Performance Mass Data Engineering with PCS 7 Advanced ES on a Practical Example


SIMATIC PCS 7 Application Description July 2013

Applications & Tools


Answers for industry.

Industry Automation and Drive Technologies Service & Support Portal This article is taken from the Service Portal of Siemens AG, Industry Automation and Drive Technologies. The following link takes you directly to the download page of this document: http://support.automation.siemens.com/WW/view/en/61627479

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

Task Solution Creating and Adapting the PCS 7 Project Configuring with AdvES

1 2 3 4 5 6 7

SIMATIC PCS 7 Performance Mass Data Engineering with PCS 7 AdvES on a Practical Example
Siemens AG 2013 All rights reserved

Conclusion Further Links History

Application Description

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

Warranty and Liability

Warranty and Liability


Note The Application Examples are not binding and do not claim to be complete regarding the circuits shown, equipping and any eventuality. The application examples do not represent customer-specific solutions. You are responsible for ensuring that the described products are used correctly. These application examples do not relieve you of your responsibility to use safe practices in application, installation, operation and maintenance. When using these application examples, you recognize that we cannot be made liable for any damage/claims beyond the liability clause described. We reserve the right to make changes to these application examples at any time without prior notice. If there are any deviations between the recommendations provided in this application example and other Siemens publications e.g. catalogs the contents of the other documents have priority. We do not accept any liability for the information contained in this document. Any claims against us based on whatever legal reason resulting from the use of the examples, information, programs, engineering and performance data etc., described in this application example will be excluded. Such an exclusion will not apply in the case of mandatory liability, e.g. under the German Product Liability Act (Produkthaftungsgesetz), in case of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or breach of a condition which goes to the root of the contract (wesentliche Vertragspflichten). The damages for a breach of a substantial contractual obligation are, however, limited to the foreseeable damage, typical for the type of contract, except in the event of intent or gross negligence or injury to life, body or health. The above provisions do not imply a change of the burden of proof to your detriment. Any form of duplication or distribution of these application examples or excerpts hereof is prohibited without the expressed consent of Siemens Industry Sector.

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

Preface

Preface
Objective of this application This application describes the functionality of a PCS 7 Advanced Engineering System V8.0 (AdvES) based on a practical example. Furthermore, the advantages of AdvES in comparison to the import/export wizard are explained. Main topics of this application The following core points are discussed in this application: Describing AdvES and its advantages Configuring an example project using AdvES

Validity Valid from SIMATIC PCS 7 V8.0 SP1 (incl. option package PCS 7 Advanced Engineering System V8.0 SP1)

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

Table of Contents

Table of Contents
Warranty and Liability .............................................................................................. 4 Preface ...................................................................................................................... 5 Table of Contents ..................................................................................................... 6 1 2 Task................................................................................................................. 7 Solution........................................................................................................... 8 2.1 2.2 2.3 2.4 3 3.1 3.2 3.3 3.4 3.5 3.6
Siemens AG 2013 All rights reserved

PCS 7 Advanced Engineering System ............................................... 8 AdvES advantages .......................................................................... 10 AdvES Principle of Operation........................................................... 12 Required engineering components................................................... 15 Required prerequisites of the PCS 7 project..................................... 17 Creating a project ............................................................................ 18 Deriving a CMT from Advanced Process Library (APL) .................... 23 Changes in the CMT and the technological connections................... 26 Configuring optional blocks of the "ValveAnalog" CMT ..................... 30 Configuring messages ..................................................................... 31 Data import from PCS 7 to AdvES ................................................... 33 Assigning mapping labels for the technological I/Os of a CMT.......... 39 Assigning the mapping labels .......................................................... 42 Creating variants and copy templates in AdvES ............................... 46 Creating individual mapping labels ................................................... 49 Transferring mapping labels............................................................. 53 Data import of external data ............................................................. 55 Creating the configurator for importing ............................................. 58 Importing Data ................................................................................. 71 Specifying control modules .............................................................. 75 Configuring connections .................................................................. 80 Determine connections at the CMTs ................................................ 80 Execute interconnections for the CM instances ................................ 82 Assigning hardware ......................................................................... 84 Consistency check ........................................................................... 91 Exporting data to PCS 7 .................................................................. 94 Other useful functions in AdvES..................................................... 103 Report folder.................................................................................. 103 Control module (CM) test sheets.................................................... 105 Procedure ...................................................................................... 105 Table views ................................................................................... 107 Project properties .......................................................................... 110

Creating and Adapting the PCS 7 Project ................................................... 17

Configuring with AdvES ............................................................................... 33 4.1 4.2 4.2.1 4.2.2 4.2.3 4.2.4 4.3 4.3.1 4.3.2 4.4 4.5 4.5.1 4.5.2 4.6 4.7 4.8 4.9 4.9.1 4.9.2 4.9.3 4.9.4

Copyright

5 6 7

Conclusion.................................................................................................. 111 Further Links .............................................................................................. 112 History ........................................................................................................ 113

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

1 Task

Task
Different planning and engineering tools will be used for planning and realizing a process control system. Most of the time the software data cannot be easily used in another software, since they use different data formats. Handling these different data formats is time consuming and resource intensive.

Introduction

Overview of the automation task


Figure 1-1: Engineering so far

Copyright

Siemens AG 2013 All rights reserved

Description of the automation task The following requirements must be met in order to improve the current process of engineering and save costs and resources: One-time entry and reuse of data. Support of data exchange between different tools. System support in case of modifications. Detection and documentation of data changes at the interfaces.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

2 Solution

2
2.1

Solution
PCS 7 Advanced Engineering System
SIMATIC PCS 7 Advanced Engineering System (AdvES) expands the functionality of the system configuration. It serves as a link between standard engineering tools from the SIMATIC PCS 7 Engineering Toolset (CFC, HW config, technological hierarchy (Plant Hierarchy)) and basic and detail planning tools, e.g. EPlan, ELCAD, or SmartPlant.

Properties AdvES is a SIMATIC PCS 7 optional package. AdvES prepares data for use in the PCS 7 ES. AdvES is an application for importing data. Data can be imported into AdvES from process tag and signal lists and can be transferred to PCS 7 ES. After a first assignment, AdvES will detect the control module types (CMTs) and automatically generate the control modules (CMs). In this context, technological hierarchy, signal, and parameter settings can automatically be taken over from the process tag and signal lists. Hardware (decentralized periphery including channel assignment) can be generated from the signal lists. Object-dependent mass data processing and queries are possible.
Figure 2-1: Engineering with AdvES

Copyright

Siemens AG 2013 All rights reserved

Note

Automatic generation of SFCs is not yet possible in this version of AdvES.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

2 Solution

Range of functions of AdvES Generating CMs from process tag and signal lists Creating hardware configurations from signal lists (including symbol table) Using CMs from PCS 7 (e.g. Basic Control Module - library and customerspecific libraries) Defining variants through optional blocks Mass data processing of control modules, signals, parameters, and messages Checking data consistency and plausibility Generating the PCS 7 automation data Using messages to control modules
Figure 2-2: Overview of AdvES functionality

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

2 Solution

2.2

AdvES advantages
Reduction of configuration and start-up times Easier qualification through standardized interfaces Less coordination efforts with the systems planner Technological engineering in Advanced ES without PCS 7 system knowledge Changes to process tags can be exchanged bidirectionally

General information

Increase in quality Fault prevention through standardized interfaces Verifiability of plausibility and data consistency Secured return of automation changes to systems planning Change management for supplied planning data

Siemens AG 2013 All rights reserved

Saving the expenditures for creating and maintaining separate tools and solutions

Advantages of AdvES over the import/export wizard The following table shows the advantages of AdvES over the import/export wizard:
Table 2-1: Comparison of AdvES and import/export wizard Import/export wizard PCS 7 Advanced Engineering System

Copyright

- Import of arbitrary Excel structures is + Any Excel structures can be imported.


not possible. An IEA file must be created for each process tag type prior to every import of process tag or signal lists. Process tag or signal lists can be imported directly without intermediate steps.

- No change identification during


import

+ Change identification during Excel


import

10

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

2 Solution

Import/export wizard

PCS 7 Advanced Engineering System

- No support of the new type concept


(CMT and CM)

+ Support of the new type concept


(CMT and CM)

- Not extendable for


functional planning and E&IC planning with COMOS

+ Extendable for functional planning


and E&IC planning with COMOS

- No check for data plausibility and


completeness
Siemens AG 2013 All rights reserved

+ Check for data plausibility and


completeness.

