TECHNICAL MANUAL
First published June 2006 No part of this publication may be reproduced in any manner whatsoever without permission in writing from the Sr. General Manager, Packaged Airconditioning Division, Blue Star Limited. While due care has been taken to avoid errors or misinterpretation, Blue Star Limited is neither liable nor responsible for consequence of any action taken, on the basis of this publication. Since ASHRAE standards use the FPS system, FPS nomenclature is used in some places in this publication for convenient reference. Published by Blue Star Limited, 9, Bazullah Road, TNagar, Chennai 600 017, India. For restricted circulation only. Not for sale.
TECHNICAL MANUAL
Contents
Basics ....................................................................................... 2
What is airconditioning? What is a Packaged Airconditioner? Main Components General layout of components within the IDU What is a Split Airconditioner? What is a Ducted Split Airconditioner? HiPer+ Packaged ACs HiSen Packaged ACs Scroll Compressor Technology The Tandem Scroll 2 3 4 4 5 5 6 8 10 10
Troubleshooting ..................................................................... 22
Diagnosing faults Quick-check Troubleshooting Chart 22 22
Condenser Water Piping Schematic ............................................................................... 25 Troubleshooting the Water Circuit ........................................................................... 26 Technical Specifications ....................................................... 27 Schematics & Wiring Diagrams .......................................... 37 Warranty & Service ................................................................ 73
Basics
What is airconditioning?
An airconditioning system consists of many pieces of mechanical and electrical equipment assembled together to produce in an enclosed space acceptable conditions of Temperature, Humidity, Air purity and Air motion. The basic compression refrigeration cycle, the most important part of an airconditioning system, is explained in the schematic diagram given below:
TECHNICAL MANUAL
Outdoor Units
22 TR Model
Main Components
Air-cooled Packaged AC
A. Indoor Unit (IDU) COMPRESSOR COOLING COIL EXPANSION VALVE BLOWER FAN BLOWER FAN MOTOR FILTER CONTROL PANEL B. Outdoor Unit (ODU) CONDENSER COIL CONDENSER FAN WITH MOTOR
Water-cooled Packaged AC
A. Indoor Unit (IDU) B. Water cooled condenser (EXTRA)
TECHNICAL MANUAL
Outdoor Units
3 TR Model
7.5 TR Model
22 TR Model
Features
Here are some of the features that make the Hi Per Plus Packaged Airconditioner a high-end, superior quality product: Efficient heat transfer: The upsized evaporator offering enhanced surface area ensures removal of the high sensible heat and handles a higher indoor air volume of 550 CFM per ton. The inner grooved copper tubes with mechanically bonded slit aluminium fins ensure efficient heat transfer. Higher capacity evaporator fan: Optimally selected DIDW forward curved centrifugal type fan exclusively designed for delivering more air volume at 550 CFM/ton, with low noise levels. Optimum expansion valve: Optimally selected expansion valve with accurate preset super heat settings, minimizes splash gas and eliminates the problem of improper cooling in the evaporator. Condenser with higher heat rejection capability: The upsized condenser coil and twin fan condenser with higher heat rejection capability, ensures lower condensing temperature, thereby delivering full capacity even at temperatures as high as 45o C with extraordinary energy efficiency and substantially lower power consumption. Corrosion resistant blue fin condenser: The special precoated Blue Fin Condensers are resistant to both chemical and saline corrosion. They are tested for 500 hours of salt spray as per international standard JIS-Z-2371.
TECHNICAL MANUAL
Energy efficient scroll compressors: Scroll type, hermetically sealed highly energy efficient Copeland compressors. Acoustically treated and polyester powder painted panels: High-density EPE Insulation dampens the unit noise in the plant room.The panels are finished with glossy polyster powder paint, for longer life. Safety alarms and controls: Built-in safety features in the compressor and in the refrigeration circuits ensure high level of protection to the unit. Advanced Microcomputer Controller: A feature-packed microcomputer controller with Run Time Equalization, Auto Restart after power failure, Fuzzy Logic, Self-Fault Diagnostics and much more.
