You are on page 1of 5

Project : ITCC - SPORTS CLUB Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty.

Point Description
Plumbing and Fire Protection Equipments Water Meters Incoming Water Flow [Water Meter] Total per Unit Total for all Units Total Water Meters Points Flow Meter for Swimming Pool Water Flow Total per Unit Total for all Units Total FlowMeters Points Swimming Pool Surge Tank 1 2 3 4 1 Tank Low Level Alarm Tank High Level Alarm Potable Make-up Incoming Water Flow Tank Level (%) Monitor Total per Unit Total for all Units Total Swimming Pool Surge Tank Points Grey Water Tanks 1 2 3 4 5 6 1 Tank Low Level Tank High Level Potable Make-up Incoming Water Flow Influent Dirt Interceptor SHOCKED Alarm Tank water volume reading Tank Level (%) Monitor Total per Unit Total for all Units Total Grey Water Tank Points 1 1 3 3 1 1 1 2 2 1 1 2 1 1 1

AI

Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration

Remarks

Flow Meter 0 0 1 0 0 0 0

Flow Meter 0 0 2 0 0 0 0

1 1

From Tank Float Switch From Tank Float Switch Solenoid valve (4-20)mA from the Level Indicator

2 2 4

0 0

0 0

1 1 1

From Tank Float Switch From Tank Float Switch Solenoid valve Float Switch Relay Output From BMS (4-20)mA from the Level Indicator

3 3 6

0 0

0 0

1 of 5

Project : ITCC - SPORTS CLUB Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty.
1 2 3 4 5 4 Pump on/off Status Pump Trip Status Pressure in the Common Discharge Header Pump Auto / Manual Status Sump High & Low Level Total per Unit Total for all Units Total Sump Pumps Points Chrlorine Injection Unit & Acid Injection Unit for Swimming Pool 1 2 3 4 5 6 7 2 Dosing Pump On/Off Status Chemical flow status Dosing Pump Trip Alarm Dosing Pump Auto / Manual Status Dosing Pump Start/stop command Chemical Tank Level Chemical Tank Low Level Alarm TOTAL Total Chlorine Unit & Acid Unit Points Total Chlorine & Acid Unit Points 0 0 1 2 1

Point Description
Sump Pumps-SP1 TO SP-2 [1-Duty & 1-Lag] - 2Lift Sta.

AI

Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
2 1 1 2 6 24 26 0 0 0 0

Remarks
From Pump Control Panel From Pump Control Panel Liquid Pressure Sensor From Pump Control Panel From Tank Float Switch

1 1 1 1 1 1 1 6 12 14 0 0 1 2

From Swimming Pool Control Panel Flow switch From Swimming Pool Control Panel From Swimming Pool Control Panel Relay Output From BMS From Swimming Pool Control Panel From Swimming Pool Control Panel

Odor Control Unit, Chlorination Unit & Coloring Dye Unit of Grey Water Treatment Plant (1 unit each plant x 1no. plant) 1 2 3 4 5 6 7 3 Dosing Pump On/Off Status Chemical flow status Dosing Pump Trip Alarm Dosing Pump Auto / Manual Status Dosing Pump Start/stop command Chemical Tank Level Chemical Tank Low Level Alarm TOTAL Total Odor Control, Chlorination, Coloring Dye Units Points Total Odor, Chlorination, Coloring Dye Units Points 0 0 1 1 6 18 21 0 0 1 3 1 1 1 1 1 From Grey Water Treatment Plant Panel Flow switch From Grey Water Treatment Plant Panel From Grey Water Treatment Plant Panel Relay Output From BMS From Grey Water Treatment Plant Panel From Grey Water Treatment Plant Panel

2 of 5

Project : ITCC - SPORTS CLUB Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty.
1

Point Description
Air Purification Unit (Aerator) - 1no. each Grey Water Treatment Plant Aerator On/Off /Fault Status TOTAL Total Aerator Unit Points Total Aerator Unit Points Non-Potable water pumps [2-Duty&1-Standby]- 1set

AI

Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
3

Remarks
From Grey Water Treatment Plant Panel

0 0

3 3 3

0 0

0 0

1 2 3 4 5 6 7 8 3

Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Discharge header pressure Pump motor temperature high TOTAL Total Non-Potable Water Pumps Points Total Non-Potable Water Pumps Points Filter Pumps for Grey Water Treatment Plant, [2-pumps x 1-set] 1 1 2 6

1 1 1 1 1 1

VFC From Pump Control Panel Flow switch VFC From Pump Control Panel VFC From Pump Control Panel Relay Output From BMS Liquid pressure switch Liquid pressure sensor From Pump Control Panel

5 15 24

0 0

1 3

1 2 3 4 5 6 7 2

Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Pump motor temperature high TOTAL Total Filter Pumps for Grey Water Treatment Plant -Points Total Filter Pumps for Grey Water Treatment Plant -Points 1 1 2

1 1 1 1 1 1 5 10 14 0 0 1 2

From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure switch From Pump Control Panel

Sand Filters & Activated Carbon Filters for Grey Water Treatment Plant [1 nos. Sand Filters x 1 nos.plant + 1 nos. Activated C.Filters x 1 plant] High D P of Sand Filters 1

DP Differential Pressure Switch from Grey Water

3 of 5

Project : ITCC - SPORTS CLUB Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty.
2 TOTAL Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points Swimming Pool Filter High D P of Sand Filters TOTAL Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points Swimming Pool Circulating Pumps [2-Duty&1-Standby]- 1set 1 2 3 4 5 6 7 8 3 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Discharge header pressure Pump motor temperature high TOTAL Total Swimming Pool Circulating Pumps Points Total Swimming Pool Circulating Pumps Points Hot Water Circulating Pumps [1-Duty & 1-Standby] 1 2 3 4 5 2 Pump On/Off Status Pump Trip Alarm Pump Start/stop command Discharge header pressure Pump motor temperature high TOTAL Total Hot Water Circulating Pumps Points Total Hot Water Circulating Pumps Points 1 1 2 4 1 1 2 6

Point Description

AI
1 2

Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
0 0 2 0 0 0 0

Remarks
Treatment Plant Panel

1 1 2 0 0 2 0 0 0 0

DP Differential Pressure Switch from Swimming Pool Control Panel

1 1 1 1 1 1

From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure switch Liquid pressure sensor From Pump Control Panel

5 15 24

0 0

1 3

1 1 1

From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure sensor From Pump Control Panel

2 4 10

0 0

1 2

4 of 5

Project : ITCC - SPORTS CLUB Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Water Quality Monitor Unit for swimming pool 1 1 PH of swimming pool water TOTAL Total Water Quality Monitor Points Total Water Quality Monitor Points UV Reactor for Swimming Pool 1 2 1 UV Reactor ON/Off /Fault Status UV Lamps run hours TOTAL Total Aerator Unit Points Total Aerator Unit Points Electric Water Heaters [EWH] for Swimming Pool 1 1 EWH On/Off Status TOTAL Total Electric Water Heaters -Points Total Electric Water Heaters -Points Electric Water Heaters [EWH] for Building 1 11 EWH On/Off Status TOTAL Total Electric Water Heaters -Points Total Electric Water Heaters -Points 0 0 0 0 0 0 0 0

AI

Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration

Remarks

1 1 1 1 0 0 0 0

From Swimming Pool Control Panel

3 3 3 4 0 0 1 1 1

From UV Reactor Panel Relay Output From BMS

1 1 1 1 0 0 0 0

From Swimming Pool Control Panel

1 1 11 11 0 0 0 0

From Building Local Control Panel

5 of 5