Property Inspection Report

Fairfax, Fairfax, VA Inspection prepared for: Happy Customer Real Estate Agent: Date of Inspection: 3/6/2013 Time: 11:00 am Weather: Sunny Inspector: Paul DeFelice 2616 Morse Lane, Woodbridge, VA 22192 Phone: 703-595-8431 Fax: 703-357-9170 Email: paul@capital-inspect.com www.capital-inspect.com

Capital Inspection Services

Fairfax, Fairfax, VA

Report Summary Report Summary The summary below consists of potentially significant findings. These findings can be a safety hazard, a deficiency requiring a major expenses to correct or items I would like to draw extra attention to. The summary is not a complete listing of all the findings in the report, and reflects the opinion of the inspector. Please review all of the pages of the report as the summary alone does not explain all the issues. All repairs must be done by a licensed &bonded trade or profession. I recommend obtaining a copy of all receipts, warranties and permits for the work done. Grounds Page 6 Item: 1 Driveway and Potential Trip Hazard(s) at sidewalk; monitor / repair as Walkway Condition necessary. Page 6 Item: 5 Patio and Porch Improper attachment of ledger board. Deck Page 7 Item: 6 Stairs & Handrail Uneven and excessive riser heights on spiral stairs create a safety hazard. The stairs leading from the kitchen have uneven riser heights, this is a major safety hazard, The stairs outside the side basement door have uneven riser heights and are also missing the handrail. Page 8 Item: 13 Exterior Faucet Not operational. Condition Roof Page 9 Item: 4 Sky Lights The skylight over the garage appears to leak and needs repair. Page 9 Item: 7 Gutter Clean gutters: Significant amounts of debris evident. Exterior Areas Page 10 Item: 1 Doors The two rear basement doors and the bedroom door have rotted wood frames. Page 11 Item: 2 Window Condition Several windows had visible wood rot, some of these areas had been covered with caulk and paint that covered the damage. Recommend having all windows , doors, siding and trim further evaluated for more damage that has been concealed. Page 11 Item: 3 Siding Condition Trim areas need minor prep, priming and painting Fresh paint was observed. Although it improves the appearance, it may conceal any possible defects or prior repairs. Some wood deterioration noted. Have repaired as necessary. Some siding deterioration noted. Have repaired as necessary. Page 13 Item: 5 Exterior Paint Suggest sealing/caulking as part of routine maintenance to prevent further deterioration. Several areas of the exterior wood are damaged and in need of repair. Interior Areas

Page 1 of 43

Capital Inspection Services Page 14 Item: 6 Doors

Fairfax, Fairfax, VA

Seal failure Several doors are a bit tight in jams. The basement furnace room and laundry room doors need to be vented due to gas furnace, hot water heater and future gas dryer. Page 15 Item: 7 Electrical A few lights are not working. Page 15 Item: 9 Smoke Detectors Smoke detectors and CO detectors are missing. Safety hazard. Page 16 Item: 13 Patio Doors The rear patio doors have a rotted frames. Basement side doors has wood damage. Page 16 Item: 16 Fireplace Viewed from the fire box no problems were found. Unable to remove chimney caps and unable to inspect the entire flu liners. May want to have further evaluated. Page 16 Item: 17 Window Condition Deterioration noted due to contact with moisture, repairs needed. Some windows are very difficult to open. Three sets of tall windows set lower than 18" above the floor , these need to have tempered glass installed. This is a Safety Hazard. Bedrooms Page 18 Item: 10 Smoke Detectors There were no smoke detectors present in the bedroom(s). No CO detector was observed at time of inspection. Page 19 Item: 15 Patio Doors The exterior wood storm doors need repair. Bathroom Page 20 Item: 5 Doors The door to the attic storage area in the master bathroom rubs the floor. Page 21 Item: 12 Plumbing Bidet handle leaks. Page 22 Item: 15 Shower Walls Missing/damaged grout observed, suggest regrouting as necessary. Page 22 Item: 18 Sinks Slow drain at sink. Recommend clearing. Page 23 Item: 20 Window Condition Deterioration noted due to contact with moisture, repairs needed. Kitchen Page 24 Item: 4 Doors The side door is difficult to operate. Page 24 Item: 6 Microwave The Microwave built in vent fan is missing the filter screens. Page 25 Item: 9 Sinks Supply line leaks. The basement bar sink leaks and the fixture is loose. (no picture provided) Page 26 Item: 15 Vent Condition The vent fan filter screens are missing. Heat/AC Page 31 Item: 10 Filters Basement unit is missing a filter coverplate. Garage Page 33 Item: 1 Roof Condition The skylight flashing needs repair. Appears to be leaking. Page 33 Item: 2 Walls There are two small holes above the garage access door that need to be filled. The attic access door over the living area is not fire rated, this is a safety hazard. Page 34 Item: 6 Electrical Outlet cover plates missing. Page 2 of 43