Features
Here are some of the features that make the HiSen Packaged Airconditioner a high-end, superior quality product. Efficient heat transfer cooling coil, with enhanced surface area: The inner grooved copper tubes with mechanically bonded slit aluminum fins ensure efficient heat transfer. The upsized-cooling coil offering enhanced surface area ensures removal of the high sensible heat and handles a higher indoor air volume of 550 CFM per ton. Higher capacity evaporator fan: Optimally selected DIDW forward curved centrifugal type fan exclusively designed for delivering more air volume at 550 CFM/ton with low noise levels. Optimum expansion valve: Optimally selected expansion valve with accurate preset super heat settings, minimizes splash gas and eliminates the problem of improper cooling in the evaporator. Corrosion resistant blue fin condenser: The special precoated Blue Fin Condensers can take on the harsh combination of salty air, rain and other corrosive atmospheres. They are tested for 500 hours of salt spray as per international standard JIS-Z-2371. Energy efficient scroll compressors: Scroll type, hermetically sealed highly energy efficient Copeland compressors. Acoustically treated and polyester powder painted panels: High density rigid acoustic board insulation, with over layer protection, dampens the unit noise in the plant room. The panels are finished with glossy polyester powder paint, for longer life. Ready-made air outlet flange connections: Units are provided with readymade flanged air outlets, to enable ease of connection to the canvas or the duct flange. Safety alarms and controls: Built in safety features in the compressor and in the refrigeration circuits ensure high level of protection to the unit.
TECHNICAL MANUAL
Tandem Compressor
A tandem scroll compressor consist of two individual compressors, mounted on a common base, manifolded in to a single refrigerant circuit. A tandem compressor (set) has the common suction, discharge, oil and also additional crank gas equalizer lines between the two compressors. For example, two scroll compressors are linked in tandem to form one tandem scroll compressor.
10
TECHNICAL MANUAL
In a conventional multi-circuit air conditioning system (as in a 11 ton Scroll Packaged AC), two 5.5-ton compressors drive two independent circuits, each with its own evaporator and condenser, each circuit rated to 5.5 tons. In a tandem scroll air conditioner, the 11-ton tandem scroll drives just one circuit, which therefore consists of just one condenser and evaporator, both of which are however designed for the full capacity of 11 tons.
11
B) Specifications
1. Power supply Single phase, Voltage: 175 to 260 V AC. Frequency: 50 Hz + 3% 2. Operating temperature limit 3. Display 0 - 65o C 2 Digit 7-Segment LED Display, LED indicators and touch key pad 4. Temperature control accuracy 5. Set temperature range 6. Temperature sensors + 1% 19 - 32o C NTC thermister bit sensor with 5 meter long cable
7. LED Display & Keypad HANDSET Pendant mounting 8. Micro Computer Base unit Base mounting (enclosed in fire-retardant box)
COOL MODE LED : If Cool Mode is Selected, then only this LED indicator glows blue. COMPR 1,2,3 LED : If Compr 1, 2, 3 are ON, this LED indicator is Green, and Red it it is OFF. ON/OFFLED UP/DN Key : This indicator is green if the unit is in ON mode and Red if it is in OFF. : These keys are used to increment values of the selected parameter.
12
TECHNICAL MANUAL
: This key is used for selecting either Fan or Cool Mode. : This key is used for switching ON or OFF the unit. : This key is used for resetting a Fault or for restarting the unit after removing the existing fault.
D) Setting of Temperature
The 2-digit seven-segment display shows Actual Return Air Temperature. To view Set Temp, press UP/DN key once. At any time of operation, if no key is pressed for next successive 10 seconds, the display will show Actual Return Air Temperature. Temperature can be set between 19 to 32o C by pressing the UP/ DN keys. After you press UP or DN key Display will indicate the old setting. Press desired key to set new values. As soon as you reach the desired Temperature stop adjusting the keys. The digits will start blinking for 5 seconds. When the blinking stops the LED will show the Actual Return Air Temperature. Recommended Temperature for optimum comfort and power saving is 24 +/- 1o C.
