Punch Points Checklist of BTS site

Site Name-Mumbai Sr.no 1 2 3 4 5 Site ID-145MUM783 Status Remark Particulars Outdoor Unit Connection of outdoor jumper cables & GSM antenna ports should be properly tighten. Weather proofing of connection between outdoor jumper with antenna port should be properly done. Weather proofing should be done from bottom to top of antenna port and jumper connection. before installing GSM antenna,proper labelling of GSM antenna should be done. While pulling GSM antenna through ropway at resp. height,care should be taken that face of antenna(front) should be in opposite direction of tower. Connections of outdoor jumper cables & Feeder cables should be properly tighten. While removing outer insulation of Feeder cables,care should be taken that inner core of cables should not be damaged. While removing outer insulation of Feeder cables,care should be taken that direction of knife should be away from the body. Connectors of Feeder cables should be properly assembled.

6 7

10 RF cable,connector & RF connector tool should be from same manufacturer. 11 Weather proofing of connection between outdoor jumper with RF cables should be properly done. 12 Weather proofing should be done from bottom to top of RF cables and jumper connection. 13 While assembling earthing kits on each cables,care should be taken that all the earthing kits should be on same point of contact on all cables. 14 All cu cables of earthing kits should be routed alongwith the respective RF cable in downward direction i.e. there should not be any loop. 15 All cu lugs from earthing kits should be routed & grounded separately on EGB. 16 Weather proofing of earthing kits should be done properly. 17 While installing C-clamp on the tower body,care should be taken that paint should be removed from tower body where C-clamp is going to be installed.

18 While bending the RF cables care should be taken that bending radius should be greater than 300mm. 19 RF clamps should be assembled properly on cable tray. 20 Routing of RF cables through Six-way clamp should be proper in such way that cables from 1st sector should be routed through top or bottom section of six-way clamp,2nd sector should be routed through middle section of six-way clamp,3rd sector should be routed through bottom or top section of six-way clamp. 21 Cable tie should provided on eac h & every strip of cable tray. 22 Cable tie should be cutted properly. 23 Direction of knot of cable tie should be same for all. 24 Tie should be provided in double cross with single cable tie only. 25 While routing cables through Roxtec from outside to inside of shelter,care should be taken that it should take S-shaped structure to avoid any entrance of water. 26 As for 4 rubber boot Roxtec,routing of cables should be proper such that cables from each sector should be inserted through separate rubber boot and through the holes which are horizontal to each other on separate rubber boot. 27 All the remaining holes on the boots which are not used should be properly filled by weather proofing tape. 28 The gap between Roxtec and shelter's wall should be properly filled by Silicon gel. Indoor 29 We should wear ESD band while taking entry inside the shelter. Connection of Surge arrestors. 30 Connection between Surge arrestor and feeder cable should be properly tighten. 31 Connection between Surge arrestor and jumper cable should be properly tighten. 32 Surge arrestors should be properly grounded to IGB. 33 All the grounding connections of surge arrestors should be separately routed & grounded on IGB. 34 Grounding connections of surge arrestors at the IGB should be properly tightened. 35 lugs should be properly crimped by crimping tool at IGB end.

36 While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. 37 While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body. 38 PVC tape should be properly wrapped around lugs and cable connections at IGB end. 39 There should not be any gap in between connection of cu lug and cables at IGB end. 40 While routing cables from IGB to Surge arrestors there should not be any cross routing. 41 Cable tie should provided on eac h & every strip of cable tray. 42 Cable tie should be cutted properly. 43 Direction of knot of cable tie should be same for all. 44 Tie should be provided in double cross with single cable tie only. 45 While routing cables on the cable tray,it should be routed in straight way. 46 There should not be any vertical bending or loop. 47 lugs should be properly crimped by crimping tool at Surge arrestor end. 48 While removing outer insulation of grounding cable at Surge arrestor end,care should be taken that inner core of cable should not be damaged. 49 While removing outer insulation of grounding cable at Surge arrestor end,care should be taken that direction of knife should be away from the body. 50 PVC tape should be properly wrapped around lugs and cable connections at Surge arrestor end. 51 There should not be any gap in between connection of cu lug and cables at Surge arrestor end. 52 Connection between indoor jumper and BTS ports should be properly tightened. Installation of BTS53 There should not be any continuity in between the fastner and BTS. 54 BTS should be properly levelled. 55 BTS should not be moved while applying any force from its original position. 56 Fastners should be tight in random diagonal manner. 57 BTS should be placed at accurate position as mentioned in floor plan. 58 Bit of drill machine used to make a holes should be aligned with the centre of marked position.

