16100 S. Lathrop Ave. Harvey, Illinois 60426 (708) 339-1610 (800) 882-5543 Fax (708) 339-0615
UL LISTED RIGID SCH-40 ELECTRICAL CONDUIT RATED FOR 90 DEGREE CELSIUS WIRING
Allied Schedule-40 is sunlight resistant and manufactured in accordance and complies to: Underwriters Laboratories, Inc. NEMA UL-651 TC-2
Meets or exceeds the requirements of NEMA TC-2 and UL-651 for Schedule 40 Conduit.
Schedule 40 PVC Conduit Dimensions (10' lengths with belled ends) Trade Size 2 4 1 114 112 2 212 3 312 4 5 6
1 3
No. 8102 8103 8104 8105 8106 8108 8110 8112 8114 8116 8120 8124
O.D. .840 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.000 4.500 5.563 6.625
Min. I.D. .622 .824 1.049 1.380 1.610 2.067 2.469 3.068 3.548 4.026 5.047 6.065
Wall .109 .113 .133 .140 .145 .154 .203 .216 .226 .237 .258 .280
Wt/Ft .164 .218 .321 .434 .518 .695 1.096 1.435 1.729 2.043 2.776 3.600
Ft/Pallet 6000 4400 3600 3300 2250 1400 930 880 630 570 380 260
SPECIAL INFORMATION 1. 20' lengths available on special request. 2. Minimum shipment: full pallet quantity per size.
16100 S. Lathrop Ave. Harvey, Illinois 60426 (708) 339-1610 (800) 882-5543 Fax (708) 339-0615
UL LISTED EXTRA HEAVY WALL SCHEDULE-80 PVC CONDUIT 90 DEGREE CELSIUS RATED
Allied Schedule-80 is sunlight resistant and manufactured in accordance and complies to: Underwriters Laboratories, Inc. NEMA UL-651 TC-2
Meets or exceeds the requirements of NEMA TC-2 and UL-651 for Schedule 80 Conduit.
Schedule 80 PVC Conduit Dimensions (10' lengths with belled ends) Trade Size 2 4 1 114 112 2 212 3 4 5 6
1 3
Cat. No. 9302 9303 9304 9305 9306 9308 9310 9312 9316 9320 9324
I.D. .546 .742 .957 1.278 1.500 1.939 2.323 2.900 3.826 4.813 5.761
O.D. .840 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.500 5.563 6.625
Min. Wall .147 .154 .179 .191 .200 .218 .276 .300 .377 .375 .432
Wt/Ft .205 .278 .409 .567 .686 .949 1.449 1.938 2.833 3.850 5.411
Ft/Pallet 6000 4400 3600 3300 2250 1400 930 880 570 380 260
SPECIAL INFORMATION 1. 20' lengths available on special request. 2. Minimum shipment: full pallet quantity per size.
16100 S. Lathrop Ave. Harvey, Illinois 60426 (708) 339-1610 (800) 882-5543 Fax (708) 339-0615
RIGID PVC UTILITY DUCT RATED FOR 90 DEGREE CELSIUS WIRE TYPE DB-60 FOR DIRECT BURIAL
NEMA TC-6 DB-60 Trade Size 2 3 4 5 6 Part No. 7508 7512 7516 7520 7524 O.D. 2.375 3.500 4.500 5.563 6.625 Min. Wall .060 .092 .121 .152 .182 Weight /foot .361 .716 1.171 1.778 2.500 Ft/ lift 2800' 1760' 1140' 760' 520'
SPECIAL INFORMATION 1. 20' lengths are standard, 10' lengths available on special request. 2. Minimum shipment: full pallet quantity per size.