Cooling Tower Fault Fan Overload Fault Cond Fan1 MCB trip/off Fault Cond Fan2 MCB trip/off Fault Cond Fan3 MCB trip/off Fault
Ct
BF
CF
CF
CF
13
HP LP (scrolling)
COMPR 1 LED indicator will flash Red if the fault exists. RESET LED indicator will flash after the fault is cleared, now press Reset Key to restart the unit. COMPR 2 LED indicator will flash Red if the fault exists. RESET LED indicator will flash after the fault is cleared, now press Reset Key to restart the unit. COMPR 3 LED indicator will flash Red if the fault exists. RESET LED indicator will flash after the fault is cleared, now press Reset Key to restart the unit. IF Temp sensor is open or bad then only LED will display Fault. This fault is Auto reset.
HP LP (scrolling)
HP LP (scrolling)
tH
14
TECHNICAL MANUAL
F) Operating Instructions
Switch ON the unit by pressing ON/OFF key. ON LED will glow Green.
ON/OFF Key
To Start Evaporator Blower (FAN Mode) Press AC MODE Key to select the FAN Mode. FAN Mode LED will glow. The Blower Fan will come on immediately (if fan overload relay is not tripped.) To Start Compressor (COOL Mode) Press AC MODE Key once again to select the COOL Mode. COOL Mode LED will glow & Fan Mode LED will be Off. The compressor will come on with pre-set delay of 2 minutes. In case of multi compressor system the 2nd & 3rd compr. will come on after additional 15 sec. delay per compressor. Simultaneously the compressor indication starts blinking Green & then glow continuously thereafter. The Controller will select the number of compressors to be on based on Actual Room Temp & Set Temp. as follows: If actual Temp =/> Set Value + 3, all the Compressors will be ON. If actual Temp =/< Set Value + 2, only two Compressors will be ON. If actual Temp =/< Set Value + 1, only one Compressor will be ON. If actual Temp =/< Set Value - 1, all the Compressors will be OFF.
15
B) Specifications
1. Powers supply 2. Operating temperature limit 3. Display 4. Temperature control accuracy 5. Set temperature range 6. Temperature sensors 7. LED Display & Keypad HANDSET 8. Micro Computer Base Unit Single Phase, Voltage: 185 to 260 V AC. Frequency: 50 Hz 3% 0 - 65C 2 Digit 7-Segament LED Display, LED indicators and touch key pad 1% 19 - 32C NTC thermister Bit sensor with 5 meter long cable Pendant mounting Base mounting (enclosed in fire-retardant box)
COOL MODE LED : If Cool Mode is Selected then only this LED indicator will glow blue. COMPR 1,2,3 LED : Compr 1,2,3 is ON, this LED indicator is Green and Red if it is OFF. ON/OFF LED UP/DN Key : This indicator is Green if the unit is in ON mode and Red if it is OFF. : These keys are used for increment / decrement value of the selected parameter.
16
TECHNICAL MANUAL
: This key is used for selecting either Fan or Cool Mode. : This key is used for switching ON or OFF the unit. : This key is used for switching Fan speed High/Low. : This key is used for resetting the Fault or for restarting the unit after removing the existing fault.
D) Setting of Temperature
The 2-digit seven-segment display will show the Actual Return Air Temperature. To view Set Temp. press UP/DN key once. At any time of the operation, if no key is pressed for next successive 10 seconds, the display will show Actual Return Air Temperature. Temperature can be set between 19 to 32 Degree Centigrade by pressing UP/DN keys. After you press UP or DN key Display will indicate the old setting. Press desired key to set new values. As soon as you reach the desired Temperature stop adjusting the keys. The digits will start blinking for 5 seconds. When the blinking stops the LED will show the Actual Return Air Temperature. Recommended Temperature for optimum comfort and power saving is 24 +/- 1 Deg. Cen.