59 All the fastners should be tightened simaltaneously i.e. 2 to 3 rounds of drive to each fastner simaltaneously. 60 All the fastners should be properly tightened. Installation of TR61 There should not be any continuity in between the fastner and TR. 62 TR should be properly levelled. 63 TR should not be moved while applying any force from its original position. 64 Fastners should be tight in random diagonal manner. 65 TR should be placed at accurate position as mentioned in floor plan. 66 Bit of drill machine used to make a holes should be aligned with the centre of marked position. 67 All the fastners should be tightened simaltaneously i.e. 2 to 3 rounds of drive to each fastner simaltaneously. 68 All the fastners should be properly tightened. Installation of B.B.&P.P. cabinet69 There should not be any continuity in between the fastner and Cabinet. 70 Cabinet should be properly levelled. 71 Cabinet should not be moved while applying any force from its original position. 72 Fastners should be tight in random diagonal manner. 73 Cabinet should be placed at accurate position as mentioned in floor plan. 74 Bit of drill machine used to make a holes should be aligned with the centre of marked position. 75 All the fastners should be tightened simaltaneously i.e. 2 to 3 rounds of drive to each fastner simaltaneously. 76 All the fastners should be properly tightened. 77 P.P. should be properly placed on the base above the B.B. Installation of DDF78 All the screws should be properly tighten. 79 DDF block should be properly aligned on the wall of shelter. 80 Bit of drill machine used to make a holes should be aligned with the centre of marked position. Grounding connections of EquipmentsGrounding connection of BTS81 Grounding connections of BTS at the IGB should be properly tightened.

82 lugs should be properly crimped by crimping tool at IGB end. 83 While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. 84 While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body. 85 PVC tape should be properly wrapped around lugs and cable connections at IGB end. 86 There should not be any gap in between connection of cu lug and cables at IGB end. 87 While routing cable from IGB to BTS there should not be any cross routing. 88 Cable tie should be provided on eac h & every strip of cable tray. 89 Cable tie should be cutted properly. 90 Direction of knot of cable tie should be same for all. 91 Tie should be provided in double cross with single cable tie only. 92 While routing cables on the cable tray,it should be routed in straight way. 93 There should not be any vertical bending or loop. 94 lugs should be properly crimped by crimping tool at BTS end. 95 While removing outer insulation of grounding cable at BTS end,care should be taken that inner core of cable should not be damaged. 96 While removing outer insulation of grounding cable at BTS end,care should be taken that direction of knife should be away from the body. 97 PVC tape should be properly wrapped around lugs and cable connections at BTS end. 98 There should not be any gap in between connection of cu lug and cables at BTS end. Grounding connection of TR99 Grounding connections of TR at the IGB should be properly tightened. 100 lugs should be properly crimped by crimping tool at IGB end. 101 While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. 102 While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body.

103 PVC tape should be properly wrapped around lugs and cable connections at IGB end. 104 There should not be any gap in between connection of cu lug and cables at IGB end. 105 While routing cable from IGB to TR there should not be any cross routing. 106 Cable tie should be provided on eac h & every strip of cable tray. 107 Cable tie should be cutted properly. 108 Direction of knot of cable tie should be same for all. 109 Tie should be provided in double cross with single cable tie only. 110 While routing cables on the cable tray,it should be routed in straight way. 111 There should not be any vertical bending or loop. 112 lugs should be properly crimped by crimping tool at TR end. 113 While removing outer insulation of grounding cable at TR end,care should be taken that inner core of cable should not be damaged. 114 While removing outer insulation of grounding cable at TR end,care should be taken that direction of knife should be away from the body. 115 PVC tape should be properly wrapped around lugs and cable connections at TR end. 116 There should not be any gap in between connection of cu lug and cables at TR end. Grounding connection of B.B.117 Grounding connections of B.B. at the IGB should be properly tightened. 118 lugs should be properly crimped by crimping tool at IGB end. 119 While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. 120 While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body. 121 PVC tape should be properly wrapped around lugs and cable connections at IGB end. 122 There should not be any gap in between connection of cu lug and cables at IGB end. 123 While routing cable from IGB to B.B. there should not be any cross routing. 124 Cable tie should be provided on eac h & every strip of cable tray. 125 Cable tie should be cutted properly.

