Connection Diagram
8
9 5 7 3 4 1 2 13 14 11 12 10 6 8
1(+)
6 2 7 11 13
Description
Electronic plug-in railway monitoring relay for battery voltages. The relay reacts on the mean value of a DC-voltage with ripple. The pull-in voltage and hysteresis is adjustable by means of multiturn trimpotentiometers. The pull-in time after crossing the setpoint is < 15ms. The drop-out time is approximately 20 ms, which can be extended to 250 ms. (see below) Optional the relay can be supplied with fixed (sealed) set values, or led indication. The ACD relays are pluggable into standard D and D-U sockets.
Input data
Type ACD-U201 ACD-U202 ACD-U203 ACD-U204 ACD-U205 ACD-U207 U nom (V) 24 48 72 110 96 36 U max (V) 35 70 105 160 140 52 U pull-in (V) *) U hysteresis (V) Power consumption (W) 2133 18 < 0.55 4266 216 < 0.85 6399 324 < 1.15 90140 537 < 1.35 84132 432 < 1,30 3150 1,512 < 0.75 <15 ms 20 ms 250 ms 1% 0.1 %/K
Working Principle
Adjustments
NIEAF-SMITT
330403101.TSP-01
16-02-2005
Contact data
Max. make current 15 A Material Ag+0.2m Au Max. cont. current 6 A ( AC1 ; IEC 60947 ) Contact gap 0.3 mm Max. switching voltage Insulation between 1 kV; 50 Hz; DC 300 V, 300 mA open contacts 1 min AC 250 V, 2.6 A Contact force > 20 cN Min. switching voltage 4V / 2mA / 0.1W-VA Note : contacts cannot have a different 15 m Max. contact resistance position. (Forced contacts, Weld-no-transfer) Maximum switching capacity and contact life: see graph
Max Switching Capacity
1000 100
Contact Life
DC 2 contacts in serie
DC resistive
Watt
100
10
DC inductive
DC 1 contact
1 0,10
1,00
100,00
General Data
Dielectric strength Pole-Pole Cont-Coil Pulse withstanding EMC Vibration IEC 60255-5 IEC 60077 IEC 60255-5 IEC 60255-5 IEC 60077 IEC 60571-1 IEC 60068-2-6 IEC 60068-2-27 3,5 kV, 50 Hz 4 kV, 50 Hz 5 kV ( 1.2/50 s ) 2.5 kV, 1 MHz, 400 Hz, 10 s 5 g at 50 Hz 2 g, 10-150 Hz 15 g, 11 ms 30*106 ops 1200 ops/h 120 g + 70 C - 25 C 80 %, temporary permitted condensation IP 40 Polyester Makrolon
Shock Mechanical life Max. switching frequency Weight Temperature Humidity Protection Materials
Tamb,max Tamb,min
NIEAF-SMITT
330403101.TSP-02
16-02-2005