CF
HP LP (scrolling)
HP LP (scrolling)
tH
17
F) Operating Instructions
Switch ON the unit by pressing ON/OFF key. ON/OFF key LED will glow Green.
On/Off Key
Fan Mode
Speed LO To Start Evaporator Blower (FAN Mode): Press AC MODE Key to select the FAN Mode, then FAN Mode LED will glow. The Blower Fan will come on immediately. To Start Compressor (COOL Mode): Press AC MODE Key once again to select the COOL Mode, then COOL Mode LED will glow & Fan Mode LED will be Off. The compressor will come on with pre-set delay of 1 minutes. In case of multi compressor system the 2nd & 3rd compr. will come on after additional 10 sec. delay per compressor. Simultaneously the compressor indication will start blinking in Green for time period stated & glow continuously thereafter. Controller will select number of compressors based on Actual Room Temp & Set Temp. as following If Actual Temp =/> Set Value + 3, all the Compressors will be ON. (Only for DSA 903) If actual Temp =/< Set Value + 2, only two Compressors will be ON. (for DSA 903 / 1322) If actual Temp =/< Set Value + 1, only one Compressor will be ON. If actual Temp =/< Set Value - 1, all the Compressors will be OFF.
18
TECHNICAL MANUAL
A healthy supply
CHECK IF INCOMING POWER IS AS PER THE RATED POWER SUPPLY: VOLTS PHASE CYCLES TYPE 380-420V THREE PHASE 50 Hz AC ONLY
Regular inspection
Regular inspection must be carried out as follows: Item Filter cleaning Period Once a week Inspection Procedure For Packaged AC
Filter Water hose
Pull out from top ends and lift to remove the front GRILLE from the UNIT. Then remove the internal filter and wash it with water. Dry the filter in the shade and re-install it. For Ducted Split AC Slide the filter from lifting upwards and wash it with water. Dry the filter in the shade and re install it.
19
Item
Period
Inspection Procedure For Packaged AC Oil leaks... Verify that there are no oil leaks. Crank case heater...Touch the heater body to verify that it is warm. Vibration isolation rubber ... Inspect the vibration isolation rubber for wear. For Ducted Split AC Oil leaks... Verify that there are no oil leaks. Vibration isolation rubber ... Inspect the vibration isolation rubber for wear. Check for bolts tight at the mounting legs.
Twice a year
Twice a year
For Packaged AC
Remove the grille and front bottom cover and conduct test for gas leaks in all refrigerant pipe joints. Gas leak check Four times a year For Ducted Split AC Indoor Unit
Remove the cover from the bottom and conduct test for gas leaks inside portion of the coil and remove filter for outer portion. Outdoor Unit
Test for leaks in condenser coil tubes and also compressor joints.
20
TECHNICAL MANUAL
Item
Period
Thorough cleaning of coil and the overall unit can reduce atmospheric dust pollution and improves performance. For Ducted Split AC Electrical circuits & terminals Four times a year Check all wires/cables and connector terminals are tight with screwed ends. If not, tighten and pull the wire for proper grip/ holding. Clean the condenser coils with portable blower to blow out dust. This improves the performance.
Condenser coils
Once in a month
21
Troubleshooting
Faults and complaints in Packaged AC systems can be broadly classified under three areas. The first step in troubleshooting is to identify the area and diagnose the fault.
Diagnosing faults
Malfunctions can be classified under any of the following: A. The Electrical Circuit The malfuntioning of electrical circuit is due to LOW or HIGH voltage variations, frequent power failures, loose electrical contacts, defective electrical components, etc. Proper periodical maintenance of the unit will reduce such malfunctioning. Problems due to power supply quality must be sorted out with the concerned electricity board. B. The Refrigeration Circuit Improper cooling usually indicates poor performance of the refrigeration circuit. Reasons may be poor servicing, low/high gas in the system, noncondensible gases, and lower efficiency of the compressor. Periodical service helps avoid such problems. The troubleshooting chart that follows will help isolate the exact fault and suggest remedies. C. The Conditioned Air Circuit Less air flow, poor cooling, uneven temperature, excessive airleaks are complaints that come under this classification. Most of them can be eliminated by periodical servicing. The troubleshooting chart that follows will help isolate the exact fault and suggest remedies.
