Inverter systems are normally used for AC backup requirements in a telecom / datacom site or anywhere a highly reliable AC power back up source is needed. NOVA is a compact and scalable inverter providing a pure sine wave AC supply. In conjunction with a DC Power system, it provides an excellent AC backup solution. The TSI (Twin Sine Inverter) uses the latest inverter technology, providing superior energy efficiency in a compact size. The inverter is designed to work from 230Vac and 48Vdc sources through AC/AC and DC/AC conversions. Unlike traditional inverters, the TSI features an AC to AC conversion that assures double filtering function. This results in an efficiency of 94% without any compromise in quality and stability of the output wave form! This off line operation mode is called Enhanced Power Conversion (EPC) . The EPC mode, which is the filtering of current and voltage, is similar to a rectifier combined with an inverter (online mode) but gives a significantly better efficiency. Compared to a UPS operating in offline mode (no current conversions) the efficiency is the same, but the rejection of grid disturbances is much higher. The online mode is usually only used during a mains outage when inverters are fed by batteries. Therefore, the TSI inverters will almost constantly provide an efficiency of 94%. It will always be the most reliable AC backup solution! The TSI inverters also have an in-built static switch function. Because no external static switch is needed, the inverter system becomes smaller, more reliable and easily expandable. As many as 32 inverter modules can be used in parallel.
AC in
AC
AC
AC in AC out
DC in
AC AC out
DC in
DC
AC DC
Output power comes from DC in Inverter is fed from the DC Power system
* Operation within lower voltage networks leads to derating of power. ** Available while Mains is available at AC input port, with magnitude control and management.
Transfer Performance
AC Output Power Nominal Output Power Output Power (resistive load) Short Time Overload Capacity Permanent Overload Capacity Admissible Load Power Factor Internal Temperature Mgmt. DC Input Specifications Nominal Voltage (DC) Voltage Range (DC) Current (at 40Vdc) Maximum Input Current Recommended Protection Voltage Ripple Input Voltage Boundaries AC Input Specifications Nominal Voltage (AC) Voltage Range (AC) Current (at 185Vac) Conformity Range Power Factor Frequency Range (selectable) Synchronization Range 230 V 185 - 265 V 12A per shelf Adjustable >99% 50 - 60 Hz 47 - 53 Hz, 57 - 63 Hz 48 V 40 - 60 V 14A (56A per shelf) 21A (84A per shelf for 5 seconds) 63A circuit breaker per shelf 2mV User selectable 750 VA 525 W 135% 15 second 110% Full (power rating from 0 inductive to 0 capacitive) Switch off
Maximum Voltage Interruption Total Transient Voltage Duration (max) Environment Altitude Above Sea Ambient Temperature Storage Temperature Relative Humidity Signaling & Supervision Display Alarms Output Supervision Weight & Dimensions Width x Depth x 1U Weight Material (casing)
0s 0s
<1500m 750VA -20 to 40C, 675VA -40 to 50C, derating up to 65C -40 to 70C 95% , non-condensing
Embedded Power
Infrastructure Management & Monitoring Outside Plant Power Switching & Controls
Emerson Network Power reserves the right to alter without notice the specification, design or conditions of supply of any product or service.