HL TECK 90 MINUS 40 C, FT4, 600 VOLTS (14 AWG)

14 AWG Multiconductor RW90 (.030" XLPE Insulation) No. 14 AWG Grounding Conductor Inner PVC Jacket, Aluminum Armor, Outer PVC Jacket
APPLICATION: As flame retardant multiconductor control, signal or power cables rated 600 volts, 90C in wet or dry locations. Widely used in the pulp and paper, petroleum, petrochemical, mining industries where cables with outstanding resistance to mechanical abuse, chemical attack and high reliability are required. Suitable for use in direct burial, open wiring, ventilated flexible cableways, and in non-ventilated, ventilated or ladder type cable trays. Inner and outer PVC jacket have low acid gas evolution and low flame spread properties along with excellent low temperature properties. STANDARDS: 1. Listed as TECK 90 MINUS 40C per CSA Std C22.2 No. 131. 2. Passes FT-4 70000 BTU/Hr cable tray flame test of CSA Std C22.2 No. 0.3. 3. Complies with Acid Gas Evolution Test of Ontario Hydro Provisional Spec L-891SM-77. Less than 14% acid gas evolution. 4. HL approved for use in hazardous locations per CSA Std C22.2 No. 174. CONSTRUCTION: Stranded uncoated concentric copper conductors, 30 mils XLP crosslinked polyethylene insulation, color coded. Two or more conductors twisted with one No. 14 AWG 7-strand bare copper grounding conductor and suitable fillers, tape, PVC inner jacket, aluminum interlocked armor, PVC outer jacket, surface printed.
Diameters No. of USAWC Part # 14-02WGTECK90 14-03WGTECK90 14-04WGTECK90 14-05WGTECK90 14-06WGTECK90 14-07WGTECK90 14-08WGTECK90 14-09WGTECK90 14-10WGTECK90 14-11WGTECK90 14-12WGTECK90 14-13WGTECK90 14-14WGTECK90 14-15WGTECK90 14-16WGTECK90 14-17WGTECK90 14-18WGTECK90 14-19WGTECK90 14-20WGTECK90 14-25WGTECK90 14-30WGTECK90 14-40WGTECK90 14-50WGTECK90 Condrs. Mils 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 25 30 40 50 45 45 45 45 45 45 60 60 60 60 60 60 60 60 60 60 60 60 80 80 80 80 80 mm 1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2,03 Inner Jacket Thickness Inner Jacket In. .385 .405 .443 .482 .525 .525 .597 .638 .692 .692 .715 .725 .750 .789 .789 .830 .830 .830 .913 1.01 1.07 1.19 1.34 mm 9.78 10.3 11.3 12.2 13.3 13.3 15.2 16.2 17.6 17.6 18.2 18.4 19.0 20.0 20.0 21.1 21.1 21.1 23.2 25.6 27.2 30.2 34.0 In. .550 .570 .607 .647 .690 .690 .762 .803 .857 .857 .879 .890 .915 1.01 1.01 1.05 1.05 1.05 1.13 1.23 1.29 1.41 1.56 Armor mm 14.6 14.5 15.4 16.4 17.5 17.5 19.4 20.4 21.8 21.8 22.3 22.6 23.2 25.6 25.6 26.7 26.7 26.7 28.7 31.2 32.8 35.8 39.6 Outer Jacket In. .655 .677 .713 .752 .795 .795 .867 .908 .962 .962 .984 1.00 1.02 1.12 1.12 1.16 1.16 1.16 1.24 1.33 1.39 1.52 1.67 mm 16.6 17.2 18.1 19.1 20.2 20.2 22.0 23.1 24.4 24.4 25.0 25.4 25.9 28.4 28.4 29.5 29.5 29.5 31.5 33.8 35.3 38.6 42.4 Net 210 230 270 300 330 350 405 435 505 525 545 570 640 660 690 720 750 770 790 960 1110 1330 1530 Copper 39 52 68 81 95 104 117 130 149 156 176 182 195 217 221 234 247 260 285 337 402 531 661 Weight lbs/1000 ft.

