You are on page 1of 52

Section Updated 09 / 2012

Panelboards

Section 9

FE as a main breaker in A-Series Panelboards: Expanding GEs selectivity offering. The FE main breaker in A-Series allows full instantaneous selectivity, which can be coordinated with upstream and downstream GE breakers. A-Series Branch Circuit Monitoring (BCM): This new energy management product allows for monitoring key electrical parameters down to a branch circuit level. This product is factory installed which makes for a clean installation and reduced labor in the field. AS style A-Series panel: New AE subtype panel, AS, allows for the combination of expanded selectivity and fully rated solution up to 65kAIC at 480V. This solution also decreases overall footprints of our panelboard, which has an important aspect of current day installations.

A-Series Panelboards Applications...................................................................................................9-3 Types ................................................................................................................9-4 Terminal Lugs...............................................................................................9-7 Pricing and Ordering.................................................................................9-8 Column Field Installed Kits/Replacement Parts/Enclosures ...................................................................................9-10 Accessories.................................................................................................9-12 Lighting Control PanelRemote Operated Circuit Breakers .....................................................................................9-12 Pro-Stock Panelboards Unassembled .......................................9-13 Product Options .......................................................................................9-19 Spectra Series Panelboards Fusible Switches Load and Interrupting Ratings......................9-25 Merchandisable Kits and Sizing Information .............................9-27 Terminal Lugs ............................................................................................9-28 PCU Selection ............................................................................................9-29 Interior, Enclosure Options ..................................................................9-30 Spectra Series Integrated Submetering Panelboard............9-32 Replacement Boxes and Fronts........................................................9-33 Renewal Parts Modular Concept .....................................................9-36 Renewal Parts Circuit Breaker Sizing .............................................9-37 Renewal Parts Product Number Structure..................................9-38 Renewal Parts Mounting Hardware............................................9-41 Renewal Parts Main Lug Modules; Neutral and Ground Kits ...................................................................9-46 Renewal Parts Accessories .............................................................9-47 Renewal Parts Interiors, Boxes and Fronts .............................9-48 Renewal Parts Type SCP Panelboards.......................................9-49 Renewal Parts Type CCB and QMR Panelboards..................9-50 Available Publications ...............................................................9-52

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-1

This page left blank intentionally.

9-2

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
A-Series Panelboards
Applications
Standards All GE panelboards meet the latest revision of the following standards. National Electrical Code-Ref. Article 384. UL67 panelboards: UL50 cabinets and boxes. UL943 GFCI. UL489 molded case circuit breakers. UL98 fusible switches. CSA or C-uL listing for Spectra Series Power Panelboards. C-uL Listing for A-Series non-service entrance panelboards International Building Code Seismic Zone 3 and 4. California Building Code Seismic Zone 4. NEMA PB1. Federal Specifications Panelboards, W-P-115c. Type 1Circuit breaker equipped Class 1Panelboards Class 2Load centers Molded case circuit breakers, WC-375B/GEN. Fusible switches, W-S-865c. Application The following classifications and limitations of panelboards have been established by the Underwriters Laboratories and the National Electrical Code. Note an overcurrent protective device is a circuit breaker pole or single fuse. Panelboards have no fire wall ratings. All 50/60 Hz rated. There is no limitation as to the number and rating of branch circuits, except as determined by available enclosures. Interrupting RatingsCircuit Breakers Panelboards have integrated short circuit ratings. When fully rated, the rating is that of the lowest rated device in the panelboard. When series connected rated, the rating is that of the main device in panel (or remote line side protected device) and branch-tested/UL Listed combination. Features

Section 9

Symmetrical design, no required top or bottom mountings Wide, easy-to-install galvanized enclosures with removable endwalls Flush or surface mounting Standard concealed mounting hardware and hinges Interiors that allow straight-in wiring Split neutral Field-installable, UL Listed, 200% neutral for non-linear loads Branch-bus direct connection Captive hardware on branch breakers Short circuit ratings allow up to 100KA @ 480Y/277Vac; 200KA @ 240Vac Main bus ratings of 125 to 800 amps copper, 125 to 600 amps aluminum Spectra RMS and vertically mounted main circuit breakers available Bus-connected TVSS for maximum surge protection Optional door-in-door or front-hinged-to-box door Enclosures available in NEMA Type 1, Type 3R/12, Type 4/4X

Short-Circuit RatingsFusible Switch Units The interrupting rating of the fuse must equal or exceed the short-circuit rating of the switch. If it is lower, then the interrupting rating of the switch is the same as the fuse. Switches have no short-circuit rating if renewable fuses are used. Seismic Ratings All A-Series Lighting Panels and Spectra Power Panels have been tested and certified to meet the International Building Code (IBC) Zone 3 and Zone 4 as well as the California Building Code (CBC) Zone 4.

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-3

Panelboards
A-Series Panelboards
Type AL
Service Information: 1P, 3W-120/240 Vac 3P, 3W-240 Vac 3P, 4W-240/120 Vac, 208/120 Vac Mains Breakers: 100A-THQB, THHQB, TEY, SE, FE 225A-TQD, THQD, SF, FE 400A-TJD, SG 600A-SG 800A-SK Main Lug: 125-800A Branch Breakers (Plug-in): Amperage-15-100A Poles-1, 2, 3 Types-THQL, THHQL, TXQL Enclosures Length-25.5, 31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5 Width-20 Depth-5.81

Section 9

Type AQ
Service Information: 1P, 3W-120/240 Vac 3P, 3W-240 Vac 3P, 4W-240/120 Vac, 208/120 Vac Fully Rated: 65kAIC at 240V Series Rated: 200kAIC at 240V Mains Breakers: 100A-THQB, THHQB, TEY, SE, FE 225A-TQD, THQD, SF, FE 400A-TJD, SG, FG 600A-SG 800A-SK Main Lug: 125-800A Branch Breakers (Bolt-on): Amperage-15-100A Poles-1, 2, 3 Types-THQB, THHQB, TXQB Enclosures Length-25.5, 31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5 Width-20 Depth-5.81

9-4

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
A-Series Panelboards
Type AE (includes subtype AS)
Service Information: 1P, 3W-120/240 Vac, 125/250 Vdc 3P, 3W-240 Vac 3P, 4W-480/277 Vac, 208/120 Vac, 240/120 Vac Fully Rated: 65kAIC at 480Y/277V, 100kAIC at 240V Series Rated: 100kAIC at 480V Mains Breakers: 100A-TEY, SE, FE 225A-TFJ, SF, FE 400A-TJJ, SG, FG 600A-SG 800A-SK Main Lug: 125-800A Branch Breakers (Bolt-on): Amperage-15-100A Poles-1, 2, 3 Types-TEY, TEYF, TEYD, TEYH, TEYL Amperage-110A, 125A Poles-2, 3 Types-TEYD, TEYH, TEYL Enclosures Length-25.5, 31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5 Width-20 Depth-5.81
Note: Bold items are features of AS Panels

Section 9

Type AD
Service Information: 3P, 3W-480 Vac, 600 Vac 3P, 4W-208/120 Vac, 480/277 Vac, 600/347 Vac Fully Rated: 35kAIC at 600Y/347V, 100kAIC at 480V Series Rated: 35kAIC at 600Y/347V Mains Breakers: 150A-THED, SE 225A-TFJ, SF 400A-TJJ, SG 600A-SG 800A-SK Main Lug: 150-800A Branch Breakers (Bolt-on): Amperage-15-100A (1P, 2P) 15-150A (3P) 220A Max. double branch Types-TED, SE, FB Enclosures Length-31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5 Width-20 Depth-5.81

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-5

Panelboards
A-Series Panelboards
Types
Panelboard Types
A-Series AL Pg. 9-4 240Vac AQ Pg. 9-4 240Vac AE/AS Pg. 9-5 480Y/277Vac1 125/250Vdc 800A 800A 800A 800A 400A 225A 225A AD/AD Plus Pg. 9-5 600Vac Lighting Control Panel Pg. 9-11 480Y/277Vac ALC Pg. 9-9 240Vac Column Type Panels AQC Pg. 9-9 240Vac AEC Pg. 9-9 480/277Vac 125/250Vdc 225A

Section 9

Distribution Panels Spectra Pg. 9-24 600Vac 250Vdc 1200A

Item Max. Voltage Max. Main Lug Amperes Max. Main Breaker or Switch Amperes

800A

800A

800A TEY, TFJ, TJJ, TEYF, TEYD, TEYH, TEYL

800A

400A TEY, SE, TFJ, SF, TJJ, SG 100A

225A

225A

225A TEY, TFJ, SE, SF

1200A SF, SG, SK, ADS Switches, FB, FC, FE, FG 1200A TED, SE, SF, SG, SK, THQB, THHQB, TEY, TQD, ADS Switches, FB, FC, FE, FG

Main Devices

THQB, THHQB, TQD, THQD, TEY, TJD, TFJ

THED, TFJ, TJJ

SE, SF, SG, SK Branches Max. Amps 100A 100A THQB, THHQB, TXQB (Bolt-on) 225 125A 100A-1 ph, 2ph 150A-3 ph TEY. TEYF, TEYD, TEYH, TEYL FB,TED, THED, SE

THQB, THHQB, TQD, THQD, TEY, TFJ, SE, SF 100A 100A THQB, THHQB, TXQB (Bolt on) 150

80A-8 1/2 Box 80A-7 1/2 Box

Branch Devices Subfeeds Max. Amps (100% Rated) Subfeed Breaker Types

THQL, THHQL

TEYRC, TEY, THQBGF

THQL, THHQL

TEY

225

225

225

225

150

150

TQD, THQD

TQD, THQD

TED, TFJ, SE, SF

TED, TFJ, SE, SF

TED, TFJ, SE, SF

TQD, THQD

TQD, THQD

TED

A-Series Standard Main Breaker Types and Ratings


Panel Type IC Ratings 10 22 65 100 200 142 35 18 25 65 100 142 65 100 182 25 480Y/277 480Y/277 480 480 480 600 600 SEHA4/TEYD SFHA4 SELA4/TEYL SFLA4 SEPA4 SFPA SGLA4 SGLA6 SEPA TED SELA SEPA THED SELA SEPA SFPA TFJ SFLA SFPA TFJ SFLA SFPA SGPA4 TJJ SGLA4 SGPA4 TJJ SGHA4 SGPA4 SGPA6 SGHA6 SGLA6 SGLA6 SGHA6 SGHA6 SGPA6 SKHA6 SEHA SFHA AQ/AL Voltage 240 240 240 240 240 480Y/277 480Y/277 100A THQB THHQB TEY SEL/TEYL SEP 225A TQD/TFJ THQD SFHA SFL SFP TJD SGHA4 SGL SGPA4 TEY4 TFJ4 SGHA/TJJ4 SGHA6 SKHA8 TED SEHA TFJ SFHA TJJ SGHA4 SGHA6 SKHA8 SGHA6 SGHA6 SGL6 SFHA4 SGHA44 SGHA6 400A3 600A3 800A3 SKHA8 150A AE / Lighting Control Panel 225A 400A 600A 800A 150A 225A AD / AD Plus 400A 600A 800A

35k2 600Y/347 1 AE Panels are suitable for use on 3-PH, 3W applications when derived from 3PH, 4W 480V/277 service 2 Not series rated. 3 Not available in column panelboards. 4 Light Control Panel ratings.

where the neutral is not connected to the panel. For 3ph-Delta use AD Panels.

9-6

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
A-Series Panelboards
Terminal Lugs
Molded Case Circuit Breakers
Circuit Breaker Frame Standard THQL THQB TEY TEB TED TED4 TED6 Hi-Break TXQL, THHQL TXQB, THHQB THED1 THED Tri-Break Current Limiting FBV FBN FBH FBL FCS FCV FCN FCH FCL SELA SEPA FES1T FEV1T FEN1T FEH1T FEL1T FES1E FEV1E FEN1E FEH1E FEL1E SFLA SFPA FES2T FEV2T FEN2T FEH2T FEL2T FES2E FEV2E FEN2E FEH2E FEL2E SGL SGP SGL SGP FGV2 FGN2 FGH2 FGL2 FGP2 FGV4 FGN4 FGH4 FGL4 FGP4 FGV6 FGN6 FGH6 FGL6 FGP6 THLC1 THLC2 THLC4 High Interrupting Poles 1,2,3 1 1,2,3 1,2,3 1,2,3 1 2-3 2-3 1,2,3 1 TCAL14 TCAL12 TCAL12A TCAL15 FCAL12 FCAL13 FCAL14 FCALK12 FCALK13 FCALK14 TCAL18 FCALK15 FCALK15 TCAL25 TCAL29 TCAL24, 26 FCALK16 FCALK16 TCLK2652 TCLK3652 FCALK318H Fixed to Breaker Terminal 1 1 No. Per Pole Terminal Lugs (Cu-Al) Product Number

Section 9

WireCu-Al (Unless otherwise noted) Per Lug Range (15-30A) #14-4 Cu or #12-4 Al (35-100A) #14-1/0 Cu or #12-1/0 Al (15-25A) #14-#12 Cu or #12-#10 Al (30-60A) #10-#6 Cu or #8-#4 Al (70-100A) #4-#1 Cu or #2-1/0 Al (15-30A, TCAL14)#14-8 (30-60A, TCAL12)#14-3 Cu, #12-1 Al (70-90A, TCAL12A)#6-2/0 Cu, #4-2/0 Al (100-150A, TCAL15)#3-3/0 (15-20A) #14-#12 Cu or #10-#12 Al (35-60A) #10-#6 Cu or #8-#4 Al (70-100A) #4-#1 Cu or #2-1/0 Al (15-20A) #14-#12 Cu or #10-#12 Al (35-60A) #10-#6 Cu or #8-#4 Al (70-100A) #4-#1 Cu or #2-1/0 Al #12-3/0 Cu, #12-3/0 Al #12-3/0 Cu, #14-1/0 Al #12-3/0 Cu, #14-1/0 Al #1-300kcmil #8-350kcmil #4-300kcmil #8-250kcmil Cu, #8-250kcmil #8-250kcmil Cu, #8-250kcmil 2(2/0-400kcmil Cu) or 2(2/0-500kcmil Al) or #6-600kcmil 2(2/0-400kcmil Cu) or 2(2/0-500kcmil Al) or #6-600kcmil Top hole #8-400kcmil Cu or #6-500kcmil Al Bottom hole #2/0-600kcmil Cu & Al Top hole #8-400kcmil Cu or #6-500kcmil Al Bottom hole #2/0-600kcmil Cu & Al Top hole #8-400kcmil Cu or #6-500kcmil Al Bottom hole #2/0-600kcmil Cu & Al #6-600kcmil or 2-(2/0-250kcmil) #6-600kcmil or 2-(2/0-250kcmil) #6-600kcmil or 2-(2/0-250kcmil) 250-350kcmil, Cu, or 350-500kcmil, Al 2/0-500kcmil #4-600kcmil or 2-(1/0-250kcmil) 2/0-500kcmil 3/0-500kcmil 3/0-500kcmil 3/0-500kcmil 3/0-500kcmil 250-350kcmil Cu or 350-5000kcmil Al 250-350kcmil Cu or 350-500kcmil Al (15-60A, TCAL12)#14-#3 Cu or #12-#1 Al (70-100A, TCAL12A)#6-2/0 Cu or #4-2/0 Al (100-150A, TCAL15)#3-3/0 Cu or #1-3/0 Al (125-225A, TCAL27)#4-300kcmil 3/0-500kcmil or 2-(3/0-250kcmil)

SEDA TQD SFHA TFJ, TFK SGDA SGHA SGDA SGHA

SEHA THQD THFK

2,3 2-3 2-3 2-3 2-3 2-3 2-3 2-3 2-3 2 3 2-3

1 1 1 1 1 1 1 1 1 1 1 1

1 1 1 1 1 1 1 1 1

2-3

FCALK318H

TJJ, TJK4 TJD TJK6 SKHA8 TKM84 SKHA12, TKM124

THJK4 THJK6, THJ4V THKM8 THKM12

TB4 TB6 TB8 TB1

SKLA8 SKPA8 Load End SKLA12, SKPA12 Load End TLB44

2-3 2-3 2-3 2-3 3 2-3 3 2-3 2-3 3 3 3

1 1 1 1 1 1 1 1 1 1 1 1 1

FCALK318H TCAL43 TCAL43 TCAL43 TCAL63 TCAL61 TCAL41 TCAL61 TCAL81 TCAL91 TCAL81 TCAL81 TCAL121 TCAL131 TCAL12 TCAL12A TCAL15 TCAL27 TCLK433

1 1 1 2 2 1 2 3 3 3 3 4 4 1 1

1One-pole THED frame available only in 15-30 amp trip. 2Lug kitincludes line or load end cover.

3Three-pole lug assembly suitable for line or load end. 4For replacement use only.