- No generation of the PCS 7 hardware + Generation of the PCS 7 hardware


configuration configuration

+ Change management for data


exchange with PCS 7

Copyright

+ Table editors with convenience


functions for searching/filtering/filling out

+ Well-structured user interface + Rule-based interconnecting of


process tags

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

11

2 Solution

2.3

AdvES Principle of Operation


With AdvES you can import engineering data such as hardware, control module types (CMs) and the technological hierarchy from the SIMATIC PCS 7 process control system in AdvES and merge it with data from process tag and signal lists (in Microsoft Excel format). The data from process tag and signal lists can be automatically imported in AdvES. When exporting data from AdvES to PCS 7, the technological hierarchy, the control modules (CMs), symbolic names and the appropriate I/O modules are generated in PCS 7. AdvES provides the user with an integrated change management for importing changed data from Microsoft Excel. Within AdvES, you can also manually create the CMs, signals, parameters, etc. on the basis of the imported CMTs. AdvES is based on an object model which is different from that of the PCS 7 world. The AdvES database model is based on a relational SQL database. In this database, data records are stored as objects. The properties of an object depend on the type that the object is based on. There are 5 object types in AdvES: Technological Hierarchy (TH) Control module (CM) CM parameter CM signal Signal parameter

General overview

Note

Note

Copyright

Siemens AG 2013 All rights reserved

Note

The AdvES database is not identical with the PCS 7 database. It will not be archived together with the PCS 7 multi-project. The AdvES database must be secured separately. This procedure is described in detail in chapter 2.5 of the Process Control System PCS 7 Advanced Engineering System manual.

12

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

2 Solution

Every AdvES project includes many objects of these types; each of these must adhere to a certain structure: TH folders can be found underneath the object node or underneath other TH folders. CMs are inside TH folders. CM parameters are placed underneath CMs. Signal parameters are placed underneath signals. Signals are placed underneath CMs.

Figure 2-3: Objects in AdvES

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

13

2 Solution

Overview of the AdvES workflow The figure below shows the AdvES principle of operation:

Figure 2-4: AdvES Principle of Operation

Copyright

Siemens AG 2013 All rights reserved

14

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

2 Solution

2.4

Required engineering components


Advanced Engineering is an independent application for additional installation on the PCS 7 engineering system already installed. AdvES is subject to license and free storage capacity of about 2 GB will be required. A setup is available for installation. The application was set up with the following components:

Standard software components


Table 2-2: Required software Component SIMATIC PCS 7 V8.0 SP1 1 No. Order number 6ES7658-5AX08-0YA5 Note Updating the SIMATIC PCS 7 V8.0 software or V8.0 update 1 to V8.0 SP1:

http://support.automati on.siemens.com/WW/v iew/en/67798122


Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced Engineering System V8.0

6ES7658-1GX08-2YA5

Updating the SIMATIC PCS 7 V8.0 Advanced Engineering System software or V8.0 update 1 to V8.0 SP1:

http://support.automati on.siemens.com/WW/v iew/en/68402701


MS Excel 2003 All Excel versions that are approved for the respective SIMATIC PCS 7 version.

Copyright

Sample files and projects The following list contains all files that are used in this example.
Table 2-3: Supplied project files Component DEMO_AdvES.zip Note This zipped file includes a PCS 7 library with 4 CMTs and one Excel signal list This document.

61627479_Application_AdvES_en.pdf

Note

The types used in the examples must be checked for use outside of this application.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

15

2 Solution

Example project The ZIP file includes a library with 4 CMTs from the basic control module library and a signal list for the example project. The signal list includes information for 170 CMs, TH, hardware, signals and parameters. The following steps must be taken to import, generate, and export this data to PCS 7 through AdvES:
Table 2-4: Configuration steps in AdvES Chapter 3 4.1 4.2 4.3 4.4 4.5
Siemens AG 2013 All rights reserved

Action Creating and Adapting the PCS 7 Project Data import from PCS 7 to AdvES Assigning mapping labels for the technological I/Os of a CMT Data import of external data Specifying control modules Configuring connections Assigning hardware Consistency check Exporting data to PCS 7 Other useful functions in AdvES

4.6 4.7 4.8 4.9

Copyright

16

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

3 Creating and Adapting the PCS 7 Project

3
3.1

Creating and Adapting the PCS 7 Project


Required prerequisites of the PCS 7 project
Prerequisites for working with AdvES are the following components in the PCS 7 multiproject: A master data library with the required control module types. At least one sub-project with an AS. At least one PROFIBUS master system in the hardware configuration of the AS.
Figure 3-1: Project step in the overall workflow

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

17

3 Creating and Adapting the PCS 7 Project

3.2
Procedure

Creating a project
1. Open the SIMATIC Manager. 2. Create a new multi-project with a sub-project using the 'New project' Wizard. File > New Project Wizard...
Figure 3-2: Creating a multi-project

Siemens AG 2013 All rights reserved

The PCS 7 Wizard: New Project opens. 3. Click on the Next button.
Figure 3-3: PCS 7 Wizard: New Project dialog

Copyright

18

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

3 Creating and Adapting the PCS 7 Project

4. Select a "AS 417-4" CPU with a matching bundle. 5. Select "0" for the "number of communication modules" of the CP-443-5 in the drop-down menu. 6. Click on the Next button.
Figure 3-4: PCS 7 Wizard: New Project dialog

Siemens AG 2013 All rights reserved

7. Select 1 for the number of levels for the technological hierarchy. OS objects for PCS 7 OS, SIMATIC BATCH, route control and open PCS 7 are not required.
Figure 3-5: PCS 7 Wizard: New Project dialog

Copyright

8. Click on the Next button. Assign a suitable name for the project, e.g. AdvES_example. 9. Then click on the Finish button. A new PCS 7 multi-project is generated.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

19

3 Creating and Adapting the PCS 7 Project

Figure 3-6: PCS 7 Wizard: New Project dialog

10. When you have created the project, change the name of the AS to AS1 and the Process cell(1) technical hierarchy folder to Process cell.
Siemens AG 2013 All rights reserved

11. Delete the plans SFC(1) and CFC(1) in the Process cell technological hierarchy folder.
Figure 3-7: Deleting the plans

Copyright

12. Open NetPro in the toolbar of the SIMATIC Manager and delete the MPI bus there.
Figure 3-8: "NetPro

20

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

3 Creating and Adapting the PCS 7 Project

13. Retrieve the included library with the CMTs.


Figure 3-9: Retrieving library

Siemens AG 2013 All rights reserved

14. Drag the included CMTs ("AMON_Std", "CTRL_Std", "MOT_1sp_2fb_1cm" and "MOT_2sp") into the master data library of your project.
Figure 3-10: Accepting the control module types

Copyright

Note

As of V8.0, PCS7 provides you with a new type concept which, together with PCS 7 Advanced Engineering (AdvES), allows for improved mass data engineering as well as for changes to control module types already instantiated. For details on the new type concept, please refer to chapter Handling of control module types in the SIMATIC Process Control System PCS 7 CFC for SIMATIC S7 (V8.0) function manual.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

21

3 Creating and Adapting the PCS 7 Project

Figure 3-11: PCS 7 configuration

The default functions are automatically created when you are dragging the CMTs into the project.

Copyright

Siemens AG 2013 All rights reserved

22

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

3 Creating and Adapting the PCS 7 Project

3.3
Procedure

Deriving a CMT from Advanced Process Library (APL)


1. Open the "PCS 7 AP Library V80" library and drag the process tag type "ValveAnalog" into the "Process Tag Type" folder of the master data library.
Figure 3-12: Integrating the ValveAnalog process tag type

Siemens AG 2013 All rights reserved

2. Select the ValveAnalog process tag type, open the context menu and click Process Tag > Create/Change Process Tag Type...: The Create/Change Process Tag Type... dialog box opens. 3. Click on the Next button.
Figure 3-13: Adapting the "ValveAnalog" type

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

23

3 Creating and Adapting the PCS 7 Project

4. Delete all connecting points for parameters and signals.


Figure 3-14: Deleting the connecting points of the "ValveAnalog" process tag type

5. Click on the Finish button.


Siemens AG 2013 All rights reserved

6. Delete any external interconnections in the chart of the type. 7. Select the Process tag types folder in the master data library of your multiproject and open the context menu. 8. In the context menu, select Control Modules > Create control module type from process tag type.... A selection dialog box opens.
Figure 3-15: Converting process tag types into CMTs

Copyright

24

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

3 Creating and Adapting the PCS 7 Project

Figure 3-16: Selection dialog for converting process tag types into CMTs.