6301 EAST STASSNEY LANE, SUITE 100 AUSTIN, TEXAS 78744, USA 1-800-880-9473, FAX 512-443-6329, SALES@USAWIRE-CABLE.COM

7-11

Specification

HL TECK 90 MINUS 40C, FT4, 600 VOLTS


14AWG Multiconductor RW90 (.030 XLPE Insulation)
1. SCOPE 1.1 This specification describes multiconductor 14AWG TECK 90 MINUS 40C cable with XLP crosslinked polyethylene insulation, PVC inner jacket, aluminum interlocked armor, and PVC outer jacket. The cables may be used in circuits not exceeding 600 volts at temperatures of 90C in wet or dry locations. Cables are intended for use indoors or outdoors in open wiring, ventilated flexible cableways, cable trays and direct burial installations in commercial or industrial applications. 2. STANDARDS 2.1 The following standards shall form a part of this specification to the extent specified herein: 2.1.1 CSA Std C22.2 No. 131 TECK 90 MINUS 40C cable. 2.1.2 CSA Std C22.2 No. 0.3 Clause 4.11.4 FT-4 flame test. 2.1.3 Ontario Hydro Provisional Spec L891 SM-77. 2.1.4 CSA Std C22.2 No. 174 Cables and Cable Glands for Use In Hazardous Locations. 2.1.5 CSA Std C22.2 No. 38 Thermoset Insulated Wires and Cables. 3. CONDUCTORS 3.1 Shall be 14 AWG Class B concentric stranded annealed uncoated copper conforming to CSA C22.2 No. 131. A nonhygroscopic separator may be used over the conductor at the option of the manufacturer. 4. INSULATION 4.1 Shall be XLP crosslinked polyethylene meeting the requirements of CSA C22.2 No. 38 for Type RW90. Average thickness of insulation shall be 30 mils. Minimum thickness at any point shall be not less than 90% of the specified average thickness. 5. CIRCUIT IDENTIFICATION 5.1 Conductors shall be colored; black,white (2/C); black, red, blue (3/C); black, red, blue, white (4/C). Cables with more than four conductors shall have circuit identification consisting of printed numbers. 6. ASSEMBLY 6.1 Insulated circuit conductors shall be cabled together with a 14 AWG 7 -strand uncoated copper grounding conductor and honhygroscopic fillers where necessary. Maximum length of lay shall be as specified in Table 3 of CSA C22.2 No. 131. A suitable nonhygroscopic tape may be applied over the assembly. 7. INNER PVC JACKET 7.1 Shall be PVC meeting the requirements of C22.2 No. 131 including requirements for low temperature classification of -40C. Thickness of jacket shall be as specified in Table 6 of C22.2 No. 131. 8. INTERLOCKED ARMOR 8.1 An aluminum alloy interlocked armor shall be applied over the inner PVC jacket meeting the requirements of C22.2 No. 131, Clause 4.11. 9. OUTER JACKET 9.1 Cables shall be covered with a black PVC jacket meeting the requirements of C22.2 No. 131 including requirements for low temperature classification of -40C. Thickness of covering shall not be less than 40 mils. 10. IDENTIFICATION 10.1 Cables shall be surface ink printed with a legend identifying the manufacturer, number of conductors, size, voltage rating, TECK 90 MINUS 40C, XLPE, FT4, HL and length markings in meters. 11. TESTS 11.1 Completed cable shall be capable of compliance with the FT4 flame test of C22.2 No. 0.3, HL requirements of C22.2 No. 174 and acid gas evolution test of OH L891-SM77 in addition to the requirements for Type TECK 90 MINUS 40C cable in C22.2 No. 131.
11

7-12

6301 EAST STASSNEY LANE, SUITE 100 AUSTIN, TEXAS 78744, USA 1-800-880-9473, FAX 512-443-6329, SALES@USAWIRE-CABLE.COM

HL TECK 90 MINUS 40 C, FT4, 600 VOLTS (12AWG)


12AWG Multiconductor RW90 (.030 XLPE Insulation) No. 14 AWG Grounding Conductor Inner PVC Jacket, Aluminum Armor, Outer PVC Jacket
APPLICATION: As flame retardant multiconductor control, signal or power cables rated 600 volts, 90C in wet or dry locations. Widely used in the pulp and paper, petroleum, petrochemical, mining industries where cables with outstanding resistance to mechanical abuse, chemical attack and high reliability are required. Suitable for use in direct burial, open wiring, ventilated flexible cableways, and in non-ventilated, ventilated or ladder type cable trays. Inner and outer PVC jacket have low acid gas evolution and low flame spread properties along with excellent low temperature properties. STANDARDS: 1. Listed as TECK 90 MINUS 40C per CSA Std. C22.2 No. 131. 2. Passes FT-4 70000 BTU/Hr cable tray flame test of CSA Std C22.2 No. 0.3. 3. Complies with Acid Gas Evolution Test of Ontario Hydro Provisional Spec L-891 SM-77. Less than 14% acid gas evolution. 4. HL approved for use in hazardous locations per CSA Std C22.2 No. 174. CONSTRUCTION: Stranded uncoated concentric copper conductors, 30 mils XLP crosslinked polyethylene insulation, color coded. Two or more conductors twisted with one No. 14 AWG 7-strand bare copper grounding conductor and suitable fillers, tape, PVC innerjacket, aluminum interlocked armor, PVC outer jacket, surface printed.
Diameters Inner Jacket Thickness Inner Jacket Mils 12-02WGTECK90 12-03WGTECK90 12-04WGTECK90 12-05WGTECK90 12-06WGTECK90 12-07WGTECK90 12-08WGTECK90 12-09WGTECK90 12-10WGTECK90 12-11WGTECK90 12-12WGTECK90 12-13WGTECK90 12-14WGTECK90 12-15WGTECK90 12-16WGTECK90 12-17WGTECK90 12-18WGTECK90 12-19WGTECK90 12-20WGTECK90 12-25WGTECK90 12-30WGTECK90 12-40WGTECK90 12-50WGTECK90 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 25 30 40 50 45 45 45 60 60 60 60 60 60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 mm 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 In. .425 .450 .490 .567 .615 .615 .665 .710 .770 .770 .795 .810 .838 .923 .923 .970 .970 .970 1.02 1.13 1.20 1.34 1.51 mm 10.8 11.4 12.4 14.4 15.6 15.6 16.9 18.0 19.6 19.6 20.2 20.6 21.3 23.4 23.4 24.6 24.6 24.6 25.9 28.7 30.5 34.0 38.4 In. .590 .615 .655 .735 .780 .780 .830 .875 .990 .990 1.02 1.03 1.06 1.14 1.14 1.19 1.19 1.19 1.24 1.35 1.42 1.56 1.73 Armor mm 15.0 15.6 16.6 18.7 19.8 19.8 21.1 22.2 25.1 25.1 25.9 26.2 26.9 29.0 29.0 30.2 30.2 30.2 31.5 34.3 36.1 39.6 43.9 Outer Jacket In. .695 .720 .760 .840 .884 .884 .933 .980 1.10 1.10 1.12 1.14 1.16 1.25 1.25 1.30 1.30 1.30 1.34 1.46 1.52 1.66 1.84 mm 17.6 18.3 19.3 21.3 22.4 22.4 23.7 24.9 27.9 27.9 28.4 29.0 29.5 31.8 31.8 33.0 33.0 33.0 34.0 37.1 38.6 42.2 46.7 Net 245 280 325 375 445 470 515 550 630 660 700 730 770 810 840 930 960 990 1020 1195 1390 1710 2050 Copper 55 75 96 116 137 157 177 202 219 244 261 286 307 322 349 370 391 412 424 527 630 837 1044

No. of USAWC Part # Condrs.

