38CKC 018060 50 Hertz

Visit www.carrier.com

Wiring Diagrams
*CH (NOTE #9)

CONNECTION DIAGRAM
BLK COMP CONT 11 13 EQUIP GND 21 23 BLK BLK C YEL OFM S R YEL BLU H C F BRN YEL A1 BLU BLU YEL +t *ST BRN 1 *SC (NOTE #8) EQUIP GND 2 5 *SR

SCHEMATIC DIAGRAM (LADDER FORM)


*CH

RED or BLK RED or BLK A1 A2

CAP

CONT 11 21 5 2 1 *SR *SC

R COMP S *ST +t H CONT C A2

230 1 POWER SUPPLY

(NOTE #14) BLU *HPS BLU BLU BLK *DTS BLK

BRN

YEL BLK VIO *LPS T2 YEL LOGIC T1 *CTD BRN T3 *HPS *DTS (NOTE #14)

OFM

F CAP

23

13

YEL

CONT *LPS LOGIC T1 T3 *CTD IFR G R R C *LLS Y T2

*LLS BLU BLU BLK BLK IFR C R EXTERNAL POWER SUPPLY 24 V (NOTE #3) Y G R INDOOR BLOWER MOTOR

INDOOR THERMOSTAT (NOTE #5)

INDOOR THERMOSTAT

EXTERNAL POWER SUPPLY 24 V

-LEGENDFACTORY POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING FIELD POWER WIRING COMPONENT CONNECTION *LPS FIELD SPLICE OFM JUNCTION *SC CONT CAP *CH COMP CONTACTOR CAPACITOR (DUAL RUN) CRANKCASE HEATER COMPRESSOR * MAY BE FACTORY OR FIELD INSTALLED. *SR *ST START CAPACITOR START RELAY START THERMISTOR OUTDOOR FAN MOTOR LOW PRESSURE SWITCH *CTD *DTS *HPS IFR *LLS COMPRESSOR TIME DELAY DISCHARGE TEMP. SWITCH HIGH PRESSURE SWITCH INDOOR FAN RELAY LIQ. LINE SOLENOID VALVE

-NOTES1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Symbols are electrical representation only. Compressor and fan motor furnished with inherent thermal protection. To be wired in accordance with National Electric N.E.C. and local codes. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS. Use copper conductors only. Use conductors suitable for at least 75C (167F). Connection for typical cooling only thermostat. For other arrangements, see installation instructions. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN lead. When start relay and start capacitor are installed, start thermistor is not used. CH not used on all units. If any of the original wire, as supplied must be replaced, use the same or equivalent wire. Check all electrical connections inside control box for tightness. Do not attempt to operate unit until service valves have been opened. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting. 14. Wire not present if HPS, LPS, DTS or CTD are used.

CAUTION
1. Compressor damage may occur if system is overcharged. 2. This unit is factory charged with R-22 in accordance with the amount shown on the rating plate. The charge is adequate for most systems using matched coils and tubing not over 15 feet long. The best performance will be achieved when the unit operates with a suction gas superheat at the compressor inlet of 5 F at normal rating conditions of the air conditioning and refrigeration institute (ARI). This chart may be used to approximate the charge if ARI rating conditions cannot be obtained. ARI rating conditions are equivalent to DOE test "A" conditions. See product data literature for required indoor air flow rates and for use of line lengths over 15 Ft. 3. Carefully relieve refrigerant pressure within this unit before final disposal. 320668-101 REV. C

A96164

Fig. 138CKC018, 024, 036 230v, 1 Phase, 50 Hertz

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 101 Catalog No. 003-844 Printed in U.S.A. Form 38CKC-C3W Pg 1 5-99 Replaces: 38CKC-C2W Tab 3a 2a

CONNECTION DIAGRAM
A2 400 3 POWER SUPPLY A1 A3 CONT 12 11 13 ALERT ! EQUIP GND SEE NOTE #12 RED or BLK RED or BLK *CH BRN 22 21 23 YEL YEL BRN BLK OFM BLK *LPS BLU YEL YEL LOGIC T1 CTD BRN *LLS BLK BLK IFR C R EXTERNAL POWER SUPPLY 24 V (NOTES #3 & #6) G R Y INDOOR THERMOSTAT (NOTE #5) 1. INDOOR BLOWER MOTOR T3 YEL VIO T2 CONT CAP *CH COMP *CTD IDF *HPS IFR *LLS *LPS OFM BLU BLK T1 T3 CAP T2 COMP

