CAR

Conical Diffuser

Horizontal air supply, suitable also for exhaust Cooling applications with supply/room air temperature difference as low as -16 C Suited also for heating Suitable for high airflow rates Installation flush to the ceiling or exposed Circular duct connection with rubber gasket Openable cone module, enabling the cleaning of the diffuser and ductwork

Product Models & Accessories Models available integrated in a panel for installation in modular 600 x 600 mm suspended ceilings Balancing plenum with adjustment functions (PLC) or even with measurement function (TRI)

MATERIAL AND FINISHING


PART Diffuser Plenum box MATERIAL Steel Steel FINISHING Epoxy-painted (White RAL 9010)

CAR - Conical Diffuser


94

20/CAR/3500/0606/EN

qv CAR-160

Pa l/s m 3/h LpA D Pst D Ptot Ld Lmin L0.2 LpA D Pst D Ptot Ld Lmin L0.2 LpA D Pst D Ptot Ld Lmin L0.2 LpA D Pst D Ptot Ld Lmin L0.2 LpA D Pst D Ptot Ld Lmin L0.2 LpA D Pst D Ptot Ld Lmin L0.2 LpA D Pst D Ptot Ld Lmin L0.2 LpA D Pst D Ptot Ld Lmin L0.2

360 30 108 6 2 3 1,0

600 50 180 15 5 9 0,5 1,6 16 2 4 1,0

840 70 252 25 10 18 0,5 2,2 24 5 8 1,4

1080 90 324 33 17 29 0,9 2,6 31 8 13 0,5 1,8

1440 120 432 42 31 52 1,5 3,4 39 14 22 0,7 2,2 23 6 10 0,5 1,8 8 3 4 1,2

1800 150 540

2400 200 720

3000 250 900

3960 330 1188

5400 450 1620

7200 600 2160

10800 900 3240

18000 1500 5400

24000 2000 7200

36000 3000 10800

CAR-200

45 21 35 1,1 2,6 28 10 15 0,6 2,0 14 4 6 0,5 1,4 35 17 27 1,1 2,6 24 7 11 0,5 1,8 20 4 7 0,5 1,6 20 2 4 2,0 0,5 2,0 41 27 42 1,7 3,0 31 11 18 0,9 2,2 26 6 11 0,6 2,0 25 3 6 2,2 0,5 2,4 41 20 31 1,5 2,6 33 11 18 1,2 2,4 32 6 10 2,6 0,9 3,0 23 3 6 2,4 0,6 2,8 41 21 34 2,0 3,0 39 10 18 3,0 1,5 4,2 31 7 11 2,8 1,2 3,8 46 19 32 3,4 2,4 5,6 38 12 20 3,2 2,0 5,0 23 6 10 3,0 1,5 4,0 50 26 45 4,0 3,5 7,4 37 14 22 3,6 2,7 6,2 54 40 62 4,6 5,2 10,0

CAR-250

CAR-315

CAR-355

CAR-400

CAR-450

CAR-560

LpA values presented with room attenuation 4 dB (red 10m2 sab). When using room attenuation 8 dB (red 25m 2 - sab): LpA - 4dB. Pa LpA D Pst Supply air cooling capacity, W A-weighted sound pressure level, reduced by total equivalent absorption surface of 10m 2, dB(A) red 10m 2 - sab Static pressure drop, Pa

D Ptot Total pressure drop, Pa Ld Distance from the supply unit, at which air jet detaches from ceiling, m Lmin Minimum distance between central lines of two supply units, m (V3 = 0,25m/s at 1.8m height) L0.2 Isotermal throw length, m when residual velocity of supply air jet 0,2 m/s Room temperature (Tr) = 24 C Supply air temperature (Ta) = 14 C Room height = 2,8 m

CAR - Conical Diffuser


95

20/CAR/3500/0606/EN

QUICK SELECTION

ACCESSORIES
ACCESSORY Plenum Balancing plenum with airflow measurement and adjustment unit Sound attenuation Airflow measurement and adjustment unit CODE PLC TRI/N IN MSM DESCRIPTION Plenum for duct connection (with or without insulation) For balancing, equalising the airflow Polyester fibre as sound attenuation material in the TRI plenum. Mineral wool as sound attenuation material in the PLC plenum For supply installation

PRODUCT MODELS
PRODUCT MODEL Diffuser integrated in front panel, 600 x 600 mm CODE CAR/B DESCRIPTION Sizes 160, 200 and 250 are available integrated in a steel panel for installation in a modular 600x600 mmsuspended ceiling. The external dimensions of the front panel are 595 mm x 595 mm.