CAUSE
REMEDY
(continued)
22
TECHNICAL MANUAL
SYMPTOMS
CAUSE
REMEDY
Clogged suction strainer No cooling load Choked air filter Thermostat erratic Air in the system Overcharged gas Condenser fan not working Liquid knock Defective valve reeds
Clean/replace strainer Check thermostat Clean air filter Check thermostat Purge the system Remove excess charge Check ODU performance Check return air filter/ Check for coil chokeup Replace compressor
COMPRESSOR NOISY
SCROLL COMPRESSOR COMPRESSOR PRESSURE DOES NOT BUILD UP TO HIGH PRESSURE COMPRESSOR PRESSURE DOES NOT GO DOWN ON LOW PRESSURE COMPRESSOR NOISY Compressor motor working in reverse rotation Do Interchange any two phases of polarity for changing direction Do
Do
Do
Restore power supply Reset relay Check electrical circuit and replace
3. OVERALL UNIT NOISY OPERATION Blower touching scroll Bearing noise Belt loose Realign blower Lubricate bearings Tighten the belt
(continued)
23
SYMPTOMS
CAUSE
Loose panels
REMEDY
Check & tighten screws Charge gas Replace thermostat Recheck heatload
4. CONDITIONED AREA DISCOMFORT IN THE CONDITIONED AREA Less air flow High humidity Poor cooling Excess heat load Inadequate cooling Less airflow Compressor trips soon after start TOO COLD IN CONDITIONED SPACE Check air filter / belt Regulate fresh air Check refrigeration circuit Check & regulate heat load Check compressor ON/ Check filter choke up Check reversal of blower fan Change incoming supply phase polarity on any two phases (for scroll compressor) Replace thermostat Replace contactor
24
TECHNICAL MANUAL
25
CAUSE
Faulty drift elimination
REMEDY
Check to be sure all Louvres, Eliminator Sections or slats and splash retainers are in place. Top deck assemblies and wood fill splash bars must be intact and level. There must be no tendency to channel water. Fill packs must be intact and in place with no sagging or gaps between packs.
Over-pumping
Reduce water flow to tower to design conditions or use larger metering orifices. Tighten all bolts and cap screws on all mechanical equipment and supports. Be sure blades are properly positioned in correct sockets. Check match numbers. Make certain all blades are as far from centre of fan as safety devices permit. All blades must be pitched the same. Clean-off deposit build up on blades. Disconnect load and operate motor. If motor still vibrates, check for bent shaft or unbalanced rotor. Replace shaft or rebalance rotor. Tighten fan hub cover fasteners. Check water quality Install Water Treatment System
Fan
Motor
Loose fan hub cover Insufficient blow down Poor water quality
26
TECHNICAL MANUAL
Technical Specifications
MODELS
Floor-Mounted Packaged ACs