The CMT will now be created in the master data library. 9. Delete the "ValveAnalog" process tag type and assign the name "ValveAnalog" to the "ValveAnalog(1)" CMT.
Siemens AG 2013 All rights reserved

Figure 3-17: "ValveAnalog CMT

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

25

3 Creating and Adapting the PCS 7 Project

3.4
Procedure

Changes in the CMT and the technological connections


1. Open the "ValveAnalog" control module. 2. Open the Technological connections view in the CFC Editor. 3. Check the assignment of the control module type. A ValveAnalog chart must be assigned to the name of the ValveAnalog control module in the field of the Assignment column and the Name row (see Figure 3-18).
Figure 3-18: Assigning the control module name

Siemens AG 2013 All rights reserved

4. If this is not the case, right-click into the field of the Assignment column and the Name row. The "Plan ValveAnalog" button will open. Click on the button and you will have assigned a plan to the name.
Figure 3-19: Assigning the control module name

Copyright

NOTICE

If this assignment does not exist, the chart names of the instances will not be created correctly in the process of creation.

26

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

3 Creating and Adapting the PCS 7 Project

5. Select the "ValveAnalog" object and open the object by right clicking the context menu of the object. 6. Click on the Insert new object > Control module entry. A new object named Control unit is created. In the next step, instantiate the object with the FbkOpen input driver block.
Figure 3-20: Technological connections

Siemens AG 2013 All rights reserved

7. Select the Control module object. The attributes of the object are opened. 8. Drag the "FbkOpen" block into the field of the "assignment" column and the "assigned block" row via drag & drop. 9. Assign the name FbkOpen for this object.
Figure 3-21: Instantiating the "FbkOpen" object

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

27

3 Creating and Adapting the PCS 7 Project

10. Select the PV_In input of the FbkOpen block and drag it onto the FbkOpen object. A Signal type control tag is automatically created. 11. Adjust the name of the control tag.
Figure 3-22: Defining CMT connecting points

Siemens AG 2013 All rights reserved

Note

You can also create objects via drag & drop. For this purpose you have to select the respective block and drag it via drag & drop to the respective object.

Copyright

The object is created automatically.

28

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

3 Creating and Adapting the PCS 7 Project

12. Please perform these steps also for the following blocks.
Table 3-1: Blocks that must be instantiated Block FbkClose Output ValveAnalog PV_In (Signal) PV_Out (Signal) MV_Ext (Parameter) Input/Output

Note

If the Select Structure Element dialog opens up during the assignment of a parameter, you have the following options:
1. 2. Select a complete structure Select an individual structure member if you do not use the complete structure

Siemens AG 2013 All rights reserved

1.

2.

Copyright

Figure 3-23: Result: Objects of the "ValveAnalog" type

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

29

3 Creating and Adapting the PCS 7 Project

3.5

Configuring optional blocks of the "ValveAnalog" CMT


In AdvES you have the option to create different variants from one control module type (CMT). One or several function blocks have to be marked as optional. This makes it possible to create different variants of the type in AdvES.

Procedure 1. Enable the Optional attribute in the attributes of the FbkOpen and FbkClose blocks. Chapter 4.2.1 of the application example shows you how you can form different variants of the ValveLean type in this way.
Figure 3-24: "Optional" block attribute

Copyright

Siemens AG 2013 All rights reserved

Note

The optional blocks, for example, can be disabled in an instance of the type and can be enabled in another instance. The huge advantage is that you no longer require many different process tag types, for a valve for example. A universal control module type which contains and can reproduce all variants of a valve is sufficient.

30

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

3 Creating and Adapting the PCS 7 Project

3.6

Configuring messages
The block at which you wish to configure the messages must support the messaging function.

Requirements

Procedure 1. Open the Technological connections of the ValveAnalog control module type. 2. Right click on the ValveAnalog object. A context menu opens. 3. Click on Insert new object > Message.
Figure 3-25: Creating the message object

Siemens AG 2013 All rights reserved

Copyright

4. Select the ValveAnalog block and using drag & drop, move it into the field for assigning the message (Column: Assignment row: Assigned message) and select the SIG1 message identifier (possible message identifiers: SIG1 ...SIG8).
Figure 3-26: Configuring messages

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

31

3 Creating and Adapting the PCS 7 Project

Note

"MsgEvID2" messages cannot be configured in this way. For blocks containing more than one Alarm_8P, hence also an MsgEvID2, you need to proceed as follows:
1. 2. Switch the connections "MsgEvID1" and "MsgEvID2" visible. Select the MsgEvID2 connection and use drag & drop to move it onto the object of the appropriate block. A message with the assignment to the message-capable block is automatically generated. Select the desired message identifier.

3.

Copyright

Siemens AG 2013 All rights reserved

32

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Configuring with AdvES


Based on an example project, this chapter describes how to perform mass data engineering with AdvES V8.0.

4.1

Data import from PCS 7 to AdvES


This chapter describes how PCS 7 data is imported to AdvES. The procedure will be described in the following. The technological hierarchy, control modules and hardware already available in the project as well as the control module types available in the master data library can be transferred to AdvES through importing the PCS 7 data.
Figure 4-1: Project step in the overall workflow

Copyright

Siemens AG 2013 All rights reserved

Procedure 1. Select your sub-project and right click to open the context menu. 2. Click on "Open project in AdvancedES" to open AdvES.
Figure 4-2: Opening AdvES

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

33

4 Configuring with AdvES

Note

The "Open project in AdvancedES" item will only be shown with correct installation and can only be selected with a valid license. Standard templates will be transferred when an AdvES project is opened for the first time, the opening process will therefore take a little longer. The progress of copying will be displayed.

AdvES will open with an empty project, i.e. no data will be available in the three tabs of the navigation area, only the name of the project.
Figure 4-3: AdvES dialog

Copyright

Siemens AG 2013 All rights reserved

3. Click on "PCS 7 Import" in the workflow bar.


Figure 4-4: "PCS 7 Import" menu

34

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4. Select the "Import from PCS 7" tab. 5. Enable all selectable filter options. For the first import of PCS 7 data or after hardware changes (or changes to the control module types) it is mandatory to enable the filters for control module types and the hardware. 6. Click on the "Import" button to start importing.
Figure 4-5: Filter selection dialog for data import

Note

Siemens AG 2013 All rights reserved

After that, AdvES will automatically check for differences between the PCS 7 project and the AdvES project. The result of the comparison will be displayed in the "Data transfer - Generate/import" window. 7. Click on the button to start the import to AdvES.

Copyright

Figure 4-6: Comparison of AdvES and PCS 7 project

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

35

4 Configuring with AdvES

Note

The found.

button will only be enabled if differences between the two projects are

Note

Enable the "delete at target" function if you wish to delete obsolete data in the AdvES project. Only the changes will be imported. Example You have already imported control module types and a hardware configuration into the AdvES project. Then you delete a control module type in the master data library and change the name of the PROFIBUS master system in the hardware config. With the Delete at target function, the new name of the PROFIBUS master system will be adopted when importing, and the old control module type will be removed from the AdvES project. Without the delete at target function, an additional PROFIBUS master system is created and the data of the already existing PROFIBUS master system remains in COMOS.

Note

Siemens AG 2013 All rights reserved

8. After the import, you will be shown a log for the import process, acknowledge the dialog with OK.
Figure 4-7: Dialog box for the import process

Copyright

9. The Data transfer dialog box opens. Here you have the option of comparing the AdvES project with the PCS 7 project. 10. Click on the "Yes" button to start the data synchronization. After synchronization, check whether all data were correctly transferred to AdvES.

36

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Figure 4-8: Dialog box for starting data synchronization

Figure 4-9: Synchronized data (data identical in both projects)

Siemens AG 2013 All rights reserved

11. Click on the Close button to close the import dialog box. Subsequently, the data is adopted in AdvES and displayed in the automation view. You will see a generation log with errors, warnings and messages.
Figure 4-10: Generation log after data import

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

37

4 Configuring with AdvES

12. Click on the button to confirm the "PCS 7 Import" menu item. This enables the next menu item "Assign signals/parameters".
Figure 4-11: Confirming the "PCS 7 Import" step

Copyright

Siemens AG 2013 All rights reserved

38

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4.2

Assigning mapping labels for the technological I/Os of a CMT


Mapping labels are required because the names for signals and parameters in PCS 7 projects or the master data library may differ in the process tag or signal lists. In order for Advanced ES to be able to merge such different data, it is necessary to standardize this data. The terms from Namur 1.10 are used for standardization. You will find the list with the Namur labels available in AdvES V8.0 in chapter 7.5 of the "Process Control System PCS 7 Advanced Engineering System" configuration manual. You can also create individual mapping labels (see chapter 4.2.3).

