PLCC Technology
PLCC system uses the same High Voltage transmission line connecting two
PLCC is used in all power utilities as a primary communication service to transmit speech, telemetry and protection tripping commands. This is economic and reliable for inter grid message transfer.
The voice/data are mixed with radio frequency carrier (40-500kHz), amplified and injected in to high voltage power line using a suitable coupling capacitor. The power line as a rigid long conductor parallel to ground, guides the carrier waves to travel along the transmission line.
CC
RF carrier (40-500kHz)
PAX
RTU PLCC
TERMINAL
(ABB-ETL41)
Transmission line
4
H.V Line
Line Trap
Coupling
capacitor
PLCC Terminal = Translates voice and data into High Frequency Carrier. Output Power =10 to 80W LMU = Line Matching Unit = For impedance matching between line and coaxial cable, includes high voltage protection devices like drainage coil(20mH), lightening arrestor(500V) and an earth switch. Coupling Capacitor = Couples high frequency carrier with Power Line ( 4000 to10000pF) Line Trap = Do not allow the transmitted HF carrier to enter inside the sub-station. (L = 0.5 to 2mH) With out Line trap HF carrier get by-passed to some other line on the same bus bar and may leak to ground ( a earth switch inside the yard provided for each bay is kept closed during maintenance)
5
Front
To remote substation
Coupling Capacitor
Transformer(s) BusBar
Coaxial
Local substation
PLC terminal
PLC Signal
Substation
Line Trap = High Impedance for PLC signal Low Impedance for Power energy
Vertical Pedestal
Horizontal Pedestal
Suspension
LMU function
LMU = impedance matching Transformer
Line Trap
Coaxial
Matching
Protection
LMU
10
11
Earth switch for grounding of line terminals during maintenance. High-pass or band-pass filter elements for efficient matching. connectivity to equipment room through coaxial cable.
12
HF Coupling modes
LT
LT
Cc
LT
Cc PLC
LMU
Cc
LT
LT
PLC
LMDU
LMU
Phase-to-Ground
PLC
Cc
Cc
LMDU
LMU
Inter circuit
Phase-to-Phase
13
Cabinet
Modules
14
Because of the skin effect, the carrier signal tries to propagate on the ice instead of the conductor. The attenuation can change as much as 4:1 depending on the frequency.
The contaminats (on the insulators) have a larger effect when it is raining than when the line is dry. The worst condition is a light rain with the presence of contaminants on the insulators
15
CONCLUSION
PLCC is the most economical and reliable method of
communication because of higher mechanical strength and insulation level of the high voltage power lines which contribute to the increased reliability of communication and lower attenuation over longer distances.