ADS Fusible Switch Module Terminations (CU/AL Mechanical)5


Amp Rating 30 60 60 100 200 400 600 800 1200 Voltage 240/600 240 600 240/600 240/600 240/600 240/600 600 600 Wire Size (CU/AL) #2-#14 #2-#14 #14-I/O #14-I/O #6-250kcmil I/O-250kcmil or #2-600kcmil I/O-250kcmil or #2-600kcmil I/O-250kcmil or #2-600kcmil I/O-250kcmil or #2-600kcmil # Wires Per Lug 1 1 1 1 1 2 or 1 2 or 1 2 or 1 2 or 1 # Lugs Per Phase 1 1 1 1 1 1 1 1 1

5 For optional mechanical or compression lugs refer to GET-7006.

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-7

Panelboards
A-Series Panelboards
Pricing and Ordering
Information Required to Price and Order a Panelboard Short-circuit Rating (10kA, 18kA, etc.) Service Entrance Label (Yes) or (No) Mark(s) (LPA, MDP, RPC, etc.) Service (3-ph, 4-w 208Y/120; 3-ph, 3-w 480 volts, etc.) Entrance of Incoming Line (Top) or (Bottom). (Bottom Supplied as Standard) Trim (Surface) or (Flush) Incoming Wire Size (500kcmil, 250kcmil, etc.) Incoming Number of Wires per phase (1, 2, 3, etc.) Wire Material (Copper or Aluminum) Main Type (Main Lugs Only, Circuit Breaker, Fusible Switch, etc.) Amperage of Main Bus Frame of Main Circuit Breaker (SG, SK, TJK, etc.) (if applicable) Options to Mains (Shunt Trip, Lighting Contactor, etc.) Equipment Ground (Optional) Branches Amp Rating (20, 30, 50, etc.) Poles (1, 2, or 3) Frame (THQB, TED, etc.) Quantity (1, 10, 15, etc.) Options: Interior (Copper bus, 200% rated neutral, etc.) Box (Painted, Increased Gutter, etc.) Front (Door in Door, etc.) Ground Fault Protection (Yes) or (No) Type of Panel (AQ, AE, Spectra Bolt-on, etc.) How to Price Factory Assembled Panelboards

Section 9

Main Price (or Interior Price for A-Series) + Branch Circuits + Options = Total List of Panelboard. The sum of these list prices is the total list for the complete panelboard including box and front.
Please refer to Speedi for quoting, pricing and ordering GE panels

How to Lay Out Factory Assembled Panelboards Multi-section panels must have a main circuit breaker or main lugs in each section. Double (dual) main lugs or thru-feed lugs must be added as required in all but the last section.
Please refer to Speedi for quoting, pricing and ordering GE panels

How to price a Pro-Stock, unassembled panelboard Total the following components: Interior Box (add ground bars as required) Front Main breaker or lug kit Subfeed breaker or feed thru lug kit (if required) Branch Breakers (from Section 3) Accessories (200% neutral, service entrance etc.) = Total List Price Please consult your local distributor for net pricing and current stock levels.

9-8

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
A-Series Panelboards
Column Panels
Type ALC
Service Information: 1P, 3W-120/240 Vac 3P, 4W208/120 Vac, 480/277 Vac 3P, 4W-240 Vac Mains Breakers: 100A-THQB, THHQB, TEY, SE 225A-TQD, THQD, SF Main Lug: 125-225A Branch Breakers (Plug-in): Amperage-15-100A (1P, 2P, 3P) Types-THQL, THHQL, TXQL Enclosures Length-37.5, 43.5, 49.5, 55.5, 64.5, 76.5 Width-8.62 Depth-5.81

Section 9

Type AEC
Service Information: 3P, 4W-480/277 Vac Mains Breakers: 100A-TEY, SE 225A-TFJ, SF Main Lug: 125-225A Branch Breakers (Bolt-on): Amperage-15-80A (1P, 2P, 3P) Types-TEY Enclosures Length-37.5, 43.5, 49.5, 55.5, 64.5, 76.5 Width-8.62 Depth-5.81

Type AQC
Service Information: 1P, 3W-240/120 Vac 3P, 3W-240 Vac 3P, 4W-240 Vac Mains Breakers: 100A-THQB, THHQB, TEY, SE 225A-TQD, THQD, SF Main Lug: 125-225A Branch Breakers (Bolt-on): Amperage-15-100A (1P, 2P, 3P) Types-THQB, THHQB, TXQB Enclosures Length-37.5, 43.5, 49.5, 55.5, 64.5, 76.5 Width-8.62 Depth-5.81

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-9

Panelboards
A-Series Panelboards
Column
Field Installed Kits/Replacement Parts

Section 9

Miscellaneous Kits Order by Product Number from the National Service Center
Description Equipment Grounds: Standard Terminal Strip With Provision for (11) 14-8 Cu or 12-8 Al (3) 14-4 Cu or 6-4 Al Above terminal with Copper Strap Main Lug 6-2/0 Cu/Al Standard Isolated Insulated (11) 14-8 Cu or 12-8 Al (3) 14-4 Cu or 6-4 Al Above terminal with Copper Strap Handle Locking Devices: THQL, THHQL THQB, THHQB TEY TED TFJ, TFL, TLB4 Padlocking Devices: THQL, THHQL, TXQL THQB, THHQB, TXQB TEY TED, TEL TQD TFJ, TFL Filler Plate for Q Line and TEY Breakers Gasketing Kit Safety Catch for Trough Covers 1
1

Panelboards Parts Order from Factory


Description Directory Card Circuit Numbering Strips - 1-48
TGL2 137A

Product Number

GO Sched.

Product Number 139C5612P2

569B806G1 569B806G2 139C5491P4

43-84 Directory Card Holder

TGC2 TGL20 EGS12 EGC12

134B 137A 134B 134B

Permanent Circuit Number Kits Order from Factory


Product Number APN48 APN84 Description No's 1-48 No's 43-84

THL103 TEYLD1 TLD3 TFKLD1

137A 135B 135B 135B

THP100 TEYPLD1 TEFPLD1 TQDPLD1 TFKPLD1 TQLFP1 AGSK ACHK

137A 135B 135B 137A 135B 137A 101 101

Standard on pull box.

9-10

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
A-Series Panelboards
Lighting Control Panel
480Y/277 Vac/120/208 Vac Remote Operated Circuit Breakers Bolt-On Factory Assembled Three-Phase, 4-Wire Pricing Service Information: 1P, 3W-120/240 Vac 3P, 4W-208/120 Vac, 480/277 Vac Mains Breakers: 100A-TEY, SE 225A-TFJ, SF 400A-TJJ, SG Main Lug: 125-400A Branch Breakers (Bolt-on): Amperage-15-30A (1P, 2P): TEYRC 15-100A (1P, 2P, 3P): TEY 220A Max. double branch Types- TED, SE, FB Enclosures Length-25.5 31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5 Width-20 Depth-5.81

Section 9

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-11

Panelboards
A-Series Panelboards
Lighting Control Panel
480Y/277 Vac/120/208 Vac Remote Operated Circuit Breaker Accessories
Product Description Programming Software PC-based start up software Daylight Optimization Module Peforms sunlight harvesting by measuring the amount of light and provides a control signal to a dimming mechanism to maintain a preset lighting level. Remote Switch Expansion Module Provides additional 16 digital input signals to the controller for each module Control Wiring Insulation Tubing Requirement per UL67 and NEC725.55, that low voltage class 2 and 3 control wiring be separated with tubing having an insulation rating equal to branch load wiring. Number ASROCBPRGM ASRGLCDOK

Section 9

ASRGLCDSK

ASRGLCCWT

Programming Software

Dimming Module

Remote Switch Module

9-12

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
A-Series Panelboards
Pro-Stock, Unassembled Lighting Panels
100-600A 240 Vac 1 or 3 Phase or 480Y/277 Vac 3 Phase Order by Product Number from the Customer Service Center
1 Select Interior

Section 9

Select the interior by bus type, panel rating and number of circuits. Identify the box/front height for use in Steps 2 and 3. Copper Bus
Rating Voltage (Amps) 100225 400 600 100225 400 600 100225 400 600 No. of Circuits 18 30 42 18 42 18 42 18 30 42 18 42 18 42 18 30 42 18 42 18 42 Feed-thru Product Box/Front Number1 Height AQU1182RCXAXT1B4 AQU1302RCXAXT1B4 AQU1422RCXAXT1B4 AQU1184RCXAXT1B4 AQU1424RCXAXT1B4 AQU1186RCXAXT1B4 AQU1426RCXAXT1B4 AQU3182RCXAXT1B4 AQU3302RCXAXT1B4 AQU3422RCXAXT1B4 AQU3184RCXAXT1B4 AQU3424RCXAXT1B4 AQU3186RCXAXT1B4 AQU3426RCXAXT1B4 AEU3182RCXAXT1B4 AEU3302RCXAXT1B4 AEU3422RCXAXT1B4 AEU3184RCXAXT1B4 AEU3424RCXAXT1B4 AEU3186RCXAXT1B4 AEU3426RCXAXT1B4 37.5" 43.5" 49.5" 64.5" 76.5" 64.5" 76.5" 37.5" 43.5" 49.5" 64.5" 76.5" 64.5" 76.5" 37.5" 43.5" 49.5" 64.5" 76.5" 64.5" 76.5" Non Feed-thru Product Box/Front Number1 Height AQU1182RCXAXB4 AQU1302RCXAXB4 AQU1422RCXAXB4 AQU1424RCXAXB4 AQU1426RCXAXB4 AQU3182RCXAXB4 AQU3302RCXAXB4 AQU3422RCXAXB4 AQU3424RCXAXB4 AQU3426RCXAXB4 AEU3182RCXAXB4 AEU3302RCXAXB4 AEU3422RCXAXB4 AEU3424RCXAXB4 AEU3426RCXAXB4 31.5" 37.5" 43.5" 64.5" 64.5" 31.5" 37.5" 43.5" 64.5" 64.5" 31.5" 37.5" 43.5" 64.5" 2 64.5" TGL2 Ground Bars2,3 2 3 4 2 4 2 4 2 3 4 2 4 2 4 2 3 4 2 4 4

240 Vac, 1 Phase

208/120 Vac, 3 Phase

480/277 Vac, 3 Phase

Aluminum Bus
Voltage 240 Vac, 1 Phase 208/120 Vac, 3 Phase 480/277 Vac, 3 Phase Rating (Amps) No. of Circuits 18 30 42 100-225 18 30 42 100-225 18 30 42 Feed-thru Product Number1 AQU1182RCXAXT1 AQU1302RCXAXT1 AQU1422RCXAXT1 AQU3182RCXAXT1 AQU3302RCXAXT1 AQU3422RCXAXT1 AEU3182RCXAXT1 AEU3302RCXAXT1 AEU3422RCXAXT1 Box/Front Height 37.5" 43.5" 49.5" 37.5" 43.5" 49.5" 37.5" 43.5" 49.5" TGL2 Ground Bars2,3 2 3 4 2 3 4 2 3 4

100-225

TGL20 Ground Lug Quantities


No. of TGL20s Required by Panel Rating Interior Type Main Lug Only Main Lug and Feed-thru Main Breaker Only Main Breaker and Sub-feed Main Breaker and Feed-thru 100A-225A 1 2 1 1 2 400A 1 2 1 1 2 600A 2 4 1 1 3

1For CSA label, add "M8" suffix to product number. 2For TGL20 ground lug quantities, see TGL20 Ground Lug Quantities table above. 3For isolated ground, use EGS12. When using the EGS12, 3, 5 and 7 ground lugs

(TGL20s) are required for 18, 30 and 42 circuits respectively.

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-13

Panelboards
A-Series Panelboards
Pro-Stock, Unassembled Lighting Panels

Section 9

2 Select Box

Select a box of the correct height (see Step 1). Boxes come with blank endwalls. If endwalls with knockouts are required, also order knockout endwall kit AKEW2, List Price $21.00, GO-134B.
NEMA 1 Box Height 31.5" 37.5" 43.5" 49.5" 64.5" 76.5" 20" Wide Product Number1 AB31B AB37B AB43B AB49B AB64B AB76B 30" Wide Product Number1 AB31BW AB37BW AB43BW AB49BW AB64BW AB76BW NEMA 3R/12 20" Wide Product Number1 AB313 AB373 AB433 AB493 AB643 AB763

NEMA 1

1For CSA label, add "A" suffix to product number.

NEMA 3R/12

3 Select Front

Select a front of the correct height (see Step 1).


Standard (20" wide) Front Height 31.5" 37.5" 43.5" 49.5" 64.5" 76.5" Flush1 AF31F AF37F AF43F AF49F AF64F AF76F Surface1 AF31S AF37S AF43S AF49S AF64S AF76S Door Within Door (20" wide) Flush1 AF31FP AF37FP AF43FP AF49FP AF64FP AF76FP Surface1 AF31SP AF37SP AF43SP AF49SP AF64SP AF76SP Front Hinged To Box (20" wide) Flush1 AF31FD AF37FD AF43FD AF49FD AF64FD AF76FD Surface1 AF31SD AF37SD AF43SD AF49SD AF64SD AF76SD Standard (30" Wide) Flush1 AF31FW AF37FW AF43FW AF49FW AF64FW AF76FW Surface1 AF31SW AF37SW AF43SW AF49SW AF64SW AF76SW

1For CSA label, add "A" suffix to product number.

Door Within Door

Standard

Front Hinged to Box

9-14

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
A-Series Panelboards
Pro-Stock, Unassembled Lighting Panels
4 Select Main and/or Sub-feed Breaker Kit

Section 9

Select main breaker kit appropriate for your interior type (see Step 1), amp rating and kAIC rating. If a sub-feed breaker is required, repeat the selection process. Note: 400A and 600A breaker kits cannot be used for sub-feed applications in Pro-Stock panelboards. For additional details and pricing, see Section 4 of the BuyLog.

Interior Type

Product Number1 MB612 MB614 MB512 MB332 MB332 MB332WB MB613 MB616 MB513 MB516 MB233 MB233WB MB23325 MB2332WB5 MB333 MB333 MB333WB MB423 MB426 MB133 MB133 MB133WB MB233 MB233WB MB23325 MB2332WB5 MB333 MB333 MB333WB

Rating Amps 100 100 225 400 600 600 100 100 225 400 225 225 400 400 400 600 600 100 100 150 150 150 225 225 400 400 400 600 600

No. of Poles 2 4 2 2 2 2 3 6 3 6 3 3 65 65 3 3 3 3 6 3 3 3 3 3 65 65 3 3 3

10 THQB (2) THQB TQD

14

22

Breaker Rating (kAIC) 25 65

100

200

AQU1: 240 VAC 1 Phase

THHQB (2) THHQB THQD SGHA SGHA SGHA+Kit SGLA SGLA SGPA SGPA

AQU3: 208/120 VAC, 3 Phase

THQB (2) THQB TQD (2) TQD

THHQB (2) THHQB THQD (2) THQD SFHA SFHA+Kit 2nd SFHA 2nd SFHA+Kit SGHA SGHA SGHA+Kit TEY (2) TEY TED2 SFLA SFPA

SGLA SGLA

SGPA SGPA

AEU3: 480/277 Vac, 3 Phase

THED SEHA SEHA+Kit SFHA4 SFHA+Kit4 2nd SFHA4 2nd SFHA+Kit4 SGHA4 SGHA4 SGHA+Kit4

SELA SFLA

SEPA SFPA

SGLA SGLA

SGPA SGPA

1Breaker not included except for WB kits (where product number ends in WB). WB kits include a breaker, mounting kit and load-side lugs. Rating plugs must be

ordered separately.
2Actual breaker rating is 18kAIC. 3Actual breaker rating is 30kAIC. 4Actual breaker rating is 35kAIC. 5To achieve 6 poles of subfeed, the MB233WB or MB233 kit is also required. 6 poles of subfeed only work with 400A and 600A interiors.

MB513 Breaker Kit

MB516 6-Pole Breaker Kit

MB233WB WB Breaker Kit

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-15

Panelboards
A-Series Panelboards
Pro-Stock, Unassembled Lighting Panels
5 Typical Main Breakers

Section 9

Skip Step 5 if you selected a main breaker kit ending in WB no breaker is required. To correlate breaker types with the kAIC rating in specific panelboards, see the table for Step 4. For more rating details, see A-Series Lighting Panels Rating Series Labels (DEH-40007).
Breaker Poles Current Sensor Product Number SEDA36AT0100 SEHA36AT0100 SELA36AT0100 SEPA36AT0100 SEDA36AT0150 SELA36AT0150 SEPA36AT0150 Amp Rating

All TQD and Spectra main breakers require line-side lugs. For TEY and THQB main breakers, see branch breakers tables in Step 7.

Digital, Solid State Spectra RMS Breakers (3-pole) For use with appropriate main breaker kit (see Step 4).
Rating Plug1 Product Number Terminal Lugs for Front Connection2 Product Number Wire Range (Cu/Al)

100

100 110 125 150 70 90 100 110 125 150 175 200 225 125 150 175 200 225 250 300 350 400 250 300 350 400 500 600

SRPE100A100 TCAL18 SRPE150A110 SRPE150A125 SRPE150A150 SRPF250A70 SRPF250A90 SRPF250A100 SRPF250A110 SRPF250A125 SRPF250A150 SRPF250A175 SRPF250A200 SRPF250A225 SRPG400A125 SRPG400A150 SRPG400A175 SRPG400A200 SRPG400A225 SRPG400A250 SRPG400A300 SRPG400A350 SRPG400A400 SRPG600A250 SRPG600A300 SRPG600A350 SRPG600A400 SRPG600A500 SRPG600A600 #12-3/0

150 3

250

SFLA36AT0250 SFPA36AT0250

TCAL29

#8-350 MCM

400

SGHA36AT0400 SGLA36AT0400 SGPA36AT0400 SGHA26AT0400 SGLA26AT0400 SGPA26AT0400 SGLA36AT0600 SGPA36AT0600 SGLA26AT0600 SGPA26AT0600

TCLK365 Al: (2) 2/0-500 MCM or (1) #6-600 MCM Cu: (2) 2/0-400 MCM or (1) #8-600 MCM

400

TCLK265

600

TCLK365

600

TCLK265

1Any rating plug within a given current sensor group may be paired with any breaker in that group. 2Except for WB kits, lugs must be ordered separately for Spectra breakers. All Spectra breakers also require an appropriate rating plug.

Main or subfeed breakers for use with AQ panels (208/120 Vac 3-phase or 240 Vac single phase). See Step 4.
2-pole 10kAIC Amp Rating 100 125 150 175 200 225 250 300 350 400 Product3 Number TQD22100X2 TQD22125X2 TQD22150X2 TQD22175X2 TQD22200X2 TQD22225X2 22kAIC Product Number THQD22100X2 THQD22125X2 THQD22150X2 THQD22175X2 THQD22200X2 THQD22225X2 TJD422250L2 TJD422300L2 TJD422350L2 TJD422400L2 10kAIC Product3 Number TQD32100X2 TQD32125X2 TQD32150X2 TQD32175X2 TQD32200X2 TQD32225X2 3-pole 22kAIC Product Number THQD32100X2 THQD32125X2 THQD32150X2 THQD32175X2 THQD32200X2 THQD32225X2 TJD432250L3 TJD432300L3 TJD432350L3 TJD432400L3

Main or subfeed breakers for use with AE panels (480/277 Vac 3-phase). See Step 4.
3-pole
Amp Rating 100 125 150 175 200 225 250 300 350 400 18kAIC Product Number TED134110WL TED134125WL TED134150WL 22kAIC Product Number THED134110WL THED134125WL THED134150WL 30kAIC Product Number MB233WB MB233WB MB233WB MB233WB MB233WB MB233WB TJJ436250L3 TJJ436300L3 TJJ436350L3 TJJ436400L3

3Any load-side lugs on TQD breakers must be removed before assembly. TQD breakers with X2 product number suffix feature line-side lugs only.