-LEGENDFACTORY POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING FIELD POWER WIRING COMPONENT CONNECTION FIELD SPLICE JUNCTION CONTACTOR CAPACITOR (DUAL RUN) CRANKCASE HEATER COMPRESSOR COMPRESSOR TIME DELAY INDOOR FAN HIGH PRESSURE SWITCH INDOOR FAN RELAY LIQ. LINE SOLENOID VALVE LOW PRESSURE SWITCH OUTDOOR FAN MOTOR

*HPS BLU BLU

* MAY BE FACTORY OR FIELD INSTALLED.

NOTES:
SYMBOLS ARE ELECTRICAL REPRESENTATION ONLY. 2. COMPRESSOR AND FAN MOTOR FURNISHED WITH INHERENT THERMAL PROTECTION. 3. TO BE WIRED IN ACCORDANCE WITH NATIONAL ELECTRIC N.E.C. AND LOCAL CODES. 4. N.E.C. CLASS 2, 24 V CIRCUIT, MIN. 40 VA REQUIRED, 60 VA ON UNITS INSTALLED WITH LLS. 5. USE COPPER CONDUCTORS ONLY. USE CONDUCTORS SUITABLE FOR AT LEAST 75C (167F). 6. TYPICAL COOLING ONLY THERMOSTAT, FOR OTHER ARRANGEMENTS SEE INSTALLATION INSTRUCTIONS. 7. IF INDOOR SECTION HAS A TRANSFORMER WITH A GROUNDED SECONDARY, CONNECT THE GROUNDED SIDE TO THE BRN LEAD. 8. IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED MUST BE REPLACED, USE THE SAME OR EQUIVALENT WIRE. 9. CHECK ALL ELECTRICAL CONNECTIONS INSIDE CONTROL BOX FOR TIGHTNESS. 10. DO NOT ATTEMPT TO OPERATE UNIT UNTIL SERVICE VALVES HAVE BEEN OPENED. 11. DO NOT RAPID CYCLE COMPRESSOR. COMPRESSOR MUST BE OFF 3 MINUTES TO ALLOW PRESSURES TO EQUALIZE BETWEEN HIGH AND LOW SIDE BEFORE STARTING. 12. IT IS IMPERATIVE TO CONNECT 3 FIELD POWER TO UNIT WITH CORRECT PHASING. WRONG PHASING WILL CAUSE REVERSE ROTATION OF SCROLL COMPRESSOR WHICH WILL RESULT IN REDUCED CURRENT DRAW, ELEVATED NOISE LEVEL AND IMPROPER OPERATION. IF ROTATION IS REVERSED, SIMPLY INTERCHANGE ANY TWO OF THE THREE POWER CONNECTIONS ON FIELD SIDE.

A1

SCHEMATIC DIAGRAM (LADDER FORM)


COMP CONT T1 21 T3 OFM CAP 23 *CH CONT *HPS *LPS LOGIC T1 *LLS CTD IFR T3 T2 CONT 13 T2 CONT 22 12 A2 A3

EQUIP GND

11

Y G R R INDOOR THERMOSTAT C

EXTERNAL POWER SUPPLY 24 V

! CAUTION
1. Compressor damage may occur if system is over charged. 2. This unit is factory charged with R-22 in accordance with the amount shown on the rating plate. The charge is adequate for most systems using matched coils and tubing not over 15 feet long. The best performance will be achieved when the unit operates with a suction gas superheat at the compressor inlet of 5 F. at normal rating conditions of the Air Conditioning and Refrigeration Institute (ARI). This chart may be to approximate the charge if ARI rating conditions cannot be obtained. ARI rating conditions are equivalent to DOE test "A" conditions. See product data literature for required indoor air flow rates and for use of line lengths over 15 ft. 3. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open al flow-control devices, including solenoid valves. 325512-101 REV. A
A99095

Fig. 238CKC036, 048, 060 400v, 3 Phase, 50 Hertz

Copyright 1999 CARRIER Corp. 7310 W. Morris St. Indianapolis, IN 46231

38ckcc3w

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 101 Catalog No. 003-844 Printed in U.S.A. Form 38CKC-C3W Pg 2 5-99 Replaces: 38CKC-C2W Tab 3a 2a