RIGID PVC UTILITY DUCT RATED FOR 90 DEGREE CELSIUS WIRE TYPE DB-120 FOR DIRECT BURIAL
NEMA TC-8 DB-120 Trade Size 2 3 4 5 6 Part No. 6108 6112 6116 6120 6124 O.D. 2.375 3.500 4.500 5.563 6.625 Min. Wall .077 .118 .154 .191 .227 Weight /foot .371 .836 1.402 2.150 3.045 Ft/ lift 2800' 1760' 1140' 760' 520'
SPECIAL INFORMATION 1. 20' lengths are standard, 10' lengths available on special request. 2. Minimum shipment: full pallet quantity per size.
16100 S. Lathrop Ave. Harvey, Illinois 60426 (708) 339-1610 (800) 882-5543 Fax (708) 339-0615
RIGID PVC UTILITY DUCT RATED FOR 90 DEGREE CELSIUS WIRE TYPE EB-20 FOR ENCASED BURIAL
NEMA TC-6 EB-20 Trade Size 2 3 4 5 6 Part No. 2008 2012 2016 2020 2024 O.D. 2.375 3.500 4.500 5.563 6.625 Min. Wall .060 .061 .082 .103 .125 Weight /foot .361 .514 .843 1.268 1.729 Ft/ lift 2800' 1760' 1140' 760' 520'
SPECIAL INFORMATION 1. 20' lengths are standard, 10' lengths available on special request. 2. Minimum shipment: full pallet quantity per size.
RIGID PVC UTILITY DUCT RATED FOR 90 DEGREE CELSIUS WIRE TYPE EB-35 FOR ENCASED BURIAL NEMA TC-8 EB-35
Trade Size 2 3 4 5 6 Part No. 3508 3512 3516 3520 3524 O.D. 2.375 3.500 4.500 5.563 6.625 Min. Wall .060 .076 .100 .126 .152 Weight /foot .361 .533 .923 1.437 2.064 Ft/ lift 2800' 1760' 1140' 760' 520'
SPECIAL INFORMATION 1. 20' lengths are standard, 10' lengths available on special request. 2. Minimum shipment: full pallet quantity per size.
16100 S. Lathrop Ave. Harvey, Illinois 60426 (708) 339-1610 (800) 882-5543 Fax (708) 339-0615
PROPERTIES:
Physical Properties
Specific Gravity Tensile Strength, psi @ 73.4F Impact (Izod) ft. lbs/in. of Notch @ 73.4F Flexural Strength, psi Compressive Strength, psi Hardness (Shore D)
Value
1.4 6000 1.2 14,700 9,000 98
Thermal Properties
Heat Distortion in F at 264 psi Thermal Conductivity BTU/F2/F/in. Coefficient of Thermal Expansion in./in./F at 73.4F Coefficient of Thermal Expansion in./in./C at 23C D648 D696 D696 172 1.3 2.85x10 -5 5.13x10 -5
Electrical Properties
Dielectric Strength volts/mil Dielectric Constant 60 Cps @ 30C 1000 Cps @ 30C Power Factor 60 Cps @ 30C 1000 Cps @ 30C D149 D150 D150 1100 4.00 1.93
EXPANSION/CONTRACTION CONSIDERATIONS
Precautions to guard against expansion or contraction due to changes in the temperature should be taken. Expansion joints should be installed to eliminate stress caused by changes in length. Please see chart to determine possible expansion/contraction.
Temperature, Rise or Drop, in Deg. Fahrenheit
180 160 140 120 100 80 60 40 20 0 0.125 0.250 0.375 0.500 0.625 0.750
Change in Length of 10-Foot-Length in inches.
16100 S. Lathrop Ave. Harvey, Illinois 60426 (708) 339-1610 (800) 882-5543 Fax (708) 339-0615
16100 S. Lathrop Ave. Harvey, Illinois 60426 (708) 339-1610 (800) 882-5543 Fax (708) 339-0615
Sched-40 Wt/Ft .164 .218 .321 .434 .518 .695 1.096 1.435 1.729 2.043 2.776 3.600
Ft/Pallet 6000' 4400' 3600' 3300' 2250' 1400' 930' 880' 630' 570' 380' 260'
Full Truck 276,000' 206,800' 140,400' 102,300' 85,500' 56,000' 37,200' 28,160' 20,160' 18,240' 12,160' 8,320'
Maximum Weight per Truckload: 45,000 Lbs. Maximum Loading Units per Truckload: Approx. 44-48 Units.
