___ Reviewthedesigndocumentsandthespecifications. ___ VerifythattheVFD___description,___specifications,___technicaland troubleshootingguideandtheinstallation,___programmingrecordand___balance reportareonsite. Fromthedesigndocumentsdetermine:LocationfortheDPmeasurement: _____________________________________________________________________ Controlstrategyforthepump:__________________________________________ _________________________________________________________________________
II.
VFD Installation
File: 158431442.doc
Page 1 of 5
-SAMPLE-
PressureOffset(Po) Conversion:psix2.31=ftH 2O DPpumpisbeingcontrolledto:_______feet[A]. Pressureriseacrosspumpatdesignconditions(frombalancereport):_______feet[B]. Pressureoffset,Po,[A][B]=_______. Optimally,Poshouldbe0.3orlessinorderfortheVFDandpumptobeabletorespond tosmallpressurechangesandrealizeadequateenergysavings.IfPoisgreaterthan0.4, theDPsensorisprobablylocatedtooclosetothepump. ___Complies? BalancingtoLowestPressure ReviewtheHVACbalancereportandverify,accordingtothereport,thatthesystem wasbalancedsotheVFDcontrolstothelowestpossibleDP(thatisacapacitytestwas performed).ThecontrollingDPfrombalancereportsis_________feet.Atdesign,the correspondingVFDfrequencyorpumpRPMfromthebalancereportis:Pump1 ________,Pump2_______;Pump3_____.Thecorrespondingflowfromthebalance reportis_______GPM.Refertothecapacitytestattheendofthisformfordetails. ___BalancedtolowestDP? GeneralIssues ___ Verifythatanypowerqualitymitigationmeasuresrequiredfromthespecificationshave beencompleted. ___ Verifythatthereareno3waycoilvalvesthatmaynegatethevalueoftheVFDby allowingflowtobypassthecoil,exceptforaverysmallmin.flowbypass. ___ VerifyverballythattheaccelerationanddecelerationramptimeoftheVFDisbetween oneandfourminutes.Actualramptime:up_____min.down_____min.(tooshort oframptimeswillresultin"hunting"andexcessmodulationbytheVFD;typicalramp timesare1to4minutes) ___ VerifythateachVFDhasbeenintegratedintotheEMSasperspecification. ___ Verifythatthelowerfrequencylimitisprogrammedto1030%(thelowerthebetter). ___ VerifythattheEMSmonitorstheDP. ___ Min.flowbypasswith2wayorconstantflowvalve,ifpresent,hasflowlessthan2%of designflow? ___ ShutoffpowerfeedingVFD.RestorepowerandverifythatVFDresetsautomatically.
Notes:
File: 158431442.doc
Page 2 of 5
-SAMPLE-
2.
3.
Notes:
File: 158431442.doc
Page 3 of 5
-SAMPLE-
IV. Analysis
Table 1.
Speed(HzorRPM) Condition 1.AtdesignflowbyTAB Secondary PumpNo. Lead Lag1 Lag2 Lead 2.Atdesignflow(during commissioning) 3.Atintermediateflow (duringcommissioning) 4.Atnoflow(during commissioning) Lag1 Lag2 Lead Lag1 Lag2 Lead Lag1 Lag2 Conversion:0.434xftH2O=psi,2.31xpsi=ftH2O Reading Average DPatSensor(psi) Reading Average Total Flow (gpm)
1. 2.
InTable1,averagethespeedandtheDPforallpumpsateachofthefourconditions. IfthespeedatCondition1(TABtest)isnotwithin10%ofthecurrenttestatCondition2, alltheboxesmaynothavebeendrivenwideopenduringtheCxgtest,orthereadings weretakenbeforethelagtimewascomplete.Investigateandrepeattestsasappropriate. ___Lessthan10%variance? 3. Duringoperationofleadlagpumpcombinations,theaverageDPreadingsatallfour conditionsshouldremainwithin10%ofeachother.Ifthethereismorethana10% variance,thesensormaybefaulty.(Duringleadlagpumptransition,theDPmay appropriatelyvarybyasmuchas20%) ___Lessthan10%variance? 4.___Atnoflow,Condition4,istheflowandDPzeroorequaltothemin.flowbypass? 5.___ForthetotalflowreadingsinTable1,arethevaluesinCondition2>3>4? 6.___CollaborativeTrending Thesystemoperationwill,willnot(circle)betrendedtofurtherverifytheproper operationoftheVFD.PointstobetrendedarelistedintheTrendingRequestForm. ___Fromstudyingthetrends,istheVFDisfunctioningproperly?
Notes:
File: 158431442.doc
Page 4 of 5
-SAMPLE-
7.
Additionaltests.Refertothechilledwatersystemssequenceofoperationstestsfor furthercollaborationontheVFDperformance.
V. Training
___Thetrainingspecifiedinthedesignincentiveagreementhasbeencompleted.
___AnacceptableO&MPlanhasbeenputintoplace.Describe:
Toinsurethatenergyuseisminimized,thehydronicsystemmustbebalancedatdesignconditions atthelowestpossibledifferentialpressure(DP)possible.ThisrequiresthatthelowestpossibleDP atthesensorbefoundthatwillallowthedeliveryofdesignflowthroughthevalvemostdifficultto satisfy.ThissystemminimumDPfoundiswhattheVFDshouldcontrolto.Thisisaccomplished bychangingthetemperaturesetpointforallzonesto55Fforcoolingcoilsor85Fforheatingcoils, causingallAHUcoilvalvestobecallingforfullcoolingorheating,asapplicable.Eachcoilsflow isthenmeasuredagainstthedesignflow.Thecoilthatisreceivingthelowestfractionofdesignis identified.ThecurrentDPatthecontrollingsensorisnoted.Acalculationismade,givingtheDP requiredatthesensortoallowtheidentifiedmostcriticalcoiltomeetitsdesignflow.Theequation isDP2=DP1xQ22/Q12.WhereQ1=actualorfractionofdesignflowduringcapacitytest.Q 2= designflowor1.0ifusingfractions.DP 1=DPatsensor.DP2=DPtocontrolto.Itisnotedthatif allcoilswerecallingforfullcoolingsimultaneously,thepumpcouldnotmaintainthenewDP 2 value,duetodiversitypumpsizereductionhavingbeenmadebythedesignengineer.
Parties required for VFD site commissioning work CommissioningagentTowitnessandrecordthetests. EMSoperatorTodriveboxesopenandshutbychangingthesetpoints,etc. VFDtechnicianTousethekeypadtoverifytheramptime.(unlessverifiedatstartup,whichisrecommended).Sequencing thekeypadtodisplayramptimecouldbedonebythecommissioningagent,aloneafterreviewingtheVFDtechnicalmanual.
Notes: