BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

EarthingSystem ProtectionAgainstElectricShocks EarthFaultsProtection ProtectionAgainstVoltageSurges

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Earth:TheconductivemassoftheEarth,whose electric l t i potential t ti lat tanypoint i tis i conventionally ti ll takenaszero. Anearth isdefinedasaconnectiontothe generalmassofearth.

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

(1)Earthelectrode (2)Earthing conductor (3)Protectiveconductor (4)Electricalinstallation (5)Bondingconductor (6)Mainearthing terminal (7)Removablelink

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Aconductororothermetalisearthedwhenit is i effectually ff t ll connected t dto t the th general lmassof f earth bymeansofametalrodorasystemof metalwaterpipesorotherconductingobject. SolidlyearthedorBoltedearthedwhenitis earthedwithout theinterventionofafuse, , switch,circuitbreaker,resistor,reactor,or solenoid.
5

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Earthing ismeantbyhavingeveryitemof apparatus t and deveryconductor d t shall h llbe b preventedfromgivingrisetoearthleakage currents. Itiscarriedoutbyensuringanymetalliableto becomecharge g shouldbeearthandevery yp part oftheearthing circuitshouldbeproperly installed.
6

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Otheralternatives toearthing thatcouldbe employedarebyhavinganallinsulted construction,doubleinsulationandbyhaving anisolation. Earthing protectspeopleandequipmentfrom potentiallydangerousovervoltages and leakages associatedwithelectricalequipment inhomes,offices,retailoutletsandindustrial plant.
7

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Grounding
Connectingequipment eq ipmentandpointsonelectricalsystems s stems totheearth oranearthsubstitute. Purposeistolimitovervoltages betweentheequipment andtheearthduetolightning,faults,etc.

Bonding
Connectingequipmenttogetherandtothesystem neutral point. Purposeistolimitvoltages betweenequipmentandto provideapathforgroundfaultcurrent.
8

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Reason(1) Minimiseovervoltages
Lightning strike Utilityphase conductor Lightning arrester transformer

Utilityneutral conductor

Transformerearthrod

Serviceearthrod
10

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Reason(2) Limitvoltagepotentialon equipment i tenclosures l


Ungrounded motorframe Insulation breakdown Grounded motorframe Insulation breakdown

415V feeder conductors

240V

Equipment earthing conductor 400Vmotor

0V

400Vmotor

Earthing surface

Earthing surface
11

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Reason(3) Providealowimpedancepathfor fault f ltcurrent t


Ungrounded motorframe Overcurrent devices 415V feeder conductors Insulation breakdown Overcurrent devices I=0A IF Equipment earthing conductor IF IF IF 400Vmotor Grounded motorframe Insulation breakdown

400Vmotor

12

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Designingasafeearthing systemmeans providing idi the th easiest i tand dshortest h t t path thfor f the th faultcurrentwithoutexposingapersonto electricshock. Satisfactoryearthing isthemostimportantpart ofanelectricalinstallationbecauseoperation p ofalltheprotectivedevicesdependuponit.

13

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Thetotalimpedanceoftheconductor, connectingthemetalwork oftheinstallation totheearthelectrode(earthcontinuity conductor)measuredbetweentheearth electrodeandanyotherpart oftheinstallation atsupplyfrequencyshouldnotexceed1.0. Iftheresistanceishigherthan1.0 1 0 (excessive resistance),itisanindicationofimproper earthing.
14

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Earthlugterminalrusty Loosewireconnection Layersofpaintontheelectricapparatus Looseconnectionofearthwiretotheplugand socketoutlet Looseconnectionbetweenconduitand terminalbox

15

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

T = Terre (French word for earth) I = Isolation (all live parts isolated from earth or supply connected to earth through an impedance for isolation. N = Neutral (in AC system, the earth point is normally the neutral point). S = Separ (neutral and protective functions provided by separate conductors). C = Combin (neutral and protective functions combined in a single conductor, PEN).
16

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

TTsystem(earthedneutral)

One point at the supply source is connected directly to earth. All exposed and extraneousconductiveparts are connected to a separate earth electrode at the installation. This electrode may or may not be electrically independent of the source electrode.
17

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

TNCsystem

Theneutralconductorisalsousedasaprotectiveconductorandisreferredtoasa PEN(ProtectiveEarthandNeutral)conductor.
18

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

TNSsystem

The protective conductor and the neutral conductor are separate. On underground cable systems where leadsheathed cables exist, the protective conductor is generally the lead sheath.
19