Note

Siemens AG 2013 All rights reserved

The mapping labels for 2 areas are assigned on a separate basis in AdvES. On one hand for the data from PCS 7 and on the other hand for the external data from the Excel lists. The identifiers are a link between PCS 7 and AdvES as well as between AdvES and Excel tables. They enable the file import and fulfill the function of maintaining the structure during import, i.e. the assignment of signals and parameters to the CMTs.
Figure 4-12: Project step in the overall workflow

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

39

4 Configuring with AdvES

Example Looking for example at the ValveAnalog CMT from the example project. The CMT has an input signal for the feedback open and closed and an analog output signal for the current position of the valve (see Figure 4-13). The signal name is made up of the block name and the input name in the control module type.
Figure 4-13: Technological connections of the "ValveAnalog" CMT

Siemens AG 2013 All rights reserved

Copyright

The same information for the signals of a valve is also included in the signal list of the example project (see Figure 4-14).
Figure 4-14: Excerpt of a signal list

In AdvES, the labels "FBO", "FBC", and "OUTOC" are assigned as mapping labels for the signals from the control module type and from the Excel list. This way AdvES can link the information from the "ValveAnalog" CMT with the information from the Excel list (see Figure 4-15).

40

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Figure 4-15: Linking information from PCS 7 and AdvES

You will find a detailed description of how to assign the mapping labels in chapters 4.2.1, 4.2.3 and 4.3.1.
Siemens AG 2013 All rights reserved

Note

The mapping labels only have to be assigned once. If the same master data library is used in a different AdvES project, which means the mapping labels have already been assigned, the mapping labels can be imported from that project (see chapter 4.2.3).

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

41

4 Configuring with AdvES

4.2.1

Assigning the mapping labels

Introduction In this section you will learn how to assign mapping labels to the technological connections (signals and parameters) of the CMTs imported into AdvES (see Figure 4-16).
Figure 4-16: Assigning signals and parameters

Siemens AG 2013 All rights reserved

Procedure 1. Click on the "Assign signals/parameters" button in the workflow bar.


Figure 4-17: "Assign signals and parameters" menu

Copyright

In the AdvES work area all CMTs in the project are displayed with the corresponding status for assignment. In this example the "AMON_Std", "CTRL_Std", "MOT_1sp_2fb_1cm", "MOT_2sp", and "ValveAnalog" CMTs are displayed. Possible statuses:
Red no mapping label assigned yet Yellow mapping labels incomplete Green mapping labels complete

Note

42

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Figure 4-18: Dialog box for assigning mapping labels

Siemens AG 2013 All rights reserved

2. Click a CMT, e.g. AMON_Std. You will receive a list of all technological connections (signals and parameters) of the type. Here you can assign the mapping labels. 3. Click the icon in the Mapping label" column. A dropdown selection menu is opened with a list of the mapping labels for parameters or signals stored in AdvES. 4. As shown in the following diagram, assign the mapping labels to the signals of the "AMON_Std" type.
Figure 4-19: Mapping labels of the "AMON_Std" CMT

Copyright

Note

After you assigned a label, the status of the type will change to "yellow". After you assigned the mapping labels for all signals, the status will change to "green".

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

43

4 Configuring with AdvES

5. Now assign the mapping labels for the remaining CMTs.


Figure 4-20: Mapping labels of the "CTRL_Std" CMT

Siemens AG 2013 All rights reserved

Figure 4-21: Mapping labels of the "MOT_1sp_2fb_1cm" CMT

Copyright

Note

If you assign a mapping label to a connection for the first time, it will be applied to all equal connections in the CMTs. These connections will then be marked blue, as shown in Figure 4-22. If you change existing mapping labels you can choose whether the mapping label will also be changed for the connections with the same name of all CMTS. Alternatively, you can define exceptions via the "Only for this connector" button. These will then be marked red.

44

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Figure 4-22: Mapping labels of the "MOT_2sp" CMT

Siemens AG 2013 All rights reserved

6. In the next step, as shown in the following diagram, assign the mapping labels to the signals of the "ValveAnalog" type.
Figure 4-23: Mapping labels for the "ValveAnalog" CMT

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

45

4 Configuring with AdvES

4.2.2
Procedure

Creating variants and copy templates in AdvES

1. Open the Variants tab. If the status of all CMTs is green than the Variants tab is enabled. 2. Click the "ValveAnalog" entry. 3. Click on "Click here to add a new variant".
Figure 4-24: Creating variants of the "ValveAnalog" type

Note

Siemens AG 2013 All rights reserved

4. Enter the name "Valve_FBC". 5. Disable the option for the "FbkOpen" block. 6. Create another variant for the "ValveAnalog" CMT:
Table 4-1: Variants of the type "ValveAnalog" Variant 2 Name Valve_no_FB FbkOpen disable FbkClose disable

Copyright

Figure 4-25: Variants of the type "ValveAnalog"

46

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Note

The blocks "FbkOpen" and "FbkClose" are included in the "ValveAnalog" basic type.

Variants of the basic type


Valve_FBC Valve_no_FB

Siemens AG 2013 All rights reserved

This way you created, as described in chapter 3.5, two variants from one "ValveAnalog" CMT. 7. After you assigned all signals and parameters of the types, click the "Generate" button in order to create the copy templates of the CMTs. Loss of the assignments When generating the copy templates, the selection of the mapping labels is not saved in this dialog. To save, click the OK button or Apply.
Figure 4-26: Generating copy templates

Copyright

NOTICE

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

47

4 Configuring with AdvES

Figure 4-27: Copy templates of the example project

Siemens AG 2013 All rights reserved

You need the copy templates in order to specify the process tags later on (see chapter 4.4).

Result
Figure 4-28: Assignments for data from PCS 7

Copyright

48

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4.2.3

Creating individual mapping labels


With AdvES V8.0 SP1 it is possible to create individual mapping labels. This section is for information purposes and is not relevant for the example project.

Note

Procedure 1. Click the button in the header bar next to the Menu. A drop-down menu will open. 2. Click the Manage mapping labels menu entry.
Figure 4-29: Creating mapping labels

Copyright

Siemens AG 2013 All rights reserved

The Manage mapping labels dialog box opens. The editing mask is divided into three areas: parameter, signal and signal parameters. If you would like to, for example, create a new mapping label for a parameter, you have to proceed as follows:
Figure 4-30: Manage mapping labels dialog

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

49

4 Configuring with AdvES

3. Click the Parameter tab. 4. Click the Add new element button . A new empty row is recreated. It is stored under the User defined status.
Figure 4-31: Creating mapping labels for parameters

Siemens AG 2013 All rights reserved

5. Here, you assign the new name and the description of the new mapping labels. 6. The mapping labels have to be switched visible, so that they can be used as mapping labels. 7. Subsequently, click the "Apply" button. 8. Click the Manage mapping labels dialog box. Only once the Manage mapping labels dialog has been closed, are newly created mapping labels read out and can be used for assignments.
Figure 4-32: Creating mapping labels for parameters

Copyright

Note

50

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

9. If you have created a mapping label, assigned it and created the copy template, the mapping label status in User-defined mapping label will change. You can therefore no longer delete the mapping labels via the button.

Figure 4-33: Assigning mapping labels

Siemens AG 2013 All rights reserved

Figure 4-34: Created mapping label for a parameter

Copyright

10. If you are replacing the mapping label you have created by another one and you are creating the copy template again, your mapping label created by you is no longer used and this is displayed under the user defined status. You can therefore delete the mapping label again.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

51

4 Configuring with AdvES

Figure 4-35: Assigned mapping label is not assigned to a parameter

Siemens AG 2013 All rights reserved

Note

When you enable the Show predefined labels option box, all default mapping labels are displayed. You cannot edit or delete them. They can only be switched visible or invisible. This has the advantage that only all relevant default mapping labels are visible and that they are displayed in the dropdown selection menu.

Copyright

52

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4.2.4

Transferring mapping labels


In a multi-project there is only one master data library which is used in all subprojects and therefore also in all AdvES projects. If the mapping labels have already been assigned in an AdvES project, the assignment will not have to be repeated. In this case the mapping labels can be transferred from the existing AdvES project to the new AdvES project. This section is for information purposes and is not relevant for the example project.

Note

Procedure 1. Click the button in the header bar next to the Menu. A drop-down menu will open. 2. Click the Transfer mapping labels menu entry. In the working area, an overview of all AdvES projects is opened.
Siemens AG 2013 All rights reserved

Figure 4-36: Transferring mapping labels

Copyright

3. Select the project from which you wish to transfer the mapping labels. 4. Subsequently, click the transfer "Apply mapping labels" button. The mapping labels are applied in your current project.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

53

4 Configuring with AdvES

Figure 4-37: Project selection for importing mapping labels

Siemens AG 2013 All rights reserved

Note
NOTICE

Subsequently check the mapping labels and, if required, correct them. Variants will not be transferred here. New variants must be generated for the project.