126 Direction of knot of cable tie should be same for all. 127 Tie should be provided in double cross with single cable tie only. 128 While routing cables on the cable tray,it should be routed in straight way. 129 There should not be any vertical bending or loop. 130 lugs should be properly crimped by crimping tool at B.B. end. 131 While removing outer insulation of grounding cable at B.B. end,care should be taken that inner core of cable should not be damaged. 132 While removing outer insulation of grounding cable at B.B. end,care should be taken that direction of knife should be away from the body. 133 PVC tape should be properly wrapped around lugs and cable connections at B.B. end. 134 There should not be any gap in between connection of cu lug and cables at B.B. end. Grounding connection of P.P.135 Grounding connections of P.P. at the IGB should be properly tightened. 136 lugs should be properly crimped by crimping tool at IGB end. 137 While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. 138 While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body. 139 PVC tape should be properly wrapped around lugs and cable connections at IGB end. 140 There should not be any gap in between connection of cu lug and cables at IGB end. 141 While routing cable from IGB to B.B. there should not be any cross routing. 142 Cable tie should be provided on eac h & every strip of cable tray. 143 Cable tie should be cutted properly. 144 Direction of knot of cable tie should be same for all. 145 Tie should be provided in double cross with single cable tie only. 146 While routing cables on the cable tray,it should be routed in straight way. 147 There should not be any vertical bending or loop. 148 lugs should be properly crimped by crimping tool at P.P. end.

149 While removing outer insulation of grounding cable at P.P. end,care should be taken that inner core of cable should not be damaged. 150 While removing outer insulation of grounding cable at P.P. end,care should be taken that direction of knife should be away from the body. 151 PVC tape should be properly wrapped around lugs and cable connections at P.P. end. 152 There should not be any gap in between connection of cu lug and cables at P.P. end. Grounding connection of DDF block153 Grounding connections of DDF block at the IGB should be properly tightened. 154 lugs should be properly crimped by crimping tool at IGB end. 155 While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. 156 While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body. 157 PVC tape should be properly wrapped around lugs and cable connections at IGB end. 158 There should not be any gap in between connection of cu lug and cables at IGB end. 159 While routing cable from IGB to DDF block there should not be any cross routing. 160 Cable tie should be provided on eac h & every strip of cable tray. 161 Cable tie should be cutted properly. 162 Direction of knot of cable tie should be same for all. 163 Tie should be provided in double cross with single cable tie only. 164 While routing cables on the cable tray,it should be routed in straight way. 165 There should not be any vertical bending or loop. 166 lugs should be properly crimped by crimping tool at DDF block end. 167 While removing outer insulation of grounding cable at DDF block end,care should be taken that inner core of cable should not be damaged. 168 While removing outer insulation of grounding cable at DDF block end,care should be taken that direction of knife should be away from the body. 169 PVC tape should be properly wrapped around lugs and cable connections at DDF block end.

170 There should not be any gap in between connection of cu lug and cables at DDF block end. DC connections from P.P.DC connection between P.P. & PIU171 lugs should be properly crimped by crimping tool at both ends. 172 While removing outer insulation of grounding cable at both ends,care should be taken that inner core of cable should not be damaged. 173 While removing outer insulation of grounding cable at both ends,care should be taken that direction of knife should be away from the body. 174 PVC tape should be properly wrapped around lugs and cable connections at both ends. 175 There should not be any gap in between connection of cu lug and cables at both ends. Connection of Busbar to B.B.176 lugs should be properly crimped by crimping tool at both ends. 177 While removing outer insulation of grounding cable at both ends,care should be taken that inner core of cable should not be damaged. 178 While removing outer insulation of grounding cable at both ends,care should be taken that direction of knife should be away from the body. 179 PVC tape should be properly wrapped around lugs and cable connections at both ends. 180 There should not be any gap in between connection of cu lug and cables at both ends. 181 Connections at the both ends should be properly tightened. Connection of fuse to B.B.lugs should be properly crimped by crimping tool at both ends. While removing outer insulation of grounding cable at both ends,care should be taken that inner core of cable should not be damaged. While removing outer insulation of grounding cable at both ends,care should be taken that direction of knife should be away from the body. PVC tape should be properly wrapped around lugs and cable connections at both ends. There should not be any gap in between connection of cu lug and cables at both ends. Connections at the both ends should be properly tightened. DDF,P.P. alarm connections-