9-16

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
A-Series Panelboards
Pro-Stock, Unassembled Lighting Panels
6 Select Main Lug Kit and Accessories

Section 9

Select lug kit(s) for main lug and/or feed-thru applications, if required. (All lugs are suitable for interiors with either copper or aluminum bus.) Also select any accessories required. Main Lug Kits
Standard Lug Type Pressure Amp Rating 225 400 600 225 400 600 225 400 225 400 Product Number MLA1 MLA41 MLA61 MLR1 MLR41 MLR61 MLT1 MLT42 MLA2 MLA61 Wire Range 6-350 MCM 2-600 MCM or (2) 1/0-250 MCM (2) 2/0-500 MCM 4-350 MCM 1-600 MCM (2) 2/0-500 MCM 2/0-300 MCM 250-600 MCM 1-600 MCM or (2) 1/0-250 MCM (2) 2/0-500 MCM Product Number MLA2 MLA62 MLA62 MLR2 MLR61 MLT2 MLT41 Oversized Wire Range 1-600 MCM or (2) 1/0-250 MCM 3/0-800 MCM 3/0-800 MCM 1-600 MCM (2) 2/0-500 MCM 4/0-500 MCM 500-750 MCM1 200% Neutral Product Number NKA NKA42 NKR NKR4 NKT NKT4

Copper Compression Dual Main

1500 MCM Cu, 750 MCM Al. 2For 200% neutral feed-thru, order NKA4FT, (GO-101P). Wire range (2) 2/0 600 MCM or (4) 4-250 MCM.

Accessories
Service Entrance3 Amp Rating 225A 400A 600A Product Number BNDKT BNDKT6 BNDKT6 Description ProCare Kit for Pro-Stock panelboard installation and maintenance ProCare Kit4 Product Number PROCARE

3Service entrance kit includes a bonding strap with hardware and a service entrance

4ProCare Kit includes: (5) filler plate hardware kits, (9) bus stud nuts, (5) MLA1 filler

label.

plates, (2) 225A phase barriers, (2) feed-thru barriers, (1) 400/600A phase barrier, (50) directory cards/rating books, (50) circuit number strips (1-48), (50) circuit number strips (43-84), (5) standard locks and keys, (50) deadfront screws, (10) AQ/AE front hardware kits, (10) AD front hardware kits, (50) service disconnect labels, (50) main labels.

7 Typical Bolt-On Branch Breakers

These tables show typical branch breakers, but do not include all branch breakers that can be used with Pro-Stock panelboards. Branch circuit breakers for use with AQ panels (208/120 Vac 3-phase or 240 Vac single phase)
Amp Rating 15 20 25 30 35 40 45 50 60 70 80 90 100 1-pole Product Number THQB1115 THQB1120 THQB1125 THQB1130 THQB1135 THQB1140 THQB1145 THQB1150 THQB1160 THQB1170 10kAIC 2-pole Product Number THQB2115 THQB2120 THQB2125 THQB2130 THQB2135 THQB2140 THQB2145 THQB2150 THQB2160 THQB2170 THQB2180 THQB2190 THQB21100 3-pole Product Number THQB32015 THQB32020 THQB32025 THQB32030 THQB32035 THQB32040 THQB32045 THQB32050 THQB32060 THQB32070 THQB32080 THQB32090 THQB32100 1-pole Product Number THHQB1115 THHQB1120 THHQB1125 THHQB1130 THHQB1135 THHQB1140 THHQB1145 THHQB1150 THHQB1160 THHQB1170 22kAIC 2-pole Product Number THHQB2115 THHQB2120 THHQB2125 THHQB2130 THHQB2135 THHQB2140 THHQB2145 THHQB2150 THHQB2160 THHQB2170 THHQB2180 THHQB2190 THHQB21100 3-pole Product Number THHQB32015 THHQB32020 THHQB32025 THHQB32030 THHQB32035 THHQB32040 THHQB32045 THHQB32050 THHQB32060 THHQB32070 THHQB32080 THHQB32090 THHQB32100

Branch circuit breakers for use with AE panels (480/277 Vac 3-phase)
1-pole Product Number TEY115 TEY120 TEY130 TEY140 TEY150 TEY160 TEY170 TEY180 TEY190 TEY1100 14kAIC 2-pole Product Number TEY215 TEY220 TEY230 TEY240 TEY250 TEY260 TEY270 TEY280 TEY290 TEY2100 3-pole Product Number TEY315 TEY320 TEY330 TEY340 TEY350 TEY360 TEY370 TEY380 TEY390 TEY3100

Amp Rating 15 20 30 40 50 60 70 80 90 100

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-17

Panelboards
A-Series Panelboards
Pro-Stock, Unassembled Lighting Panels
Pro-Stock Interiors Product Number Structure

Section 9

AEU 1 18 2 RCXAX T1 B4
Interior Type AQU 240 Vac AEU 480Y/277 Vac

Catalog Number Structure

No. of Circuits 18 18 Circuits 30 30 Circuits 42 42 Circuits Max. Amp Rating 2 225A 4 400A 6 600A

Bus B4 Copper Blank Aluminum

Phase 1 1 Phase 3 3 Phase

T1 Feed-thru Blank Non Feed-thru* (requires copper bus [B4])


* For retrofit applications

9-18

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
A-Series Panelboards
Product Options
Enclosure Options BOX EXTENSIONSFor additional end gutter space or conduit skirt applicationssee page 9-20. Equipment GroundsFactory Supplied with Panelboard
Description Field installed kits Standard bonded to box-for each 12 branch positions Copper bonded to box-for each 12 branch positions Standard-isolated/insulated-for each 12 branch positions Copper-isolated/insulated-for each 12 branch positions Main lug for above terminal kits TGL2 TGC2 EGS12 EGC12 TGL20 Product Number

Section 9

AEBG

Optional Equipment Grounds


Description Aluminum Extruded Bonded Copper Extruded Bonded Aluminum Extruded Isolated Copper Extruded Isolated Copper Isolated/Bonded 18GO-101 Product Number AEBG AEBGC AEIG AEIGC ASPGIBC

AEBGC

AEIG

AEIGC

ASPGIBC

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-19

Panelboards
A-Series Panelboards
Accessories Field Installed Kits/Replacement Parts Order By Product Number from Factory Endwall Kits Field installed. For standard 20"w x 5.81"d boxes.
Product Number ABEW2 AKEW2 Description Blank Knockout Qty. 1 1

Section 9

Panelboards Parts
Description Directory Card Replacement Lock with Std. Key Replacement Lock with GE75 Key Additional Keys for Above Lock Circuit Numbering Strips1-48 49-84 85-126 Adhesive Backed Lamicoid Nameplate 3/4 in. x 3 in. Metal Directory Card Holder Directory Card Holder Delta Hi-leg Conversion Kit, to Add B-Phase Plug on AL Panels Bolt on AE/AQ Panels NEMA 3R/12 Tamper Proof Tork Screw Kit 2P to 3P TQD Conv. Kit 2P to 3P SF Conv. Kit for horizontal subfeed AD 25 to 65 kAIC Barrier kit Service Entrance Kit 2 wire Relay Kit Yale Lock Kit Corbin Lock Kit 2-3 pole TQD Mechanical Interlock AQ/AL/AE Rail Bracket Front Flush Adjust Kit AE Front Mounting Kit AQ/AL Front Mounting Kit AD Front Mounting Kit Front Hinge to Box Mounting Kit Front Extension Mounting Kit
1

Product Number 139C5612P3 569B737P1 569B737P2 569B737P5

Replacement Lock with Standard Key

Replacement Lock with GE75 Key

Box Extensions
569B806G1 569B806G2 569B806G3 315A7190P1 139C5491G1 139C5491P4

Bolts to A-SERIES box with or without box endwall in place. Extensions can be combined to obtain lengths greater than 18 and 24 inches.
Box Width and Depth Box Mounting Box Extension Length (Inches) 9 Box Extension Product Number ABX2509F ABX2518F ABX2524F ABX2509S ABX2518S ABX2524S ABX2531S ABX2537S ABX2543S ABX2549S ABX2555S ABX2564S ABX2576S ABX3518F ABX3524F ABX3518S ABX3524S ABX3718F ABX3724F ABX3718S ABX3724S

APHBL APHBQ NEMATRX ASP2PTQD3P ASP2PTFJ3P ASP25AD65KA ASPSERENT ASP2WRelay ASPYALE47 ASPCORBNTEU1 TQDFM1 ASPAQLEBKT ASPFLUSHADJ 139C5720G3 139C5720G6 139C5720G9 139C5700G6 139C5700G11
1

Flush

18 24 9 18 24

20 x 5.81 Surface

31 37 43 49 55 64 76 Flush 18 24 Surface 18 24 Flush 18 24 Surface 18 24

30 x 5.81

30 x 7.81

Included in factory assembled panelsAD panels with Spectra branch breakers.

Permanent Circuit Number Kits


Product Number AQ, AL, AE APN48 APN84 APN126 AD APN48AD APN84AD APN126AD Description Nos 1-48 Nos 43-84 Nos 85-126

Box Extensions Covers Only 10 covers per kit.


Description 9" Covers Surface 9" Covers Flush 18" Covers Surface 18" Covers Flush 64" to 76" Covers Surface 64" to 76" Covers Flush Product Number ASPABX09S ASPABX09F ASPABX18S ASPABX18F ASPABX20S ASPABX20F

9-20

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
A-Series Power Panels
Features Symmetrical design, no required top or bottom mountings Single-piece deadfront no filler plates needed Smaller, lighter panel than Spectra Series panelboards Easy-to-install galvanized enclosures with removable endwalls Ready-to-install hinged trim options Branch-bus direct connection Up to 600A breaker mounted as a branch device Deeper (8"), wider (30") A-Series box to accommodate larger wire sizes Double branched 150A (ED/SE) and 225A (QD) breakers Vertically mounted main circuit breakers in 800A Captive hardware on branch breakers Staggered, center-mounted, larger frame breakers (SG, SF) for easy installation Bus-connected TVSS for maximum surge protection Narrow design to minimize footprint Enclosure available in NEMA Type 1, Type 3R/12, Type 4/4X

Section 9

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-21

Panelboards
A-Series Power Panelboards
Type AQP
Service Information: 1P, 3W-240/120 Vac 3P, 3W-240 Vac 3P, 4W-208/120 Vac Fully Rated-65kAIC at 240 Vac Series Rated-200kAIC at 240 Vac Mains Breakers: 125-800A: SG, SK MainLug: 600-800A Branch Breakers (Bolt-on): 15A-100A (1P, 2P, 3P): QB Double Branch- TQD, SE Center-Mounted- SF, SG Enclosures Length-25.5, 31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5 Width-30 Depth-8

Section 9
Type ADP
Service Information: 1P, 3W-240/120 Vac 3P, 3W-240 Vac 3P, 4W-208/120 Vac, 480/277 Vac Fully Rated-100kAIC at 480 Vac Series Rated-100kAIC at 480 Vac Mains Breakers: 125-800A: SG, SK MainLug: 600-800A Branch Breakers (Bolt-on): 15A-100A (1P, 2P, 3P): FB Breakers 15A-100A (1P, 2P, 3P): THED Breakers 15A-150A (3P): THED Breakers Double Branch-TED, SE Center-Mounted-SF, SG Enclosures Length-25.5, 31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5 Width-30 Depth-8

Type AEP
Service Information: 1P, 3W-240/120 Vac 3P, 3W-240 Vac 3P, 4W-208/120 Vac, 480/277 Vac Fully Rated- 18kAIC at 480/277 Vac, 65kAIC at 240Vac Series Rated- 100kAIC at 480 Vac, 200kAIC at 240 Vac Mains Breakers: 125-800A: SG, SK MainLug: 600-800A Branch Breakers (Bolt-on): 15A-100A (1P, 2P, 3P): TEY, TEYF Double Branch- TED, SE Center-Mounted-SF, SG Enclosures Length-25.5, 31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5 Width-30 Depth-8

9-22

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
A-Series Panelboards Branch Circuit Monitoring
This panelboard provides branch circuit reporting capabilities in a Type AQ or AE panelboard. It delivers valuable branch usage data, similar to the Spectra Integrated Submetering Panelboard, but in the A-Series platform. Via a building automation system, users can tap this data to analyze usage and identify potential costsavings measures, create load based cost allocation billing, and head off potential problems before they occur.

Section 9

Features Accuracy: Revenue Class, +-0.5%; IEC 62053-21 Class 1, ANSI C12.1-2008 Ability to report volts, amps, power, and energy for each circuit Monitors 42 circuits (and mains as an option) with one product 4 user-configurable alarm threshold registers improve load management Built-in ability to set the orientation and numbering of the circuits 1/4 amp to 100 amp monitoring the widest dynamic range in the industry 1, 2, 3 pole breaker support 5 year warranty Modbus RTU via RS485 communications

References
DEA-539 for additional information Speedi for configuration/quotation purposes

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-23

Panelboards
Spectra Series Panelboards
MCCB and Fusible Mains and Feeders Service Information: 600 Vac maximum 250 Vdc maximum 1ph-3w, 3ph-3w/4w Mains: 1200 A maximum main lugs, circuit breaker, or fusible switch Branches: 15-1200 Circuit Breakers 30-1200 (2P, 3P) Fusible Switch Fuse: Not Included Fuse Provisions: 30-600 Amp Units: Class R1 800-1200 amp units: Class L2 Features Main bus, 250-1200 amp, copper or aluminum Wide, easy-to-install galvanized enclosures with removable endwalls 5 box widths simplify installation and design Enclosures available in NEMA Type 1, Type 3R/12, Type 4/4X Integrated TVSS for maximum surge protection Optional door-in-door or front-hinged-to-box construction Reduced density copper or aluminum bus 200% rated neutrals available Vertically mounted main circuit breakers available Branch-bus direct connection Captive hardware on branch breakers Front accessible main lug assembly Process control unit in plug-in style Spectra MVT breaker option for main/branch breakers 100% rated breakers available Individual breaker cover plates Bolt On Service Information: 1P, 3W-600/347 Vac 3P, 4W-600/347 Vac Fully Rated- 200KAIC at 480/277 Vac Series Rated- 200KAIC at 480/277 Vac Mains Breakers: 250A-1200A: SF, SG, SK, FG

Section 9

Branch Breakers (Bolt-on): Double Branch-SE, SF, SG, FG, FB, TEY, TEB, TQD Breakers Center-mounted-SK Breakers Plug In Service Information: 1P, 3W-600/347 Vac 3P, 4W-600/347 Vac Fully Rated-200KAIC at 480/277 Vac Series Rated-200KAIC at 480/277 Vac Mains Breakers: 250A-1200A: SF, SG, SK, FG Branch Breakers/Switches (Plug In): Double Branch-SE, SF, SG, FG, FB, TEY, TEB, TQD Breakers Center-mounted- SK Breakers 30A-1200A Fused Switches (R, J, H, K, T Fuses)

9-24

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Fusible Switches Load and Interrupting Ratings
Short Circuit RatingsFusible Switch Units (Plug-In Only)
Available Amp Rating 30-600 30-600 Maximum Short-Circuit Rating in Sym. rms Amps 10,000 200,000 50,000 K 30-600 100,000 200,000 Rejection means available in two forms L 800-1200 200,000 600 Fast-acting mains & feeders Time-delay motor starting current limiting R T 30-600 100-600 100,000 200,000 200,000 250/600 250/600 Dual element rejection means, motor starting current limiting Fast-acting small physical size mains & feeders, current limiting
1

Section 9

Maximum Horsepower Ratings1 ADS Fusible Switch


Volts, ac Volts, dc 3-Pole 600 240 480 600 2-Pole 125 2-Pole 250 Rating in Amps1 2-Pole 120 240 480

UL Class H J

Max. Voltage 250/600 600

Application One-time general purpose Fast-acting rejection sizing mains & feeders, current limiting Dual element no rejection means, motor starting current limiting

With Standard Fuses 30 60 1/2 1 1/2 1 1/2 3 7 1/2 15 3 5 10 25 3 10 15 30 3 7 1/2 15 25 50 75 5 15 25 50 100 150 7 1/2 15 30 60 125 200 2 5 5 10 20 40 50 50

250/600

100 200 400 600

With "Time-delay" Fuses 30 60 100 200 400 600 2 3 3 10 15 15 7 1/2 20 30 50 10 25 40 50 7 1/2 15 30 60 125 200 15 30 60 125 250 400 20 50 75 150 350 500 3

Panelboard Terminal Lugs - Main Lugs2 and Neutral Incoming Lugs Lighting Panels (A-Series)
Panelboard Max. Main Bus Rating in Amps 125 225 AL AQ AE AD 400 600 800
2

Ratings are based on latest revision of the National Electrical Code Article 430. Horsepower ratings for switches with Standard Class H fuses are based on one-time fuses having minimum time-delay. When time-delay fuses are used, the horsepower ratings are maximum for the switches.

Terminal Lugs (Cu-Al) Wire (Cu-Al) No. Per 1 1 1 2 1 2 2 2 No. Per Lug 1 1 1 Range #14-2/0 #6-350kcmil #4-600kcmil or 1/0-250kcmil 2/0-500 mcm 3/0-500 mcm

Spectra Optional Main Lug Terminations


Max. # Lugs Per Phase # Wires Per Lug CU/AL Mechanical #6-350 kcmil #2-500 kcmil #2-600 kcmil 3/0 750 kcmil CU/AL Compression3 1/0 2/0 1 1 1 1 1 1 1 1 1 1 1 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 8 8 8 8 8 8 8 8 8 8 8 1 2 2 2 2 2 2 2 2 2 2 2 4 4 4 4 800A 1200A 21" 800A 1200A 27"

Types

250-600A

Additional lug sizes available using oversize items.