Copyright

5. After assigning all mappings, generate the CMTS copy templates, as described in chapter 4.2.2.

54

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4.3

Data import of external data


In order to import data from an Excel signal list into AdvEs, you need to define a configurator. There you determine which data from the Excel list shall be imported to AdvES and what kind of information it is. This way, using AdvES, you can read in technological hierarchy levels, control modules, signals, parameters, and hardware information from an external system. The required data from external systems must be supplied in Excel-readable format, since AdvES uses the data in the form of Excel lists.
Figure 4-38: Project step in the overall workflow

Copyright

Siemens AG 2013 All rights reserved

Requirements for importing Excel lists must meet the following requirement to ensure the correct transfer of information from Excel and generation of data in AdvES: Each column must be clearly defined (identical information in one column). The sequence of entry of the columns with the respective information into the Excel list is not specified. A configurator selects the columns and assigns them correctly (see chapter 4.3.1 "Creating the configurator for importing").

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

55

4 Configuring with AdvES

Types of Excel lists AdvES can process two types of Excel lists: Process tag list The process tag list includes all process tags with name and associated detailed information. Signal list (used in this application example) The signal list includes all signals with name and associated detailed information. In the table below the list types are clearly illustrated. In this table it is shown what information has to be included in the lists in order to generate the respective data. The following table shows which information must or can be available in a process tag or signal list (Excel list).
1. 2. 3. The column "mapping target" and "mapping class" indicates the assignment you have to select in the configurator for the respective information. The "must/can" column shows which information is optional or mandatory for the respective list type. The column "when" shows the list types. It specifies which information must be available to achieve the corresponding target, e.g. importing data for generating signals and hardware. The following applies to the technological hierarchy levels: Whether and how the technological hierarchy is used here depends on the level on which the signal data or process tag data is imported to AdvEs. The TH must be gapless from the used import level on.

Note

Siemens AG 2013 All rights reserved

4.

Copyright

56

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Figure 4-39: Required/possible external data from the Excel list

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

57

4 Configuring with AdvES

4.3.1

Creating the configurator for importing


In this chapter you will learn how to create a configurator in AdvES in order to be able to import data from Excel lists.

Procedure 1. Click on the "Import signal/process tag list" button in the workflow bar.
Figure 4-40: "Import signal/process tag list" menu

The "PCS 7 Import/Export" dialog box will open, with the "Import" tab open. 2. Click on the "Configuration" tab to create a new configurator.
Siemens AG 2013 All rights reserved

3. Click on the "New..." button to create a new configuration object. 4. Assign a suitable name.
Figure 4-41: Creating a new Excel configurator

Copyright

58

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

5. Then select the Excel list for the example project and click on the Load button.
Figure 4-42: Loading the Excel list

Note
Siemens AG 2013 All rights reserved

The selected Excel file will be opened. It is a signal list with hardware information.

Figure 4-43: Configuration dialog box

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

59

4 Configuring with AdvES

6. Check the Excel list for relevant information Note Take the list from Figure 4-39 and compare which information is available in the signal list. Please note the following:
Which data is relevant and to be imported? Which import type can be used and is the required information available?

In this example, we are looking at a signal list with hardware information, i.e. you can generate the control modules (CMs) with the TH, the corresponding signal interconnections, and the corresponding hardware (DP slaves) from this list. 7. Select the Excel worksheet ("signal_list_example") and the Excel start row from which the configurator will read out the data later on. 8. Select line "2" as the Excel start row. 9. Using drag & drop, move the hierarchy folder of level 1 to the "Import target" field.
Siemens AG 2013 All rights reserved

Figure 4-44: Setting the configurator

Copyright

10. Define the significance of the columns in the signal list in AdvES. There are two variants according to which you can approach: 1st variant You can transfer all Excel columns to the configurator, via the "transfer all Excel columns" function. Since the list includes a lot of information which is not required, the second variant is recommended. 2nd variant You can add the Excel columns individually to the configurator via Add column definition and via drag & drop from the Excel list to the configurator. This step is required for AdvES to be able to read in the data and to correctly assign it.

60

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Example:
Table 4-2: Assigning columns Column AJ M B Unit CMT Function Controller Name Significance in AdvES project TH1 Process tag function Name of station (AS)

11. Select a cell in the "AJ" column and place the cursor on the frame of the cell until the cursor changes its icon. This will work on one of the side edges of the cell, but not on the corners. 12. With the mouse button pressed down drag the cell to AdvES. A column object is generated. 13. Enter line 1 as header row. For all other column objects, the name entered in row one is used.
Figure 4-45: Generating a column object

Note

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

61

4 Configuring with AdvES

Table 4-3: Establishing a column object

Row Column Caption Mapping class

Content Includes the letter of the Excel column Includes the cell value of the "Excel start row" that you defined in the configuration Defining a category of mapping labels. Mapping labels can be: Technological hierarchy Process tag Control module attribute Control module parameter Signal Signal attribute Signal parameter

Siemens AG 2013 All rights reserved

Data

Includes the first three values of the Excel column from the defined "Excel start row"

After you inserted the column into the configuration and thus communicated it to AdvES, you now have to map it, so that AdvES can detect which information is read and can process it correctly. 14. Assign the mapping class for TH, use Figure 4-39 for this purpose. 15. Click the arrow field of the mapping class in the column definition. 16. A menu with the selectable definitions will open. 17. Select the entry "Technological hierarchy".
Figure 4-46: Assigning the mapping class

Copyright

62

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

18. After assigning the mapping class you now need to assign the associated mapping target (see Figure 4-39). Depending on the selection of the assignment class, other assignments are offered in the dropdown menu. Select TH level 2.
Figure 4-47: Assigning the mapping target

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

63

4 Configuring with AdvES

19. Repeat this procedure also for the following required columns.
Table 4-4: Configuring the column objects Column L Name Control Module Name Mapping class Process tag Mapping target 02 (Control module AdvES) (splitting... see paragraph below "Splitting and assigning information from Excel lists") Function of the control module PCS 7 control module name (splitting... see paragraph below "Splitting and assigning information from Excel lists") Station name Variable mapping (see paragraph below "Assigning the mapping labels for signal names of the Excel list") (splitting... see paragraph below "Splitting and assigning information from Excel lists") Address DP slave order number HW signal type Channel PCS 7 signal name Signal module number Station name Slot Subnet

M L

CMT Function Control Module Name

Process tag attribute Process tag attribute

B K

Controller Signal Name

Process tag attribute Signal

Siemens AG 2013 All rights reserved

D H I F K Y B E C

Station Address DP-IM MLFB I/O Type Channel Signal Name I/O Module MLFB Controller Slot Bus

Signal attribute Signal attribute Signal attribute Signal attribute Signal attribute Signal attribute Signal attribute Signal attribute Signal attribute

Copyright

64

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Splitting and assigning information from Excel lists AdvES provides the option of splitting information in Excel columns. Using the "splitting" button you can split the content of a cell and assign different mapping classes and mapping targets to the contents. This example shows you how to separate and assign the information for the mapping class "process tag" in column "J". Procedure 1. Click on the column definition for mapping class "process tag". 2. In the properties view of the column click on the "Splitting" button.
Figure 4-48: Splitting a column object

Copyright

Siemens AG 2013 All rights reserved

3. Then click the button. The "Splitting" dialog box will open. There you can define the criteria for splitting. 4. Use the following options for splitting: Split character From the back: with a space character

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

65

4 Configuring with AdvES

Figure 4-49: Defining the splitting criterion

Siemens AG 2013 All rights reserved

5. After splitting, a second box will open which is referenced to the same column.
Figure 4-50: Splitting the "L" column

Copyright

66

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

6. Hide the left splitting of column L. Click the Hide button (see Figure 4-50). 7. Assign "process tag" as the mapping class and "02 (control module AdvES)" as the mapping target.
Figure 4-51: Assigning the mapping target for column "L"

Copyright

Siemens AG 2013 All rights reserved

8. Also split information for further mapping classes as follows:


Table 4-5: Splitting criteria for column objects of the example project Column L Splitting options Split character From the back: With one (blank) (right part of the splitting is relevant) Split character From the front: With underscore ( _ ) (right part of the splitting is relevant)

Note

Splittings can also be disabled via the "Hide" button. The hidden content will not be used and will not be imported to AdvES.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

67

4 Configuring with AdvES

Assigning the mapping labels for signal names of the Excel list (Variable mapping) When assigning the mapping labels for signals you perform a variable assignment. For the signals found in the Excel list, the corresponding NAMUR labels will be assigned.