182 183

184

185 186 187

188 At alarm panel,all pcm cables should be properly screwed. 189 At DDF end, all pcm cables should be properly punched by krone tool. Connection to -ve of BTS190 lugs should be properly crimped by crimping tool at both ends. 191 While removing outer insulation of grounding cable at both ends,care should be taken that inner core of cable should not be damaged. 192 While removing outer insulation of grounding cable at both ends,care should be taken that direction of knife should be away from the body. 193 PVC tape should be properly wrapped around lugs and cable connections at both ends. 194 There should not be any gap in between connection of cu lug and cables at both ends. 195 Connections at the both ends should be properly tightened. Connection to +ve of BTS196 lugs should be properly crimped by crimping tool at both ends. 197 While removing outer insulation of grounding cable at both ends,care should be taken that inner core of cable should not be damaged. 198 While removing outer insulation of grounding cable at both ends,care should be taken that direction of knife should be away from the body. 199 PVC tape should be properly wrapped around lugs and cable connections at both ends. 200 There should not be any gap in between connection of cu lug and cables at both ends. 201 Connections at the both ends should be properly tightened. Power connections to DCDBlugs should be properly crimped by crimping tool at both ends. While removing outer insulation of grounding cable at both ends,care should be taken that inner core of cable should not be damaged. While removing outer insulation of grounding cable at both ends,care should be taken that direction of knife should be away from the body. PVC tape should be properly wrapped around lugs and cable connections at both ends. There should not be any gap in between connection of cu lug and cables at both ends.

202 203

204

205 206

SITE NAME:-KADI SITE ID:-KD1234 Sr.no 1 2 3 4 5 Punch Points Checklist of BTS site Particulars Outdoor Unit Connection of outdoor jumper cables & GSM antenna ports should be properly tighten. Weather proofing of connection between outdoor jumper with antenna port should be properly done. Weather proofing should be done from bottom to top of antenna port and jumper connection. before installing GSM antenna,proper labelling of GSM antenna should be done. While pulling GSM antenna through ropway at resp. height,care should be taken that face of antenna(front) should be in opposite direction of tower. Connections of outdoor jumper cables & Feeder cables should be properly tighten. While removing outer insulation of Feeder cables,care should be taken that inner core of cables should not be damaged. While removing outer insulation of Feeder cables,care should be taken that direction of knife should be away from the body. Connectors of Feeder cables should be properly assembled. RF cable,connector & RF connector tool should be from same manufacturer. Weather proofing of connection between outdoor jumper with RF cables should be properly done. Weather proofing should be done from bottom to top of RF cables and jumper connection. While assembling earthing kits on each cables,care should be taken that all the earthing kits should be on same point of contact on all cables. All cu cables of earthing kits should be routed alongwith the respective RF cable in downward direction i.e. there should not be any loop. All cu lugs from earthing kits should be routed & grounded separately on EGB.

SITE ADDRESS:-PATIA OPERAYOR:-IDEA Status Remark

6 7

9 10 11 12 13

14

15

16 17

Weather proofing of earthing kits should be done properly. While installing C-clamp on the tower body,care should be taken that paint should be removed from tower body where C-clamp is going to be installed. While bending the RF cables care should be taken that bending radius should be greater than 300mm. RF clamps should be assembled properly on cable tray. Routing of RF cables through Six-way clamp should be proper in such way that cables from 1st sector should be routed through top or bottom section of six-way clamp,2nd sector should be routed through middle section of six-way clamp,3rd sector should be routed through bottom or top section of six-way clamp. Cable tie should provided on each & every strip of cable tray. Cable tie should be cutted properly. Direction of knot of cable tie should be same for all. Tie should be provided in double cross with single cable tie only. While routing cables through Roxtec from outside to inside of shelter,care should be taken that it should take S-shaped structure to avoid any entrance of water. As for 4 rubber boot Roxtec,routing of cables should be proper such that cables from each sector should be inserted through separate rubber boot and through the holes which are horizontal to each other on separate rubber boot. All the remaining holes on the boots which are not used should be properly filled by weather proofing tape. The gap between Roxtec and shelter's wall should be properly filled by Silicon gel. Indoor

18 19 20

21 22 23 24 25

26

27 28

29

We should wear ESD band while taking entry inside the shelter.