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

TNCSsystem

In the TNCS system, the TNC (4 wires) system must never be used downstream of the TNS (5 wires) system, since any accidental interruption in the neutral on the upstream part would lead to an interruption in the protective conductor in the downstream part and therefore a danger.
20

10

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

ITsystem(isolatedneutral)

No intentional connection is made between the neutral point of the supply source and earth. Exposed and extraneousconductiveparts of the installation are connected to an earth electrode.
21

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

ITsystem(impedanceearthedneutral)

An impedance Zs (in the order of 1,000 to 2,000 ) is connected permanently between the neutral point of the transformer LV winding and earth
22

11

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

23

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Simplest solution to design and install. Used in installations supplied directly by the public LV distribution network. k Does not require continuous monitoring during operation. Protection is ensured by special devices, the residual current devices (RCD), which also prevent the risk of fire when they are set to 500 mA. Each insulation fault results in an interruption in the supply of power, power however the outage is limited to the faulty circuit by installing the RCDs in series or in parallel. Loads or parts of the installation which, during normal operation, cause high leakage currents, require special measures to avoid nuisance tripping.
24

12

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

TNCsystem

TNSsystem

25

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Requires the installation of earth electrodes at regular intervals throughout the installation. Requires that the initial check on effective tripping for the first insulation fault be carried out by calculations during the design stage, followed by mandatory measurements to confirm tripping during commissioning. Requires that any modification or extension be designed and carried out by a qualified electrician. May y result, , in the case of insulation faults, , in g greater damage g to the windings of rotating machines. May, on premises with a risk of fire, represent a greater danger due to the higher fault currents

26

13

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

27

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Solutionofferingthebestcontinuityofserviceduring operation. Indicationofthefirstinsulationfault,followedbymandatory locationandclearing,ensuressystematicpreventionof supplyoutages. GenerallyusedininstallationssuppliedbyaprivateMV/LVor LV/LVtransformer. Requiresmaintenancepersonnelformonitoringand operation. p Requiresahighlevelofinsulationinthenetwork(implies breakingupthenetworkifitisverylargeandtheuseof circuitseparationtransformerstosupplyloadswithhigh leakagecurrents).
28

14

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

An electric shock is the pathophysiological effect of an electric current through the human body. body The degree of danger for the victim is a function of the magnitude of the current, the parts of the body through which the current passes, and the duration of current flow. When a current greater than 30 mA passes through a human being from one hand to feet, the person concerned is likely to be killed, unless the current is interrupted in a relatively short time.
29

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Zonestime/currentofeffectsofACcurrentonhumanbodywhenpassingfromlefthandtofeet
30

15

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Adirectcontactreferstoapersoncominginto contact islive t twith ithaconductor d t which hi hi li in i normalcircumstances.

Is=Touchcurrent

31

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Anindirectcontactreferstoapersoncoming i t contact t twith ithanexposed dconductive d ti part t into whichisnotnormallyalive,buthasbecome aliveaccidentally(duetoinsulationfailureor someothercause).
Is=Touchcurrent Id=Insulationfaultcurrent

32

16

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

33

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Protectionbytheinsulation ofliveparts Protectionbymeansofbarriersorenclosures Useofresidualcurrentoperatingdevice,which operateat30mA orless,andarereferredtoas RCDs ofhighsensitivity


RCD Insulation Envelope
34

17

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Theearthing ofallexposedconductivepartsof electricalequipmentintheinstallationandthe constitutionofanequipotentialbonding network. Automaticdisconnection ofthe supplyofthesectionofthe installationconcerned concerned,insucha waythatthetouchvoltage/time safetyrequirementsare respectedforanyleveloftouch voltage(Vc).
35

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Maximumsafeduration(disconnectingtime)of theassumedvaluesofACtouchvoltage(in seconds)notexceeding32A:


Vc (V) System TNorIT TT 50<Vc 120 0.8 0.3 120<Vc 230 0.4 0.2 230<Vc 400 0.2 0.07 Vc >400 0.1 0.04

36

18

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

37

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Theimpedanceoftheearthfaultloopconsistsmainly inthetwoearthelectrodes(i.e. (i e thesourceand installationelectrodes)inseries. Themagnitudeoftheearthfaultcurrentisgenerally toosmalltooperateovercurrent relayorfuses,and theuseofaresidualcurrentoperateddeviceis essential. essential Protectionbyautomaticdisconnectionofthesupply usedinTTsystemisbyRCD ofsensitivity:
I n 50 RA
RA istheresistanceoftheearthelectrodefortheinstallation
38