DIMENSIONS

NS 160 200 250 315 355 400 450 560

W 343 457 571 686 857 857 1030 1200

H 65 80 87 91 102 100 120 124

H1 54 70 88 106 133 133 157 184

D 159 199

D
W

249 314 354 399 449 558

Special dimensions are not available.

CAR - Conical Diffuser


96

H1

20/CAR/3500/0606/EN

Installation with plenum TRI or PLC

D H2

W1
CAR D 159 199 249 314 TRI TRI-160-160 TRI-200-200 TRI-250-250 TRI-315-315 H2 304334 369399 440470 490520 H1 54 70 88 106

Function Supply air is divided into several jets through the cones. The divergent sections of the diffuser create negative pressure under the diffuser so room air is induced into the supply air terminal. Room air and supply air mix. This internal induction reduces temperature and the air velocity into the space. The process is the same outside the diffuser between the supply and mixed room air, with external induction further reducing velocity and the temperature difference between supply and room air. The diffuser can also be used as an exhaust unit.

160 200 250 315

CAR 160 200 250 315 355 400 450 560

D 159 199 249 314 349 399 449 559

PLC PLC-160 PLC-200 PLC-250 PLC-315 PLC-355 PLC-400 PLC-450 PLC-560

H2 290320 395425 402432 556686 567597 565595 785815 789819

H1

H1 54 70 88 106 133 133 157 184

When the TRI spigot is installed in the plenum, the H dimensions can be reduced by 60 mm. Dimensions of the ceiling opening

Installation The CAR diffuser can be installed flush with a suspended ceiling or fully exposed in the space. The diffuser is connected directly to the duct using a PLC plenum or TRI balancing plenum. When it is connected directly to ductwork, a safety distance of minimum 3D upstream of the diffuser should be maintained. The technical performance for the combination of supply air diffuser and TRI plenum is presented separately for the two different installations. See HIT Design software.

CAR 160 200 250 315 355 400 450 560

W1 290 406 510 610 760 760 915 1065

CAR - Conical Diffuser


97

20/CAR/3500/0606/EN

The airflow rate can be adjusted and measured only when the diffuser is installed. In order to enable airflow adjustment and measurement of airflow rate, it is recommended to connect the diffuser to a plenum equipped with the MSM module. The supply flow rate is determined using measurement and adjustment module MSM. Detach the conical central core and pass the tubes and control spindle through the diffuser. Measure the differential pressure with a manometer. The flow rate is calculated using the formula below.
qv = k * pm

Remove the conical central core by unscrewing it from the frame (the central core is fixed by small screws). Clean the parts by wiping them with a damp cloth. Put each screw back in place, and screw on until the conical central core fits in place. Option: with balancing plenum TRI + MSM or PLC + MSM Remove the measurement and adjustment module by pulling gently on the shaft (not the control spindle). Wipe the parts with a damp cloth, instead of immersing in water. Reassemble the measurement and adjustment module by pushing the shaft until the module meets the stopper. Put each screw back in place, and screw on until the conical central core fits in place.

Adjust the airflow rate by rotating the control spindle until the desired setting is achieved. Lock the damper position with a screw. Replace the tubes and spindle in the plenum and push the conical central core back into place. K factor for installations with different safety distances (D= duct diameter)

PLC/TRI 125 160 200 250 315

>8XD 9.9 16.9 28.3 47.9 78.6

min 3XD 12.6 21.9 31.0 51.5 -

CAR - Conical Diffuser


98

20/CAR/3500/0606/EN

Adjustment

Servicing

Pressure drop, throw pattern and sound data

CAR-160, CAR-200, CAR-250

CAR-315, CAR-350, CAR-380, CAR-400, CAR-450

CAR-560

Selection example : Requirements: qv = 100 l/s Selection: Lp(A) < 35 dB(A) L0.2 < 4.0 m CAR-200 Lp(A) = 34 dB(A) L0.2 = 3.0 m DPtot = 16 Pa