Connection of Surge arrestors. 30 31 Connection between Surge arrestor and feeder cable should be properly tighten. Connection between Surge arrestor and jumper cable should be properly tighten.

32 33 34 35 36

Surge arrestors should be properly grounded to IGB. All the grounding connections of surge arrestors should be separately routed & grounded on IGB. Grounding connections of surge arrestors at the IGB should be properly tightened. lugs should be properly crimped by crimping tool at IGB end. While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body. PVC tape should be properly wrapped around lugs and cable connections at IGB end. There should not be any gap in between connection of cu lug and cables at IGB end. While routing cables from IGB to Surge arrestors there should not be any cross routing. Cable tie should provided on each & every strip of cable tray. Cable tie should be cutted properly. Direction of knot of cable tie should be same for all. Tie should be provided in double cross with single cable tie only. While routing cables on the cable tray,it should be routed in straight way. There should not be any vertical bending or loop. lugs should be properly crimped by crimping tool at Surge arrestor end. While removing outer insulation of grounding cable at Surge arrestor end,care should be taken that inner core of cable should not be damaged. While removing outer insulation of grounding cable at Surge arrestor end,care should be taken that direction of knife should be away from the body. PVC tape should be properly wrapped around lugs and cable connections at Surge arrestor end.

37

38 39 40 41 42 43 44 45 46 47 48

49

50

51 52

There should not be any gap in between connection of cu lug and cables at Surge arrestor end. Connection between indoor jumper and BTS ports should be properly tightened. Installation of BTS

53 54 55 56 57 58 59 60 61 62 63

There should not be any continuity in between the fastner and BTS. BTS should be properly levelled. BTS should not be moved while applying any force from its original position. Fastners should be tight in random diagonal manner. BTS should be placed at accurate position as mentioned in floor plan. Bit of drill machine used to make a holes should be aligned with the centre of marked position. All the fastners should be tightened simaltaneously i.e. 2 to 3 rounds of drive to each fastner simaltaneously. All the fastners should be properly tightened. Grounding connections of BTS at the IGB should be properly tightened. lugs should be properly crimped by crimping tool at IGB end. While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body. PVC tape should be properly wrapped around lugs and cable connections at IGB end. There should not be any gap in between connection of cu lug and cables at IGB end. While routing cable from IGB to BTS there should not be any cross routing. Cable tie should be provided on eac h & every strip of cable tray. Cable tie should be cutted properly. Direction of knot of cable tie should be same for all.

64

65 66 67 68 69 70

71 72 73 74 75

Tie should be provided in double cross with single cable tie only. While routing cables on the cable tray,it should be routed in straight way. There should not be any vertical bending or loop. lugs should be properly crimped by crimping tool at BTS end. While removing outer insulation of grounding cable at BTS end,care should be taken that inner core of cable should not be damaged. While removing outer insulation of grounding cable at BTS end,care should be taken that direction of knife should be away from the body. PVC tape should be properly wrapped around lugs and cable connections at BTS end. There should not be any gap in between connection of cu lug and cables at BTS end. lugs should be properly crimped by crimping tool at +ve port of BTS and Busbar end. While removing outer insulation of grounding cable at +ve port of BTS and Busbar end,care should be taken that inner core of cable should not be damaged. While removing outer insulation of grounding cable at +ve port of BTS and Busbar end,care should be taken that direction of knife should be away from the body. PVC tape should be properly wrapped around lugs and cable connections at +ve port pf BTS and Busbar end. There should not be any gap in between connection of cu lug and cables at +ve port BTS and Busbar end. Connections at +ve port of BTS and Busbar end should be properly tightened. lugs should be properly crimped by crimping tool at -ve port of BTS and MCB's end. While removing outer insulation of grounding cable at -ve port of BTS and MCB's end,care should be taken that inner core of cable should not be damaged. While removing outer insulation of grounding cable at -ve port of BTS and MCB's end,care should be taken that direction of knife should be away from the body.

