Control and remote control Remote control dimmers

and dimmer TV700, TVe700, TVo1000, TVBo and Vo1000


Function
The (remote control) dimmers modulate lighting brightness for unit powers from 50 to 1000 VA from one or more switch-on points. Products in the range whose terminology includes an "o" are fitted-out with an optical link enabling them to communicate with one another without wiring to allow: extensions to powers greater than 1000 VA b additional functions (brightness regulation, indication, lighting level override, time delayed scale, etc.) by combining auxiliaries b a three-phase distribution b a distribution on different types of lamps with centralised control. Optical transmission runs from left to right: the device furthest to the left controls the other devices.

Description
A (remote control) dimmer is chosen according to: b the type of lighting, the control and variation range required b the auxiliary function required (maintaining a constant level of brightness, overriding a pre-set level of brightness, time delayed scale, etc.). The dimmers and remote control dimmers comply with standards: IEC 669-2.1, NF EN 60669-2.1, EN 55-014, NF EN 55-014 (disturbance suppression). The dimmers and remote control dimmers are designed to operate from -5 C to +50 C. However, between 30 C and 50 C, a 30 % reduction in acceptable power must be anticipated: b for small unventilated enclosures or cubicles housing many power switchgear items (circuit-breakers, contactors, solid state contactors, remote control dimmers, etc.) b for ambient temperature in room likely to be greater than 30 C (allow for annual temperature variations). Inserts (catalogue number 27062) are then necessary to separate remote control dimmers from devices with high losses. Choice according to lighting type Technical data Autonomous remote control dimmers
TV700 Controlled lighting Incandescent lamp LV halogen (230 V) ELV halogen (12 or 24 V) with: electronic transformer universal electronic transformer ferromagnetic transformer Fluorescent tube with electronic ballast 1-10 V controllable Discharge ferromagnetic ballast lamp + starter with electronic supply (1) For TVo1000 and Vo1000, PTV1 required in ELV in the following cases: b if the transformer is charged with a power less than 80% of the rated power b if the load consists of a single transformer and a single lamp b if the total load is less than 100 VA. b b TVe700 b b b b b

Lighting fluctuation systems


TVo1000 b b b b Vo1000 b b PTV1 (1) b b b b TFu70-TFu105-TFu150 PTV1 (1) TFt50 PTV1 (1) TVBo Type of transformer Precharge

no variation possible with this load type

Choosing auxiliary functions


Function Auxiliary TVo1000 Vo1000 TVBo b b b b b TV700 TVe700 no optical link and association possible

Maintaining constant brightness Load control (on/off) or remote indication Override a lighting level Progressive lighting on/off (adjustable time) Optical repeater

RGo ISo NTVo TTVo RPo

Remark on the Vo1000 Associated with the TVo1000, the Vo1000 is recommended as a power extension (knob and ON/OFF control de-activated). Comment on the lighting supplied by a backed-up network Operation on backed-up power supply (by generating set) may cause disturbances in lighting.

92029E.fm/2

Schneider Electric

Control and remote control Remote control dimmers

and dimmer TV700, TVe700, TVo1000, TVBo and Vo1000


Characteristics
Technical data Autonomous remote control dimmers
TV700 Characteristics Local control on front face by pushbutton (1) by knob Remote control by pushbutton (1) non illuminated illuminated (max. 2.5 mA) by switch (2) Control by optical link Memorisation of setting Setting the minimum lighting threshold Power extension by association Energisation delay Protection Preservation, on brownout < 0.2 s, of the lighting level setting Short-circuit (by 5 x 20 mm rapid fuse) (A): spare fuse in a rack on the front face Short-circuit (electronic protection) Fuse out of operation: lighting switchoff red indicator light permanently on Overload (electronic protection): - progressive reduction of lighting level until stabilised - total switch-off of lighting Operation indication on front panel Variation, faults, OFF Variation, OFF Power supply 230 V power supply (50 Hz 10 %) Consumption (VA) Power loss (W) Connection Tunnel terminals (2 x 2,5 mm2) TVe700

Lighting fluctuation systems


TVo1000 Vo1000 TVBo

b b

b b

b b b b b b 3s b 5 b b b b b 3s knob 5

b b b b b 3s b

b 3,2

b b b b b b b b 10 % 5 10 b 10 % 2,5 10 b 10 % 5 15 b 10 % 5 15 b -10...+6 % 5 15 b b b b

(1): control order using pushbutton: b ON/OFF by impulse (duration: 100...300 ms) b variation by pressing for a min. of 390 ms (reversal of variation direction between two actions).

(2): control order using switch: ON/OFF.

Schneider Electric

92029E.fm/3

Control and remote control Remote control dimmers

and dimmer TV700, TVe700, TVo1000, TVBo and Vo1000


Specific technical data
Acceptable power according to luminous load Watt 60 - 700 50 - 700 50 - 550 50 - 650 60 - 1000 60 - 800 60 - 900

TV700
Incandescent-LV halogen (230 V)

TVe700
Incandescent-LV halogen (230 V) ELV halogen (12/24 V): with ferromagnetic transformer with electronic and universal electronic transformer

TVo1000/Vo1000
Incandescente-halogne BT (230 V) ELV halogen (12/24 V): with ferromagnetic transformer with electronic and universal electronic transformer

Vo1000 b alone, used as a dimmer controlled from its front face by knob and/or optional remote ON/OFF b associated with a remote control dimmer, it is recommended as a power extension (knob and ON/OFF control de-activated). TVBo b maximum number of acceptable tubes (1-10 V ballast):
Tube type 18 W 36 W 58 W single-corrected dual-corrected single-corrected dual-corrected single-corrected dual-corrected Nbr of tubes 50 40 40 20 30 15

92029E.fm/4

Schneider Electric

Control and remote control Remote control dimmers

and dimmer TV700, TVe700, TVo1000, TVBo and Vo1000


Catalogue numbers
Type TV700 Power 60...700 W Cat. No. 15287 Width in mod. of 9 mm 6

15287
Type TVe700 Power 50...700 VA Cat. No. 15285 Width in mod. of 9 mm 6

15285
Type TVo1000 Power 60...1000 VA Cat. No. 15289 Width in mod. of 9 mm 10

15289
Type Vo1000 Power 60...1000 VA Cat. No. 15290 Width in mod. of 9 mm 10

15290
Type

TVBo

Power 1500 VA maxi

Cat. No. 15297

Width in mod. of 9 mm 6

15297

Additional informations
Schneider Electric

Auxiliaries: page 92039/2 Practical advice: page 92318/2 Dimensions: page 90149/2 92029E.fm/5