Capital Inspection Services Page 35 Item: 11 Garage Door Condition Page 35 Item: 14 Garage Door's Reverse Status

Fairfax, Fairfax, VA Rotted wood at overhead door. Recommend repairing damaged areas. deteriorated jamb Garage vehicle door auto-reverse is inoperable. The door requires a great deal of resistance to trigger the auto-reverse mechanism. We recommend adjusting the opener for proper reverse tension. No eye beam system present. Missing. Improperly sized breakers for the Main A/C. Safety Hazard. Attic is inadequately vented. Recommend review by a qualified professional for repair as necessary to ensure proper ventilation. Soffit vents and ridge are blocked with insulation. The insulation appears to be blocking the ridge and soffit vents and is touching the roof sheathing. This is a ventilation problem and also creates a adverse condition that can prematurely age the shingles. The foundation walls were mostly finished with drywall and not visible. Deterioration noted due to contact with moisture, repairs needed. Three or more risers require a handrail.

Electrical Page 36 Item: 5 Attic Page 37 Item: 3

Breakers Ventilation

Page 37 Item: 8

Insulation Condition

Foundation Page 39 Item: 2

Foundation Perimeter Basement/Crawlspace Page 41 Item: 3 Windows Page 41 Item: 9 Railings

Page 3 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

We appreciate the opportunity to conduct this inspection for you! Please carefully read your entire Inspection Report. Call us after you have reviewed your report, so we can go over any questions you may have. Remember, when the inspection is completed and the report is delivered, we are still available to you for any questions you may have, throughout the entire closing process. Properties being inspected do not "Pass" or "Fail. - The following report is based on an inspection of the visible portion of the structure; inspection may be limited by vegetation and possessions. Depending upon the age of the property, some items like GFI outlets may not be installed; this report will focus on safety and function, not current code. This report identifies specific noncode, non-cosmetic concerns that the inspector feels may need further investigation or repair. For your safety and liability purposes, we recommend that licensed contractors evaluate and repair any critical concerns and defects. Note that this report is a snapshot in time. We recommend that you or your representative carry out a final walk-through inspection immediately before closing to check the condition of the property, using this report as a guide.

Page 4 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Inspection Details
1. Attendance In Attendance: Client present Buyer Agent present Inspectors Helper 2. Home Type Home Type: Single Family Home 3. Occupancy Occupancy: Vacant

Page 5 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Grounds 1. Driveway and Walkway Condition Good Fair Poor N/A None Materials: Concrete driveway noted. X Observations: Driveway in good shape for age and wear. No deficiencies noted. Potential Trip Hazard(s) at sidewalk; monitor / repair as necessary.

Trip hazard 2. Grading


Good Fair Poor N/A None

X 3. Vegetation Observations Good Fair Poor N/A None Observations: X Prune or remove any plants that are in contact or proximity to home to eliminate pathways of wood destroying insects. 4. Gate Condition
Good Fair Poor N/A None

X 5. Patio and Porch Deck Good Fair Poor N/A None . MAINTENANCE: Whether treated or not, it is important to keep a wood X X deck surface free of all forms of fungal growth and debris that retains moisture and will cause the deck to eventually rot. Recommend cleaning and resealing the deck annually. Cleaning can be accomplished by scrubbing the deck with a sodium-hypochlorite (bleach) and Tri-Sodium-Phosphate (TSP) deck wash and then rinsing with a pressure washer. Finally, a wood deck should be recoated with a high quality deck sealant. Improper attachment of ledger board.

Page 6 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

6. Stairs & Handrail


Good Fair Poor N/A None

Observations: Uneven and excessive riser heights on spiral stairs create a safety hazard. The stairs leading from the kitchen have uneven riser heights, this is a major safety hazard, The stairs outside the side basement door have uneven riser heights and are also missing the handrail.

Uneven riser heights. Missing handrail. 7. Grounds Electrical


Good Fair Poor N/A None

Fall hazard.

X 8. GFCI
Good Fair Poor N/A None

X 9. Main Gas Valve Condition Good Fair Poor N/A None Observations: X Meter located at exterior. All gas appliances have cut-off valves in line at each unit. No gas odors detected. 10. Plumbing
Good Fair Poor N/A None

X 11. Water Pressure


Good Fair Poor N/A None

Materials: Copper piping noted.

X 12. Pressure Regulator


Good Fair Poor N/A None

Page 7 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

13. Exterior Faucet Condition Good Fair Poor N/A None Observations: X Not operational. 14. Balcony
Good Fair Poor N/A None

X 15. Patio Enclosure


Good Fair Poor N/A None

X 16. Patio and Porch Condition


Good Fair Poor N/A None

X 17. Fence Condition


Good Fair Poor N/A None

X 18. Sprinklers
Good Fair Poor N/A None

Materials: Stone

Page 8 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Roof 1. Roof Condition


Good Fair Poor N/A None

X 2. Flashing
Good Fair Poor N/A None

X 3. Chimney
Good Fair Poor N/A None

X 4. Sky Lights
Good Fair Poor N/A None

X 5. Spark Arrestor
Good Fair Poor N/A None

Observations: The skylight over the garage appears to leak and needs repair.

X 6. Vent Caps
Good Fair Poor N/A None

X 7. Gutter
Good Fair Poor N/A None

Observations: Clean gutters: Significant amounts of debris evident.

Page 9 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Exterior Areas 1. Doors


Good Fair Poor N/A None

Observations: The two rear basement doors and the bedroom door have rotted wood frames.

Door wont close. Basement.

Door rubs.

Wood damage

Rotted door frame.

Page 10 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Wood damage to frame. 2. Window Condition


Good Fair Poor N/A None

Wood damage/ repair.

Observations: Several windows had visible wood rot, some of these areas had been covered with caulk and paint that covered the damage. Recommend having all windows , doors, siding and trim further evaluated for more damage that has been concealed.

Basement window. 3. Siding Condition


Good Fair Poor N/A None

Wood damage.

Observations: Trim areas need minor prep, priming and painting Fresh paint was observed. Although it improves the appearance, it may conceal any possible defects or prior repairs. Some wood deterioration noted. Have repaired as necessary. Some siding deterioration noted. Have repaired as necessary.

Page 11 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Cracks in brick mortar.

Siding and window damage.

Not sealed

Not sealed.

Needs to be sealed.

Page 12 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

4. Eaves & Facia


Good Fair Poor N/A None

X 5. Exterior Paint
Good Fair Poor N/A None

Observations: Suggest sealing/caulking as part of routine maintenance to prevent further deterioration. Several areas of the exterior wood are damaged and in need of repair.

6. Stucco
Good Fair Poor N/A None

X 7. Deck
Good Fair Poor N/A None

Non galvinized nails.

Improperly attached to house.

Page 13 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Interior Areas The Interior section covers areas of the house that are not considered part of the Bathrooms, Bedrooms, Kitchen or areas covered elsewhere in the report. Interior areas usually consist of hallways, foyer, and other open areas. Within these areas the inspector is performing a visual inspection and will report visible damage, wear and tear, and moisture problems if seen. Personal items in the structure may prevent the inspector from viewing all areas on the interior. The inspector does not usually test for mold or other hazardous materials. A qualified expert should be consulted if you would like further testing. 1. Bar
Good Fair Poor N/A None

X 2. Cabinets
Good Fair Poor N/A None

X 3. Ceiling Fans
Good Fair Poor N/A None

X 4. Closets
Good Fair Poor N/A None

X 5. Door Bell
Good Fair Poor N/A None

X 6. Doors
Good Fair Poor N/A None

Observations: Seal failure Several doors are a bit tight in jams. The basement furnace room and laundry room doors need to be vented due to gas furnace, hot water heater and future gas dryer.

Page 14 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Bad glass seal. 7. Electrical


Good Fair Poor N/A None

Observations: A few lights are not working.

Light is not working. 8. Security Bars


Good Fair Poor N/A None

Light is not working.

X 9. Smoke Detectors
Good Fair Poor N/A None

X 10. Stairs & Handrail


Good Fair Poor N/A None

Observations: Smoke detectors and CO detectors are missing. Safety hazard.

Page 15 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

11. Window-Wall AC or Heat Good Fair Poor N/A None Observations: X Garage A/C works. Heat was not tested due to exterior temperature. 12. Ceiling Condition
Good Fair Poor N/A None

X 13. Patio Doors


Good Fair Poor N/A None

Materials: There are drywall ceilings noted.

X 14. Screen Doors


Good Fair Poor N/A None

Observations: The rear patio doors have a rotted frames. Basement side doors has wood damage.

15. Wall Condition


Good Fair Poor N/A None

X 16. Fireplace
Good Fair Poor N/A None

Materials: Drywall walls noted.

Materials: Living Room Dining Room Materials: Masonry fireplace noted. Observations: Viewed from the fire box no problems were found. Unable to remove chimney caps and unable to inspect the entire flu liners. May want to have further evaluated. Materials: Wood framed windows. Observations: Deterioration noted due to contact with moisture, repairs needed. Some windows are very difficult to open. Three sets of tall windows set lower than 18" above the floor , these need to have tempered glass installed. This is a Safety Hazard.

17. Window Condition


Good Fair Poor N/A None

Page 16 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Non tempered glass/ safety hazard.

Missing handle, hard to open.

Hard to open

Windows are not tempered glass. Safety Hazard.

Page 17 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Bedrooms The main area of inspection in the bedrooms is the structural system. This means that all walls, ceilings and floors will be inspected. Doors and windows will also be investigated for damage and normal operation. Personal items in the bedroom may prevent all areas to be inspected as the inspector will not move personal items. 1. Locations Locations: Master Guest Basement 2. Cabinets
Good Fair Poor N/A None

X 3. Ceiling Fans
Good Fair Poor N/A None

X 4. Closets
Good Fair Poor N/A None

X 5. Doors
Good Fair Poor N/A None

X 6. Electrical
Good Fair Poor N/A None

X 7. Fireplace
Good Fair Poor N/A None

X 8. Floor Condition
Good Fair Poor N/A None

X 9. Security Bars
Good Fair Poor N/A None

X 10. Smoke Detectors


Good Fair Poor N/A None

Observations: X There were no smoke detectors present in the bedroom(s). No CO detector was observed at time of inspection. Materials: Drywall walls noted.

11. Wall Condition


Good Fair Poor N/A None

Page 18 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

12. Window-Wall AC or Heat


Good Fair Poor N/A None

X 13. Window Condition


Good Fair Poor N/A None

X 14. Ceiling Condition


Good Fair Poor N/A None

Materials: Wood framed window noted.

X 15. Patio Doors


Good Fair Poor N/A None

Materials: There are drywall ceilings noted.

X 16. Screen Doors


Good Fair Poor N/A None

Observations: The exterior wood storm doors need repair.

Page 19 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Bathroom Bathrooms can consist of many features from jacuzzi tubs and showers to toilets and bidets. Because of all the plumbing involved it is an important area of the house to look over. Moisture in the air and leaks can cause mildew, wallpaper and paint to peel, and other problems. The home inspector will identify as many issues as possible but some problems may be undetectable due to problems within the walls or under the flooring.. 1. Locations Locations: Master Bathroom Main Floor Bathroom Full bathrooms in basement. 2. Cabinets
Good Fair Poor N/A None

X 3. Ceiling Condition
Good Fair Poor N/A None

X 4. Counters
Good Fair Poor N/A None

X 5. Doors
Good Fair Poor N/A None

Observations: The door to the attic storage area in the master bathroom rubs the floor.

Door rubs. 6. Electrical


Good Fair Poor N/A None

7. GFCI
Good Fair Poor N/A None

Page 20 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

8. Exhaust Fan
Good Fair Poor N/A None

X 9. Floor Condition
Good Fair Poor N/A None

X 10. Heating
Good Fair Poor N/A None

Materials: Ceramic tile is noted.

X 11. Mirrors
Good Fair Poor N/A None

X 12. Plumbing
Good Fair Poor N/A None

Observations: Bidet handle leaks.

