600 V Flexible Thermoplastic Insulated Multiconductor. Each single conductor has a Thermoplastic Insulation protected with a Nylon Sheath, then the whole Multiconductor is protected by a Thermoplastic Jacket
PVC Jacket
Application
This product has been designed to operate at no more than 60C in dry or wet conditions. Besides that, the Nylon sheath provides protection to chemical agents and petroleum derivatives, therefore this product might be used for wiring solutions at either industrial or commercial and residential applications. Its black pigmentation on the external jacket resist the ultraviolet sun light exposure, thereby, these might be used at outside or wet applications.
Marking
PHELPS DODGE TSJ # X (GAUGE) AWG (GAUGE) mm) 600V WATER RESISTANT.
www.tecnojar.com
Tel. ( 5281 ) - 50 00 79 00
TSJ / TSJ-N
600 V Flexible Thermoplastic Insulated Multiconductor. Each single conductor has a Thermoplastic Insulation protected with a Nylon Sheath, then the whole Multiconductor is protected by a Thermoplastic Jacket
Installation
TSJ are widely used as part of non permanent installations as specied at article 400 of NEC: Low voltage appliance wiring. Tooling and portable lamps wiring. When its required to feed suspended and unhide lamps thru an outlet connector. To feed portable systems. As part of non permanent wiring system. Not permitted use and recommendations: In order to substitute outlets wiring for a permanent installation. It shall not be installed inside walls, suspended oor or roof. It shall not be wire up thru any hole at walls, suspended oor or roof. It shall not pass thru doors, windows or any opening where it could be damaged by sharp points. It shall not be stapled or nail down on the solid parts of the installation. It shall not be tubing in conduit. When used in an electric circuits derivation box, its recommended to use suitable connectors to insure the cable integrity. TSJ cannot substitute installation elements which need mechanical resistance since it is not designed for heavy duty applications. It is recommended that the installation instructions indicated by the Local Electric Code, or any equivalent, be followed in order to keep persons safe and the integrity of the product will not be affected by installation deciencies. For current ampacity details please refer to NEC table 400-5A, column according to each application.
www.tecnojar.com
Tel. ( 5281 ) - 50 00 79 00
TSJ / TSJ-N
600 V Flexible Thermoplastic Insulated Multiconductor. Each single conductor has a Thermoplastic Insulation protected with a Nylon Sheath, then the whole Multiconductor is protected by a Thermoplastic Jacket
Construction
Number of Strands
AWG / MCM 2x20 2x18 2x16 2x14 2x12 2x10 2x8 2x6 3x18 3x16 3x14 3x12 3x10 3x8 3x6 4x18 4x16 4x14 4x12 4x10 4x8 4x6
mm 0,52 0,82 1,31 2,08 3,31 5,26 8,37 13,30 0,82 1,31 2,08 3,31 5,26 8,37 13,30 0,82 1,31 2,08 3,31 5,26 8,37 13,30 7 10 16 26 41 65 105 168 10 16 26 41 65 105 168 10 16 26 41 65 105 168
in 0,030 0,030 0,030 0,030 0,045 0,060 0,060 0,060 0,030 0,030 0,030 0,045 0,060 0,060 0,060 0,030 0,030 0,030 0,045 0,060 0,060 0,060
mm 0,76 0,76 0,76 0,76 1,14 1,52 1,52 1,52 0,76 0,76 0,76 1,14 1,52 1,52 1,52 0,76 0,76 0,76 1,14 1,52 1,52 1,52
in 0,225 0,250 0,275 0,315 0,380 0,480 0,590 0,690 0,265 0,290 0,330 0,400 0,500 0,630 0,700 0,285 0,320 0,360 0,440 0,540 0,680 0,775
mm 5,72 6,35 6,99 8,00 9,65 12,19 14,99 17,53 6,73 7,37 8,38 10,16 12,70 16,00 17,78 7,24 8,13 9,14 11,18 13,72 17,27 19,69
www.tecnojar.com
Tel. ( 5281 ) - 50 00 79 00
TSJ / TSJ-N
600 V Flexible Thermoplastic Insulated Multiconductor. Each single conductor has a Thermoplastic Insulation protected with a Nylon Sheath, then the whole Multiconductor is protected by a Thermoplastic Jacket
Construction
Minimum Curvature
Max.C.D. Electrical Resistance @ 30C / Km 36,2 22,9 14,4 9,07 5,74 3,59 2,25 1,42 22,9 14,4 9,07 5,74 3,59 2,25 1,42 22,9 14,4 9,07 5,74 3,59 2,25 1,42
Standard Packaging
AWG / MCM 2x20 2x18 2x16 2x14 2x12 2x10 2x8 2x6 3x18 3x16 3x14 3x12 3x10 3x8 3x6 4x18 4x16 4x14 4x12 4x10 4x8 4x6
Kg / Km 38 48 63 86 134 217 336 475 58 78 108 168 272 424 609 70 96 134 209 337 528 765
mm 86 95 105 120 145 183 225 263 101 110 126 152 191 240 267 109 122 137 168 206 259 295
A ----------------7 10 15 20 25 35 45 7 10 15 20 25 35 45
B 7 10 13 18 25 30 40 55 10 13 18 25 30 40 55 ---------------
m CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000 CB 100, WR 500, WR 1000