HiPer Plus + Packaged Airconditioner HiSen Packaged Airconditioner Tandem Packaged Airconditioner Air Cooled Packaged Airconditioner DPAP 661S, 1052S, 1322S, 1983S DPAN 661S, 1052S, 1322S, 1983S DPAY 1321S, 1982S DPA 661BS, 1052BS, 1322BS, 1983BS, 2642S DPW 661AS, 1322AS, 1983AS
Ducted Splits
Aircooled Ductable Splits with Recip. Compressor Air Cooled Ductable Splits with Scroll Compressor Water Cooled Ductable Splits with Scroll Compressor and Recip DSA 361D, 601D, 903B
27
HiPer Plus
(Hi Sensible Air-cooled Packaged Airconditioners with Scroll Compressors & High EER Condensers)
Model Nominal Cooling Capacity Units KCAL/HR TR Indoor Unit Dimensions Cooling Coil Blower Fan Nominal Airflow Fan Motor Compressor Conrol Panel External Static Outdoor Unit (high ambient) Dimensions Condenser Coil Quantity Condenser Fan Type Nominal Airflow Fan Motor Quantity Indoor Unit Weight Outdoor Unit Weight Safety Devices for Compressor Protection Kg Kg CMH Watts 7500 188 2 195 75 W x D x H (mm) 1020 x 406 x 1270 1 1020 x 406 x 1270 2 Propeller 7500 188 2 295 75 7500 188 2 470 75 7500 188 2 600 75 1020 x 406 x 1270 2 1020 x 406 x 1270 3 Inner Grooved with Slit Fins-Anti Corrosion Coating 6 CMH Watts Type Quality 1 4675 560 W x D x H (mm) 900 x 660 x 1700 1160 x 660 x 1700 Centrifugal 7450 1500 Scroll 2 Inbuilt 7.5 8 10 2 9350 2250 14025 3000 1500 x 750 x 1800 1500 x 930 x 2000 Internally Grooved Copper Tubing with Slit Fins DPAP-661S 16500 5.5 DPAP-1052S 26250 8.75 DPAP-1322S 33000 11 DPAP-1983S 49500 16.5
Inbuilt Internal Thermal Protector Internal Pressure Relief Valve High Pressure Cutout Low Pressure Cutout
Refrigerant Piping/Elecrical Hot Gas Line Liquid Line Condensate Drain GI / PVC MCB Rating Power Cable Incoming Earthing Double Loop Copper Od Inches X Gauge 7/8 X 16G 5/8 X 19G 32mm 32A 4Cx6mm Sq Cu 2 X 8 G GI Wires
Hard Drawn Grade - L Copper Tubes Only 7/8 X 16G 5/8 X 19G 32mm 40A 4Cx10mm Sq Cu 2 X 8 G GI Wires 7/8 X 16G 5/8 X 19G 32mm 40A 4Cx10mm Sq Cu 2 X 8 G GI Wires 7/8 X 16G 5/8 X 19G 32mm 63A80A 4Cx16mm SQ CU 2 X 8 G GI Wires
28
TECHNICAL MANUAL
HiSen
(Hi Sensible Air-cooled Packaged Airconditioners with Scroll Compressors & Standard Condensers)
Model Nominal Cooling Capacity Units KCAL/HR TR DPAN-661S 16500 5.5 DPAN-1052S 26250 8.75 4 Wire System-415V -3PH-50Hz Indoor Unit Dimensions Cooling Coil Blower Fan Nominal Airflow Fan Motor Power Compressor CMH Watts Type Quality Conrol Panel External Static Outdoor Unit (Normal ambient) Dimensions Condenser Coil Quantity Condenser Fan Type Nominal Airflow Fan Motor Power Quantity Indoor Unit Weight Outdoor Unit Weight Safety Devices for Compressor Protection Kg Kg CMH Watts 7500 240 1 195 86 W x D x H (mm) 1020 x 406 x 954 1020 x 406 x 954 1020 x 406 x 954 1020 x 406 x 954 MM 6 1 4675 560 W x D x H (mm) 900 x 660 x 1700 1160 x 660 x 1700 1500 x 750 x 1800 1500 x 930 x 2000 DPAN-1322S 33000 11 DPAN-1983S 49500 16.5
