FreseAutomaticFlowControlValve

InnovativeDesign,NoAdjustment,LightWeight,EasyInstallation

ThenewgenerationofFreseAutomaticFlowControlValveisparticularlydesignedandmanufacturedfor
maintaining optimum flow rate at constant flow even under fluctuating pressure conditions. The Frese
Cartridge introduces a replaceable orifice plate for higher performance and flexibility; it is no longer
needed to change the cartridge every time the design flow is modified. Furthermore, the use of a high
quality diaphragm between the piston and the housing eliminates friction, noise & leakage that could
influencetheaccuracyofthevalve.
The design of the inlet and outlet areas makes sure that impurities cannot stay inside the cartridge
compromising its performance. The differential pressure operating range up to 600 kPa (60 meterH2O)
makesthesizingofthecartridgeveryeasy,dependingonlyonthedesignflow.
Advantages
Timeconsumingadjustmentofthesystemiseliminated
Flowdependsonlyonthereplaceableorificeplate
Simpleselectionandidentificationofflowrate
Accuracyunaffectedbydirtordebris
Plugandplayoperation
Canbefittedadjacenttobendorfittinginpipe
Maintains5percentaccuracyofdesignflow
Suitableforflowratesfrom1.06to967literspersecond

FreseTechnicalData

Flo

FreseCartridgeOperation
Theinteractionoftwocomponents,P1andP3aresystem
pressures.P1minusP3isthetotalpressuredropacrossthe
cartridge.P2isgivenbythepressurelossacrosstheorifice
plate.
When the pressure increases, the spring will be
compressed and thereby the piston will reduce the outlet
area and vice versa. Interaction with the spring, P1 minus
P2 remains constant keeping the constant P across the
orificeplate.Theresultisaconstantflowratethroughthe
valve,independentofpressurefluctuations.

Flowrategraph

Schematicviewoftheflowdevelopmentforthecartridgetype40,Freseno.4944176.Nominalflow1.388l/s.
Thecartridgeentersthepressurerangeat23kPa(2.3meterH2O)andmaintainstheflowataconstantlevelall
thewaytill600kPa(60meterH2O).

Indicationofflowrateontheorificeplate

49=HPHighPressure
50=LPLowPressure

AfourdigitnumberontheorificeplateisidenticalwiththelastfourdigitintheFresenumber.Thecartridge
can be identified by means of this number and the corresponding flow rate can be read from the flow rate
showninthetables.


FreseTechnicalData

FreseCartridgeSpecificationdata(ForValveDN50DN800)
Material

Orings

Spring

Diaphragm

DifferentialPressure
MediumTemperature

:AISI304
:AISI316(optional)
:EPDMRubber
:AISI304
:AISI316(optional)
:ReinforcedEPDM
:13to600kPa(1.3to60meterH2O)
:20to120C

FreseAutomaticFlowControlValveSpecificationdata
ValveHousing
Orings
Fasteners
PressureRating

EndConnection
FlowRange

:DuctileIronDIN1693GGG40
:EPDM
:StainlessSteel306
:PN16(DN50DN80PN25Rating)
:DN100andabovewithPN25isoptional
:WaferTypetosuitDINPN16Flange
:RefertoCartridgeSelectionTable

TechnicalData

Freseno.
499073
499083
499093
499103
499163
499113
499123
499133
499143
499153
499173
499183
499193
499203
499213

ValveSize

L[mm]

D[mm]

H[mm]

Weight[kg]

Cartr./Valve[Pcs]

DN50
DN65
DN80
DN100
DN125
DN150
DN200
DN250
DN300
DN350
DN400
DN450
DN500
DN600
DN800

170
170
170
170
170
170
170
170
170
170
170
170
170
170
170

100
119
131
163
193
216
271
326
383
443
496
545
601
715
880

218
237
249
281
311
334
389
440
501
561
614
663
719
833
998

3.41
4.91
4.97
6.90
9.00
11.73
18.75
23.44
33.41
44.21
51.63
57.47
67.75
88.90
127.30

1
1
1
2
3
4
7
12
15
19
26
33
40
56
85

BlindCap(Freseno.4905000)canbefittedinsteadofcartridgeifdonotrequiretoutilizethefullflow
capacity.

FreseTechnicalData

CartridgeSelectionTable
Article
type

Freseno.

50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

5255179
5255184
5255189
5255194
5255200
5255206
5255213
5255220
5255227
5255235
5255243
5255251
5255260
5255269
5255279
5255287
5255292
5255298
5255303
5255308

Flow
[gpm]
16.82
17.31
17.83
18.49
19.37
20.43
21.80
23.38
25.10
27.34
28.67
31.18
34.79
39.19
45.79
50.00
55.00
59.00
65.00
70.45

Flow
[l/s]
1.061
1.092
1.125
1.167
1.222
1.289
1.375
1.475
1.583
1.725
1.808
1.967
2.194
2.472
2.889
3.154
3.470
3.722
4.100
4.444

Min.DP
[kPa]
13
13
13
13
13
14
14
14
14
14
14
14
15
16
19
22
23
24
27
29

Article
type

Freseno.

Flow
[gpm]

Flow
[l/s]

Min.DP
[kPa]

60
5266285 75.02
4.733
34
60
5266292 79.91
5.041
34
60
5266302 82.77
5.221
35
60
5266305 85.72
5.408
35
60
5266312 90.11
5.684
35
60
5266319 94.79
5.980
36
60
5266326 98.85
6.236
36
60
5266332 103.40 6.523
36
60
5266338 108.02 6.815
37
60
5266344 112.82 7.117
38
60
5266349 116.81 7.369
38
60
5266356 121.91 7.690
38
60
5266362 128.39 8.099
38
60
5266367 131.90 8.320
39
60
5266373 136.40 8.605
39
60
5266379 142.05 8.961
40
60
5266385 147.80 9.324
40
60
5266391 153.91 9.709
40
60
5266393 160.00 10.093
42
60
5266398 165.94 10.468
43

60
5266400 170.00 10.724
44
60
5266407 180.41 11.381
46
Theminimumrequireddifferentialpressureismeasuredusingthemeasurementoutletsonthevalvehousing.Inpressure
rangefrom0to400kPatheflowrateis5percents.Inpressurerangesupto600kPatheflowrateis10percents.

Selfcleaning

Duetotheadvanceddesign

Oftheinletandoutletarea

Onlyonedifferentialpressure

rangeupto600kPa

Duetothereinforceddiaphragm
ofthecartridge

FreseA/S

Sorvej8

DK4200Slagelse
Tel +4558560000
Fax+4558560091
www.frese.dk

Easier handling
Flowdependsonlyonthe
replaceableorificeplate
Minimizedfrictionandnoise,
Highaccuracy
Duetothepresenceofthediaphragm
betweenthehousingandthepiston

SoleAgent: