9290 007 05103M

Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

Output Power (W)

Output Voltage (V)

Output Current (A)

Efficiency@ Max Load

Max Case Temp. (C)

Input Current

Max. Input Power (W)

Inrush Current (Apk/50%-s)

THD @ Max Load (%)

Power Factor @ Max Load

Surge Protection Common/Diff (KV)

Weight (Lbs/kgs)

IP Rating

120 V 150 125 ~ 280 0.350 0.70 91.5

230 V

277 V 80 C

120 Vin 120 200 240 277 165 230 Vin 277 Vin

58/ 140 108 / 140 126 / 140

20

>0.95

4/4

2.8/ 1.27

IP66

93.0

93.0

1.4

0.85

0.7

0.6

Wire Diagram
Dimming Method 1-10V Isolated DALI Amp Dimming Dimming Range 10% ~ 100%
1~ 254 10% ~ 100%

Minimum Output Current (A) 0.050

Other Comments

Dimming source current: 150 A Linear or Logarithmic variation Linear

0.050 0.105

30% ~ 100%

Input and output use lead- wires. Lead-wires are 18AWG 105C/600V solid copper.

Enclosure

Standard Lead Length is 500mm+/-10mm on all wires outside the can

Case Length Case Width Case Height Mounting Length Mounting Width Overall Length
Revised 10/07/2011 NT

in. (mm) 8.38 (211.1) 2.35 (59.1) 1.47 (37.1) 9.0 (226.2) 1.7 (42.9) 9.54 (240.5)

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status Product Data
Order code Full product code Full product name Net weight per piece Interfaces Ambient Temp Range Corresponding Tcase Line Voltage Line Current Line Frequency IP Classification Life @ TC 70 C Life @ TC 80 C Suitable for Outdoor use? Max TC Inrush current Width Maximum ballast number on MCB 16A Input Over-voltage LED Current Tolerance Earth leakage current Mains voltage safety (AC) Mains voltage performance (AC) Min. Mains voltage operational Max. Mains voltage operational Output Current ripple THD total rd THD 3 Harmonic PF @ Max Load Wire Isolation Protections Standby power 929000705103M 929000705103M Xitanium150W 0.35-0.7A GL Prog+ sXt 1.27 KG / 2.8 lbs 1-10V Dimming, DALI, Amp Dimming, Integrated Dynadimmer, AOC, MTP, CLO, OTL -40C to +55C -15C to +80C 120-277V 1.4A @ 120V, 0.7A @ 240V, 0.6 @ 277V 50/60Hz 66 100000 hr [nom] refer to graph below 48000 hr [nom] refer to graph below Yes 80C Refer to table 11 [max] Can survive input over-voltage stress of 320VAC for 48 hours and 350VAC for 2 hours +/-5% 0.7 mA [max] +/-10% +/-10% 108 V [min] 305V [max] 30% @ 700 mA (ripple = pk-pk/avg) < 20% < 15% >0.95 All wires are Double isolated to ground Short Circuit and Open Circuit Protection for LED + and LED<1.0W

Electrical Specifications

XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Installation & Application Notes: Section I Physical Characteristics 1.1 LED Driver shall be installed inside an electrical enclosure 1.2 Wiring inside electrical enclosure shall comply with 600V/105C rating or higher. Section II Performance 2.1 LED Driver has a rated lifetime of 50,000 hours @ TC <=80C. 2.2 LED Driver tolerates sustained open circuit and short circuit output conditions without damage. 2.3 LED Driver maximum allowable case temperature is 80C see product label for measurement location. 2.4 LED Driver reduces output power to LEDs if its case temperature exceeds >90C thermal protection and eventually reduces output current to zero. 2.5 LED Driver complies with the requirements of UL, CSA, CE, ENEC, CISPR 15 Ed 7.2 and CQC (TBD).

Revised 10/07/2011 NT

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

AOC (Adjustable Output Current) Settings: LED current tolerance with variation of Rset is within +/- 5% of Imax

Iout VS Rset (between Yellow and BLU/WHT wires)


800 700 600 500 400 300 200 100 0
1 10 100 1000 10000 100000 Rext (Ohm)

Rset (Ohms) 1 100 620 910 935 1500 2200 3000 4115 4300 8200 18000 100000 1000000

Current(mA) 191 214 309 347 350 406 455 494 530 536 599 649 691 700

Nominal Iout (mA)

Vout vs. Iout


300 Driver Output Voltage (V) 280 260 240

220
200 180 160 140 200 300 400 500 Driver Output Current (mA) 600 700

Revised 10/07/2011 NT

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

Module Thermal Protection can be implemented between 50C to 85C. Please refer to design guide for more details Two NTC parts can be used: NTC1 from Murata Part Number NCP18XH103J03RB NTC2 from Murata Part Number NCP15XW153E03RC

120 100 80 Iout (%) 60 40 20 0

Iout (%) vs. NTC -Temp (@ Vin = 120 V, Tcase = 70 C, NTC_warn = 65 C, NTC_max = 75 C)

95

85

75

65

55

45

35

25

Estimated Module Temperature (C)

Revised 10/07/2011 NT

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

1-10V Dimming Curve: Dimming source current from the driver: 150 A (+/- 3%) LED Current tolerance at any value of Vdim: +/- 5% of Imax Minimum Dim Level: 10% - 100%

Iout vs. Vdim


100 80 Iout (%) 60 40 Tcase = 70 C

20
0 0 2 4 Vdim(V) 6 8 10

Revised 10/07/2011 NT

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

Amp Dimming Curve:

