 48PY1

Total length(m) of liquid piping size at 9.5

0.059

Total length(m) of liquid piping size at 6.4

0.022

HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT 3.6kg REYQ8 ~ 16PY1 1.0kg REYQ18 ~ 20PY1 1.5kg REYQ22 ~ 24PY1 2.0kg REYQ26PY1 2.5kg REYQ28 ~ 30PY1 3.0kg REYQ32 ~ 40PY1 3.5kg REYQ42PY1 4.0kg REYQ44 ~ 46PY1 4.5kg REYQ48PY1 MORE THAN 100% 0.5kg 120% OR LESS MORE THAN 120% 0.5kg 1.0kg 130% OR LESS

Example for refrigerant branch using REFNET joint and REFNET header for the systems and each pipe length as shown below. Outdoor system : REYQ34PY1 Total capacity of indoor unit : 116% R = ( 50 0.26 + 1 0.18 + 3 0.12 + 156 0.059 + 20 0.022 )1.02 + 3.0 + 0.5 a : 19.1 30m b : 19.1 20m c : 9.5 10m d : 9.5 10m e: f : g: h: 9.5 10m 9.5 10m 9.5 10m 9.5 10m i : 9.5 10m j : 9.5 10m k : 9.5 20m l : 9.5 20m m : 9.5 20m n : 9.5 10m o : 6.4 10m p : 6.4 10m r : 12.7 3m s : 9.5 3m t : 9.5 3m u : 15.9 1m

VRVIII heat recovery

a, b u = 27.148 27.1kg Round off in units of 0.1 kg. REYQ34PY1 116%

c~n, s, t

o, p

Refrigerant pipe selection

Note 1. System REYQ8 ~ 10PY1 REYQ12 ~ 16PY1 REYQ18 ~ 24PY1 REYQ26 ~ 48PY1 Liquid pipe 9.5 12.7 12.7 15.9 15.9 19.1 19.1 22.2

Air-cooled selection procedure

When the equivalent pipe length between outdor and indoor units is 90m or increased according to the right table. (Never increase suction gas pipe and HP/LP gas pipe.)

(Refer to figure 9) 1.Outdoor unit 2.Main pipes 3.Increase only liquid pipe size 4.First refrigerant branch kit 5.BS unit 6.Indoor unit Note 2. Allowable length after the first refrigerant branch kit to indoor units is 40m or less, however it can be extended up to 90m if all the following conditions are satisfied. (In case of Branch with REFNET joint)

VRV Systems Air cooled selection procedure


Example Drawings 8 b + c + d + e + f + g + p 90 m increase the pipe size of b, c, d, e, f, g Increase the pipe size as follows 9.5 12.7 15.9 19.1 12.7 15.9 19.1 22.2 22.2 25.4* 28.6 31.8* a+b2+c2+d2+e2+f2+g2 + h + i + j + k + l + m + n + p 1000 m h, i, j....... p 40 m
a
A

Required Conditions

1. It is necessary to increase the pipe size between the first branch kit and the final branch kit. (Reducers must be procured on site) However, the pipes that are same pipe size with main pipe must not be increased.

34.9 38.1*

2.For calculation of Total extension length, the actual length of above pipes must be doubled. (except main pipe and the pipes that are not increased)

Outdoor unit
b
B

REFNET joint (A-G)


c
C

3. Indoor unit to the nearest branch kit 40 m

d
D

e
E

f
F

g
G

H1 h 1 i 2 j 3 k 4 l 5 m 6 n 7 p 8

4. The difference between [Outdoor unit to the farthest indoor unit] and [Outdoor unit to the nearest indoor unit] 40 m

The farthest indoor unit 8 The nearest indoor unit 1 ( a + b + c + d + e + f + g + p ) - ( a + h ) 40 m

Indoor units ( 1 - 8 )

3P201178-3B

*If available on the site, use this size. Otherwise it can not be increased.

1
6

53

Air-cooled selection procedure

6
6-4

Refrigerant pipe selection


Piping thickness
Piping diameter 6.4 9.5 12.7 15.9 19.1 22.2 25.4 28.6 31.8 34.9 38.1 41.3 Material O O O O 1/2H 1/2H 1/2H 1/2H 1/2H 1/2H 1/2H 1/2H Minimum thickness [mm] 0.8 0.8 0.8 0.99 0.8 0.8 0.88 0.99 1.10 1.21 1.32 1.43

:O

: annealed : half-hard

1
6

1/2H

For half hard pipes the maximum allowed tensile stress is 61 N/mm2. For this reason the 0.2% proof strength of the half hard pipe shall be minimum 61 N/mm2. The bending radius is more than or equal to 3 times the diameter of the pipe.

54

VRV Systems Air cooled selection procedure

Daikin units comply with the European regulations that guarantee the safety of the product.

Naamloze Vennootschap Zandvoordestraat 300 B-8400 Oostende, Belgium www.daikin.eu BTW: BE 0412 120 336 RPR Oostende

VRV products are not within the scope of the Eurovent certification programme.

EEDEN07-200/

EEDEN07-200 07/2007 Copyright Daikin

ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.

The present publication supersedes EEDE06-2 Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern for the environmont is set in the EMAS and ISO 14001 systems. Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B- 8400 Oostende

Daikins unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intension to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..