Weight lbs/1000 ft

6301 EAST STASSNEY LANE, SUITE 100 AUSTIN, TEXAS 78744, USA 1-800-880-9473, FAX 512-443-6329, SALES@USAWIRE-CABLE.COM

7-13

Specification

HL TECK 90 MINUS 40C, FT4, 600 VOLTS


12AWG Multiconductor RW90 (.030 XLPE Insulation)
1. SCOPE 1.1 This specification describes multiconductor 12AWG TECK 90 MINUS 40C cable with -XLP crosslinked polyethylene insulation, PVC inner jacket, aluminum interlocked armor, and PVC outer jacket. The cables may be used in circuits not exceeding 600 volts at temperatures of 90C in wet or dry locations. Cables are intended for use indoors or outdoors in open wiring, ventilated flexible cableways, cable trays and direct burial installations in commercial or industrial applications. STANDARDS 2.1 The following standards shall form a part of this specification to the extent specified herein: 2.1.1 CSA Std C22.2 No. 131 TECK 90 MINUS 40C cable. 2.1.2 CSA Std C22.2 No. 0.3 Clause 4.11.4 FT-4 flame test. 2.1.3 Ontario Hydro Provisional Spec L891 SM-77. 2.1.4 CSA Std C22.2 No. 174 Cables and Cable glands for Use In Hazardous Locations. 2.1.5 CSA Std C22.2 No. 38 Thermoset Insulated Wires and Cables. CONDUCTORS 3.1 Conductors shall be Class B concentric stranded annealed uncoated copper conforming to CSA C22.2 No. 131. A nonhygroscopic separator may be used over the conductor at the option of the manufacturer. INSULATION 4.1 Shall be XLP crosslinked polyethylene meeting the requirements of CSA C22.2 No. 38 for Type RW90. Average thickness of insulation shall be 30 mils. Minimum thickness at any point shall be not less than 90% of the specified average thickness.
11

2.

3.

4.

5. CIRCUIT IDENTIFICATION 5.1 Conductors shall be colored; black, white (2/C); black, red, blue (3/C); black, red, blue, white (4/C). Cables with more than four conductors shall have circuit identification consisting of printed numbers. 6. ASSEMBLY 6.1 Insulated curcuit conductors shall be cabled together with a 14 AWG 7 strand uncoated copper grounding conductor and nonhygroscopic fillers where necessary. Maxirnum length of lay shall be as specified in Table 3 of CSA C22.2 No. 131. A suitable nonhygroscopic tape may be applied over the assembly. INNER PVC JACKET 7.1 Shall be PVC meeting the requirements of C22.2 No. 131 including requirements for low temperature classification of -40C. Thickness of jacket shall be as specified in Table 6 of C22.2 No. 131. INTERLOCKED ARMOR 8.1 An aluminum alloy interlocked armor shall be applied over the inner PVC jacket meeting the requirements of C22.2 No. 131, Clause 4.11. OUTER JACKET 9.1 Cables shall be covered with a black PVC jacket meeting the requirements of C22.2 No. 131 including requirements for low temperature classification of -40C. Thickness of covering shall not be less than 40 mils.

7.

8.

9.

10. IDENTIFICATION 10.1 Cables shall be surface ink printed with a legend identifying the manufacturer, number of conductors, size, voltage rating, TECK 90 MINUS 40C, XLPE, FT4, HL and length markings in meters. 11. TESTS 11.1 Completed cable shall be capable of compliance with the FT4 flame test of C22.2 No. 0.3, HL requirements of C22.2 No. 174 and the acid gas evolution test of OH L891 SM-77 in addition to the requirements for Type TECK 90 MINUS 40C cable in C22.2 No. 131.