200% Neutral Lugs 125A - (2) - #142/0 225A - (2) - #6250 MCM 400A - (2) - #4600 MCM 600A - (4) - #4600 MCM Branch Neutral Lugs Small Holes #14#4 Large Holes #142/0 Column Type Panels
Panelboard Max. Main Bus Rating in Amps 100 225 Terminal Lugs (Cu-Al) Wire (Cu-Al) No. Per 1 1 No. Per Lug 1 1 Range #6-2/0 #6-350kcmil

3/0 4/0 250 kcmil 300 kcmil 350 kcmil 400 kcmil 500 kcmil 600 kcmil 750 kcmil

3 Not available on 19" main lug module.

Types ALC AQC AEC

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog dr_panelbd_13_6b

9-25

Panelboards
Spectra Series Panelboards
Fusible Switches Load and Interrupting Ratings
Spectra Series Neutral Kits

Section 9

Includes mechanical lugs and bonding strap. 250 to 600A neutral kits can be converted to dual main version by doubling the main lug quantity using lug kits (see Accessories). Main lug on neutral kit can be converted to compression main using AMKP lug kit.
Standard Neutral (Single Main Lug) 4 Amps Product Number List Price, GO-103C Accepts Wire Qty. 2 ( Main) 16 250 ANKN400 $237.00 5 24 2 ( Main) 16 400 ANKN400 $237.00 5 24 8 ( Main) 9 600 ANKN120 $555.00 10 10 8 ( Main) 9 800 ANKN120 $555.00 10 10 8 ( Main) 9 1200 ANKN120 $555.00 10 10
4

Dual Main Neutral 5 Accepts Wire Size (Cu/Al) #2 - 600kcmil #14 - 2/0 #6 - 300kcmil #14 - #4 #2 - 600kcmil #14 - 2/0 ANKN120 #6 - 300kcmil #14 - #4 #2 - 600kcmil #14 - 2/0 ANKN120 #6 - 300kcmil #14 - #4 #2 - 600kcmil #14 - 2/0 ANK800D #6 - 300kcmil #14 - #4 #2 - 600kcmil #14 - 2/0 ANK120D #6 - 300kcmil #14 - #4 $757.00 10 4 #6 - 300kcmil #2 - 500kcmil $664.00 10 4 8 ( Main) 8 #6 - 300kcmil #2 - 500kcmil #2 - 500kcmil #14 - 2/0 $555.00 10 10 8 ( Main) 8 #6 - 300kcmil #14 - #4 #2 - 500kcmil #14 - 2/0 $555.00 10 10 8 ( Main) 9 #6 - 300kcmil #14 - #4 #2 - 600kcmil #14 - 2/0 ANKN400 $237.00 Product Number List Price, GO-103C Accepts Wire Qty. 2 ( Main) 16 5 24 8 ( Main) 9 Accepts Wire Size (Cu/Al) #2 - 600kcmil #14 - 2/0 #6 - 300kcmil #14 - #4 #2 - 600kcmil #14 - 2/0

For 3ph, 4W single-section panelboards, use a standard neutral. 5 For 3ph, 4W multi-section panelboards, use a standard neutral on the last section, and a dual main neutral on the first and middle sections.

Breaker Side Gutter Space


EY, QB T(H)E, SE, FC, FE T(H)QD T(H)J, SF SG, FG FE T(H)J, SF SG, FG EY, QB T(H)E, SE, FC, FE T(H)QD T(H)J, SF SG, FG

A B C D E J F G H

ENCLOSURE SIDE WALL

smallest, lowest amperage furthest from the main incoming. The spaces, if any, will follow after the breakers. All main breakers are mounted horizontally and incoming lugs are, as a standard and if not specified, always oriented to the left gutter regardless if top or bottom feed. If 2 or more large branch breakers (SK, SG single mounted) are supplied with the board then the factory will start the first breaker with the lugs to the right and the second breaker with lugs to left and will continue staggering them until all have been installed. If any further clarification is needed, please contact your local GE representative.
Enclosure Width Letter Reference A 27 7.88 5.75 5.63 N/A N/A 8.88 8.13 N/A 31 9.88 7.75 7.63 5.50 N /A 10.88 10.13 N /A 36 12.38 10.25 10.13 8 6.38 13.38 12.63 N/A 40 14.38 12.25 12.13 10 8.38 15.38 14.63 12.63 44 16.38 14.25 14.13 12 10.38 17.38 16.63 14.63

T(H)K, SK

B C D E

ALL DIMENSIONS ARE FROM FACE OF LUG, SHOWN IN INCHES AND .250 Single mounted devices as branch or main Breakers are arranged, as a standard and if not specified, with largest and highest amperage closest to main incoming and the

F G H J

Breaker not available at time of printing

9-26

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Merchandisable Kits and Sizing Information
Spectra Series Type ANKN/ANK/ANKT Neutral Kits
Amps (N = Neutral, GF = Ground Fault) Box Width 27-36" 27-36" 27-36" 36" 36" 36" 36" 36" 27-44" 27-44" 27-44" 27-44" 27-44" 36-44" 36-44" 27-44" 36-44" 36-44" 36" 40" 44" 36" 40" 44" 27-44" 27-44" 27-44" 36-44" 36-44" 27-44" 36-44 36" 40" 44" 36" 40" 44" 31-44" 31-44" 31-44" 36-44" 36-44" 31-44" 36-44" 36" 40" 44" 36" 40" 44" 31-44" 36-44" 31-44" 31-44" 31-44" 31-44" 31-44" 36-44" 36-44" 31-44" 36-44" 36" 40" 44" 36" 40" 44" Main Single/Dual Single Dual Single Dual Single/Dual Single Dual Single Single Single Dual Dual Single Dual Single Single Single/Dual Single Single Single Dual Dual Dual Single/Dual Single Dual Single Dual Single Single Single Single Single Dual Dual Dual Single Single Dual Single Dual Single Single Single Single Single Dual Dual Dual Single Single Single Single Single Dual Dual Single Dual Single Single Single Single Single Dual Dual Dual Lug Type Mechanical Mechanical Mechanical Crimp Main & Feeders Crimp Main & Feeders Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Crimp Main & Feeders Crimp Main & Feeders Mechanical Crimp Main, Mech. Feeders Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Crimp Main & Feeders Crimp Main & Feeders Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Crimp Main & Feeders Crimp Main & Feeders Mechanical Crimp Main & Feeders Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Crimp Main & Feeders Mechanical Mechanical Mechanical Mechanical Mechanical Crimp Main & Feeders Crimp Main & Feeders Mechanical Crimp Main & Feeders Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Ground Fault No No No No No No No No No No No No No No No Yes Yes No No No No No No No No No No No No Yes No No No No No No No No No No No No Yes Yes No No No No No No Yes Yes No No No No No No No Yes Yes No No No No No No

Section 9

Product Number ANKN4001 ANK2502 ANK250D2 ANK250C ANK250DC ANKN1201 ANKT362502 ANKT36250D2 ANKN4001 ANK4002 ANKCU4004 ANKN1201 ANK400D2 ANK400C ANK400DC ANK400GF ANK400GFCM ANKN1201 ANKT364002 ANKT404002 ANKT444002 ANKT36400D2 ANKT40400D2 ANKT44400D2 ANKN1201 ANK6002 ANK600D2 ANK600C ANK600DC ANK600GF ANKN1201 ANKT366002 ANK406002 ANK446002 ANKT36600D ANKT40600D ANKT44600D ANKN1201 ANK8002 ANK800D3 ANK800C ANK800DC3 ANK800GF3 ANK800GFC3 ANKT368003 ANKT408003 ANKT448003 ANKT36800D3 ANKT40800D3 ANKT44800D3 ANK100GF3 ANK100GFC3 ANKN1201 ANKNCU1204 ANK1202 ANK120D3 ANKNCU120D4 ANK120C ANK120DC3 ANK120GF3 ANK120GFC3 ANKT361203 ANKT401203 ANKT441203 ANKT36120D3 ANKT40120D3 ANKT44120D3

250A Single & Dual

250A 200%N

400A Single & Dual

400A GF

400A 200%N

600A Single & Dual

600A GF

600A 200%N

800A Single & Dual

800A GF

800A 200%N

1000A GF

1200A Single & Dual

1200A GF

1200A 200%N

1Wire range #2AWG through 600 kcmil. 2Wire range above 600 kcmil. 3These neutrals require the 29 inch A gutters in the 75" and 96" high enclosures (75 High-23X or 96 High-38X) 4Material = Copper main lugs, copper feeder.

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-27

Panelboards
Spectra Series Panelboards
Terminal Lugs
Spectra Series Main Lugs Top or Bottom Feed 240 Vac and 600 Vac, 200-1200 Amperes Main Lug Kits (Factory Installed and/or Merchandise Panelboards)

Section 9

Kit bolts directly to interior bus bars (either APN Plug-In Style or APNB Bolt-On Style). Can be used for feed-through lug application by replacing standard cover plate with AFL feed-through cover plate kit (See Accessories). F suffix indicates all AFPML cover plates are included to fit applicable box widths. If cover plates are not necessary, remove the F suffix. For 2 pole applications, replace the third digit or numeral 3 in the product number with the number 2. Aluminum mechanical lugs can be converted to copper by replacing the first from last digit from an A to a C.
Standard Main Lug Kit (Mechanical Lugs) Module X Height 4X 4X 4X 4X 4X 4X 4X 4X 4X Lugs. Incl. Per Phase 1 1 1 1 1 1 1 1 1 Wires Per Lug 2 2 4 2 4 4 8 4 8 Cover Plate Kit Included Product Number AFPML4X AFPML4X AFPML4X AFPML4X AFPML4X AFPML4X AFPML4X AFPML4X AFPML4X Min. Box Width 27" 27" 27" 27" 27" 31" 36" 31" 36"

Main Amps 250

Single or Dual Configuration Single & Dual Single Dual

Product Number AMB3600MAF AMB3600MAF AMB3120MAF AMB3600MAF AMB3120MAF AMB3120MAF AMB3120DMAF AMB3120MAF AMB3120DMAF

Wire Range (Cu/Al1 ) 8-500kcmil(1) 2/0-600kcmil(1) 8-500kcmil(1) 2/0-600kcmil(1) 2/0-600kcmil(4) 8-500kcmil(1) 2/0-600kcmil(1) 2/0-600kcmil(4) 2/0-600kcmil(4) 2/0-600kcmil(8) 2/0-600kcmil(4) 2/0-600kcmil(8)

400

600

Single Dual

800

Single Dual

1200
1

Single Dual

Copper lugs can only be used with copper wire

.
Compression Main Lug Kit

Main Amps 250

Single or Dual Configuration Single Dual

Module X Height 6X 6X 6X 6X 6X 6X 6X 6X 6X 6X

Product Number AMB3250CAF AMB3250DCAF AMB3600CAF AMB3600DCAF AMB3600CAF AMB3600DCAF AMB3800CAF AMB3800DCAF AMB3120CAF AMB3120DCAF

Lugs. Incl. Per Phase 1 2 2 4 1 4 3 6 4 8

Wires Per Lug 2 1 1 1 2 1 1 1 1 1

Wire Range (Cu/Al) 350 kcmil 350 kcmil 500 kcmil 500 kcmil 500 kcmil 500 kcmil 500 kcmil 500 kcmil 500 kcmil 500 kcmil

Cover Plate Kit Included Product Number AFPML6X AFPML6X AFPML6X AFPML6X AFPML6X AFPML6X AFPML6X AFPML6XW AFPML6X AFPML6XW

Min. Box Width 36" 36" 36" 36" 36" 36" 36" 36" 36" 36"

400

Single Dual

600

Single Dual

800

Single Dual

1200

Single Dual

Provisional Main Lug Kit Main Amps 250 Single or Dual Configuration Single Dual 400 Single Dual 600 Single Dual 800 Single Dual 1200 Single Dual Module X Height 6X 6X 6X 6X 6X 6X 6X 6X 6X 6X Product Number AMB3120NF AMB3120NF AMB3120NF AMB3120NF AMB3120NF AMB3120NF AMB3120NF AMB3120DNF AMB3120NF AMB3120DNF Max. Wires Per Phase 4 4 4 4 4 4 4 8 4 8 Cover Plate Kit Included Product Number AFPML6X AFPML6X AFPML6X AFPML6X AFPML6X AFPML6X AFPML6X AFPML6XW AFPML6X AFPML6XW Min. Box Width 36" 36" 36" 36" 36" 36" 36" 36" 36" 36"

9-28

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
PCU Selection Order from the Customer Service Center Available in Spectra Plug-in Only Spectra Series PCU Selection Guide (Ref DET-104) Specify Overload Relay Amps (Included w/PCU) Description: 15hp max, 22A, 600V max Configuration: 3PH, 3W, & ground; all units are 4X height, 120V control.
Pilot Device Yes Yes No Mount Double Single Double Product Number1 APCU151FNDPD** APCU151FNDPSX* APCU151FNDND**
2

Section 9

Spectra PCU Control Power Transformer Kits One kit required per panel unless an external, 120VAC is brought into the panel.
Continuous kVA .200 .300 .200 .300 .200 .300 Primary Voltage 2 600 600 480/240 480/240 208 208 Capacity Standard Extra Standard Extra Standard Extra Product Number APCUCKA200 APCUCKA300 APCUCKB200 APCUCKB300 APCUCKC200 APCUCKC300

No Single APCU151FNDNSX* 1Replace * with required overload range from table.

Secondary voltage is 120Vac.

PCU Overload Selection


* B C D F G H J K L M N P S T X Overload Range 0.16-0.26A 0.25-0.41A 0.40-0.65A 0.65-1.1A 1.0-1.5A 1.3-1.9A 1.8-2.7A 2.5-4.1A 4.0-6.3A 5.5-8.5A 8.0-12.0A 10.0-16.0A 14.5-18.0A 17.5-22.0A BLANK

Spectra PCU Kits


Description Spectra PCU Pilot Light Option (Kit includes red and green pilot lights) Spectra PCU Wiring Kit (Optional kit for remote wiring) Spectra PCU Expansion Kit to expand or rebuild PCU units) Spectra PCU Blank Cans (Provides space for future PCU starters, other devices) 4X 7X Product Number APCUKPLT APCUWK APCUEKAF (left side) APCURKAF (right side) APCUDCAN4X APCUDCAN7X

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-29

Panelboards
Spectra Series Panelboards
Interior, Enclosure Options Bus Bars
Description Copper 1000 Amp/sq-in. Main Vertical Bus Silver plated copper in lieu of silver plated aluminum Aluminum 600 Amp/sq-in. Main Bus Density Reduces current density from 750 amps/sq-in. to 600 amps/sq-in. Copper 800 Amp/sq-in. Main Bus Density Reduces current density from 1000 amps/sq-in to 800 amps/sq-in.

Section 9

Equipment Ground Bars Spectra grounding kits are sized according to the number of panel circuits (one per circuit or space).
Description Bondable to boxincludes bonding strap and main terminal Insulated/isolatedincludes main terminal

Enclosures (Box)
Description Painted/Increased Gage One option provides 12 gage box painted ANSI 61 gray (not available separately) NEMA 3R NEMA 12

Locking Devices
Frame Style Description Product Number GOSched.

NEMA 4X Stainless Steel Wide Box (increased gutter space) To increase to 31" from 27" box To increase to 36" from 31" box

Padlocking Device (single padlock) Q1 E FC THQB, THHQB TEY FCS, FCV, FCN, FCH, FCL, FCPF TEB, TED, THED SE, E SED, SEH, SEL, SEP FE QD SF, F SFH, SFL, SFP SG FG SGD, SGH, SGL, SGP FGV, FGN, FGH, FGL, FGP, FGPF Description FES, FEV, FEN, FEH, FEL, FEPF TQD, THQD THP100 TEYPLD1 FCPLD TEFPLD1 TLC1PLD1 SEPLD Breaker not available at time of printing
4

137A 135B 135S 135B 135B 135S

To increase to 44" from 40" box To increase to 44" from 36" box Narrow Box 4 To decrease to 27" from 36" box (circuit breakers only) To decrease to 36" from 44" box Box skirt 12" high Touch-up Paint ANSI 61 gray, 12 oz. can

TQDPLD1 TLC4PLD1 SEPLD SGPLD FGPLD SKPLD

137A 135B 135S 135S

Narrow box option limited to panels with maximum 600-amp circuit breaker feeders and 400-amp fusible feeders with T or J fuse clips. This option single branches some double branched devices and may result in additional sections. See page 9-33 and 9-34 for sizing information.

Fronts
135S 135S

SK, K 1000 Amp/sq-in. SKH, SKL, Main SKP Vertical Bus Copper Handle Locking (nonpadlocking) Q1 E
1

Silver plated copper in THQB, lieu ofTHHQB silver plated TEB,aluminum TED, THED

Standard Arrangement
THL103 TLD3 137A 135B

27"

31"

36"

40"

44"

4 piece surface only (no door)

Optional regular door (27W, surface only) Optional door within a door front Optional front hinged to box surface only
5 6 5,6

Aluminum 600 Main Bus Density Not available for Amp/sq-in. ground fault breakers. Reduces current

density from ApprovedFactory Installed Only Locking Devices EUSERC


Breaker Type

750 amps/sq-in. to 600 amps/sq-in.

Product Number TQDPLD2 FCS, FCV, FCN, FCH, FCL, FCPE TEDPLD2 SEFPLD2 FES, FEV, FEN, FEH, FEL, FEPE SGPLD2 FGV, FGN, FGH, FGL, FGP, FGPE TJKPLD2 SKPLD2

Copper 800 Amp/sq-in. Main Bus Density TQD


FC E150

Specify surface or flush. Not available in 27" wide.

Reduces current density from 1000 amps/sq-in. to 800 amps/sq-in.