Leaky Bidet connections. 13. Security Bars


Good Fair Poor N/A None

X 14. Showers
Good Fair Poor N/A None

X 15. Shower Walls


Good Fair Poor N/A None

Observations: Missing/damaged grout observed, suggest regrouting as necessary.

Page 21 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Grout repair needed. 16. Bath Tubs


Good Fair Poor N/A None

X 17. Enclosure
Good Fair Poor N/A None

X 18. Sinks
Good Fair Poor N/A None

Observations: Slow drain at sink. Recommend clearing.

Slow drainage. 19. Toilets


Good Fair Poor N/A None

Page 22 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

20. Window Condition


Good Fair Poor N/A None

Materials: Aluminum framed fixed window noted. Wood framed casement window noted. Observations: Deterioration noted due to contact with moisture, repairs needed.

Rotted window and frame.

Page 23 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Kitchen The kitchen is used for food preparation and often for entertainment. Kitchens typically include a stove, dishwasher, sink and other appliances. 1. Cabinets
Good Fair Poor N/A None

X 2. Counters
Good Fair Poor N/A None

X 3. Dishwasher
Good Fair Poor N/A None

X 4. Doors
Good Fair Poor N/A None

Observations: Operated.

Observations: The side door is difficult to operate.

Door rubs 5. Garbage Disposal


Good Fair Poor N/A None

X 6. Microwave
Good Fair Poor N/A None

Observations: The Microwave built in vent fan is missing the filter screens.

7. Cook top condition


Good Fair Poor N/A None

Observations: Gas cook top noted.

Page 24 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

8. Oven & Range


Good Fair Poor N/A None

X 9. Sinks
Good Fair Poor N/A None

Observations: Oven: gas burners

Observations: Supply line leaks. The basement bar sink leaks and the fixture is loose. (no picture provided)

Leak. 10. Drinking Fountain


Good Fair Poor N/A None

X 11. Spray Wand


Good Fair Poor N/A None

X 12. Hot Water Dispenser


Good Fair Poor N/A None

X 13. Soap Dispenser


Good Fair Poor N/A None

X 14. Trash Compactor


Good Fair Poor N/A None

X 15. Vent Condition


Good Fair Poor N/A None

Materials: Recirculating Observations: The vent fan filter screens are missing. Page 25 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Missing screens 16. Window Condition


Good Fair Poor N/A None

X 17. Floor Condition


Good Fair Poor N/A None

Materials: Wood framed window noted.

X 18. Plumbing
Good Fair Poor N/A None

Materials: Hardwood flooring is noted.

X 19. Ceiling Condition


Good Fair Poor N/A None

X 20. Security Bars


Good Fair Poor N/A None

Materials: There are drywall ceilings noted.

X 21. Patio Doors


Good Fair Poor N/A None

22. Screen Doors


Good Fair Poor N/A None

23. Electrical
Good Fair Poor N/A None

Page 26 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

24. GFCI
Good Fair Poor N/A None

X 25. Wall Condition


Good Fair Poor N/A None

Materials: Drywall walls noted.

Page 27 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Laundry 1. Locations Locations: Basement 2. Cabinets


Good Fair Poor N/A None

X 3. Counters
Good Fair Poor N/A None

X 4. Dryer Vent
Good Fair Poor N/A None

X 5. Electrical
Good Fair Poor N/A None

X 6. GFCI
Good Fair Poor N/A None

X 7. Exhaust Fan
Good Fair Poor N/A None

X 8. Gas Valves
Good Fair Poor N/A None

X 9. Wash Basin
Good Fair Poor N/A None

Observations: Valve in off position.

X 10. Floor Condition


Good Fair Poor N/A None

X 11. Plumbing
Good Fair Poor N/A None

X 12. Wall Condition


Good Fair Poor N/A None

Materials: Drywall walls noted.

Page 28 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

13. Ceiling Condition


Good Fair Poor N/A None

X 14. Security Bars


Good Fair Poor N/A None

Materials: There are drywall ceilings noted.

X 15. Doors
Good Fair Poor N/A None

X 16. Window Condition


Good Fair Poor N/A None

Page 29 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Heat/AC The heating, ventilation, and air conditioning and cooling system (often referred to as HVAC) is the climate control system for the structure. The goal of these systems is to keep the occupants at a comfortable level while maintaining indoor air quality, ventilation while keeping maintenance costs at a minimum. The HVAC system is usually powered by electricity and natural gas, but can also be powered by other sources such as butane, oil, propane, solar panels, or wood. The inspector will usually test the heating and air conditioner using the thermostat or other controls. For a more thorough investigation of the system please contact a licensed HVAC service person. 1. Heater Condition Good Fair Poor N/A None Materials: The furnace is located in the attic The furnace is located in the X basement The HVAC system in the basement is 12 years old and may need replacment within the next five years due to the age. The second level HVAC system appears to be 5+ years old. Materials: Gas fired forced hot air. Electric forced hot air. 2. Heater Base
Good Fair Poor N/A None

X 3. Enclosure
Good Fair Poor N/A None

X 4. Venting
Good Fair Poor N/A None

X 5. Gas Valves
Good Fair Poor N/A None

X 6. Refrigerant Lines
Good Fair Poor N/A None

X 7. AC Compress Condition Good Fair Poor N/A None Compressor Type: Electric X Location: The compressors are located on the exterior grounds. 8. Air Supply
Good Fair Poor N/A None

X 9. Registers
Good Fair Poor N/A None

Page 30 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

10. Filters
Good Fair Poor N/A None

Location: Located inside heater cabinet. Observations: Basement unit is missing a filter coverplate.

Missing filter cap. 11. Thermostats


Good Fair Poor N/A None

Page 31 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Water Heater 1. Base


Good Fair Poor N/A None

X 2. Heater Enclosure
Good Fair Poor N/A None

X 3. Combusion
Good Fair Poor N/A None

X 4. Venting
Good Fair Poor N/A None

X 5. Water Heater Condition Good Fair Poor N/A None Heater Type: Gas X 6. TPRV
Good Fair Poor N/A None

X 7. Number Of Gallons
Good Fair Poor N/A None

X 8. Gas Valve
Good Fair Poor N/A None

Observations: 75 gallons

X 9. Plumbing
Good Fair Poor N/A None

Materials: Copper

10. Overflow Condition Good Fair Poor N/A None Materials: Copper X 11. Strapping
Good Fair Poor N/A None

Page 32 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Garage 1. Roof Condition


Good Fair Poor N/A None

Materials: Roof was inspected from the roof. Materials: Asphalt shingles noted. Observations: The skylight flashing needs repair. Appears to be leaking.

Leak 2. Walls
Good Fair Poor N/A None

Observations: There are two small holes above the garage access door that need to be filled. The attic access door over the living area is not fire rated, this is a safety hazard.

Holes. 3. Anchor Bolts


Good Fair Poor N/A None

Page 33 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

4. Floor Condition
Good Fair Poor N/A None

X 5. Rafters & Ceiling


Good Fair Poor N/A None

Materials: Bare concrete floors noted. Observations: For the most part the floor was not visible due to storage.

X 6. Electrical
Good Fair Poor N/A None

Observations: Outlet cover plates missing.

Missing cover plate. 7. GFCI


Good Fair Poor N/A None

X 8. 240 Volt
Good Fair Poor N/A None

X 9. Exterior Door
Good Fair Poor N/A None

X 10. Fire Door


Good Fair Poor N/A None

X 11. Garage Door Condition Good Fair Poor N/A None Materials: Sectional door noted. X Observations: Rotted wood at overhead door. Recommend repairing damaged areas. deteriorated jamb Page 34 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

12. Garage Door Parts


Good Fair Poor N/A None

X 13. Garage Opener Status


Good Fair Poor N/A None

X 14. Garage Door's Reverse Status Good Fair Poor N/A None Observations: X Garage vehicle door auto-reverse is inoperable. The door requires a great deal of resistance to trigger the auto-reverse mechanism. We recommend adjusting the opener for proper reverse tension. No eye beam system present. Missing. 15. Ventilation
Good Fair Poor N/A None

X 16. Vent Screens


Good Fair Poor N/A None

X 17. Cabinets
Good Fair Poor N/A None

X 18. Counters
Good Fair Poor N/A None

X 19. Wash Basin


Good Fair Poor N/A None

Page 35 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Electrical 1. Electrical Panel


Good Fair Poor N/A None

X 2. Main Amp Breaker


Good Fair Poor N/A None

Location: Main Location: Panel box located in basement.