76

77 78 79 80

81

82 83 84 85 85

86

87 88 89

PVC tape should be properly wrapped around lugs and cable connections at -ve port pf BTS and MCB's end. There should not be any gap in between connection of cu lug and cables at -ve port BTS and MCB's end. Connections at -ve port of BTS and MCB's end should be properly tightened. Installation of TR There should not be any continuity in between the fastner and TR. TR should be properly levelled. TR should not be moved while applying any force from its original position. Fastners should be tight in random diagonal manner. TR should be placed at accurate position as mentioned in floor plan. Bit of drill machine used to make a holes should be aligned with the centre of marked position. All the fastners should be tightened simaltaneously i.e. 2 to 3 rounds of drive to each fastner simaltaneously. All the fastners should be properly tightened. Grounding connections of TR at the IGB should be properly tightened. lugs should be properly crimped by crimping tool at IGB end.

90 91 92 93 94 95 96 97 98 99

100 While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. 101 While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body. 102 PVC tape should be properly wrapped around lugs and cable connections at IGB end. 103 There should not be any gap in between connection of cu lug and cables at IGB end. 104 While routing cable from IGB to TR there should not be any cross routing. 105 Cable tie should be provided on eac h & every strip of cable tray. 106 Cable tie should be cutted properly. 107 Direction of knot of cable tie should be same for all.

108 Tie should be provided in double cross with single cable tie only. 109 While routing cables on the cable tray,it should be routed in straight way. 110 There should not be any vertical bending or loop. 111 lugs should be properly crimped by crimping tool at TR end. 112 While removing outer insulation of grounding cable at TR end,care should be taken that inner core of cable should not be damaged. 113 While removing outer insulation of grounding cable at TR end,care should be taken that direction of knife should be away from the body. 114 PVC tape should be properly wrapped around lugs and cable connections at TR end. 115 There should not be any gap in between connection of cu lug and cables at TR end. 116 lugs should be properly crimped by crimping tool at +ve port of DCDB and Busbar end. 117 While removing outer insulation of grounding cable at +ve port of DCDB and Busbar end,care should be taken that inner core of cable should not be damaged. 118 While removing outer insulation of grounding cable at +ve port of DCDB and Busbar end,care should be taken that direction of knife should be away from the body. 119 PVC tape should be properly wrapped around lugs and cable connections at +ve port of DCDB and Busbar end. 120 There should not be any gap in between connection of cu lug and cables at +ve port of DCDB and Busbar end. 121 lugs should be properly crimped by crimping tool at -ve port of DCDB and MCB's end. 122 While removing outer insulation of grounding cable at -ve port of DCDB and MCB's end,care should be taken that inner core of cable should not be damaged. 123 While removing outer insulation of grounding cable at -ve port of DCDB and MCB's end,care should be taken that direction of knife should be away from the body. 124 PVC tape should be properly wrapped around lugs and cable connections at -ve port of DCDB and MCB's end.

125 There should not be any gap in between connection of cu lug and cables at -ve port of DCDB and MCB's end. Installation of B.B.&P.P. cabinet 126 There should not be any continuity in between the fastner and Cabinet. 127 Cabinet should be properly levelled. 128 Cabinet should not be moved while applying any force from its original position. 129 Fastners should be tight in random diagonal manner. 130 Cabinet should be placed at accurate position as mentioned in floor plan. 131 Bit of drill machine used to make a holes should be aligned with the centre of marked position. 132 All the fastners should be tightened simaltaneously i.e. 2 to 3 rounds of drive to each fastner simaltaneously. 133 All the fastners should be properly tightened. 134 P.P. should be properly placed on the base above the B.B. 135 Grounding connections of B.B. at the IGB should be properly tightened. 136 lugs should be properly crimped by crimping tool at IGB end. 137 While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. 138 While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body. 139 PVC tape should be properly wrapped around lugs and cable connections at IGB end. 140 There should not be any gap in between connection of cu lug and cables at IGB end. 141 While routing cable from IGB to B.B. there should not be any cross routing. 142 Cable tie should be provided on eac h & every strip of cable tray. 143 Cable tie should be cutted properly. 144 Direction of knot of cable tie should be same for all.

145 Tie should be provided in double cross with single cable tie only. 146 While routing cables on the cable tray,it should be routed in straight way. 147 There should not be any vertical bending or loop. 148 lugs should be properly crimped by crimping tool at B.B. end. 149 While removing outer insulation of grounding cable at B.B. end,care should be taken that inner core of cable should not be damaged. 150 While removing outer insulation of grounding cable at B.B. end,care should be taken that direction of knife should be away from the body. 151 PVC tape should be properly wrapped around lugs and cable connections at B.B. end. 152 There should not be any gap in between connection of cu lug and cables at B.B. end. 153 Grounding connections of P.P. at the IGB should be properly tightened. 154 lugs should be properly crimped by crimping tool at IGB end. 155 While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. 156 While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body. 157 PVC tape should be properly wrapped around lugs and cable connections at IGB end. 158 There should not be any gap in between connection of cu lug and cables at IGB end. 159 While routing cable from IGB to B.B. there should not be any cross routing. 160 Cable tie should be provided on eac h & every strip of cable tray. 161 Cable tie should be cutted properly. 162 Direction of knot of cable tie should be same for all. 163 Tie should be provided in double cross with single cable tie only.