19

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

TNC
39

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

InallTNsystems,anyinsulationfaulttoearth resultsinaphasetoneutralshortcircuit. circuit Highfaultcurrentlevelsallowtouseovercurrent protectionbutcangiverisetotouchvoltages exceeding50%ofthephasetoneutralvoltageat thefaultpositionduringtheshortdisconnection time. time TheuseofCB,fuses,andRCDs maybenecessary onTNearthedsystems.
40

20

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

41

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Apermanentmonitoringoftheinsulationtoearth mustbeprovided, provided coupledwithanalarmsignal(audio and/orflashinglights,etc.)operatingintheeventofa firstearthfault. Duringaphasetoearthfault,thecurrentpassing throughtheelectroderesistanceRnA isthevectorsum ofthecapacitivecurrentsinthetwohealthyphases. phases TheuseofCB,fuses,andRCDs maybenecessaryon ITearthedsystems
42

21

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Earthleakagedevicesarebasedontheprinciple thattheamountofcurrententering adevice shouldbeexactlythesameastheamountof currentleaving thedevice. Earthleakageprotectiondevicesaredesignedto tripforfaultcurrentsbetween10and100mA and forinterrupt p timesbetween40and100 millisecondsafterafaultcurrentissensed. Ithasbeengraduallyreplaced byResidueCurrent Devices (RCD)suchasRCCB.
43

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

44

22

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Forregularhouses40A/63A,singlephaseor dependsonsupplydemandandmainswitch capacity,ELCB's sensitivityisnotexceeding 100mA. Forheaterwater,itshouldpossesseparate additionalELCB(otherthanno.1above)with sensitivityisnotexceeding10mAisneeded needed. Forloadwhichhigherthan100A,3phases, ELCB's sensitivitymustnotexceed100mA.
45

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

To load

fault

earth Current Transformer

Trip p coil

Circuit Breaker

3wire 3phase supply

46

23

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

DuringnormaloperationthecurrentfromsupplyLflows throughN1,totheloadandthenflowthroughN2before returningtoN. SincethenumberofturnsofN1andN2arethesame andthecurrentthroughthemisalsothesamethe resultingfluxintheironcoreiszero. However,ifthereisaleakagefromtheloadtothe ground,acertainamountofcurrentwillflowtothe ground. AssuchcurrentthroughN1andN2willnotbethesame resultinginsomemagneticfluxsettingupinthecore. Thefaultsensingwindingwilltripthetrippingdeviceif theleakagecurrentfallswithin10to100milliampere. Atestcircuitconsistingofapushbuttonandatest resistorisnormallyincludedintheELCBasshown.Its functionistocreateanunbalancecurrentintheN1and N2windings,andthecurrentflowthroughthetest resistorisgreatenoughforthefaultsensingwindingto tripthecircuitbreaker.
47

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

TherearetwomainreasonswhyRCDsareused: To p provide additional and a higher g level of p protection than that given by direct earthing, against electric shock and also against fire risk caused by earth leakage currents. Where fuses and miniature circuit breakers (MCBs) are the only means of earth fault protection, it is possible for earth fault currents to flow undetected and cause fire risk (or touch voltage problems). The use of an RCD will prevent the flow of a sustained leakage current above the sensitivity of the RCD thus greatly reducing shock and fire risk. All live conductors in the protected circuits should be disconnected in the event of earth leakage current flowing.

48

24

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

TermsassociatedwithRCDs:
RCCB: ResidualCurrentCircuitBreakerusedindistributionboardstoprotectindividual orgroupsofcircuits RCBO: ResidualCircuitBreakerwithovercurrent protection.Thisisacombined MCB/RCDandprovidesoverload,shortcircuitandearthfaultprotectioninone unit SRCD: SocketoutletwithcombinedRCD PRCD: ThisisaportableRCDunitwithaninbuiltplugtopandsocket outlet
49

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Single Phase RCD


Phase LOAD

Detection Coil

Neutral

Relay Test Button

50

25

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Three Phase RCD


Test Button Test Resistor

L1 L2 L3 Neutral Magnetic Core Detection Coil

LOAD

Earthed Metalwork

Trip Relay

Amplifier

51

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Regulation D22 (Basic Earthing Requirements) States that earth leakage protection may be provided by means of fuses or excess current circuit breakers if the earth fault current available to operate the protective device and so make the faulty circuit dead exceeds: 1. 3 times the current rating of any semi enclosed fuse or any cartridge fuse having a fusing factor exceeding 1.5, used to protect the circuit, or 2. 2.4 times the rating of any cartridge fuse having a fusing factor not exceeding 1.5, used to protect the circuit, or 3. 1.5 times the tripping current of any excess current circuit breaker used to protect the circuit.
52