Observations: 200 amp

3. Breakers in off position Good Fair Poor N/A None Observations: X 2 4. Cable Feeds
Good Fair Poor N/A None

X 5. Breakers
Good Fair Poor N/A None

X 6. Fuses
Good Fair Poor N/A None

Materials: Copper non-metallic sheathed cable noted. Observations: Improperly sized breakers for the Main A/C. Safety Hazard.

Page 36 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Attic 1. Access
Good Fair Poor N/A None

X 2. Structure
Good Fair Poor N/A None

X 3. Ventilation
Good Fair Poor N/A None

Observations: Attic is inadequately vented. Recommend review by a qualified professional for repair as necessary to ensure proper ventilation. Soffit vents and ridge are blocked with insulation.

4. Vent Screens
Good Fair Poor N/A None

X 5. Duct Work
Good Fair Poor N/A None

X 6. Electrical
Good Fair Poor N/A None

X 7. Attic Plumbing
Good Fair Poor N/A None

X 8. Insulation Condition
Good Fair Poor N/A None

Materials: Fiberglass batts with foil facing noted. Observations: The insulation appears to be blocking the ridge and soffit vents and is touching the roof sheathing. This is a ventilation problem and also creates a adverse condition that can prematurely age the shingles.

Page 37 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

No ventilation provided. 9. Chimney


Good Fair Poor N/A None

X 10. Exhaust Vent


Good Fair Poor N/A None

Observations: Could not access.

Page 38 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Foundation 1. Slab Foundation


Good Fair Poor N/A None

Observations: Not visible to inspect due to complete basement floor finished/covered.

2. Foundation Perimeter Good Fair Poor N/A None Observations: X The foundation walls were mostly finished with drywall and not visible. 3. Foundation Walls
Good Fair Poor N/A None

Observations: Limited review due to insulation cover and finished walls.

4. Cripple Walls
Good Fair Poor N/A None

Observations: Foundation supports for most of the house are not visible for inspection.

5. Ventilation
Good Fair Poor N/A None

X 6. Vent Screens
Good Fair Poor N/A None

X 7. Access Panel
Good Fair Poor N/A None

X 8. Post and Girders


Good Fair Poor N/A None

Observations: Foundation supports for most of the house are not visible for inspection.

9. Sub Flooring
Good Fair Poor N/A None

X 10. Anchor Bolts


Good Fair Poor N/A None

Observations: The anchor bolts were not visible.

11. Foundation Electrical


Good Fair Poor N/A None

X 12. Foundation Plumbing


Good Fair Poor N/A None

X Page 39 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

13. Sump Pump


Good Fair Poor N/A None

X 14. Ducting
Good Fair Poor N/A None

Page 40 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Basement/Crawlspace
1. Walls
Good Fair Poor N/A None

X 2. Insulation
Good Fair Poor N/A None

Materials: Fully finished basement.

Observations: Not visible.

3. Windows
Good Fair Poor N/A None

Materials: Wood framed single hung window noted. Wood framed casement window noted. Observations: Deterioration noted due to contact with moisture, repairs needed.

4. Plumbing Materials
Good Fair Poor N/A None

X 5. Basement Electric
Good Fair Poor N/A None

X 6. GFCI
Good Fair Poor N/A None

7. Access
Good Fair Poor N/A None

X 8. Stairs
Good Fair Poor N/A None

X 9. Railings
Good Fair Poor N/A None

Observations: Three or more risers require a handrail.

Page 41 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

Missing handrail. 10. Slab Floor


Good Fair Poor N/A None

X 11. Finished Floor


Good Fair Poor N/A None

X 12. Drainage
Good Fair Poor N/A None

X 13. Sump Pump


Good Fair Poor N/A None

X 14. Framing
Good Fair Poor N/A None

Observations: Some areas are not visible for inspection due to wall/ceilings covered which prevents review of structural members.

15. Subfloor
Good Fair Poor N/A None

X 16. Columns
Good Fair Poor N/A None

Observations: Columns are finished or concealed, unable to inspect.

17. Piers
Good Fair Poor N/A None

Page 42 of 43

Capital Inspection Services

Fairfax, Fairfax, VA

18. Basement/Crawlspace Ductwork Good Fair Poor N/A None Observations: Not visible.

Page 43 of 43