Instructions

1336 PLUS & 1336 IMPACT AC Drive Main Control Board Replacement
Frames A - H
This publication will guide you through replacement of the Main Control Board on 1336 PLUS and 1336 IMPACT AC Drives. ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference publication 8000-4.5.2, Guarding Against Electrostatic Damage or any other applicable ESD protection handbook. ATTENTION: To avoid a shock hazard, assure that all power to the drive has been removed before proceeding with the following procedure. In addition, verify that the DC bus has discharged by measuring across the +DC and DC terminals of TB1 with a voltmeter. The voltage should be 0.0VDC.

1. Remove and lock-out all incoming power to the drive. 2. Remove front cover or entire enclosure as required for adequate access. 3. If a HIM is installed, remove the module by sliding it down and out of the cradle. A Frame Drives Only - Remove the screws securing the HIM cradle. Remove the cradle and cable. 4. Remove the Language Module by carefully squeezing the sides-in, and pulling outward. 5. If a Control Interface Board (L option) is installed, carefully remove the board by loosening the 2 captive screws. Position the board and attached wires off to the side of the chassis. 6. Label and remove any remaining cables/wires (note orientation) from the board. 7. Remove the screws securing the Main Control Board. Remove the board and set aside.

1336 PLUS & 1336 IMPACT AC Drive Main Control Board Replacement

8. Install the replacement Main Control Board. Re-assemble components in reverse order. If a Control Interface Board (L option) is not being used, verify that the jumpers are correctly inserted (see the drive User Manual for details). Important: If your drive is a 1336 IMPACT (Frames B-H), attach the supplied label to the chassis in the area shown below. Important: When replacing connectors, it is essential that correct alignment is verified. Particular attention should be paid to ribbon cable connectors. Misalignment of connectors could result in damage to the drive.

ATTENTION: Replace any guards previously removed before applying power to the drive. Failure to replace guards may result in death or serious injury.

1336 IMPACT Drives Attach label to chassis above Main Control Board

DANGER

Risk of electric shock and death. Disconnect power, wait 5 minutes and verify DC bus voltage before servicing. Follow instructions in manual before use. Earth ground required.

Control Interface (L Option) Board Jumpers


LA ALL EN NG UA GE MO DU LE

Language Module Control Interface (L Option) Board


LA ALL EN NG UA GE

MO

-BR

AD

-BR

LE

AD

DU LE

LE

Frames A1 - A4
1336 IMPACT is a trademark of of Rockwell Automation, Inc.

C S E L E S C S E L E S
G JO G JO

Language Module

All Other Frames

www.rockwellautomation.com
Corporate Headquarters Rockwell Automation, 777 East Wisconsin Avenue, Suite 1400, Milwaukee, WI, 53202-5302 USA, Tel: (1) 414.212.5200, Fax: (1) 414.212.5201 Headquarters for Allen-Bradley Products, Rockwell Software Products and Global Manufacturing Solutions Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation SA/NV, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846 Headquarters for Dodge and Reliance Electric Products Americas: Rockwell Automation, 6040 Ponders Court, Greenville, SC 29615-4617 USA, Tel: (1) 864.297.4800, Fax: (1) 864.281.2433 Europe/Middle East/Africa: Rockwell Automation, Herman-Heinrich-Gossen-Strasse 3, 50858 Kln, Germany, Tel: 49 (0) 2234 379410, Fax: 49 (0) 2234 3794164 Asia Pacific: Rockwell Automation, 55 Newton Road, #11-01/02 Revenue House, Singapore 307987, Tel: (65) 6356-9077, Fax: (65) 6356-9011 U.S. Allen-Bradley Drives Technical Support Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives
Publication 1336 PLUS-5.67 January, 2005
Supersedes May, 1997

P/N 74103-909 (03)


Copyright 2005 Rockwell Automation, Inc. All rights reserved. Printed in USA.

You might also like