26

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Asinglephase240V,15kW50Hzmotorcircuit operatingat0.8powerfactorlaggingisprotectedbya cartridgefusehavingblowingcurrentof110A.Afault occursinthecircuitcausesacurrentof220amperesto flowthroughtheearthcontinuitypath.Asaresultof poorcontactduetoalocknutandbushconnectinga steelconduittoametalbox,theresistanceofthis conduitconnectionaloneis1.35.State: a) whetherthefusewillrupture b) theamountofheatproducedatthemetalbox c) thedegreeofrisk,ifany,ofafiredeveloping
53

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Yes.Theratingcurrent:
Ir = 15kW = 78.125 A 240V 0.8
110 A = 1.41 78.125 A
Sinceaccordingtoregulation D22,theprotectionisbya cartridgehavingafusingfactor notexceeding1.5.Thenthe maximumcurrentinthefaultis 2.4x78.125A=187.5A.

Fusingfactor:
FF =

I2R=(220)2 x1.35Ohms=65.34kW. HighRisk


54

27

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Whatisavoltagesurge?
Avoltagesurgeisavoltageimpulseorwavewhich issuperposedontheratednetworkvoltage.

55

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Voltagesurgeischaracterisedby:
The Th rise i time ti (tf)measured din i s Thegradient(S)measuredinkV/s

Avoltagesurgedisturbsequipmentandcauses electromagneticradiation. Furthermore,thedurationofthevoltagesurge (T)causesasurgeofenergy intheelectrical circuitswhichislikelytodestroy the equipment.


56

28

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

57

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Atmosphericvoltagesurges Operatingvoltagesurges Transientovervoltage atindustrialfrequency Voltagesurgescausedbyelectrostatic discharge

58

29

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Lightning risk.Between2,000and5,000stormsare constantlyformingaroundtheearth. earth Thesestorms areaccompaniedbylightningwhichconstitutesa seriousriskforbothpeopleandequipment. Strokesoflightninghitthegroundatarateof30to 100strokespersecond. Lightningaffectstransformers,electricitymeters, householdappliances,andallelectricaland electronicinstallationsintheresidentialsectorand inindustry.
59

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

LightningdischargevaluesgivenbytheIEC lightning li ht i protection t ti committee: itt


Beyondpeak probability P% 95 50 5 Currentpeak, I(kA) 7 33 85 Gradient, S(kA/s) 9.1 24 65 Totalduration (s) 0.001 0.01 1.1 Numberof discharges n 1 2 6

60

30

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Asuddenchangeintheestablishedoperating conditions diti in i anelectrical l t i lnetwork t kcauses transientphenomenatooccur. Thesearegenerallyhighfrequencyordamped oscillationvoltagesurgewaves.

61

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Theopeningofprotectiondevices(fuse,circuit breaker), ),andtheopening p gorclosing gofcontrol devices(relays,contactors,etc.). Inductivecircuitsduetomotorsstartingand stopping,ortheopeningoftransformers suchas MV/LVsubstations. Capacitivecircuitsduetotheconnectionof capacitorbankstothenetwork network. Alldevicesthatcontainacoil,acapacitor ora transformeratthepowersupplyinlet:relays, contactors,televisionsets,printers,computers, electricovens,filters,etc.
62

31

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Theseovervoltages havethesamefrequencyas thenetwork(50,60or400Hz).


63

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Phase/frameorphase/earthinsulatingfaultsona networkwithaninsulatedorimpedanceneutral, neutral orbythebreakdownoftheneutralconductor. Whenthishappens,singlephasedeviceswillbe suppliedin400V insteadof230V. Acable breakdown.Forexample,amedium g cablewhichfallsonalowvoltage g line. voltage Thearcing ofahighormediumvoltageprotective sparkgapcausingariseinearthpotentialduring theactionoftheprotectiondevices.
64

32

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Inadryenvironment,electricalchargesaccumulate andcreateaverystrongelectrostaticfield. Forexample,apersonwalking oncarpetwith insulatingsoleswillbecomeelectricallychargedtoa voltageofseveralkilovolts.Ifthepersonwalksclose toaconductivestructure,hewillgiveoffan electricaldischargeofseveralamperesinavery shortrisetimeofafewnanoseconds. Ifthestructurecontainssensitiveelectronics,a computerforexample,itscomponentsorcircuit boardsmaybedamaged.
65

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Primary protectiondevices(protectionof installations i t ll ti against i tlightning). li ht i ) Secondary protectiondevices(protectionof internalinstallationsagainstlightning).