Procedure 1. Assign the appropriate NAMUR ID in the column definition of the Signal mapping class (column I). Click on the button in order to transfer the signal names to the assignment field. Execute this step for all names.
Figure 4-52: Assigning the corresponding NAMUR IDs for the signal names

Copyright

Siemens AG 2013 All rights reserved

68

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

2. The mappings for the "Technological connections" of the CMTs were assigned in chapter 4.2.1. Assign the mapping labels of the associated "Technological connections" to the corresponding signal names of the Excel signal list. This creates a link (as described in chapter 4.2) between PCS 7, AdvES, and the Excel list.
Figure 4-53: Assigning the corresponding mapping labels

Siemens AG 2013 All rights reserved

This ensures that the structure of the data during the import from Excel is maintained, i.e. the assignment of signals and parameters to the CMTs. For a later export of the data from AdvES to PCS 7, for example, the signal input of the respective CM instance is assigned to the appropriate signal.
Figure 4-54: Mapping labels for SIMATIC PCS 7 and Excel

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

69

4 Configuring with AdvES

Result
Figure 4-55: Configurator part 1

Figure 4-56: Configurator part 2

Table 4-6: Mappings


Siemens AG 2013 All rights reserved

Column AJ L

Name Unit Control Module Name

Mapping class Technological hierarchy Process tag

Mapping target 02 (hierarchy file level 2) 02 (control module AdvES) (splitting... see paragraph above "Splitting and assigning information from Excel lists")

M L

CMT Function Control Module Name

Process tag attribute Process tag attribute

Function of the control module PCS 7 control module name (splitting... see paragraph above "Splitting and assigning information from Excel lists")

Copyright

B K

Controller Signal Name

Process tag attribute Signal

Station name Variable mapping (see paragraph above "Assigning the mapping labels for signal names of the Excel list") (splitting... see paragraph above "Splitting and assigning information from Excel lists") Address DP slave order number HW signal type Channel PCS 7 signal name Signal module number Station name Slot Subnet

D H I F K Y B E C

Station Address DP-IM MLFB I/O Type Channel Signal Name I/O Module MLFB Controller Slot Bus

Signal attribute Signal attribute Signal attribute Signal attribute Signal attribute Signal attribute Signal attribute Signal attribute Signal attribute

70

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4.3.2

Importing Data
Prerequisite for importing data from a signal or process tag list is a corresponding list with a matching configurator.

Procedure 1. After creating the configurator, open the import dialog box. 2. Fill in the fields according to the table below: Import type: Configuration: Edit: Create:
Siemens AG 2013 All rights reserved

Note

Here you select whether the list to be imported is a process tag or a signal list. Here you select an existing configurator. Here you change an existing configurator (e.g. after you changed the Excel list). Here you create a new configurator. Here you select the Excel file from which to import the data. When the checkbox is disabled the data to be imported is instantly integrated into the AdvES project. If the checkbox is enabled, the data to be imported is not instantly transferred to the AdvES project but is first of all saved in a working layer. This is to prevent faulty imports from being immediately transferred into the AdvES project and destroying it.

Excel file: Importing new working layer

Copyright

Import target:

Here you define the import target from the "Project" tab via drag & drop.

3. Enable the Import new working layer checkbox with a mouse click. 4. Then click on the "Import" button to import the signal list data to AdvES.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

71

4 Configuring with AdvES

Figure 4-57: Import dialog box for importing from the Excel list

During import a continuous protocol will be output. It includes information on the progress of the import and potential errors. Each empty cell in a column to be read out causes a warning message. In this example, a warning message will appear that there is no content in the cells of the columns for Subnet, DP slave order number and Signal module order number. This was done deliberately in this example, to show you how to add this data in AdvES (see chapter 4.6).

Note
Siemens AG 2013 All rights reserved

Figure 4-58: Import dialog box

Copyright

5. When the import in AdvES is completed, click "OK".

72

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Note

By enabling the Import new working layer checkbox, AdvES will work with the working layer when importing external data. Imported data will not be transferred into the AdvES project immediately, but will be stored in a working layer first. This is to prevent faulty imports from being immediately transferred into the project and destroying it.

6. Subsequently, a dialog will open, confirm it with Yes.


Figure 4-59: Info box

Siemens AG 2013 All rights reserved

The data imported to AdvES is made available in a working layer. Before you proceed you can determine whether to use or discard the imported data (in case of a faulty import). The "project" tab in the navigation area shows the status of the objects after import as follows:
Figure 4-60: Imported data from the Excel list

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

73

4 Configuring with AdvES

Figure 4-61: Color coding

As soon as the import is confirmed, the control buttons in the header bar are blocked and the buttons for releasing or discarding the import are enabled.
Siemens AG 2013 All rights reserved

Note

The release, accepts the changes fully in the project. Discarding deletes the changes from the signal or process tag lists last imported. An import can only be performed after the previous import has been released or discarded. 7. Release the import if it was performed correctly.

Copyright

Note

Clicking on the "Release import" button will fully transfer the imported data from the working layer into the AdvES project and it can be further processed. With the Discard import button, the imported data in the working layer is deleted and is not accepted in the AdvES project.

Figure 4-62: Menu: "Release import" and "Discard import"

74

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4.4

Specifying control modules


Specifying the process tags determines what CM will be connected with which CMT (from the PCS 7 master data library) in AdvES. The process tag defined in the configurator (from the Excel list) is used for this purpose (see chapter 4.3).
Figure 4-63: Project step in the overall workflow

Siemens AG 2013 All rights reserved

Procedure 1. Click on the "Specify control modules" button in the AdvES header bar.
Figure 4-64: "Specifying control modules" menu

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

75

4 Configuring with AdvES

2. Using drag & drop, move the project node into the "Start object" field. All control modules under the object node will be displayed.
Figure 4-65: Dialog box for specifying the control modules

Copyright

Siemens AG 2013 All rights reserved

3. Open the "Copy templates" tab in the navigation area. This is where you find the copy template of the imported CMTs from the master data library. Prerequisite is that you have correctly executed the steps described in chapter 4.2. 4. Perform the assignment for each function type once. Drag the respective copy template via drag & drop to the respective function type.
Table 4-7: Specifying Control Modules No. 1 2 3 4 5 6 7 Function of the control module M IC V V_C V_OC I MSF CTRL_Std Valve_no_FB Valve_FBC ValveAnalog AMON_Std MOT_2sp Copy template MOT_1sp_2fb_1cm

76

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Figure 4-66: Assigning the copy templates to the corresponding CMs

Siemens AG 2013 All rights reserved

Note

Copyright

Open the "Copy templates" tab in the navigation area. From there you can assign a copy template to each CM using drag & drop. This procedure is more efficient and is used in this example.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

77

4 Configuring with AdvES

After you performed the mapping for each function type once, you assign the missing mappings automatically via the button on the right. This initiates the assignment of the CMTs to the remaining CMs according to their function.
Figure 4-67: Automatic assignment of the CMs

Copyright

Siemens AG 2013 All rights reserved

5. Enable the mappings via the down menu will open.

icon in the

button on the right. A drop-

6. Click on "Execute (all)" in the drop-down menu. The assignments will be executed and their status checked.
Figure 4-68: "Execute (all)" menu

78

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

7. As soon as the status of all mappings is green you can close the dialog box.
Figure 4-69: Specifying of all CMs completed

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

79

4 Configuring with AdvES

4.5

Configuring connections
You can configure cross-chart interconnections in AdvES (connections between control modules). In this example the CMs of the CTRL_Std controller type are to be interconnected with the appropriate analog valves. Two work steps are required in AdvEs to configure interconnections: 1. You determine which signals of the control module types are to be always interconnected (chapter 4.5.1). 2. You determine for which control module instances this option of interconnection shall be used (chapter 4.5.2).

4.5.1
Procedure

Determine connections at the CMTs

1. Click on the "Connect types" button in the AdvES workflow bar.


Siemens AG 2013 All rights reserved

Figure 4-70: "Connect types" menu

Copyright

The "Connect types" dialog box will open. Define the predecessor and successor control module. In this example, we want the "CTRL_Std" type to control the types "ValveAnalog", "ValveFBC", and "Valve_no_FB", which means the "CTRL_Std" type is the predecessor control module and the "ValveAnalog" type and its variants is the successor control module. 2. Drag the CTRL_Std copy template via drag & drop into the field for the predecessor control module and the ValveAnalog copy template into the field for the successor control module. All signals of the selected control module types are displayed. 3. Using drag & drop, connect the "MV" output of the predecessor control module ("CTRL_Std") with the "MV_Ext" input of the successor control module ("ValveAnalog", "Valve_FBC, and "Valve_no_FB").