16100 S. Lathrop Ave. Harvey, Illinois 60426 (708) 339-1610 (800) 882-5543 Fax (708) 339-0615
LIMITED WARRANTY
Limited Warranty.
Seller only warrants to Buyer that the goods to be shipped hereunder will meet applicable Underwriters Laboratory specifications. THE FOREGOING EXPRESS WARRANTY IS EXCLUSIVE AND IN LIEU OF ANY AND ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE. SELLER HEREBY EXPRESSLY DISCLAIMS ANY OTHER WARRANTY OF ANY KIND, WHETHER WRITTEN, ORAL OR IMPLIED, THAT THE GOODS SHALL CONFORM WITH ANY SAMPLES FURNISHED BY SELLER OR BUYER, OR THAT THE GOODS SHALL NOT DISCOLOR OR THE TEXTURE OR FINISH OF THE GOODS SHALL NOT DETERIORATE AFTER SHIPMENT BY SELLER.
Remedy.
If it appears within thirty (30) days from the date of receipt by Buyer or Buyers agent that the goods shipped do not meet Sellers above express warranty and Buyer notifies Seller, in writing, within such period, Seller, at its option, will repair or replace such defective or nonconforming goods or return the purchase price paid therefore by Buyer. THE LIABILITY OF SELLER TO BUYER ARISING OUT OF THE SALE OF GOODS OR THEIR USE, WHETHER ON WARRANTY, CONTRACT OR NEGLIGENCE IS LIMITED ONLY TO THE REPLACEMENT OR REPAIR OF DEFECTIVE GOODS OR RETURN OF THE PURCHASE PRICE, AS HEREIN PROVIDED. AND UPON THE EXPIRATION OF SAID THIRTY (30) DAY PERIOD ALL SUCH LIABILITY SHALL TERMINATE. THE FOREGOING SHALL CONSTITUTE THE SOLE REMEDY OF THE BUYER AND THE SOLE LIABILITY OF SELLER. IN NO EVENT SHALL THE SELLER BE LIABLE FOR SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES. Buyer shall bear all cost of disassembly, shipment and re-installment of any defective, repaired or replaced goods and shall return to Seller only upon written authorization of Seller, all goods for which refund of purchase price is made.
Solvent Weld Pipe Disclaimer for Both Standard and Non-Standard Products.
Because Allied cannot be assured that solvent weld pipe will be installed by persons fully acquainted with the proper installation techniques involved and the limitations upon such techniques caused by variations installation conditions, Allied DOES NOT WARRANT AND WILL NOT BE RESPONSIBLE OR LIABLE FOR ANY EXPENSES, DAMAGES, OR LOSSES WHATSOEVER CONNECTED WITH OR GROWING OUT OF OR CAUSED BY THE FAILURE OF ANY SOLVENT WELD JOINT OR BY DEFECTIVE SOLVENT USED IN MAKING ANY SUCH JOINT. This disclaimer does not apply to factory-made solvent welds.
16100 S. Lathrop Ave. Harvey, Illinois 60426 (708) 339-1610 (800) 882-5543 Fax (708) 339-0615
10
AFC Cable Systems Allied Tube & Conduit Cope Cable Tray Power-Strut Metal & Fiberglass Framing
Allied and Tyco are trademarks or registered trademarks of Tyco and/or its affiliates in the United States and in other countries. All other brand names, product names, or trademarks belong to their respective owners.
2004 Allied Tube & Conduit All Rights Reserved. Printed in U.S.A. 11/04
ATC-L-1718