Front Modifications (Add to price of front)


Description Lexan Cardholder for fronts with doors Lamicoid Nameplate (1 per panel) Yale 511S Spring Bolt Lock with Rosette Sleeve Corbin 15767 Latch Bolt 3 pt Catch and Vault Handle Permanent Number Tabs #1-49 Permanent Number Tabs #1-99

SE150, SF250 2 FE SG600 FG J600 SK1200


2

Field Installable

9-30

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards

Section 9

TVSS (Transient Voltage Surge Suppression)


Product Number Panel Width X Height Panel Type Surge Current Capability (per mode) 65ka 27" - 44" 7X Plug-in/ Bolt-on 80ka 100ka 27" - 44" 7X Plug-in/ Bolt-on 150ka 200ka

System Voltage 120/208V, 240V Delta, 120/240V Delta, 120/240V Delta, 277/480V, 480V Delta 120/208V, 240V Delta, 120/240V Delta, 120/240V Delta, 277/480V, 480V Delta

ATME

ATHE

*Field installable kits are available for adding to existing boards. *Kits include: TVSS unit, 3 cover sizes, cover mounting brackets and cable. *Add a K to the end of the full Product Number for the kit number.

Energy Management Meters


Product Number EPM2200/ EPM6000/ EPM7000 System Voltage 600/347V 480V 208/120V 600/347V 480V PQM Meter Module 240V 240/120V HI-Leg 208/120V 600/347V 480V PQMII Meter Module 240V 240/120V HI-Leg 208/120V Phase/ Wire 3P 4W/3P 3W 3P 4W/3P 3W 3P 4W 3P 4W/3P 3W 3P 4W/3P 3W 3P 3W 3P 4W 3P 4W 3P 4W/3P 3W 3P 4W/3P 3W 3P 3W 3P 4W 3P 4W N N N Ship Cycle

7X required for panel distribution section mounting Fits in 27", 31", 36", 40" and 44" wide sections

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-31

Panelboards
Spectra Series Panelboards
Spectra Series Integrated Submetering Panelboard

Section 9

Submetering lets you measure and bill energy use (electrical, water, gas) in master-metered commercial and/or residential buildings. Suitable for either new construction or retrofit, the Spectra Series Integrated Submetering Panelboard combines the benefits of a multi-tenant digital meter with a reliable GE Spectra Series panelboard. Save Valuable Real Estate GEs fully-integrated solution maximizes valuable real estate by combining meters, current transformers, communications and overload protection into a single UL Listed, factory-assembled panel. It requires only a fraction of the space needed for traditional modular metering. Lower Construction Costs Because this panelboard requires no special communications wiring, youll reduce wire, conduit and installation costs. Individual branch circuit readings communicate through power line communication. All in all, its lighter, more flexible, faster and easier to install than conventional utility metering. Save Time Fully assembled and wired in the factory. Features and benefits Factory assembled/wired internal meters minimize installation labor Factory installed/wired CTs eliminate lengthy wiring runs and wiring errors Small footprint takes up less wall space than separate panels and meters UL Listed Communication: Power line communication standard on all meters Optional Modbus RS-485 communication Up to 48 pulse inputs to capture energy data from other pulsetype energy devices (water, gas, steam meters) IEC optical front panel interface for programming Real-time, per-phase viewing of voltage, current, power factor, phase angle, watts, VARs, VA and frequency Event reporting with time and date stamps Local LCD display Push-button scroll 32-digit liquid crystal display (16 digit x 2 rows) Programmable display scroll and decimal place display Meets ANSI C12.1 and C12.16 revenue certifiable accuracy specifications and Canada (AE-1148) Data can be accessed and collected through third party readbill-collect service or, with Modbus option, the internal EPM 4000 platform utilizes GEs Energy Aggregator billing software, an ideal web-based solution for tracking and monitoring energy consumption. Energy Aggregator allows for the creation of utility rate structures and automatic billing generation. Specifications
Panel Type Certifications Services Voltages Main Amps Main Types Busing Feeder Types Feeder Amps Max Fully Rated AIC Ratings Branch Devices No. of Meter Points/Panel Series Ratings Meter Specifications Spectra Bolt-On (SBO) UL, cUL 1P3W, 3P3W, 3P4W 120/240V, 120/208V, 480/277V 250, 400, 600, 800, 1200 SF, SG, SK Cu TED, TQD, THQD, SE, SF 15-250A 65kAIC 24-2 pole max.; 18-3 pole max. 6, 9, 12, 15, 18, 21, 24 65kAIC Per EPM 4000 Brochure

Typical Dimensions
Tenants 6 12 18/24 Panel Dimensions (inches) 65H x 40W x 11.5D 76H x 40W x 11.5D 89H x 44W x 11.5D

Example of 6-unit Wiring Diagram


A B C

GE Multipoint Meter

9-32

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Renewal Parts
Modular Concept Order all components from Customer Service Center Fig. 1.1 is a front view of a typical Spectra Series fusible panelboard. Fig. 1.2 is also a front view, but with the front (4 piece trim), all fusible switches, and all filler plates removed.

Section 9

Main Lug Module

Front (4 pc)

Box

Interior

Neutral

Side Filler Plate Full Filler Plate Fusible Switch (one side blank) Fusible Switch (Branch) Ground
Note: Incoming conduit location should be in top or bottom ends of enclosure. Must avoid conduit entrances that would interfere with ground and neutral assembly location.

Fig. 1.1

Fig. 1.2

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-33

Panelboards
Spectra Series Panelboards
Renewal Parts
Circuit Breaker Sizing

Section 9

2P 3P 2P 3P 2P or 3P

2P 3P 2P 3P TQD, THQD, TEB, TED THQB, THHQB, TEY, THLC1, THED, SE-Frame, FC (FE Future) TFJ, TFK, THFK, SF-Frame, (FE Future) SG-Frame, FG THLC2, THLC4

27" W 2P or 3P

2P or 3P

2P or 3P

TJD, TJJ, TJK, THJK 2P 31" W 3P 2P SF-Frame Double, FC (FE Future), Branch Adjacent to Switch SF-Frame Single, Branch or Main Adjacent to Switch SF-Frame, TFJ, TFK, THFK

2P 3P 2P

3P

3P 36" W 2P or 3P

3P

3P

THLC2, THLC4

3P

3P 40" W 2P or 3P SG-Frame FG TKM, THKM, SKHA, SKLA 3P 44" W 2P or 3P SKPA TJD, TJJ, TJK, THJK

3P

9-34

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Replacement Boxes and Fronts Order from the Customer Service Center Type APB NEMA 1 Enclosure
Width Height Interior X-Height Modification 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge Product Number APB2765AS APB2765ASP APB2765A APB2765AP APB2765BS APB2765BSP APB2765B APB2765BP APB2765CS APB2765CSP APB2765C APB2765CP APB2775S APB2775SP APB2775 APB2775P APB2789S APB2789SP APB2789 APB2789P APB3165A APB3165AP APB3165AD APB3165ADP APB3165B APB3165BP APB3165BD APB3165BDP APB3165C APB3165CP APB3165CD APB3165CDP APB3175 APB3175P APB3175D APB3175DP APB3189 APB3189P APB3189D APB3189DP APB3196A APB3196AP APB3196AD APB3196ADP APB3196B APB3196BP APB3196BD APB3196BDP

Section 9

Type APB NEMA 1 Enclosure (Continued)


Width Height Interior X-Height 18X, 23X, 28X Modification 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 16.25"D, Std Gauge 16.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 16.25"D, Std Gauge 16.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 16.25"D, Std Gauge 16.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 16.25"D, Std Gauge 16.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 14.25"D, Std Gauge 14.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 16.25"D, Std Gauge 16.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 16.25"D, Std Gauge 16.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 16.25"D, Std Gauge 16.25"D, Painted/Heavy Gauge 11.50"D, Std Gauge 11.50"D, Painted/Heavy Gauge 16.25"D, Std Gauge 16.25"D, Painted/Heavy Gauge Product Number APB3665 APB3665P APB3665D APB3665DP APB3675 APB3675P APB3675D APB3675DP APB3689 APB3689P APB3689D APB3689DP APB3696 APB3696P APB3696D APB3696DP APB4065 APB4065P APB4065D APB4065PD APB4075 APB4075P APB4075D APB4075DP APB4089 APB4089P APB4089D APB4089DP APB4096 APB4096P APB4096D APB4096DP APB4465 APB4465P APB4465D APB4465DP APB4475 APB4475P APB4475D APB4475DP APB4489 APB4489P APB4489D APB4489DP APB4496 APB4496P APB4496D APB4496DP

18X

65

65"

23X

75" 36" 89"

23X, 28X

27"

28X

33X, 38X

75"

28X

96"

38X, 43X, 48X

89"

33X, 38X

65"

18X, 23X

18X

75" 40" 89"

23X, 28X

65"

23X

33X, 38X

28X

96"

38X, 43X, 48X

31"

75"

23X, 28X

65"

18X, 23X

89"

33X, 38X

75" 44" 89"

23X, 28X

38X, 43X 96" 48X

33X, 38X

96"

38X, 43X, 48X

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-35

Panelboards
Spectra Series Panelboards
Replacement Boxes and Fronts Order from the Customer Service Center Type APB NEMA 3R and 12 Enclosures
Width Depth Height 65" 27" 14.25" 75" 89" Interior X-Height1 18X 23X 28X 28X 33X 38X 18X 23X 28X 23X 23X GF 28X 33X 38X 18X 23X 28X 23X 23X DM 28X 33X 38X 18X 23X 23X 23X DM 28X 18X 23X 23X 23X DM 28X Product Number2 APB(D,R)276518(B,T) APB(D,R)276523(B,T) APB(D,R)276528(B,T) APB(D,R)277528(B,T) APB(D,R)278933(B,T) APB(D,R)278938(B,T) APB(D,R)316518(B,T) APB(D,R)316523(B,T) APB(D,R)316528(B,T) APB(D,R)317523E(B,T) APB(D,R)317523E(B,T) APB(D,R)317528(B,T) APB(D,R)318933(B,T) APB(D,R)318938(B,T) APB(D,R)366518(B,T) APB(D,R)366523E(B,T) APB(D,R)366528(B,T) APB(D,R)367523E(B,T) APB(D,R)367523E(B,T) APB(D,R)367528(B,T) APB(D,R)368933(B,T) APB(D,R)368938(B,T) APB(D,R)406518(B,T) APB(D,R)406523(B,T) APB(D,R)407523E(B,T) APB(D,R)407523E(B,T) APB(D,R)407528(B,T) APB(D,R)446518(B,T) APB(D,R)446523(B,T) APB(D,R)447523(B,T) APB(D,R)447523E(B,T) APB(D,R)447528(B,T)

Section 9

65" 31" 14.25"

75" 89" 65"

36"

16.25"

75" 89" 65"

40"

14.25" 75" 65"

44"

16.25" 75"

1GF = Ground Fault

DM = Dual Main, Ground Fault, 200% Neutral


2(D,R) D = NEMA 12

R = NEMA 3R (B,T) B = Bottom Feed T = Top Feed

200% Neutral Provides second neutral assembly of equal amperage rating. Compression Lugs Main Lugs, Neutral Lugs and Fusible Switches The standard sizes and number of mechanical lugs are shown on page 9-28.
Description #12 1/0 2/0-300 kcmil Description 500 kcmil 600-750 kcmil

9-36

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Renewal Parts
Product Number Structure Panelboard Interior Type APN

Section 9

Example:

APN

38
X Hgt of Interior 18 = 18X 23 = 23X 28 = 28X 33 = 33X 38 = 38X 43 = 43X 48 = 48X 53 = 53X

06
Ampere Rating 02 = 200A 04 = 400A 06 = 600A 08 = 800A 12 = 1200A

U
Interior Type U = Unassembled

B4
Modification Code Blank = Standard (Aluminum Bus) B4 = Copper Bus (100A/sq in.)

Panelboard Interior Type APNB

Example:

APNB

38
X Hgt of Interior 18 = 18X 23 = 23X 28 = 28X 33 = 33X 38 = 38X 43 = 43X 48 = 48X 53 = 53X

06
Ampere Rating 02 = 200A 04 = 400A 06 = 600A 08 = 800A 12 = 1200A

U
Interior Type U = Unassembled

B4
Modification Code Blank = Standard (Aluminum Bus) B4 = Copper Bus (100A/sq in.)

Panelboard Box Type APB

Example:

APB

36
Box Width 27 = 27" 36 = 36" 44 = 44"

89
Box Height 65 = 65" 75 = 75" 89 = 89" 96 = 96" Modification Code Blank = Any box except APB2765 A = For APB2765 with 18X interior B = For APB2765 with 23X interior C = For APB2765 with 28X interior

Panelboard Front Type APF

Example:

APF

89
Box Height 65 = 65" 75 = 75" 89 = 89" 96 = 96"

38
X Hgt of Interior 18 = 18X 23 = 23X 28 = 28X 33 = 33X 38 = 38X 43 = 43X 48 = 48X 53 = 53X Modification Code Blank = For Std Box (36" wide) S = For Slim Box (27" wide) W = For Wide Box (44" wide) E = Extra Line Gutter Space for Dual Main Neutral N = Nonvented Front (for 250A only)

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-37

Panelboards
Spectra Series Panelboards
Renewal Parts
Product Number Structure (Continued) Main Lug Module Type AMB

Section 9

Example:

AMB

3
No. of Poles 3 = 3 poles

600
Ampere Rating 250 = 200A 400 = 400A 600 = 600A 800 = 800A 120 = 1200A

S
Modification Code Blank = 6X Module with Mech Lugs S = 4X Module with Mech Lugs C = 6X Module with Compression Lugs D = Dual Main Lug

FP
Accessory Code FP = With Filler Plate Kit (cover plates) MA = Mechanical Al/Cu Rated

Disconnect Switches Type ADS

Example:

ADS

3
No. of Poles 2 = 2 poles 3 = 3 poles

6
Voltage Rating 2 = 240V 6 = 600V

200
Ampere Rating 030 = 30A 060 = 60A 100 = 100A 200 = 200A 400 = 400A 600 = 600A 800 = 800A 120 = 1200A

H
Fuse Type H = Class H, R, or K T = Class T J = Class J L = Class L

D
Unit Type D = Double Unit with 2 switches S = Single Switch in a Double Unit B = Single Branch Unit M = Main Switch K = Expansion Kit (switch only . . . no module)

FP
Accessory Code FP = With Filler Plate Kit (side fillers)

Circuit Breaker Mounting Modules Type AMC

Example:

AMC

6
No. of Total CB Poles on Module 6 = 6 poles (3-pole breakers, double branched) 4 = 4 poles (2-pole breakers, double branched) 3 = 3 poles (3-pole breakers, single branched) 2 = 2 poles (2-pole breakers, single branched)

EB
Breaker Frames QB = THQB, THHQB EY = TEY EB = TEB, TED, THED, SED, SEH, SEL, SEP FDB = FC FEB = FE Future FJ = TFJ, TFK, THFK, TFL, SFH, SFL, SFP JK = TJD, TJJ, TJK, THJK, TJ4V, TJL4V LB = TLB4, THLC2, THLC4 GB or GM = SGD, SGH, SGL, SGP FGB = FG KM = TKM, THKM, TK4V, TKL4V, SKH, SKL, SKP FB = FB

S
Unit Type Blank = Std. S = Special Type to allow TFL, SE and SF to be mounted adjacent to a switch

FP
Accessory Code FP = With Filler Plate Kit (full width plates with cutouts for handles, etc.)

9-38

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Renewal Parts
Product Number Structure (Continued)

Section 9

Bolt-on Strap Kits Type AMCB

Example:

AMCB

6
Poles 2 3 4 6

EB
C/B Frame EB = SE, TEB, T(H)ED EY = TEY FDB = FC FE = FEB Future FJ = SF G = SG FG = FGB K = SK, T(H)KM LB = THLC2,4 QD = T(H)QD SE = SE, THED

B
Mounting Blank = Main or Branch B = Branch Only M = Main Only

FP
Accessory Code FP = With Filler Plate Kit (full width plates with cutouts for handles, etc)

Neutral Kits Type ANK

Example:

ANK

800
Ampere Rating 250 = 250A 400 = 400A 600 = 600A 800 = 800A 100 = 1000A 120 = 1200A

D
Modification Code Blank = Std (single main) D = Dual Main GF = Ground Fault Only

Equipment Ground Kits Type AEG

Example:

AEG

21
No. of Circuits 10 21 31

S
Modification Code Blank = Std (bonded) S = Insulated/Isolated

NEMA 1 Box Extensions - Type APB1

Example:

APB

27
Width 27 31 36 40 44

E
Extension Depth E = 12H, 11.5D, 31/36/40/44W 12H, 14.25D, 27W ED = 12H, 14.25D, 31/40W 12H, 16.25D, 36/44W ES = 12H, 11.5D, 27W

1Note: Available in SPEEDI under EXT code on modifications screen. Also available by product number through ONE STOP.

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-39

Panelboards
Spectra Series Panelboards
Renewal Parts
Mounting Hardware Order from the Customer Service Center Product Features

Section 9

Use to mount main or branch circuit breakers into panelboard. Breakers bolt on to the mounting modules. FP suffix indicates that all AFP filler plates, with cutouts for handles, are included to fit all applicable box widths. On double branch modules, filler plates to cover any unused breaker poles are also included. Circuit breakers not included in module price. Includes all necessary hardware.