80

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Figure 4-71: Defining the predecessor and successor CMT

Siemens AG 2013 All rights reserved

Figure 4-72: Determining connections between the CMTs

Copyright

4. Click on the "Apply" button and then "OK" to close the dialog box. You can only interconnect input signals that are not connected to hardware channels and that are not listed in the icon table.

Note

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

81

4 Configuring with AdvES

4.5.2
Procedure

Execute interconnections for the CM instances

1. Click on the "Connect instances" button in the workflow bar.


Figure 4-73: "Connect instance" menu

2. Drag the project node into the "Start object" field. 3. Drag the respective IC-CM into the Interconnected predecessor cell of the appropriate V-CM from the Acid Sel and Gas Rel hierarchy folder in the navigations area (via drag & drop).
Siemens AG 2013 All rights reserved

This is how you specify which CMs are to adopt the defined interconnections (see chapter 4.5.1).
Figure 4-74: Definition of connections for the individual IC CMs to the V-CMs

Copyright

82

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4. After you assigned the associated CTRL CMs to each of the Valve CMs, click on the > "Execute (all)" button.
Figure 4-75: "Execute (all)" menu

5. When the status of all connected V CMs is green, click on the "close" button.
Figure 4-76: Connection definitions

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

83

4 Configuring with AdvES

4.6

Assigning hardware
Apart from the import of the hardware information from the external signal list, you can also process the hardware assignment in AdvES manually. Since there is no information regarding the respective order numbers for the DP slaves and the I/O modules in the signal list of the example project, you have to assign them manually in AdvES. Furthermore, you have to change the data for the subnet.

Procedure 1. Click on the "Assign hardware" button in the AdvES workflow bar.
Figure 4-77: "Assign hardware" menu

The dialog box for the hardware assignment will open in the work space.
Siemens AG 2013 All rights reserved

2. Specify your project as start object. All signals available under the object nodes will be displayed. The hardware catalog is located on the right side of the dialog box. From this catalog, you can specify the respective DP slave type and the I/O module type. 3. Using drag & drop, insert a DP slave type and a module type from the hardware catalog for each HW signal type, Execute it in accordance with Table 4-8. The DP slave type and the I/O module type needs to be assigned to a hardware signal type once only.
Figure 4-78: Single assignment of the I/O module type and DP slave type

Copyright

84

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Note

With the filter functions in the column heads, you can make the assignments faster and more efficiently. You can, for example, filter for hardware signals which you would like to assign to the hardware and do not have to look in the list fist.

Table 4-8: Hardware assignments


Siemens AG 2013 All rights reserved

HW signal type AI 2x0/4-20mA HART AI 4xRTD AO 2x0/4-20mA HART DI 16x24VDC DI 4xNAMUR DO 8xRelais

DP slave type IM 153-2 HF 6ES7 153-2BA02-0XB0 IM 153-2 HF 6ES7 153-2BA02-0XB0 IM 153-2 HF 6ES7 153-2BA02-0XB0 IM 153-2 HF 6ES7 153-2BA02-0XB0 IM 153-2 HF 6ES7 153-2BA02-0XB0 IM 153-2 HF 6ES7 153-2BA02-0XB0

I/O module type 2AE, 0/4-20mA HART, EX 6ES7 331-7TB00-0AB0 8AE thermo, 4AE PT100, EX 6ES7 331-7SF00-0AB0 2AE, 0/4-20mA HART, EX 6ES7 332-5TB00-0AB0 16DE, DC 24V 6ES7 321-1BH01-0AA0 4DE, DC 24V, EX 6ES7 321-7RD00-0AB0 8DA, Relais, DC 24V, AC 120/230V, 5A 6ES7 322-5HF00-0AB0

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

85

4 Configuring with AdvES

. Here you can check 4. Subsequently, click the "Open selection list" button whether your assignments to the respective hardware signal types have been correctly recorded by AdvES.
Figure 4-79: Overview of the assignments

Siemens AG 2013 All rights reserved

Note

There will be no verification between HW signal type and I/O module type. The hardware is assigned individually for each signal. Make sure that the signals to be connected with the same module are connected with the same module type. 5. You can automatically assign the hardware (HW) to the remaining signals of the same hardware signal type. To do this, click the Map HW (all) button.
Figure 4-80: Assigning hardware automatically

Copyright

86

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

6. Subsequently click the Refresh button so that you can see if the hardware data was correctly assigned. 7. Click "Apply" and then "OK".
Figure 4-81: Automatically assigned hardware

Siemens AG 2013 All rights reserved

8. Open the AdvES menu in the header bar and click on the "Table view signal list PLC" entry.
Figure 4-82: Opening the "Table view signal list PLC"

Copyright

You have assigned a name for the PROFIBUS master system in your PCS 7 project. Since this information is not available in the example signal list and therefore not in AdvES, you need to enter it into the PLC view manually.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

87

4 Configuring with AdvES

9. Drag your project node into the "Start object" field. The signals existing under the start object in the AdvES project are displayed as a table with the properties belonging to the signals: Signal name Signal description Station name Signal parameter Hardware assignment Bus addresses Module slot Channel assignment Existing signals can be checked and changed here.
Figure 4-83: Structure of the table

Siemens AG 2013 All rights reserved

10. Filter for "AS1" in the "station name" column.


Figure 4-84: Filtering data

Copyright

11. Select the first cell in the "Subnet" column and press "Ctrl" and "A" at the same time. All cells in the column will be selected. 12. Right click on the selection. A context menu opens. 13. Click the "Edit" entry. An entry field opens.

88

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Figure 4-85: Editing columns

14. Enter the name of your PROFIBUS master system into the input field.
Figure 4-86: Assigning the name for the subnet

Siemens AG 2013 All rights reserved

15. Subsequently click "Apply" and then the "OK" button.

Copyright

NOTICE

If you click the OK button, the following dialogs will appear. Click the No and Cancel button otherwise you will change the AdvES database.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

89

4 Configuring with AdvES

Figure 4-87: Excerpt of the table view

Siemens AG 2013 All rights reserved

You finished assigning the hardware of the example project.

Copyright

90

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4.7

Consistency check
Automatic consistency checks are performed during data transfers. In case of errors the transmission will be canceled. Advanced ES also provides the option of manually initiating a consistency check at any time. You can check the following objects: Technological hierarchy Process tags Signals Parameters

Procedure 1. Open the AdvES menu. 2. Click on "Check data consistency".


Siemens AG 2013 All rights reserved

Figure 4-88: AdvES menu

Copyright

The window for the consistency check will open in the work space. 3. Drag your project node into the "Start object" field via drag & drop. The consistency check is initiated. After the check, you will be shown a log with the respective status of the objects in the work area.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

91

4 Configuring with AdvES

Figure 4-89: Dialog box for checking data consistency

Figure 4-90: Consistency check log

Copyright

Siemens AG 2013 All rights reserved

Note

Every non-connected parameter / signal creates an inconsistency warning. In this example such warnings are also created, since not all parameters and signals are connected.

92

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Note
Status 1 State complete Description AdvES object is consistent and complete. Data can be transferred to PCS 7. A warning may indicate an error or a deliberate deviation from the standard, created by the user. An error occurred, preventing the generation to PCS 7.

Inconsistency warning

Inconsistency error

In case of errors or warnings you can double-click on the corresponding row to go to the object concerned 4. If no errors occurred during the consistency check, you can export the data.
Siemens AG 2013 All rights reserved Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

93

4 Configuring with AdvES

4.8

Exporting data to PCS 7


The entire project data available in the AdvES project (technological hierarchy, control modules, signals, parameters, hardware) can be exported to PCS 7. In the PCS 7 project, the control modules will be created as CFC in the hierarchy, the I/O modules will be created including channel assignment, and the symbol table will be filled.
Figure 4-91: Project step in the overall workflow

Copyright

Siemens AG 2013 All rights reserved

Procedure 1. Click on the "PCS 7 export" button in the workflow bar to execute the export.
Figure 4-92: "PCS 7 Export" menu

In the work area the PCS 7 Import/Export tab is opened. In the opened dialog the Import from PCS 7 tab is preselected. 2. Click on the "Export to PCS 7" tab. 3. Enable the export option selections for technological hierarchy, control modules, and hardware in the export dialog.

94

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Figure 4-93: Dialog box for data export to PCS 7

Siemens AG 2013 All rights reserved

4. Click on the Export button. The data to be exported is generated. A protocol is generated and displayed during the process.
Figure 4-94: Protocol

Copyright

Note

During this process, warnings will be generated since not all the signals of the example are connected.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

95

4 Configuring with AdvES

Note

If an error occurs during generation, you cannot proceed with the next steps. The errors must be corrected before any further processing. Perform a consistency check to analyze the errors in more detail (see chapter 4.7). Warnings will not block the export.