Internally Grooved Copper Tubing with Slit Fins Centrifugal 7450 1500 Scroll 2 Digital-Micro Controller Type Inbuilt 7.5 8 10 2 3 9350 2250 14025 3000
Inner Grooved with Slit Fins-Anti Corrosion Coating 1 2 Propeller 7500 240 1 295 86 Inbuilt Internal Thermal Protector Internal Pressure Relief Valve High Pressure Cutout Low Pressure Cutout Hard Drawn Grade - L Copper Tubes Only 7/8 X 16g 7/8 X 16g 7/8 X 16g 5/8 X 19g 32mm 32A Copper 4Cx6mm Sq Cu 2 X 8 G GI Wires 5/8 X 19g 32mm 40A 4Cx10mm Sq Cu 2 X 8 G GI Wires 5/8 X 19g 32mm 63A 4Cx10mm Sq Cu 2 X 8 G GI Wires 7/8 X 16g 5/8 X 19g 32mm 63A 4Cx16mm Sq Cu 2 X 8 G GI Wires 7500 240 1 470 86 7500 240 1 600 86 2 3
Refrigerant Piping/Electrical Hot Gas Line Od Inches X Gauge Liquid Line Condensate Drain GI/PVC MCB Rating Power Cable Incoming Earthing Double Loop
29
Control Panel Outdoor Unit Dimensions Quantity Condenser Fan Type Nominal Airflow Fan Motor Quanity Indoor Unit Weight Outdoor Unit Weight Refrigerant Piping/Elecrical Hot Gas Line Liquid Line Condensate Drain GI / Pvc MCB Rating Power Cable Incoming Earthing Double Loop
30
TECHNICAL MANUAL
W x D x H (mm)
3740 560 1 6
Conrol Panel External Static MM Outdoor Unit (Normal ambient) Dimensions W x D x H (mm) Condenser Coil Quantity Condenser Fan Type Nominal Airflow CMH Fan Motor Power Watts Quantity Indoor Unit Weight Kg Outdoor Unit Weight Kg Safety Devices for Compressor Protection Refrigerant Piping/Elecrical Hot Gas Line Liquid Line Condensate Drain Gi / PVC Mcb Rating Power Cable Incoming Earthing Double Loop Od Inches X Gauge
1160 x 660 x 1700 1160 x 660 x 1700 1500 x 750 x 1800 Internally Grooved Copper Tubing with Slit Fins Centrifugal 5900 7480 11220 1100 1500 2250 Hermetically Sealed Scroll 2 2 3 Digital-Micro Controller Type (Inbuilt) 7.5 8 9
14960 3000 2 10
1020 x 406 x 954 1020 x 406 x 954 1020 x 406 x 954 1020 x 406 x 954 Inner Grooved with Slit Fins-Anti Corrosion Blue fin coated 1 2 2 3 Propeller 7500 7500 240 240 1 1 295 302 86 86 Inbuilt Internal Thermal Protector Internal Pressure Relief Valve High Pressure Cutout Low Pressure Cutout 7/8 X 16g 5/8 X 19g 32mm 40A 4cx10mm Sq Cu 2 X 8 G GI Wires 7/8 X 16g 5/8 X 19g 32mm 40A 4cx10mm Sq Cu 2 X 8 G GI Wires
Hard Drawn Grade - L Copper Tubes Only 7/8 X 16g 5/8 X 19g 32mm 32A 4cx6mm Sq Cu 2 X 8 G GI Wires 7/8 X 16g 5/8 X 19g 32mm 63A 4cx16mm Sq Cu 2 X 8 G GI Wires 1 1 / 8 X 16g 7 / 8 X 19g 32mm 80A 4cx25mm Sq Cu 2 X 8 G GI Wires
Copper
31
Oil Charge (Ltrs) Power Supply Operating Voltage Mounting Arrangement Compressor Wt. Evaporator Coil Fin Material Tube Material Tube Dia Mm / Inches Evaporator Blower Blower Fan Nominal Airflow Fan Motor Blower Size (Od Xlg) No Of Blowers Motor Rpm Expansion Device Air Filter Size No Of Filters Condenser Water Cooled Type Tube Material/ Od Quantity Water Connections In & Out Refrigerant Conn. -Hs Inlet/ Liquid Fusible Plug Size / Melting Temp. Drain Plug And Vent Water Quantity Pressure Drop Fouling Factor Sq. Ft. Hr. Deg. F/Btu Drain Piping/Elecrical Condensate Drain GI / PVC MCB Rating Power Cable Incoming Earthing Double Loop