164 While routing cables on the cable tray,it should be routed in straight way. 165 There should not be any vertical bending or loop. 166 lugs should be properly crimped by crimping tool at P.P. end. 167 While removing outer insulation of grounding cable at P.P. end,care should be taken that inner core of cable should not be damaged. 168 While removing outer insulation of grounding cable at P.P. end,care should be taken that direction of knife should be away from the body. 169 PVC tape should be properly wrapped around lugs and cable connections at P.P. end. 170 There should not be any gap in between connection of cu lug and cables at P.P. end. 171 lugs should be properly crimped by crimping tool at both P.P. and PIU ends. 172 While removing outer insulation of grounding cable at P.P. and PIU ends,care should be taken that inner core of cable should not be damaged. 173 While removing outer insulation of grounding cable at P.P. and PIU ends,care should be taken that direction of knife should be away from the body. 174 PVC tape should be properly wrapped around lugs and cable connections at both P.P. and PIU ends. 175 There should not be any gap in between connection of cu lug and cables at P.P. and PIU ends. 176 lugs should be properly crimped by crimping tool at both B.B. and Busbar end. 177 While removing outer insulation of grounding cable at both B.B. and Busbar end,care should be taken that inner core of cable should not be damaged. 178 While removing outer insulation of grounding cable at both B.B. and Busbar end,care should be taken that direction of knife should be away from the body. 179 PVC tape should be properly wrapped around lugs and cable connections at both B.B. and Busbar end. 180 There should not be any gap in between connection of cu lug and cables at both B.B. and Busbar end.

181 Connections at the both B.B. and Busbar end should be properly tightened. 182 lugs should be properly crimped by crimping tool at both B.B. and Fuse end. 183 While removing outer insulation of grounding cable at both B.B. and Fuse end,care should be taken that inner core of cable should not be damaged. 184 While removing outer insulation of grounding cable at both B.B. and Fuse end,care should be taken that direction of knife should be away from the body. 185 PVC tape should be properly wrapped around lugs and cable connections at both B.B. and Fuse end. 186 There should not be any gap in between connection of cu lug and cables at both B.B. and Fuse end. 187 Connections at the both B.B. and Fuse end should be properly tightened. Installation of DDF 188 All the screws should be properly tighten. 189 DDF block should be properly aligned on the wall of shelter. 190 Bit of drill machine used to make a holes should be aligned with the centre of marked position. 191 Grounding connections of DDF block at the IGB should be properly tightened. 192 lugs should be properly crimped by crimping tool at IGB end. 193 While removing outer insulation of grounding cable at IGB end,care should be taken that inner core of cable should not be damaged. 194 While removing outer insulation of grounding cable at IGB end,care should be taken that direction of knife should be away from the body. 195 PVC tape should be properly wrapped around lugs and cable connections at IGB end. 196 There should not be any gap in between connection of cu lug and cables at IGB end. 197 While routing cable from IGB to DDF block there should not be any cross routing. 198 Cable tie should be provided on each & every strip of cable tray.

199 Cable tie should be cutted properly. 200 Direction of knot of cable tie should be same for all. 201 Tie should be provided in double cross with single cable tie only. 202 While routing cables on the cable tray,it should be routed in straight way. 203 There should not be any vertical bending or loop. 204 lugs should be properly crimped by crimping tool at DDF block end. 205 While removing outer insulation of grounding cable at DDF block end,care should be taken that inner core of cable should not be damaged. 206 While removing outer insulation of grounding cable at DDF block end,care should be taken that direction of knife should be away from the body. 207 PVC tape should be properly wrapped around lugs and cable connections at DDF block end. 208 There should not be any gap in between connection of cu lug and cables at DDF block end. 209 At alarm panel,all pcm cables should be properly screwed. 210 At DDF end, all pcm cables should be properly punched by krone tool.