5. If the data was generated without errors, the Data transfer - Generate/import window opens and a comparison between the AdvES project data and the PCS 7 project data is automatically triggered. The differences between the PCS 7 project and the AdvES project are marked in color.
Figure 4-95: Comparison dialog

Copyright

Siemens AG 2013 All rights reserved

6. Click on the button to trigger the object export. This transfers the technological hierarchy and the hardware. The dialog box for the data comparison opens. 7. Click on the OK button.

96

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Figure 4-96: Status dialog box

8. Click on the Yes button to update the project data once more.
Figure 4-97: Dialog box for updating the projects (AdvES - PCS 7)

Siemens AG 2013 All rights reserved

9. Click on the

button to transfer the control modules to the PCS 7 project.

Figure 4-98: Comparison dialog

Copyright

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

97

4 Configuring with AdvES

10. The dialog box for data comparison will open again. 11. Click on the "Yes" button to compare and update the project data once more.
Figure 4-99: Dialog box for updating the projects (AdvES - PCS 7)

Figure 4-100: Comparison dialog

Copyright

Siemens AG 2013 All rights reserved

12. Close the window. The data selected for transfer (TH, CFC, hardware, messages and interconnections) is now available in the PCS 7 project.

98

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Data generated in SIMATIC PCS 7


Figure 4-101: Technological hierarchy with the control modules

Siemens AG 2013 All rights reserved

Copyright

Figure 4-102: Control module K-101A-V with hardware interconnection

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

99

4 Configuring with AdvES

Figure 4-103: Hardware configuration

Siemens AG 2013 All rights reserved

(defined in chapter 4.6)


Figure 4-104: Symbol table

Copyright

100

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

Interconnections generated from the AdvES data between the B-101-IC control module and the B-101-V control module.
Figure 4-105: Interconnection between control modules B-101-IC and B-101-V

Siemens AG 2013 All rights reserved

Figure 4-106: Interconnection between control modules B-101-IC and B-101-V

Copyright

(defined in chapter 4.5)

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

101

4 Configuring with AdvES

Figure 4-107: Variant of a control module with the FbkClose block

(defined in chapter 3.5 and 4.2.2)

Copyright

Siemens AG 2013 All rights reserved

102

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4.9
4.9.1

Other useful functions in AdvES


Report folder
Report folders can only be created in hierarchy folders. In those, you can use different pre-defined report design templates. The labeling of objects is not included in the report since these texts often do not fit into the templates due to their length. In each report, the respective objects are displayed, depending on the installation location. This means the report also includes all subordinate data. If a report folder is, for example, located in TH 2, all contents of TH 2, TH 3 and the following hierarchy folders are evaluated in the report but not the contents of TH 1.

Note

Procedure 1. Open the context menu of a TH folder by right clicking in the project view.
Siemens AG 2013 All rights reserved

2. Navigate to: New > RP Report folder and click RP Report folder.
Figure 4-108: Creating report folder

Copyright

A new report folder is created.

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

103

4 Configuring with AdvES

3. By right clicking the report folder, you can create the respective report design template there.
Figure 4-109: Creating the report design templates

Copyright

Siemens AG 2013 All rights reserved

104

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4.9.2

Control module (CM) test sheets


In AdvES from version 8.0 SP1 onward, you have the option to create an CM test sheet for a control module. They can be used, for example for a Factory Acceptance Test (FAT).

Procedure 1. Open the project view in the navigation area of AdvES. 2. Navigate to the desired control module. 3. Open the control module by right clicking the context menu. Via this menu you can now create a CM test sheet.
Figure 4-110: Creating an CM test sheet

Copyright

Siemens AG 2013 All rights reserved

Figure 4-111: CM test sheet

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

105

4 Configuring with AdvES

Figure 4-112: CM test sheet

Copyright

Siemens AG 2013 All rights reserved

Note

Alternatively, you can also create the CM test sheets for several control modules via the process tag list table view or via the report folder.

106

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

4.9.3

Table views
In AdvES you can also process mass data. Different table views are available for this purpose.

Procedure The following applies to all table views: 1. The different table views can be selected via the dropdown menu in the AdvES header. Click the button next to the Menu. 2. The drop-down menu will open. Via this, different table views can be selected.
Figure 4-113: Table views

Copyright

Siemens AG 2013 All rights reserved

Functions in the tables In the header bar of a table view you can refresh all contents with a button.
Figure 4-114: Refreshing the contents

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

107

4 Configuring with AdvES

In the header of a table view there is a button for exporting the contents. Exception: Table view connections. By clicking the triangle you can select the export format and at the same time trigger the export. Microsoft Excel is preset by default.
Figure 4-115: Exporting the contents

You can edit the contents of white fields.


Siemens AG 2013 All rights reserved

a.) By writing directly into a field. b.) Several fields can also be selected (e.g. by Ctrl + A). By right clicking one of the selected fields a context menu opens. Editing (F2) can uniformly change the content of the selected cells (see chapter 4.6). c.) A text can be transferred to another field by right clicking a cell (context menu opens) and clicking Copy texts, then right clicking on a different cell and Paste texts. If the text is to be transferred to several fields, the text is to be copied first, then the fields are selected and opened for editing (see b) and the text can be inserted with Ctrl + V. By placing the cursor in the header of a column, two selection buttons become visible. With the left one you can sort the rows alphabetically.
Figure 4-116: Alphabetical sorting

Copyright

108

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

4 Configuring with AdvES

With the right one you can create a filtered view of the data. The filter value is selected in the check box (left) and executed with the flash button (see chapter 4.6).
Figure 4-117: Sorting according to contents

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

109

4 Configuring with AdvES

4.9.4

Project properties
In AdvES from version 8.0 SP1 you have the option to define project properties.

Procedure 1. Click the button in the header bar next to the Menu.

A drop-down menu will open. 2. Click the Project properties menu entry.
Figure 4-118

Siemens AG 2013 All rights reserved

Copyright

3. The "Attribute" dialog box will open. Here, you can enter general information on the project that will be used in other places, for example, in reports or test sheets.
Figure 4-119

110

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

5 Conclusion

Conclusion
This application has shown that Advanced ES provides a solution for more efficient engineering and optimized data processing in order to improve the engineering process so far. This becomes apparent by the use of a new type concept which represents a great advantage compared to IEA. Furthermore, Advanced ES is an approach to replace previous heterogeneous tools for project realization by a homogenous software option package. The great advantage here is that documentation, support as well as further development of the tool is guaranteed.

Copyright

Siemens AG 2013 All rights reserved

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

111

6 Further Links

Further Links
Table 6-1: Internet links Topic 1 SIMATIC PCS 7 Process Control System; Advanced Engineering System SIMATIC PCS 7 CFC Process Control System for SIMATIC S7 (V8.0) Siemens Whitepaper Fast Track Engineering Entry ID: 57414032
http://support.automation.siemens.com/WW/view/en/57414032

Title

Entry ID: 60283984


http://support.automation.siemens.com/WW/view/en/60283984

German:
http://www.automation.siemens.com/mcms/process-controlsystems/SiteCollectionDocuments/efiles/pcs7/support/marktstudien/W P_Fast-Track-Engineering_DE.pdf

English:
Siemens AG 2013 All rights reserved

http://www.automation.siemens.com/mcms/process-controlsystems/SiteCollectionDocuments/efiles/pcs7/support/marktstudien/W P_Fast-Track-Engineering_EN.pdf

FAQ: How can you export and then re-import PCS 7 Advanced ES project data? Application: "Integrated Engineering with COMOS and SIMATIC PCS 7 in a practical example" Online entry: Service Pack 1 for SIMATIC PCS 7 V8.0 (EU) available

Entry ID: 62884021


http://support.automation.siemens.com/WW/view/en/62884021

Copyright

Entry ID: 70922226


http://support.automation.siemens.com/WW/view/en/70922226

Entry ID: 67798122 http://support.automation.siemens.com/WW/view/en/67798122

Online entry: SIMATIC PCS 7 Advanced Engineering System V8.0 Service Pack 1 available

Entry ID: 68402701


http://support.automation.siemens.com/WW/view/en/68402701

112

SIMATIC PCS 7 Advanced ES V2.0, Entry ID: 61627479

7 History

History
Table 7-1: Document versions Version V1.0 V2.0 Date 06.2012 07.2013 First version Creating PCS 7 project, configuring messages in CMT, creating individual mapping labels, chapter 4.9 "Other useful functions in AdvES, refreshing texts and images. Modifications