Parameter Start Voltage Stop Voltage Start Percent Stop Percent Current Tolerance: Fade Time: 2s (+/- 10%)

Min 170V 150V 30% 30%

Max 250V 230V 100% 100%

Increments 1V (configurable by software) 1V (configurable by software) 1% (configurable by software) 1% (configurable by software)

Iout (%) vs. Vin (Profile: Start Voltage = 215V, Stop Voltage = 165V)
120 100 80

Start Percent Start Voltage


T = -40C

Iout (%)

60 40 20 0 120 140 160 180 200 220 240 260 280 Input Voltage (Vrms)

Stop Voltage

T = 25C

Stop Percent

T = 70C

Revised 10/07/2011 NT

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

Efficiency vs. Output Voltage (@ Vin = 120 V, Tcase = 70 C)


92 91

Efficiency (%)

90

89
88

Iout = 700 mA Iout = 530 mA

87
86 120 140 160 180 200 Output Voltage (V) 220 240 260

Iout = 350 mA

Efficiency vs. Output Voltage (@ Vin = 200 V, Tcase = 70 C)


94 93 92

Efficiency (%)

91

90 89
88 87 86 85 120 140 160 180 200 Output Voltage (V) 220 240 260

Iout = 700 mA Iout = 530 mA Iout = 350 mA

Revised 10/07/2011 NT

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

Efficiency vs. Output Voltage (@ Vin = 230 V, Tcase = 70 C)


95 93

Efficiency (%)

91 Iout = 700 mA 89 87 85 120 140 160 180 200 Output Voltage (V) 220 240 260 Iout = 530 mA Iout = 350 mA

Efficiency vs. Output Voltage (@ Vin = 277 V, Tcase = 70 C)


94 Efficiency (%)
92 90 88 86 84 120 140 160 180 200 Output Voltage (V) 220 240 260 Iout = 700 mA Iout = 530 mA

Iout = 350 mA

Revised 10/07/2011 NT

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

Power Factor vs. Output Power (@ Tcase = 70 C)


1

Power Factor

0.95 Vin = 120 V Vin = 200 V 0.9 Vin = 230 V Vin = 277 V 0.85 60 80 100 120 Output Power (W) 140

THD vs. Output Power (@ Tcase = 70 C)


25 20 THD (%) 15 10 5 0 60 80 100 120 Output Power (W) 140 Vin = 120 V Vin = 200 V Vin = 230 V Vin = 277 V

Revised 10/07/2011 NT

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

Programming Interface:

Programming Tool: Refer to Website for downloading tool.

Revised 10/07/2011 NT

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

Iout vs. Tcase of Driver:

Iout (%) vs. Tcase (driver)


120 100 80

Iout (%)

60 40 20 0 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 Tcase (C ) with +/- 5C Tolerance

Inrush Current Info:

Vin 120 Vrms 230 Vrms 277 Vrms 305 Vrms

Ipeak 58 A 108 A 126 A 142 A

T (@ 50% of Ipeak) 140 s 140 s 140 s 140 s

Revised 10/07/2011 NT

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

Lifetime vs. Tcase of Driver:

Lifetime vs. Tcase


110 100 90 80 70 60 50 40 30 25 30 35 40 45 50 55 60 65 70 75 80 85 Tcase (deg. C)
Failure Rate Info: <0.01% per 1 kHr @<= Tcase 70 C Isolation: Isolation Input Wires Output Wires+ Fortimo Interface Wires DALI Wires 1-10V Wires Chassis Input Wires NA 1750 1750 1750 3750 Output Wires 1750 NA 1750 1750 3750 DALI Wires 1750 1750 NA NA 3750 1-10V Wires 1750 1750 NA NA 3750 Chassis 3750 3750 3750 3750 NA

Revised 10/07/2011 NT

Life (kHours)

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886

9290 007 05103M


Brand Name Description Input Voltage Input Frequency RoHS Status XITANIUM Xitanium 150W .35-.7A GL Prog+ sXt 120~200~240~277 50/60Hz Yes Active

Electrical Specifications

UL COA for 929000705103M (UL File# 321253): Conditions of acceptability When installed in the end-use equipment, the following are among the considerations to be made:
1. 2. 3. 4. The equipment shall be installed in compliance with the enclosure, mounting, spacing, casualty and segregation requirements of the ultimate application. The driver case must be grounded in the end-use application. The driver is suitable for use in DAMP and DRY locations. The secondary and dimming circuit should be considered as part of the primary circuit in the end-use application. Apart from the DALI and 10 V circuits, dimming can also be achieved via an external non-variable resistor connected to the leads identified as R set and Common. The resistor value is dependent on the desired output current according to the product specification sheet and can range 620 to 1000000 Ohms for 300mA to 700mA output.

5.

When the drivers are installed in the end-use application, the case temperature should not exceed the temperature limits specified in the following table: Model No. 929000705103 Input Voltage, Hz 120-277, 50/60 Max. Case @ Tc, C 80

6.

The leakage current test should be repeated in the end device. In tests, as a Component, test results were higher than 0.5 MIU but lower than 0.75 MIU.

Revised 10/07/2011 NT

PHILIPS LIGHTING ELECTRONICS N.A.


10275 WEST HIGGINS ROAD ROSEMONT, IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 www.philips.com/advance Customer Support/Technical Service: 800-372-3331 OEM Support: 866-915-5886