Fairair Engineers Pvt.Ltd.

Project:

HEATLOAD ESTIMATION SHEET


PLAYSPAN(VISA)-GOREGAON

Design Conditions
Outdoor
Indoor
Difference

DB F

WB F

RH %

Gr/lb

100
75
25

83
-

60
55

144
72
72

Fresh air 5 cfm per person or one air change per hour

Particulars
Gain Factors
N-glass
23
1
E-glass
12
1
S-glass
12
1.00
W-glass
163
0.56
All-glass with sheet
25
0.63
All-glass without sheet 25
1.13
N-wall
22
0.36
E-wall
30
0.36
S-wall
36
0.36
W-wall
34
0.36
Part wall 6"
21
0.42
Part wall 4"
21
0.48
Part glass
20
1.13
Part ply
20
0.57
Floor load
25
0.48
Celing load
25
0.48
Lights 72 watts
3.4
72
Lights 36 watts
3.4
36
Gen. Lights w/sft
3.4
1.5
People
Office
245
1
- Gym
325
1
- Dinning
280
1
PC @ 200 Watts
3.4
200
Equipment load
3400
1
Fresh Air ( cfm )
25
1.08

M.F

AREA 1 Diversity H.LOAD AREA 2 Diversity H.LOAD

23

1.0

1.0

12

1.0

1.0

1.00

12

296

1.0

3,552

1.0

0.56

51

1.0

1.0

16

296

1.0

8,362

1.0

28

1.0

1.0

1.0

1.0

11

1.0

1.0

13.0

1.0

1.0

12.2

1.0

1.0

8.8

1.0

1.0

10.1

1.0

1.0

22.6

1.0

1.0

11.4

1.0

1.0

12.0

1.0

1.0

12.0

1.0

1.0

1.25

306.0

1.0

1.0

1.25

153.0

1.0

1.0

1.25

6.4

367

1.0

2,340

582

1.0

3,710

245

14

1.0

3,430

1.0

325

1.0

1.0

280

1.0

1.0

680

1.0

9,520

1.0

3,400

1.0

1.0

0.12

3.24

1.0

298

1.0

14
92

Sub Total

27,502
10.0%

SAFETTY FACTOR

2,750

Room Sensible Heat


People - Office
- Gym
- Dinning
Fresh Air ( cfm )
SubTotal

10.0%

371

30,252
14

3,710
4,081

205

205

2,870

525

525

270

270

72

0.68

0.12

5.88

325

1,909

4,779
5.00%

SAFETY FACTOR

239

Room Latent Heat


Room Total Heat
Fresh Air ( cfm )
25
Fresh Air ( cfm )
72
Grand Total Heat ( BTU/HR )

5.00%

5,018

35,270

4,081

1.08

0.88

23.76

92

2,186

0.68

0.88

43.08

92

3,964

41,420

4,081

3.45

0.34

0.86

1.00

55.0

56.5

Tons
SHF ( Sensible Heat Factor )
ADP F
Evap.Coil Bypass factor
Dehumidified Temperature rise F

0.03

0.17

19.40

15.36

Dehumidified CFM

1,444

246

Fairair Engineers Pvt.Ltd.


Project:

HEATLOAD ESTIMATION SHEET


PLAYSPAN(VISA)-GOREGAON

Design Conditions
Outdoor
Indoor
Difference

DB F

WB F

RH %

100
75
25

83
-

60
55

Fresh air 5 cfm per person or one air change per hour

Particulars
Gain Factors
N-glass
23
1
E-glass
12
1
S-glass
12
1.00
W-glass
163
0.56
All-glass with sheet
25
0.63
All-glass without sheet 25
1.13
N-wall
22
0.36
E-wall
30
0.36
S-wall
36
0.36
W-wall
34
0.36
Part wall 6"
21
0.42
Part wall 4"
21
0.48
Part glass
20
1.13
Part ply
20
0.57
Floor load
25
0.48
Celing load
25
0.48
Lights 72 watts
3.4
72
Lights 36 watts
3.4
36
Gen. Lights w/sft
3.4
1.5
People
Office
245
1
- Gym
325
1
- Dinning
280
1
PC @ 200 Watts
3.4
200
Equipment load
3400
1
Fresh Air ( cfm )
25
1.08

AREA 3 Diversity H.LOAD


-

1.0

1.0

1.0

1.0

1.00

1.0

1.0

0.56

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1
1

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1
1.25

1.0

1.0

1.25

1.0

1.0

1.25

160

1.0

1,020

365

1.0

2,327

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

0.12

1.0

1.0

Sub Total

1,020
10.0%

SAFETTY FACTOR

102

Room Sensible Heat


People - Office
- Gym
- Dinning
Fresh Air ( cfm )
SubTotal

2,327

10.0%

233

1,122

2,560

205

525

270

72

0.68

0.12

5.00%

SAFETY FACTOR

Room Total Heat


Fresh Air ( cfm )
25
Fresh Air ( cfm )
72
Grand Total Heat ( BTU/HR )
Tons
SHF ( Sensible Heat Factor )
ADP F
Evap.Coil Bypass factor
Dehumidified Temperature rise F

Room Latent Heat

Dehumidified CFM

AREA 4 Diversity H.LOAD

5.00%

1,122

2,560

1.08

0.88

0.68

0.88

1,122

2,560

0.09

0.21

1.00

1.00

55.0

55.0

0.12

0.12

17.60

17.60

59

135