66

33

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Thepurposeofprimaryprotectiondevicesisto protectinstallationsagainstdirectstrokesof lightning. Theycatchandrunthelightningcurrentintothe ground.Theprincipleisbasedonaprotectionarea determinedbyastructurewhichishigher thanthe rest. Therearethreetypesofprimaryprotection:


Lightningconductors Overheadearthwires ThemeshedcageorFaradaycage
67

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Thelightningconductoris ataperedrodplacedon topofthebuilding.Itis earthedbyoneormore conductors(oftencopper strips).

68

34

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Thesewiresarestretchedoverthestructuretobe protected.Theyareusedforspecialstructures:rocket launchpads,militaryapplicationsandlightningprotection cablesforoverheadhighvoltagepowerlines.


69

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Thisprincipleisusedfor verysensitivebuildings housingcomputeror integratedcircuit productionequipment. Itconsistsin symmetricallymultiplying thenumberofdownstrips outsidethebuilding.


70

35

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Thesehandletheeffectsofatmospheric, operating voltage ti orindustrial i d t i lfrequency f lt surges. Theycanbeclassifiedaccordingtotheway theyareconnectedinaninstallation:serialor parallel p p protection.

71

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Thisisconnectedinseriestothepowersupply i of fthe th system t t t t d wires tob beprotected.

72

36

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Transformers
Theyreducevoltagesurgesbyinductoreffectandmake certainharmonicsdisappearbycoupling.This protectionisnotveryeffective.

Filters
Basedoncomponentssuchasresistors,inductance coilsandcapacitorstheyaresuitableforvoltagesurges caused db byi industrial d i land doperation i di disturbance b correspondingtoaclearlydefinedfrequencyband.This protectiondeviceisnotsuitableforatmospheric disturbance.
73

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Waveabsorbers
Theyareessentiallymadeupofairinductancecoils whichlimitthevoltagesurges,andsurgearresters whichabsorbthecurrents.Theyareextremely suitableforprotectingsensitive electronicand computingequipment.

74

37

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Networkconditionersandstaticuninterrupted powersupplies(UPS)
These devices are essentially used to protect highly sensitive equipment, such as computer equipment, which requires a high quality electrical power supply. They can be used to regulate the voltage and frequency, stop interference and ensure a continuous electrical power supply even in the event of a mains power failure (for the UPS). UPS) On the other hand, they are not protected against large, atmospheric type voltage surges against which it is still necessary to use surge arresters.
75

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Theparallelprotectionisadaptedtoany i t ll ti powerlevel. l l Thi f installation Thist typeof overvoltage protectionisthemostcommonly used.

76

38

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Maincharacteristics
Theratedvoltageoftheprotectiondevicemust correspondtothenetworkvoltageattheinstallation terminals. Whenthereisnovoltagesurge,aleakagecurrent shouldnotgothroughtheprotectiondevicewhichison standby. Whenavoltagesurgeabove theallowablevoltage thresholdoftheinstallationtobeprotectedoccurs occurs,the protectiondeviceabruptlyconductsthevoltagesurge current totheearth bylimitingthevoltagetothe desiredprotectionlevel,Vp.
77

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

Whenthevoltagesurgedisappears,theprotection devicestopsconductingandreturnstostandby withoutaholdingcurrent.ThisistheidealU/I characteristiccurve:


Theprotectiondeviceresponsetime(tr)mustbeasshort aspossibletoprotecttheinstallationasquicklyas possible. The Th protection t ti d device i must th havethe th capacity it t tobe b able bl toconducttheenergycausedbytheforeseeablevoltage surgeonthesitetobeprotected. Thesurgearresterprotectiondevicemustbeableto withstandtheratedcurrent,In.
78

39

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

(1)Voltagelimiters They are used in MV/LV / substations at the transformer output, in IT earthing scheme. They can run voltage surges to the earth, especially industrial frequency surges.
79

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

(2)LVsurgearresters Lowvoltagesurgearresterscomeintheformof modulestobeinstalledinsideLVswitchboard. Theyensuresecondaryprotectionofnearby elementsbuthaveasmallflowcapacity. Someareevenbuiltintoloadsalthoughthey cannotprotectagainststrongvoltagesurges.

80

40

28/11/2012

BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy

(3)Lowcurrentsurgearresters Theseprotecttelephone orswitchingnetworks againstvoltagesurgesfromtheoutside (lightning),aswellasfromtheinside(polluting equipment,switchgearswitching,etc.). Lowcurrentvoltagesurgearrestersarealso installedindistributionboxesorbuiltinto loads.


81

41