7-14

6301 EAST STASSNEY LANE, SUITE 100 AUSTIN, TEXAS 78744, USA 1-800-880-9473, FAX 512-443-6329, SALES@USAWIRE-CABLE.COM

HL TECK 90 MINUS 40 C, FT4, 600 VOLTS (10 AWG)


10 AWG Multiconductor RW90 (.030" XLPE Insulations) No. 12 AWG Grounding Conductor Inner PVC Jacket, Aluminum Armor, Outer PVC Jacket
APPLICATION: As flame retardant multiconductor control, signal or power cables rated 600 volts, 90C in wet or dry locations. Widely used in the pulp and paper, petroleum, petrochemical, mining industries where cables with outstanding resistance to mechanical abuse, chemical attack and high reliability are required. Suitable for use in direct burial, open wiring, ventilated flexible cableways, and in non-ventilated, ventilated or ladder type cable trays. Inner and outer PVC jacket have low flame spread properties along with excellent low temperature properties. STANDARDS: 1. Listed as TECK 90 MINUS 40C per CSA Std C22.2 No. 131. 2. Passes FT-4 70000 BTU/Hr cable tray flame test of CSA Std C22.2 No. 0.3. 3. Complies with Acid Gas Evolution Test of Ontario Hydro Provisional Spec L-891 SM-77. Less than 14% acid gas evolution. 4. HL approved for use in hazardous locations per CSA Std C22.2 No. 174. CONSTRUCTION: Stranded uncoated concentric copper conductors, 30 mils XLP crosslinked polyethylene insulation, color coded. Two or more conductors twisted with one No. 12 AWG 7-strand bare copper grounding conductor and suitable fillers, tape, PVC innerjacket, aluminum interlocked armor, PVC outer jacket, surface printed.
Diameters No. of Condrs. Inner Jacket Thickness Inner Jacket Mils 10-02WGTECK90 10-03WGTECK90 10-04WGTECK90 10-05WGTECK90 10-06WGTECK90 10-07WGTECK90 10-08WGTECK90 10-09WGTECK90 10-10WGTECK90 10-11WGTECK90 10-12WGTECK90 10-13WGTECK90 10-14WGTECK90 10-15WGTECK90 10-16WGTECK90 10-17WGTECK90 10-18WGTECK90 10-19WGTECK90 10-20WGTECK90 10-25WGTECK90 10-30WGTECK90 10-40WGTECK90 10-50WGTECK90 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 25 30 40 50 45 45 60 60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 80 80 80 80 110 mm 1.14 1.14 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 In. .475 .502 .580 .630 .650 .650 .740 .795 .910 .910 .935 .950 .985 1.04 1.04 1.09 1.09 1.09 1.15 1.27 1.35 1.51 1.78 mm 12.1 12.8 14.7 16.0 16.5 16.5 18.8 20.2 23.1 23.1 23.7 24.1 25.0 26.4 26.4 27.7 27.7 27.7 29.2 32.2 34.3 38.4 45.2 In. .640 .667 .745 .795 .850 .850 .905 1.02 1.13 1.13 1.16 1.17 1.20 1.26 1.26 1.31 1.31 1.31 1.37 1.49 1.57 1.73 2.01 Armor mm 16.3 16.9 18.9 20.2 21.6 21.6 23.0 25.9 28.7 28.7 29.5 29.7 30.5 32.0 32.0 33.3 33.3 33.3 34.8 37.8 39.9 43.9 51.0 Outer Jacket In. .745 .772 .850 .900 .955 .955 1.01 1.12 1.23 1.23 1.26 1.28 1.31 1.36 1.36 1.42 1.42 1.42 1.47 1.60 1.68 1.84 2.12 mm 18.9 19.6 21.6 22.9 24.3 24.3 25.7 28.4 31.2 31.2 32.0 32.5 33.3 34.5 34.5 36.1 36.1 36.1 37.3 40.6 42.7 46.7 53.8 Net 295 345 405 480 545 590 680 735 805 840 945 990 1050 1090 1150 1210 1250 1290 1350 1590 1880 2390 2850 Copper 87 119 150 184 217 248 282 309 348 373 414 437 469 512 533 565 597 629 675 835 998 1321 1648 Weight lbs/1000 ft