CAR - Conical Diffuser


99

20/CAR/3500/0606/EN

qv (l/s) CAR-160 70 82 96 112 CAR-200 72 86 104 127 CAR-250 128 160 197 238 CAR-315 208 240 278 320 CAR-355 240 293 355 434 CAR-400 250 309 381 472 CAR-450 366 441 534 637 CAR-560 642 743 862 994 (m 3/h) 252 295 346 403 259 310 374 457 461 576 709 857 749 864 1001 1152 864 1055 1278 1562 900 1112 1372 1699 1318 1588 1922 2293 2311 2675 3103 3578

D Pst (Pa) 10 14 20 27 5 7 10 15 7 11 17 24 8 11 14 19 6 9 13 20 3 5 8 12 4 6 9 13 7 10 13 17

D Ptot (Pa) 18 24 33 45 8 12 17 25 11 17 26 38 12 16 22 29 10 14 21 32 6 9 13 20 7 11 16 23 11 15 20 27

F (Hz) 63 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 125 29 34 39 44 37 41 46 50 32 38 44 50 32 38 43 49 36 42 47 52 37 42 47 52 35 40 45 50 24 29 34 39 250 31 35 39 44 33 38 42 48 27 33 39 44 32 37 41 46 34 38 43 48 34 38 43 48 36 40 45 49 26 31 36 41 500 28 33 38 43 25 30 35 41 25 31 37 43 27 32 37 42 26 32 37 42 26 31 36 42 22 28 34 40 28 33 38 43 1000 23 28 33 38 20 25 30 36 15 23 30 37 25 30 35 39 20 26 31 36 21 26 31 36 18 24 30 36 24 28 33 38 2000 21 26 31 36 19 24 29 35 26 29 33 36 11 17 23 28 14 20 25 30 15 20 25 31 14 20 27 33 21 26 31 36 4000 6 12 19 25 16 20 25 29 5 12 19 25 10 15 20 24 9 15 20 26 9 15 20 26 12 18 24 30 13 18 23 28 8000 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

LpA [dB(A)] 25 30 35 40 25 30 35 40 25 30 35 40 25 30 35 40 25 30 35 40 25 30 35 40 25 30 35 40 25 30 35 40

NR 20 25 30 35 18 24 29 34 25 29 32 35 21 26 31 35 19 24 29 34 19 24 29 34 21 26 31 35 20 25 30 35

NC 17 23 28 34 16 21 26 32 22 26 30 34 19 24 29 34 16 22 27 33 16 21 27 33 18 23 29 33 18 23 29 34

LpA values presented with room attenuation 4 dB (red 10m 2 - sab). When using room attenuation 8 dB (red 25m 2 - sab): LpA - 4dB. NR/NC noise criteria

CAR - Conical Diffuser


100

20/CAR/3500/0606/EN

SOUND LEVEL DATA, SUPPLY

Suggested Specifications The diffuser shall be made of several stamped cones, made of epoxy-painted steel with a white (RAL 9010) or grey (RAL7004) standard colour. The diffuser shall be suitable for installation on exposed ductwork or flush to the ceiling. The diffuser shall be connected to the ductwork using a TRI balancing plenum, which utilises polyester fibre with a washable surface as sound attenuation material. The diffuser shall be connected to the ductwork using a PLC plenum, which utilises mineral wool as sound attenuation material. The plenum shall comprise an airflow measurement and adjustment unit. The diffuser shall be suitable for installation in 600 x 600-mm suspended ceilings.

Product Code CAR-D D = Diameter of duct connection Specifics and accessories WS = Width of suspended ceiling element CO = Colour Code example CAR-160, WS=NA,CO=W Sub products TRI Plenum (Diffusers) W White NA 600 Not Assigned 600 x 600 160, 200, 250, 315, 355, 400, 450, 560

The conical central core shall be removable. The air discharge pattern shall be radial around the full perimeter of the air diffuser. The cones shall form divergent sections, which shall create underpressure inducing room air into the unit.

PLC Plenum (Ceiling diffusers)

CAR - Conical Diffuser


101

20/CAR/3500/0606/EN