You are on page 1of 1

CUADRO

ITEM CONCEPTO Iluminacin y tomacorrientes 1) OFICINAS TDG 1) ALMACEN Y PATIO DE MANIOBRAS 3) SS.HH. 4) CIRCULACIN 5) 20 Equipos: Alumbrado Emergencia(30 W) 23.45 1930 11.05 6.6 50 5 5 5 30 1172.5 9650 55.25 33 600 A.Tech C.unit m2 W/m2 C.INSTAL W

DE

MAXIMA
M.DEM PARC. 1172.5 9650 55.25 33 600 M.DEM TOTAL

DEMANDA
In A Id A If A It A Ic A ALIMENTADOR PRINCIPAL L m V V

F.DEM % 100% 100% 100% 100% 100%

11,510.75 19.5 24.3 29.2

63

75

3 - 16 mm2 THW + 1-16 mm2 THW (N) +1-16 mm2 THW (T) TRIFASICO ACOMETIDA

0.207070441

MAXIMA DEMANDA TOTAL

11,510.75 19.5 24.3 29.2

100

120 3 - 16 mm2 THW + 1-16 mm2 THW (N) TRIFASICO

0.207070441

JUSTIFICACION TECNICA : In = 23,993.90 / (1.73x380x0.9) = Id = In x 1.25 = If = In x 1.5 = Id < It < Ic 50.7 A < 63 A < 75A a) ACOMETIDA : 3-16 mm2 THW, 1kv +1-16 mm2 THW,1kv(N) , Tubo de FG, Dimetro 50mm b) INTERRUPTOR TERMOMAGNETICO : 3X63 A, Capacidad de ruptura 25 KA, ubicado en el TDG 19.5 24.3 29.2 A A A

LEYENDA In = Intensidad Nominal en (A) Id = Intensidad de Diseo en (A) It = Intensidad del Termomagntico en (A) If = Intensidad de Fuse en (A) Ic = Intensidad del Conductor (A)

c) CONDUCTOR DE POZO DE TIERRA : 1-16 mm2 THW, en tubo PVC-SAP, Dimetro 20 mm, ubicado en el TDG , y 1-25 mm2 THW, en tubo de Dimetro 25 mm, ubicado en la Caja F1 Nota : El calibre de la Acometida ha sido seleccionado teniendo en cuenta la Cada de Tensin para una distancia de 5 m.