Ltrs
1.77
Kgs
38.1
mm Nos
457x933x10 3
Cu / 3/4"Od 1 32 Mm 1/2" / 3/8" 9.5mm/91 C 6.3 Mm / 1/4" 40 9 0.0005 GI/ Class B Pipes 32mm 40A 4cx10mm Sq Cu 2 X 8 G GI Wires
20 3.5
60 10
Copper
32
TECHNICAL MANUAL
Aluminium 0.16mm Thick Copper 9.5 / 3/8" Centrifugal Forward Curved Double InletCentrifugal Forward Curved Double Inlet Cmh Watts Mm Qtty Mm Mm Nos Rpm WxDx H (mm) Type Quantity Kw 3740 375 270x270 1 280x345 563 X 403 2 920/870 1020x406x954 Scroll 1 5.25 5650 5900 7480 375 Each 375 Each 375 Each 270x270 270x270 270x270 2 2 2 280x920 280x920 280x1095 Thermostatic Expansion Valve With External Eqaliser 468x403 468x403 593x403 3 3 3 920/870 920/870 920/870 1380x856x557 Scroll 1 7.86 1020x406x954 Scroll 2 4.14 1020x406x954 Scroll 2 5.25 14960 375 Each 305x229 3 342x1650 645x595 3 920/870 1435x620x947 Scroll 2 10.5
Oil Charge (Ltrs) Power Supply Operating Voltage Mounting Arrangement Compressor Wt. Condenser Coil Quantity Condenser Fan Type Nominal Airflow Fan Motor Quanity Weight Refrigerant Piping/ Elecrical Suction Line Liquid Line Condensate Drain GI / PVC Mcb Rating Power Cable Incoming Earthing Double Loop
Ltrs
Inbuilt Internal Thermal Protector Internal Pressure Relief Valve High Pressure Cutout Low Pressure Cutout 1.77 3.25
1.77
1.77
3.25
Kgs
Cmh Watts Kg
380 / 420 V , 3 Phase, 50 Hz Ac 342 / 462 4 Nos Rubber Mounts With Sleeves 38.1 69.4 35.4 3/8" (9.5mm) Cu Tubes And 0.16 Mm Thick Al Fins 1 2 2 Four Blade Propeller Fan 7500 10200 7500 240 586 240 1 1 1 107 188 107 Hard Drawn Grade - L Copper Tubes Only 7/8 X 19g 5/8 X 19g 25mm 32A 4cx6mm Sq Cu 2 X 8 G Gi Wires 1 1/8 X 19g 5/8 X 19g 25mm 40A 4cx10mm Sq Cu 2 X 8 G Gi Wires 3/4 X 19g 1/2 X 19g 25mm 40A 4cx10mm Sq Cu 2 X 8 G Gi Wires
Od InchesxGauge
Copper
33
DSA -903B
7.5
1525x660x457
CMH Watts
mm
7.5
Elec. Micro Processor Pendant Controller 60 80 Hard Drawn Grade - L Copper Tubes Only Od Inches X Gauge 3/4 X 19g 3/8 X 19g 25mm 32A 4cx6mm Sq Cu 2X8 G GI Wires 7/8 X 19g 5/8 X 19g 25mm 32A 4cx6mm Sq Cu 2X8 G GI Wires 86 112
34
TECHNICAL MANUAL
Centrifugal CMH /CFM Watts 2050/1200 180 1 1200/1100 3740/2200 375 1 2 - 920/870 230 V - 1 Ph - 50 Hz mm 4 5 6 7 5900/3440 375 2 2 - 920/870 7480/4400 375 2 2 - 920/870
1 415 V -3 Ph - 50Hz
Scroll 1 1
Electronic Micro Processor Pendant Controller 68 149 GI/ Ms Class B Pipes 40mm 40mm 25mm 32A 4cx6mm Sq Cu 2 X 8 G GI Wires 32mm 32mm 25mm 40A 4cx10mm Sq Cu 2 X 8 G GI Wires 40mm 40mm 25mm 63A 4cx10mm Sq Cu 2 X 8 G GI Wires 96 144 127 149
35
36