Circuit Breaker Mounting Modules Plug-In Spectra 3-pole


Mounting Arrangement Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Adjacent to Switch Double Branch Adjacent to Switch Double Branch Adjacent to Switch Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Adjacent to Switch Maximum Breaker Amperage 100 100 100 100 150 225 225 250 400 600 600 600 100 150 250 225 250 400 600 600 600 1200 1200 250 Breaker Frame THQB or THHQB TEY FBV, FBN, FBH, or FBL FCS, FCV, FCN, FCH or FCL TEB, TED, THED, SEDA SEHA, SELA or SEPA TQD or THQD TFJ or TFK or THFK SFHA or SFLA or SFPA TJD or TJJ TJK or THJK FGL, FGN, FGH or FGP SGDA or SGHA or SGLA or SGPA FCS, FCV, FCN, FCH or FCL SEDA or SEHA or SELA or SEPA SFHA or SFLA or SFPA TFJ or TFK or THFK SFHA or SFLA or SFPA TJD or TJJ TJK or THJK FGV, FGN, FGH or FGP SGDA or SGHA or SGLA or SGPA TKM or THKM or SKHA or SKLA SKPA SFHA or SFLA or SFPA X Height 3X 3X 3X 3X 3X 3X 3X 3X 6X 6X 4X 4X 4X 4X 4X 3X 3X 6X 6X 4X 4X 6X 6X 4X Filler Plate Kit Product Number AFP3QBD AFP3EYD AFP3FBD AFP3FDD AFP3SED AFP3QDD AFP3TFD AFP3SFD AFP6TJD AFP6TJD AFP4FGD AFP4SGD AFP4FDD AFP4SED AFP4SFD AFP3TFS AFP3SFS AFP6TJS AFP6TJS AFP4FGS AFP4SGS AFP6SKS AFP6SKS AFP4SFS Box Width Range 27", 31", 36" 40", 44" 27", 31", 36" 40", 44" 27", 31", 36", 40", 44" 27", 31", 36", 40", 44" 27", 31", 36" 40", 44" 27", 31", 36" 40", 44" 31", 36", 40", 44" 31", 36", 40" 44" 44" 44" 40", 44" 40", 44" 36", 44" 36", 44" 36", 44" 27", 31", 36", 40", 44" 27", 31", 36", 40", 44" 27", 31", 36", 40", 44" 27", 31", 36", 40", 44" 27", 31", 36", 40", 44" 27", 31", 36", 40", 44" 40", 44" 44" 36", 44" Product Number AMC6QBFP AMC6EYFP AMC6FBFP AMC6FDBFP AMC6EBFP AMC6QDFP AMC6FJFPTF AMC6FJFP1 AMC6JKFP AMC6JKFP AMC6FGBFP AMC6GBFP2 AMC6FDSPF AMC6EBSFP AMC6FLSFP AMC3FJFPTF AMC3FJFP1 AMC3JKFP AMC3JKFP AMC3FGMFP AMC3GMFP AMC3KMFP AMC3KMFP AMC3FLSFP

Circuit Breaker Mounting Modules Plug-In Spectra 2-pole


Mounting Arrangement Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Double Branch Adjacent to Switch Double Branch Adjacent to Switch Double Branch Adjacent to Switch Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Single Branch or Main Adjacent to Switch Maximum Breaker Breaker Amperage Frame 100 THQB or THHQB 100 TEY 100 FCS, FCV, FCN, FCH or FCL 150 TEB or TED 150 SEDA or SEHA or SELA or SEPA, THED 225 TQD or THQD 225 TFJ or TFK or THFK 250 SFHA or SFLA or SFPA 400 TJD or TJJ 600 TJK or THJK 600 FGV, FGN, FGH or FGP 600 SGDA or SGHA or SGLA or SGPA 100 FCS, FCV, FCN, FCH or FCL 150 SEDA or SEHA or SELA or SEPA 250 SFHA or SFLA or SFPA 225 TFJ or TFK or THFK 250 SFHA or SFLA or SFPA 400 TJD or TJJ 600 TJK or THJK 600 FGV, FGN, FGH or FGP 600 SGDA or SGHA or SGLA or SGPA 1200 TKM or THKM or SKHA or SKLA 1200 SKPA 250 SFHA or SFLA or SFPA X Height 3X 3X 3X 3X 3X 2X 3X 3X 6X 6X 4X 4X 4X 4X 4X 3X 3X 6X 6X 4X 4X 6X 6X 4X Filler Plate Kit Product Number AFP3QBD AFP3EYD AFP3FDD AFP2TED AFP3SED AFP2QDD AFP3TFD AFP3SFD AFP6TJD AFP6TJD AFP4FGD AFP4SGD AFP4FDD AFP4SED AFP4SFD AFP3TFS AFP3SFS AFP6TJS AFP6TJS AFP4FGS AFP4SGS AFP6SKS AFP6SKS AFP4SFS Box Width Range 27", 31", 36" 40", 44" 27", 31", 36" 40", 44" 27", 31", 36", 40", 44" 27", 31", 36" 40", 44" 27", 31", 36" 40", 44" 27", 31", 36" 40", 44" 31", 36", 40", 44" 31", 36", 40" 44" 44" 44" 40", 44" 40", 44" 36", 44" 36", 44" 36", 44" 27", 31", 36", 40", 44" 27", 31", 36", 40", 44" 27", 31", 36", 40", 44" 27", 31", 36", 40", 44" 27", 31", 36", 40", 44" 27", 31", 36", 40", 44" 40", 44" 44" 36", 44" Product Number AMC6QBFP AMC6EYFP AMC4FDBFP AMC4EBFP AMC4SEFP AMC4QDFP AMC4FJFPTF AMC4FJFP1 AMC4JKFP AMC4JKFP AMC4FGBFP AMC4GBFP2 AMC4FDSFP AMC4EBSFP AMC4FLSFP AMC2FJFPTF AMC2FJFP1 AMC2JKFP AMC2JKFP AMC2FGMFP AMC2GMFP AMC2KMFP AMC2KMFP AMC2FLSFP

1SE and SF breakers located adjacent to a fusible switch, PCU or TVSS require mounting modules suitable for mounting Adjacent to Switch.

SGDA circuit breaker rated 400 amps maximum.


2THLC 1/2/4 breaker no longer available.

Note: 1X = 1 3/8" vertical panel space.

9-40

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Renewal Parts
Mounting Hardware Order from the Customer Service Center Product Features Module includes fusible switch and panelboard mounting connectors. Fuses not included. Class R Fuse Clip Kit (for field installation) included with all switches that accept Class R Fuses. FP suffix indicates that all AFP filler plates are included to fit applicable box widths. Branch Switch Modules Plug-In Spectra 240 Volts 3-pole
Mounting Arrangement Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-switch plus space Double Branch-switch plus space Double Branch-switch plus space Single Branch Single Branch Single Branch Single Branch Single Branch Fuse Type H, R, or K H, R, or K H, R, or K T H, R, or K T H, R, or K H, R, or K H, R, or K H, R, or K H, R, or K T H, R, or K T Switch Amperes 30 60 100 100 200 200 30 60 100 200 400 400 600 600 X Height 4X 4X 5X 7X 7X 7X 4X 4X 5X 7X 10X 10X 10X 10X Side Filler Plate Kit Part Number AFP4X AFP4X AFP5X AFP7T AFP7X2 AFP7T AFP4X AFP4X AFP5X AFP7X AFP10X AFP10T AFP10X AFP10T Box Width Range 36", 44" 36", 44" 36", 44" 36", 44" 44" 36", 44" 36", 44" 36", 44" 36", 44" 36", 44" 44" 36", 44" 44" 36", 44"

Section 9

Product Number ADS32030HDFP ADS32060HDFP ADS32100HDFP ADS32100TDFP ADS32200HDFP ADS32200TDFP ADS32030HSFP ADS32060HSFP ADS32100HSFP ADS32200HBFP ADS32400HBFP ADS32400TBFP ADS32600HBFP ADS32600TBFP

Branch Switch Modules Plug-In Spectra 240 Volts 2-pole


Mounting Arrangement Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-switch plus space Double Branch-switch plus space Double Branch-switch plus space Single Branch Single Branch Single Branch Single Branch Single Branch Single Branch Fuse Type H, R, or K H, R, or K T H, R, or K H, R, or K T H, R, or K H, R, or K H, R, or K H, R, or K T H, R, or K T H, R, or K T Switch Amperes 30 60 100 100 200 200 30 60 100 200 200 400 400 600 600 X Height 4X 4X 7X 5X 7X 7X 4X 4X 5X 7X 7X 10X 10X 10X 10X Side Filler Plate Kit Part Number AFP4X AFP4X AFP7T AFP5X AFP7X2 AFP7T AFP4X AFP4X AFP5X AFP7X AFP7X AFP10X AFP10T AFP10X AFP10T Box Width Range 36", 44" 36", 44" 36", 44" 36", 44" 44" 36", 44" 36", 44" 36", 44" 36", 44" 36", 44" 36", 44" 44" 36", 44" 44" 36", 44" Product Number ADS22030HDFP ADS22060HDFP ADS32100TDFP ADS22100HDFP ADS22200HDFP ADS22200TD ADS22030HSFP ADS22060HSFP ADS22100HSFP ADS22200HBFP ADS22200TS ADS22400HBFP ADS22400TBFP ADS22600HBFP ADS22600TBFP

Note: 1X = 1 3/8" vertical panel space

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-41

Panelboards
Spectra Series Panelboards
Renewal Parts
Mounting Hardware Order from the Customer Service Center

Section 9

Product Features Module includes fusible switch and panelboard mounting connectors. Fuses not included. Class R Fuse Clip Kit (for field installation) included with all switches that accept Class R Fuses. FP suffix indicates that all AFP filler plates are included to fit applicable box widths. Branch Switch Modules Plug-In Spectra 600 Volts 3-pole
Mounting Arrangement Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-switch plus space Double Branch-switch plus space Double Branch-switch plus space Single Branch Single Branch Single Branch Single Branch Single Branch Single Branch Single Branch Single Branch Single Branch Fuse Type H, R, J, or K H, R, J, or K H, R, J, or K H, R, or K J H, R, J, or K H, R, J, or K H, R, J, or K H, R, or K H, R, or K J T H, R, or K J T L L Switch Amperes 30 60 100 200 200 30 60 100 200 400 400 400 600 600 600 800 1200 X Height 4X 5X 5X 7X 7X 4X 5X 5X 7X 10X 10X 10X 10X 10X 10X 19X 19X Side Filler Plate Kit Part Number AFP4X AFP5X AFP5X AFP7X2 AFP7T AFP4X AFP5X AFP5X AFP7X AFP10X AFP10T AFP10T AFP10X AFP10T AFP10T AFP19X AFP19X Box Width Range 36", 44" 36", 44" 36", 44" 44" 36", 44" 36", 44" 36", 44" 36", 44" 36", 44" 44" 36", 44" 36", 44" 44" 36", 44" 36", 44" 44" 44" Product Number ADS36030HDFP ADS36060HDFP ADS36100HDFP ADS36200HDFP ADS36200JDFP ADS36030HSFP ADS36060HSFP ADS36100HSFP ADS36200HBFP ADS36400HBFP ADS36400JBFP ADS36400TBFP ADS36600HBFP ADS36600JBFP ADS36600TBFP ADS36800LBFP ADS36120LBFP

Branch Switch Modules Plug-In Spectra 600 Volts 2-pole


Mounting Arrangement Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-2 switches Double Branch-switch plus space Double Branch-switch plus space Double Branch-switch plus space Single Branch Single Branch Single Branch Single Branch Single Branch Single Branch Single Branch Single Branch Single Branch Single Branch Fuse Type H, R, J, or K H, R, J, or K H, R, J, or K T H, R, or K J H, R, J, or K H, R, J, or K H, R, J, or K H, R, or K J H, R, or K J T H, R, or K J T L L Switch Amperes 30 60 100 100 200 200 30 60 100 200 200 400 400 400 600 600 600 800 1200 X Height 4X 5X 5X 7X 7X 7X 4X 5X 5X 7X 7X 10X 10X 10X 10X 10X 10X 19X 19X Side Filler Plate Kit Part Number AFP4X AFP5X AFP5X AFP7X2 AFP7T AFP4X AFP5X AFP5X AFP7X AFP7X AFP10X AFP10T AFP10T AFP10X AFP10T AFP10T AFP19X AFP19X Box Width Range 36", 44" 36", 44" 36", 44" N/A 44" 36", 44" 36", 44" 36", 44" 36", 44" 36", 44" 36" 44" 36", 44" 36", 44" 44" 36", 44" 36", 44" 44" 44" Product Number ADS26030HDFP ADS26060HDFP ADS26100HDFP ADS26100TDFP ADS26200HDFP ADS26200JDFP ADS26030HSFP ADS26060HSFP ADS26100HSFP ADS26200HBFP ADS26200JSFP ADS26400HBFP ADS26400JBFP ADS26400TBFP ADS26600HBFP ADS26600JBFP ADS26600TBFP ADS26800LBFP ADS26120LBFP

Note: 1X = 1 3/8" vertical space

9-42

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Renewal Parts
Mounting Hardware Order from the Customer Service Center

Section 9

Mounting Hardware With Filler Plate, Straps and Brackets Bolt-On Spectra Mounting kit with filler plate includes hardware straps, brackets and filler plate. Filler plate kit includes filler plate and associated hardware only.
Mounting Arrangement Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Single Mounted Single Mounted Single Mounted Single Mounted Single Mounted Single Mounted Single Mounted Single Mounted Single Mounted Single Mounted Single Mounted Breaker Frame Number of Poles 2-pole 2-pole 2-pole 2-pole 2-pole 2-pole 3-pole 3-pole 3-pole 3-pole 3-pole 2-pole 3-pole 2-pole 3-pole 2-pole 2-pole 3-pole 3-pole 2-pole 2-pole 2-pole 2-pole 3-pole 3-pole 3-pole 3-pole 2-pole 2-pole 3-pole Box Width Range 27"-44" 27"-44" 27"-44" 27", 31", 36", 40", 44" 27"-44" 27"-44" 27"-44" 27"-44" 27"-44" 27", 31", 36", 40", 44" 27"-44" 31"-44" 31"-44" 36"-44" 36"-44" 40", 44" 40"-44" 40", 44" 40"-44" 27"-44" 27"-44" 27", 31", 36", 40", 44" 27"-44" 27"-44" 27"-44" 27", 31", 36", 40", 44" 27"-44" 27"-44" 40"-44" 40"-44" X Height 2X 3X 2X 3X 2X 3X 3X 3X 3X 3X 3X 3X 3X 2X 3X 4X 4X 4X 4X 3X 3X 4X 4X 3X 3X 4X 4X 6X 6X 6X Product Number AMCB4EBFP AMCB4EYFP AMCB4FBFP AMCB4FDBFP AMCB4QDFP AMCB4SEFP AMCB6EBFP AMCB6EYFP AMCB6FBFP AMCB6FDBFP AMCB6QDFP AMCB4FJFP AMCB6FJFP AMCB4FJFPTF AMCB6FJFPTF AMCB4FGBFP AMCB4GBFP AMCB6FGBFP AMCB6GBFP AMCB2FJFP AMCB2FJFPTF AMCB2FGMFP AMCB2GMFP AMCB3FJFP AMCB3FJFPTF AMCB3FGMFP AMCB3GMFP AMCB3LBFP AMCB2KMFP AMCB3KMFP

TEB, TED TEY FBV, FBN, FBH, or FBL FCS, FCV, FCN, FCH or FCL TQD, THQD THED, SED, SEH, SEL, SEP TEB, TED, THED, SED, SEH, SEL, SEP TEY FBV, FBN, FBH, or FBL FCS, FCV, FCN, FCH or FCL TQD, THQD SFH, SFL, SFP SFH, SFL, SFP TFJ, TFK, THFK TFJ, TFK, THFK FGV, FGN, FGH or FGP SGH, SGL, SGP FGV, FGN, FGH or FGP SGH, SGL, SGP SFH, SFL, SFP TFJ, TFK, THFK FGV, FGN, FGH or FGP SGH, SGL, SGP SFH, SFL, SFP TFJ, TFK, THFK FGV, FGN, FGH or FGP SGH, SGL, SGP SKP SKH, SKL, SKP, TKM, THKM SKH, SKL, SKP, TKM, THKM

Filler Plates Bolt-On Spectra Filler plate kit includes filler plate and associated hardware only.
Mounting Arrangement Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Single Mounted Single Mounted Single Mounted Single Mounted Single Mounted Single Mounted Breaker Frame Number of Poles 2-pole 2-pole 2-, 3-pole 2-pole 3-pole 3-pole 2-, 3-pole 2-, 3-pole 2-, 3-pole 3-pole 2-, 3-pole 2-, 3-pole 2-, 3-pole 2-, 3-pole 2-, 3-pole 2-pole 3-pole Box Width Range 27"-44" 27"-44" 27"-44" 27"-44" 27"-44" 27"-44" 27"-44" 31"-44" 36"-44" 40", 44" 40"-44" 27"-44" 27"-44" 27", 31", 36", 40", 44" 27"-44" 27"-44" 44"-44" X Height 2X 2X 3X 2X 3X 3X 3X 3X 2X, 3X 4X 4X 3X 3X 4X 4X 6X 6X Product Number AFP2QDD AFP2TED AFP3EYD AFP2FBD AFP3FBD AFP3QDD AFP3SED AFP3SFD AFP3TFD AFP4FGD AFP4SGD AFP3SFS AFP3TFS AFP4FGS AFP4SGS AFP5LCS AFP6SKS

TQD, THQD TEB, TED TEY FBV, FBN, FBH, or FBL FBV, FBN, FBH, or FBL TQD, THQD TEB, TED, THED, SED, SEH, SEL, SEP SFH, SFL, SFP TFJ, TFK, THFK FGV, FGN, FGH or FGP SGH, SGL, SGP SFH, SFL, SFP TFJ, TFK, THFK FGV, FGN, FGH or FGP SGH, SGL, SGP SKP SKP, SKH, SKL, TKM, THKM

Notes: 1X = 1 3/8" vertical space. THLC 1/2/4 breaker no longer available.