USAWC Part #

6301 EAST STASSNEY LANE, SUITE 100 AUSTIN, TEXAS 78744, USA 1-800-880-9473, FAX 512-443-6329, SALES@USAWIRE-CABLE.COM

7-15

Specification

HL TECK 90 MINUS 40C, FT4, 600 VOLTS 10AWG Multiconductor RW90 (.030" XLPE Insulation)
1. SCOPE 1.1 This specification describes multiconductor 10 AWG TECK 90 MINUS 40C cable with XLP crosslinked polyethylene insulation, PVC inner jacket, aluminum interlocked armor, and PVC outer jacket. The cables may be used in circuits not exceeding 600 volts at temperatures of 90C in wet or dry locations. Cables are intended for use indoors or outdoors in open wiring, ventilated flexible cableways, cable trays and direct burial installations in commercial or industrial applications. STANDARDS 2.1 The following standards shall form a part of this specification to the extent specified herein: 2.1.1 CSA Std C22.2 No. 131 TECK 90 MINUS 40C cable. 2.1.2 CSA Std C22.2 No. 0.3 Clause 4.11.4 FT-4 flame test. 2.1.3 Ontario Hydro Provisional Spec L891 SM-77. 2.1.4 CSA Std C22.2 No. 174 Cables and Cable Glands for Use In Hazardous Locations. 2.1.5 CSA Std C22.2 No. 38 Thermoset Insulated Wires and Cables. CONDUCTORS 3.1 Shall be 10 AWG Class B concentric stranded annealed uncoated copper conforming to CSA C22.2 No. 131. A nonhygroscopic separator may be used over the conductor at the option of the manufacturer. INSULATION 4.1 Shall be XLP crosslinked polyethylene meeting the requirements of CSA C22.2 No. 38 for Type RW90. Average thickness of insulation shall be 30 mils. Minimum thickness at any point shall be not less than 90% of the specified average thickness. CIRCUIT IDENTIFICATION 5.1 Conductors shall be colored; black, white (2/C); black, red, blue (3/C); black, red, blue, white (4/C). Cables with more than four conductors shall have circuit identification consisting of printed numbers. ASSEMBLY 6.1 Insulated circuit conductors shall be cabled together with a 12 AWG 7-strand uncoated copper grounding conductor and nonhygroscopic fillers where necessary. Maximum length of lay shall be as specified in Table 3 of CSA C22.2 No. 131. A suitable nonhygroscopic tape may be applied over the assembly. INNER PVC JACKET 7.1 Shall be PVC meeting the requirements of C22.2 No. 131 including requirements for low temperature classification of -40C. Thickness of jacket shall be as specified in Table 6 of C22.2 No. 131. INTERLOCKED ARMOR 8.1 An aluminum alloy interlocked armor shall be applied over the inner PVC jacket meeting the requirements of C22.2 No. 131, Clause 4.11 . OUTER JACKET 9.1 Cables shall be covered with a black PVC jacket meeting the requirements of C22.2 No. 131 including requirements for low temperature classification of -40C. Thickness of covering shall not be less than 40 mils.

2.

3.

4.

5.

6.

7.

8.

9.

10. IDENTIFICATION 10.1 Cables shall be surface ink printed with a legend identifying the manufacturer, number of conductors, size, voltage rating, TECK 90 MINUS 40C, XLPE, FT4, HL and length markings in meters. 11. TESTS 11.1 Completed cable shall be capable of compliance with the FT4 flame test of C22.2 No. 0.3, HL requirements of C22.2 No. 174 and the acid gas evolution test of OH L891 SM-77 in addition to the requirements for Type TECK 90 Minus 40C cable in C22.2 No. 131.

7-16