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-43

Panelboards
Spectra Series Panelboards
Renewal Parts
Order from the Customer Service Center

Section 9

Filler Plates Plug-In or Bolt-On Spectra Use to cover unused spaces. Includes filler plate support brackets and hardware.
Space X Height1 1X 2X 3X 4X 5X 6X 1X 2X 3X 4X 5X 6X 1X 2X 3X 4X 5X 6X Box Width Range 27", 31" 27", 31" 27", 31" 27", 31" 27", 31" 27", 31" 36", 40" 36", 40" 36", 40" 36", 40" 36", 40" 36", 40" 44" 44" 44" 44" 44" 044" Switchboard Section Widths 35 35 35 35 35 35 40 40 40 40 40 40 45 45 45 45 45 45 Product Number APP1S APP2S APP3S APP4S APP5S APP6S APP1 APP2 APP3 APP4 APP5 APP6 APP1W APP2W APP3W APP4W APP5W APP6W

Mounting Hardware Single Breaker Plug-In Spectra Included when ordering AMC module. Only required when mounting breaker on existing module. Kit contains screws and washers to mount one circuit breaker on AMC circuit breaker mounting module.
Circuit Breaker Mounting Module Part Number AMC6EB AMC4SE AMC4EB AMC6EBS AMC6EL AMC2FLS AMC6FJ AMC4FJ AMC3FJ AMC2FJ AMC6FLS AMC3FLS AMC4FLS AMC2GM AMC6GB AMC4GB AMC3GM AMC2JK AMC6JK AMC4JK AMC3JK AMC3LB AMC6LB AMC4QD AMC6QD FCS, FCV, FCN, FCH or FCL FGV, FGN, FGH or FGP Product Number AHKE1

AHKEL1 AHKF1

AHKG1

1 X-height: 1X = 1 3/8"

AHKJ1

Mounting Hardware Plug-In or Bolt-On Spectra ADS Switch Replacement Load Base Kits Includes load base, clips and lugs.
Replacement for Load Base Part Number ADS22030HD ADS32030HD ADS322060HD ADS32060HD ADS26030HD ADS36030HD ADS26060HD ADS36060HD ADS36200JD ADS26200JD ADS36200JM ADS26200JM Load Base Ampere Rating 100A 100A 100A 100A 200A 200A 200A 200A 200A 200A 400A 400A 400A 400A 600A 600A 600A 600A 400-1200A Load Base No. of Poles 2-pole 3-pole 3-pole 2-pole 3-pole 2-pole 2-pole 2-pole 3-pole 2-pole 2-pole 3-pole 2-pole 3-pole 2-pole 3-pole 2-pole 3-pole Load Base Voltage 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V 240V & 600V Product Number 331A1519G1 331A1519G2 331A1519G3 331A1519G4 331A1519G5 331A1519G6 331A1519G7 331A1519G8 331A1519G12 331A1519G16 331A1519G20 331A1519G22 331A1519G9 331A1519G10 331A1519G14 331A1519G18 331A1519G11 331A1519G13 331A1519G15 331A1519G17 331A1519G19 331A1519G21 331A1545G1 331A1545G3 331A1545G5 331A1545G7 331A1545G2 331A1545G4 331A1545G6 331A1545G8 331A1543G1

AHKLB1 AHKQ1 AHKFD1 AHKFG1

Mounting HardwareHardware only; no brackets or straps Bolt-On Spectra


Breaker Frame SE SF SG THQD FCS, FCV, FCN, FCH or FCL FGV, FGN, FGH or FGP FB Product Number AHKBE1 AHKBF1 AHKBG1 AHKBQ1 AHKBFD1 AHKBFG1 AHKBFB1

9-44

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Renewal Parts
Main Lug Modules; Neutral and Ground Kits Plug-In or Bolt-On Lug Kits and Modules Plug-In Spectra FP suffix indicates all AFPML cover plates included to fit applicable box widths. Can be converted to dual main lug version by adding lug kits (see Accessories). Mechanical lug modules can be converted to compression lug modules by replacing standard lugs with AMKP compression lug kit (see Accessories) Can be used for feed-thru lugs application by replacing standard cover plate with AFL feed-thru lug cover plate kit (see Accessories).
Lug Ampere Rating 250 250 400 400 600 600 800 1200 250 400 600 800 1200 Lug Type Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Mechanical Compression Compression Compression Compression Compression X Height 4X 6X 4X 6X 4X 6X 6X 6X 6X 6X 6X 6X 6X Lugs Per Phase 1 1 1 1 1 1 2 2 2 2 2 4 4 Wires per Lug 1 1 2 2 2 2 2 2 1 1 1 1 1 Wire Range (Cu/Al) #6-350kcmil #6-350kcmil #2-500kcmil #2-500kcmil #2-500kcmil #2-500kcmil #2-500kcmil #2-500kcmil 350kcmil 500kcmil 500kcmil 500kcmil 500ckmil Included Cover Plate AFPML4X AFPML6X AFPML4X AFPML6X AFPML4X AFPML6X AFPML6XW AFPML6XW AFPML6X AFPML6X AFPML6X AFPML6XW AFPML6XW Box Width Range 27",36" 36" 27",36",44" 36",44" 27",36",44" 36",44" 36",44" 36",44" 36" 36",44" 36",44" 36",44" 36",44" Product Number AML3250SFP1 AML3250FP AML3400SFP1 AML3400FP AML3600SFP1 AML3600FP AML3800FP AML3120FP AML3250CFP AML3400CFP AML3600CFP AML3800CFP AML3120CFP

14X modules cannot be converted to compression lug version.

Lug Kits and Modules Plug-In or Bolt-On SpectraNeutral Includes mechanical lugs and bonding strap. 250 to 600A neutral kits can be converted to dual main version by doubling the main lug quantity using lug kits (see Accessories). Main lug on neutral kit can be converted to compression main using AMKP lug kit.
Lug Amp Rating Bolt-On 250/400 No. of Main Lugs Single/Dual No. of Wires 2 (MAIN) 16 5 24 8 (MAIN) 9 10 10 8 (MAIN) 8 10 4 8 (MAIN) 8 10 4 Wire Range (Cu/Al) #2 - 600kcmil #14 - 2/0 #6 - 300kcmil #14 - #4 #2 - 600kcmil #14 - 2/0 #6 - 300kcmil #14 - #4 #2 - 500kcmil #14 - 2/0 #6 - 300kcmil #2 - 500kcmil #2 - 500kcmil #14 - 2/0 #6 - 300kcmil #2 - 500kcmil Product Number ANKN400

600/800/1200

Single/Dual

ANKN120

Plug-In 800

Dual

ANK800D

1200

Dual

ANK120D

For 3ph, 4W single-section panelboards, use a standard neutral. For 3ph, 4W multi-section panelboards, use a standard neutral on the last section, and a dual main neutral on the first and middle sections.

Lug Kits and Modules Plug-In or Bolt-On SpectraGround AEG10 and AEG21 should be ordered in multiples of 10 due to 10 kits per carton bulk-packaging. AEG21S and AEG31S are packaged as quantity 1 kit per carton.
Bonding Type Bonded Bonded Total Circuits 10 21 No. of Wires 10 9 Wire Range (Cu/Al) #6-2/0 Cu/AI Solid: #14-#8 Cu or #12-#8 AI or Stranded: #12-#8 Cu or #12-#8 AI or Stranded: #10-#4 Cu or #10-#4 AI Solid: #14-#8 Cu or #12-#8 AI or Stranded: #12-#8 Cu or #12-#8 AI or Stranded: #10-#4 Cu or #10-#4 AI #6-2/0 Cu/AI Product Number AEG10 AEG21

Insulated/Isolated

21

AEG21S

Insulated/Isolated

31

10

AEG31S

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-45

Panelboards
Spectra Series Panelboards
Merchandise
Renewal Parts Accessories

Section 9

Feed Thru Lug Cover Plate Kits Use to convert AML main lug module to feed thru lug module Kit includes barrier and oversized cover plates. (Discard original cover plates.)
Lug Amp Rating 250/400/600 800/1200 X Height 9X 12X Box Width Range 27", 36", 44" 36", 44" Product Number AFL600 AFL120 Note: This lug furnished with 6 pack kits only. (For dual main lug conversion) Note: This lug furnished with all kits.

Crimp Lugs

Mechanical Lug Kits and Modules Use to convert AML main mechanical lug modules or ANK neutral modules to dual main lug version. Can be used to replace standard lugs with oversized lugs.
Wire Range (Cu/Al) #6-350kcmil #2-500kcmil #2-600kcmil 3/0-750kcmil Lugs Per Kit 3 3 3 3 Wires per Lug 1 2 2 2 Product Number AMK350 AMK500 AMK600 AMK750

Compression Lug Kits and Modules Use to convert AML main mechanical lug modules to compression lug version.
Wire Size 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250kcmil 250kcmil 300kcmil 300kcmil 350kcmil 350kcmil 400kcmil 400kcmil 500kcmil 500kcmil 600kcmil 600kcmil 700/750 kcmil 700/750 kcmil Package Type 3 PACK 6 PACK 3 PACK 6 PACK 3 PACK 6 PACK 3 PACK 6 PACK 3 PACK 6 PACK 3 PACK 6 PACK 3 PACK 6 PACK 3 PACK 6 PACK 3 PACK 6 PACK 3 PACK 6 PACK 3 PACK 6 PACK Crimp Tool Die Cat. No. Homac 15CA52 15CA52 15CA52 15CA52 15CA66 15CA66 15CA71H 15CA71H 15CA76 15CA76 15CA87H 15C87 15CA87H 15C87 15CA96H 15C96H 15CA96H 15C96H 15CA96H 15C96H 15CA96H 15C96H 15CA106A 15C106R 15CA106A 15C106R 15CA115H 15C115H 15CA115H 15C115H 15C125H 15C125H Crimp Tool Die Cat. No. Burndy 296 296 297 297 467 467 298 298 324 324 470 470 299 299 472 472 300 300 473 473 936 936 Crimp Tool Die Cat. No. T&B 50 50 54H 54H 60 60 66 66 71H 71H 76 76 87H 87H 94H 94H 99H 99H 106H 106H 115H 115H Product Number AMKP101 AMKP2101 AMKP202 AMKP2202 AMKP303 AMKP2303 AMKP404 AMKP2404 AMKP250 AMKP2250 AMKP300 AMKP2300 AMKP350 AMKP2350 AMKP400 AMKP2400 AMKP500 AMKP2500 AMKP600 AMKP2600 AMKP750 AMKP2750

Compression Lug Kits Use to replace standard load-side mechanical lugs on ADS branch switches. Each kit includes 3 lugs.
Wire Range #8-1/0 Cu/AI #4-300kcmil Cu/Al 2/0-500kcmil Cu/Al 400-500kcmil Cu or 400-600kcmil Al 500-750kcmil Cu/Al Lugs Per Phase 1 1 2, 4 2, 4 2, 4 For Switch Amperes 30, 60, or 100 200 800 or 1200 800 or 1200 800 or 1200 Product Number KLP101 KLP300 KLP500 KLP600 KLP750

Notes: For dual main applications, double the kit quantity.

Permanent Circuit Number Tabs


For Circuit Numbers 1-49 1-99 Product Number APN49 APN99

9-46

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Merchandise
Renewal Parts Interiors, Boxes and Fronts Order from Customer Service Center

Section 9

Product Features In selecting an interior X-height, add up all required main and branch module X-heights, plus any required spaces for future. UL Service Entrance label is included on all interiors. Boxes
Panel Current Rating (amperes) 250, 400 250 250, 400, 600 400 600 250, 400, 600 400, 800, 1200 250, 400, 600, 800, 1200 250, 400, 600, 800, 1200 400, 600 400, 800, 1200 400, 600, 800, 1200 400, 600, 800, 1200 Space X Height 18 28 38 28 23 18, 28 28 38 43,48 53 18, 23 23, 28 38 43, 48 Box Width/Depth 27" W x 14.5" D 27" W x 14.5" D 27" W x 14.5" D 27" W x 14.5" D 27" W x 14.5" D 36" W x 11.5" D 36" W x 11.5" D 36" W x 11.5" D 36" W x 11.5" D 44" W x 11.5" D 44" W x 11.5" D 44" W x 11.5" D 44" W x 11.5" D Box Height (inches) 64.63 64.63 89.25 75.5 64.63 64.63 75.5 89.25 96.13 64.63 75.5 89.25 96.13 Product Number APB2765A APB2765C APB2789 APB2775 APB2765B APB3665 APB3675 APB3689 APB3696 APB4465 APB4475 APB4489 APB4496

Interior Aluminum
Panel Current Rating (amperes) 250 250 250 250 400 400 400 400 600 600 600 800 800 800 1200 1200 1200 Space X Height 18 28 38 53 18 28 38 48 23 38 48 23 38 43 28 38 43 Product Number APN1802U APN2802U APN3802U APN5302U APN1804U APN2804U APN3804U APN4804U APN2306U APN3806U APN4806U APN2308U APN3808U APN4308U APN2812U APN3812U APN4312U

Interior Copper
Panel Current Rating (amperes) 250 250 250 250 400 400 400 400 600 600 600 800 800 800 1200 1200 1200 Space X Height 18 28 38 53 18 28 38 48 23 38 48 23 38 43 28 38 43 Product Number APN1802UB4 APN2802UB4 APN3802UB4 APN5302UB4 APN1804UB4 APN2804UB4 APN3804UB4 APN4804UB4 APN2306UB4 APN3806UB4 APN4806UB4 APN2308UB4 APN3808UB4 APN4308UB4 APN2812UB4 APN3812UB4 APN4312UB4

Front w/Door
Panel Current Rating (amperes) 250 250 250 400 400 600 600 Space X Height 18 28 38 18 28 23 38 Box Width/Depth 27" W x 14.5" D 27" W x 14.5" D 27" W x 14.5" D 27" W x 14.5" D 27" W x 14.5" D 27" W x 14.5" D 27" W x 14.5" D Box Height (inches) 64.63 64.63 89.25 64.63 75.5 64.63 89.25 Product Number APF6518NS APF6528NS APF8938NS APF6518S APF7528S APF6523S APF8938S

4-pc Fronts
Panel Current Rating (amperes) 250 250 250 250 400 400, 800, 1200 400, 600, 800, 1200 600 400, 600, 800, 1200 800 800, 1200 400 600 800 400, 1200 400, 600, 800, 1200 800, 1200 400, 600 Space X Height 18 28 38 53 18 28 38 23 48 23 43 18 23 23 28 38 43 48 Box Width/Depth 36" W x 11.5" D 36" W x 11.5" D 36" W x 11.5" D 36" W x 11.5" D 36" W x 11.5" D 36" W x 11.5" D 36" W x 11.5" D 36" W x 11.5" D 36" W x 11.5" D 36" W x 11.5" D 36" W x 11.5" D 44" W x 11.5" D 44" W x 11.5" D 44" W x 11.5" D 44" W x 11.5" D 44" W x 11.5" D 44" W x 11.5" D 44" W x 11.5" D Box Height (inches) 64.63 64.63 89.25 96.13 64.63 75.5 89.25 64.63 96.13 75.5 96.13 64.63 64.63 75.5 75.5 89.25 96.13 96.13 Product Number APF6518N APF6528N APF8938N APF9653N APF6518 APF7528 APF8938 APF6523 APF9648 APF7523 APF9643 APF6518W APF6523W APF7523W APF7528W APF8938W APF9643W APF9648W

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-47

Panelboards
Spectra Series Panelboards
Type SCP Plus
Renewal Parts Enclosure Options, Mounting Hardware and Spare Parts Order through the Customer Service Center unless stated otherwise below.

Section 9

Boxes
Box Width/Depth 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D X Height 15 18 21 24 27 30 33 36 39 42 15 18 21 24 27 30 33 36 39 42 Box Height (inches) 49.375 53.5 57.625 61.75 65.875 70 74.125 78.25 82.275 86.5 49.375 53.5 57.625 61.75 65.875 70 74.125 78.25 82.275 86.5 Product Number ACB311149 ACB311153 ACB311157 ACB311161 ACB311165 ACB311170 ACB311174 ACB311178 ACB311182 ACB311186 ACB401149 ACB401153 ACB401157 ACB401161 ACB401165 ACB401170 ACB401174 ACB401178 ACB401182 ACB401186

Mounting HardwareHardware Kit and Straps


Mounting Arrangement Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Single Mounted Single Mounted Single Mounted Single Mounted Single Mounted Breaker Frame SHE, SEL, SED, SEP TEB, TED, THED TEB, TED, THED TEB, TED, THED TFK, SFH, SFL, SFP TQD, THQD TQD, THQD TJD, TJJ, TJK SGD, SGH, SGL, SGP SGD, SGH, SGL, SGP SKH, SKL TB4 TB6 TB8 Maximum Breaker Amperage 150A 150A 150A 150A 250A 225A 225A 400A 400A, 600A 400A, 800A 800A, 1200A 400A 600A 800A single-pole two-pole three-pole Breaker Number of Poles Product Number ACTMKSE ACTMKEB1P ACTMKEB2P ACTMKEB3P ACTMKSF ACTMKQD2P ACTMKQD3P ACTMKJD ACTMKSG ACSMKSG ACSMKSK ACSMKTB4 ACSMKTB6 ACSMKTB8

two-pole three-pole

Box dimensions are inside dimensions. Add 1/4-inch for outside dimensions. Boxes furnished with no knockouts.

Mounting HardwareFiller Plate and Filler Hardware


Mounting Arrangement Breaker Frame SHE, SEL, SED, SEP TEB, TED, THED TEB, TED, THED TEB, TED, THED TFK, SFH, SFL, SFP TQD, THQD TQD, THQD TJD, TJJ, TJK SGD, SGH, SGL, SGP SGD, SGH, SGL, SGP SKH, SKL TB4 Maximum Breaker Amperage 150A 150A 150A 150A 250A 225A 225A 400A 400A, 600A 400A, 800A 800A, 1200A 400A single-pole two-pole three-pole Breaker Number of Poles Product Number ACTFPKSE ACTFPKEB1P ACTFPKEB2P ACTFPKEB3P ACTFPKSF ACTFPKQD2P ACTFPKQD3P ACTFPKJD ACTFPKSG ACSFPKSG ACSFPKSK ACSFPKTB4

Fronts
Box Width/Depth 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 31"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D 40"W x 11.5"D X Height 15 18 21 24 27 30 33 36 39 42 15 18 21 24 27 30 33 36 39 42 Box Height (inches) 49.375 53.5 57.625 61.75 65.875 70 74.125 78.25 82.275 86.5 49.375 53.5 57.625 61.75 65.875 70 74.125 78.25 82.275 86.5 Product Number ACF3149S ACF3153S ACF3157S ACF3161S ACF3165S ACF3170S ACF3174S ACF3178S ACF3182S ACF3186S ACF4049S ACF4053S ACF4057S ACF4061S ACF4065S ACF4070S ACF4074S ACF4078S ACF4082S ACF4086S

Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Single Mounted Single Mounted Single Mounted

two-pole three-pole

Mounting HardwareHardware to Mount One Breaker


Mounting Arrangement Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Dual Mounted Single Mounted Single Mounted Single Mounted Breaker Frame SHE, SEL, SED, SEP TEB, TED, THED TEB, TED, THED TEB, TED, THED TFK, SFH, SFL, SFP TQD, THQD TQD, THQD TJD, TJJ, TJK SGD, SGH, SGL, SGP SGD, SGH, SGL, SGP SKH, SKL TB4 Maximum Breaker Amperage 150A 150A 150A 150A 250A 225A 225A 400A 400A, 600A 400A, 800A 800A, 1200A 400A single-pole two-pole three-pole Breaker Number of Poles Product Number ACTHKSE ACTHKEB1P ACTHKEB2P ACTHKEB3P ACTHKSF ACTHKQD2P ACTHKQD3P ACTHKJD ACTHKSG ACSHKSG ACSHKSK ACSHKTB4

Flush fronts (F) are 2 inches larger than box. Surface fronts (S) are 1/4-inch larger than box.

two-pole three-pole

Note: If filler plates for SCP+ panels are required, please contact Houston equipment plant. Note: THLC 1/2/4 breaker no longer available.

9-48

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Power
Renewal Parts Type CCB and QMR Panelboards Order through the Customer Service Center unless stated otherwise below.

Section 9

Mounting HardwareCopper Straps for Use on Cu or Al Main Bus Dual Mounted


Breaker Frame TEB/TED TFJ/TFK/TFL TQD TJD/TJJ/TJK TJK TLB1/THLC1 TEL TB1 SFH/SFL Kit Ampere Rating 150A 225A 225A 400A 600A 150A 150A 150A 225A Product Number TED1DPK TF2DPK TQ2DPK TJ4DPK TJ6DPK THLC1DPK TEL1DPK TB1DPK SF2DPK1,2

Complete Hole Filler Kits Ordering is easy for applications requiring both an overcurrent device and the associated mounting hardware. To order the device plus hardware, simply select the appropriate suffix from the table below and add it to the device product number. For example, a requirement for a 100A 3-pole TED breaker and hardware for a CCB panel should be ordered as TED134100DPK: Breaker/TED134100 + Suffix/DPK = Complete Unit Shipped/(1) TED134100 Circuit Breaker, (1) TED1DPK Hardware Kit Device and Hardware Suffix Selection
Device Type Panelboard Lighting Type CCB/QMR Switchboards Twin (Double) Mount DPK DPK Single Mount SPK SPK TQD, TED, Panel Subfeed

1If mounting hardware exists must order SFCARE for additional insulators. 2225A Maximum

Mounting HardwareCopper Straps for Use on Cu or Al Main Bus Single Mounted


Breaker Frame TKM8/THKM8 TB1 TB6 TB8 TKM12/THKM12 SKH8 SKH12 Kit Ampere Rating 800A 100A 600A 800A 1200A 800A 1200A Product Number TK8SPK3 TB1SPK3 TB6SPK3 TB8SPK3 TK12SPK3,4 SK8SPK3 SK12SPK3

To ensure a unit shipment, you must order using the device product number plus suffix; orders for the device and kit as separate items will ship as separate items.

3Deep mounted interior is required. 4Requires 7x of space if mounted at extreme end (top or bottom) of interior or 8x if

mounted in center of interior.

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-49

Panelboards
Spectra Series Panelboards
Power
Renewal Parts Type CCB and QMR Panelboards Order through the Customer Service Center unless stated otherwise below.

Section 9

Replacement Panelboard CCB Front (Flush or Surface)


Box Width/Depth X Height Box Height (inches) Product Number1

Replacement Panelboard CCB Box


Box Width/Depth 31" Wide x 9 1/2" Deep Box (No Knockouts) 31" Wide x 9 1/2" Deep Box (No Knockouts) 31" Wide x 9 1/2" Deep Box (No Knockouts) 31" Wide x 9 1/2" Deep Box (No Knockouts) 31" Wide x 9 1/2" Deep Box (No Knockouts) 31" Wide x 9 1/2" Deep Box (No Knockouts) 35" Wide x 11 1/2" Deep Box (No Knockouts) 35" Wide x 11 1/2" Deep Box (No Knockouts) 40" Wide x 11 1/2" Deep Box (No Knockouts) 40" Wide x 11 1/2" Deep Box (No Knockouts) 40" Wide x 11 1/2" Deep Box (No Knockouts) 40" Wide x 11 1/2" Deep Box (No Knockouts) 40" Wide x 11 1/2" Deep Box (No Knockouts) 40" Wide x 11 1/2" Deep Box (No Knockouts) 40" Wide x 11 1/2" Deep Box (No Knockouts) 40" Wide x 11 1/2" Deep Box (No Knockouts) X Height 15X 21X 24X 27X 30X 36X 33X 39X 21X 24X 27X 30X 33X 36X 39X 42X Box Height (inches) 49 57 5/8 61 3/4 65 7/8 70 78 1/4 74 1/8 82 3/8 57 5/8 61 3/4 65 7/8 70 74 1/8 78 1/4 82 3/8 86 1/2 Product Number DASW3121 DASW3127 DASW3130 DASW3133 DASW3136 DASW3142 DACB3539 DACB3545 DACB4027 DACB4030 DACB4033 DACB4036 DACB4039 DACB4042 DACB4045 DACB4048

31" Wide x 9 1/2" 15X 49 CBA3121S,F Deep Box (No Knockouts) 31" Wide x 9 1/2" 18X 53 1/2 CBA3124S,F Deep Box (No Knockouts) 31" Wide x 9 1/2" 21X 57 5/8 CBA3127S,F Deep Box (No Knockouts) 31" Wide x 9 1/2" 24X 61 3/4 CBA3130S,F Deep Box (No Knockouts) 31" Wide x 9 1/2" 30X 70 CBA3136S,F Deep Box (No Knockouts) 31" Wide x 9 1/2" 42X 86 1/2 CBA3148S,F Deep Box (No Knockouts) 35" Wide x 11 1/2" 36X 78 1/4 CBA3542S,F Deep Box (No Knockouts) 40" Wide x 11 1/2" 21X 57 5/8 CBA4027S,F Deep Box (No Knockouts) 40" Wide x 11 1/2" 24X 61 3/4 CBA4030S,F Deep Box (No Knockouts) 40" Wide x 11 1/2" 30X 70 CBA4036S,F Deep Box (No Knockouts) 40" Wide x 11 1/2" 33X 74 1/8 CBA4039S,F Deep Box (No Knockouts) 40" Wide x 11 1/2" 36X 78 1/4 CBA4042S,F Deep Box (No Knockouts) 40" Wide x 11 1/2" 39X 82 3/8 CBA4045S,F Deep Box (No Knockouts) 1Flush fronts (F) are 2 inches larger than box. Surface fronts (S) are 1/4-inch larger

than box.

Note: Box dimensions are inside dimensions. Add 1/4-inch for outside dimensions. Boxes furnished without knockouts as standard.

Filler Plates
Panel Type QMR QMR QMR QMR CCB CCB CCB CCB CCB SCP+ SCP+ SCP+ SCP+ X Height 1X 2X 5X 3X 1X 3X 5X 2X 6X 1X 2X 3X 5X Product Number QMRFP1 QMRFP2 QMRFP5 75C145005G703 CCBFP1 CCBFP3 CCBFP5 75C145005G711 75C145005G715 SCPFP1 SCPFP2 SCPFP3 SCPFP5

(Order from Local Sales Office or Equipment Plant

9-50

BuyLog Catalog

www.geindustrial.com

Rev. 9/12
Prices and data subject to change without notice

Panelboards
Spectra Series Panelboards
Power
Renewal Parts Type CCB and QMR Panelboards Order through the Customer Service Center unless stated otherwise below.

Section 9

QMR Fusible Switch 240V1, 2


Switch Amps 30 30 60 60 60 60 100 100 200 400 600 Number of Poles 3 3 3 3 3 3 3 3 3 3 3 Description Left Hand Unit Right Hand Unit - 3X Right Hand Unit Left Hand Unit Right Hand Unit - 3X Left Hand Unit - 3X Right Hand Unit Left Hand Unit Center Mount Center Mount Center Mount Product Number THFP321L THFP321X THFP322 THFP322L THFP322X THFP322XL THFP323 THFP323L THFP324 THFP325 THFP326

QMR Fusible Switch 600V1, 2


Switch Amps 30 30 60 60 100 100 200 400 600 800 1200 Number of Poles 3 3 3 3 3 3 3 3 3 3 3 Description Right Hand Unit Left Hand Unit Right Hand Unit Left Hand Unit Right Hand Unit Left Hand Unit Center Mount Center Mount Center Mount Center Mount Center Mount Product Number THFP361 THFP361L THFP362 THFP362L THFP363 THFP363L THFP364 THFP365 THFP366 THFP367 THFP368

1Limited availability. Obsolete when inventory depleted. 2Switch and mounting hardware kit must be ordered separately

QMR Mounting Hardware Kits Are Copper for Use with Cu or Al Main Bus Dual Mounted
Breaker Frame THFP THFP THFP THFP Kit Ampere Rating 30-60A 100A 100A 100-30/60 Voltage 240 & 600V 600V 240 & 600V 600V Product Number THFP62DPK THFP63DPKJ THFP63DPK THFP63DPKC

Maximum Horsepower Ratings QMR Fusible Switch


Vac Rating in Amperes3 120 240 2-Pole 480 600 3 10 15 30 15 25 40 50 240 3 7 1/2 15 25 50 75 10 20 30 60 125 200 3-Pole 480 5 15 25 50 100 150 20 40 60 125 250 400 600 7 1/2 15 30 60 125 200 20 50 75 150 350 500 Vdc 2-Pole 3-Pole 125 2 5 3 5 250 5 10 20 40

Note: QMR Power Panelboards 600V, 100A double branch units require a minimum width of 40". 600V, 30A and 60A double branch, and 240V, 30A, 60A and 100A single and double branch units can be built in a 35" wide enclosure.

QMR Mounting Hardware Kits Are Copper for Use with Cu or Al Main Bus Single Mounted
Breaker Frame THFP THFP THFP THFP THFP THFP THFP Kit Ampere Rating 30/60A 30/60/100A 100A 200A 400A 600A 1200A Voltage 240V 240V & 600V 600V 240 & 600V 240 & 600V 240 & 600V 240 & 600V Product Number THFP22SPK THFP62SPK THFP63SPK THFP64SPK THFP65SPK THFP66SPK THFP67SPK

With Standard and Fuses (Class H) 30 1/2 1 1/2 3 60 1 1/2 3 5 100 7 1/2 10 200 15 25 400 600 With Time-delay Fuses (Class H) 30 2 5 10 60 3 10 20 100 15 30 200 30 50 400 600

3Ratings are based on latest revision of the National Electric Code Article 430.

Horsepower ratings for switches with standard class H fuses are based on one-time fuses having minimum time-delay. When time-delay fuses are used the horsepower ratings are maximum for the switches.

Note: QMR Power Panelboards 600V, 100A double branch units require a minimum width of 40". 600V, 30A and 60A double branch, and 240V, 30A, 60A and 100A single and double branch units can be built in a 35" wide enclosure.

QMR Fusible Switch Terminations4


Switch Amperes 30 60 100 200 400 600 800 1000 Voltage 250/600 250/600 250/600 250/600 250/600 250/600 250/600 250/600 Wire Range (Cu/Al) #14-10 #14-2 #10-1/0 #6-250kcmil or 2(I/O-250kcmil) #6-250kcmil or 2(I/O-250kcmil) 250-350kcmil Cu or 350-500kcmil Al #4-600kcmil #4-600kcmil Wires per Lug 1 1 1 1 1 2 1 1 Lugs per Phase 1 1 1 1 1 2 4 4

4For optional lugs refer to GEH-460B

Rev. 9/12
Prices and data subject to change without notice

www.geindustrial.com

BuyLog Catalog

9-51

Panelboards
Spectra Series Panelboards

Section 9

Available Publications Spectra Series Power Panels Plug-In and Bolt-On


Circuit Breaker Mounting Instructions (Modules) TKM, THKM, TK4V, TKL4V, SKHA, SKLA, SKPA TJK, TJD, TJJ, THJK, TJ4V, THJ4V, TJL4V TEB, TED, THED, TEL, SEDA, SEHA, SELA, SEPA TFJ, TFK, THFK, TFL, SFHA, SFLA, SEPA TQD, THQD THLC1 SGDA, SGHA, SGLA, SGPA (3 pole) SGDA, SGHA, SGLA, SGPA (2 pole) THLC2, THLC4, TLB4 (3 pole) THLC2, THLC4, TLB4 (2 pole) TEY, THQB, THHQB Circuit Breaker Mounting Hardware Kits TQD, THQD, SE TEB, TED, THED, THLC1, SF, TFJ, TFK, THFK, SG, TJK, THJK, TJD, TJJ, THLC2, THLC4 Installing Lugs Type AML Main Lug Kits Type AML Feed Thru Main Lug Kits Installing Fusible Switches Fuse Pullers Class R Fuse Rejector Kit R Fuse Rejection Pin, 400-600 Ampere Switch Units Lug Kits into GE Type ADS Switches Alternate Lugs, 30-1200 Ampere Fusible Switch Units Installing Fusible Switch Expansion Kits 30/60 Ampere Expansion Kit 60A, 100A Expansion Kits for Type ADS Fusible Switch Units 200 Ampere Expansion Kit (J, T Fuses) 200 Ampere Expansion Kit (H, K, R Fuses) Handle and Load Base Replacements on Fusible Switches Handle Replacement: 400-1200 Ampere Switches Load Base Replacement for Type ADS 400-600 Ampere Switches Miscellaneous Typical - Fusible Mains and Feeders Technical Data, Spectra Series Panelboards - Pressure Locked Connectors DE-166 DE-168 GEH-5553 GEH-5576 GEH-5547 GEH-5581 GEH-5582 GEH-5889 DEH-034 GEH-4616 GEH-5577 GEH-5944 GEJ-3050 GEH-5588 GEH-5630 GEH-5913 GEH-5623 GEH-5624 GEH-5625 GEH-5626 GEH-5643 GEH-5644 GEH-5673 GEH-5674 GEH-5675 GEH-5676 GEH-5677

Spectra Series Plug-In (Only) (continued)


Installing Fusible Switches Fuse Pullers Class R Fuse Rejector Kit R Fuse Rejection Pin, 400-600 Ampere Switch Units Lug Kits into GE Type ADS Switches Alternate Lugs, 30-1200 Ampere Fusible Switch Units Installing Fusible Switch Expansion Kits 30/60 Ampere Expansion Kit 60A, 100A Expansion Kits for Type ADS Fusible Switch Units 200 Ampere Expansion Kit (J, T Fuses) 200 Ampere Expansion Kit (H, K, R Fuses) Handle and Load Base Replacements on Fusible Switches Handle Replacement: 400-1200 Ampere Switches Load Base Replacement for Type ADS 400-600 Ampere Switches Miscellaneous Typical - Fusible Mains and Feeders Technical Data, Spectra Series Panelboards - Pressure Locked Connectors DE-166 DE-168 GEH-5553 GEH-5576 GEH-5547 GEH-5581 GEH-5582 GEH-5889 DEH-034 GEH-4616 GEH-5577 GEH-5944 GEJ-3050

Spectra Series Bolt-On (Only)


Circuit Breaker Mounting Instructions (Straps) TEB, TED, SGH, SFL, SFP SGH, SGL, SGP SKH, SKL, SKP, TKM, THKM TEY TQD, THQD D, SEH, SEL, SEP DEH-047 DEH-059 DEH-060 DEH-061 DEH-062 DEH-065

A-Series Panelboards
Lighting Panel Rating Labels GE Panelboards Stainless Steel Enclosures AD Plus Lighting Panelboards UL Recognized Series Connected Ratings DEH-40007 DEA-185 DET-386 DEP-131 DET-008

Spectra Series Plug-In (Only)


Circuit Breaker Mounting Instructions (Modules) TKM, THKM, TK4V, LA, SKPA GEH-5623 GEH-5624 GEH-5625 GEH-5626 GEH-5643 GEH-5673 GEH-5674 GEH-5675

A-Series Lighting Control Panel


Lighting Control Panel Catalog/Selection Guide Fact Sheet DEA-388 DET-398

TJK, TJD, TJJ, THJK, TJ4V, THJ4V, TJL4V TEB, TED, THED, TEL, SEDA, SEHA, SELA, SEPA TFJ, TFK, THFK, TFL, SFHA, SFLA, SEPA TQD, THQD SGDA, SGHA, SGLA, SGPA (3 pole) SGDA, SGHA, SGLA, SGPA (2 pole) THLC2, THLC4, TLB4 (3 pole) Circuit Breaker Mounting Hardware Kits TQD, THQD, SE TEB, TED, THED, THLC1, SF, TFJ, TFK, THFK, SG, TJK, THJK, TJD, TJJ, THLC2, THLC4 Installing Lugs Type AML Main Lug Kits Type AML Feed Thru Main Lug Kits

Pro-Stock Panelboard
Selection and Pricing Guide Fact Sheet Product Summary Initial Stock Order Form Branch Breaker Recommended Stock List DEP-104A DET-233 DEE-240 DEZ-176 DEE-241 DEZ-178 DEA-232 DEE-240 DEQ-068

GEH-5913

Pro-Stock Literature Order Form Sell Sheet

GEH-5588 GEH-5630

New Product Commercialization Summary Q&A

9-52

BuyLog Catalog

www.geindustrial.com

Rev. 4/12
Prices and data subject to change without notice

You might also like