GEP110-2

Diesel Generator Set Exclusively from your Caterpillar dealer

Output Ratings
Generating Set Model 380-415V,50Hz Prime* 100.0 kVA 80.0 kW 480V, 60 Hz 113.0 kVA 90.4 kW * Refer to ratings definitions on page 4. Ratings at 0.8 power factor. Standby* 110.0 kVA 88.0 kW 125.0 kVA 100.0 kW

Technical Data
Engine Make & Model: Alternator Model: Base Frame Type: Circuit Breaker Type: Frequency: Engine Speed: RPM Fuel Tank Capacity: litres (US gal) Fuel Consumption, Prime: l/hr (US gal/hr) Fuel Consumption, Standby : l/hr (US gal/hr) 21.9 (5.8) 24.1 (6.4) Perkins 1104C-44TAG2 LL3014B Heavy Duty Fabricated Steel 3 Pole MCB / 3 Pole MCCB 50 Hz 1500 227 (60.0) 26.3 (6.9) 29.3 (7.7) 60 Hz 1800

Engine Techncial Data


Physical Data
Manufacturer: Model: No. of Cylinders/Alignment: Cycle: Induction: Cooling Method: Governing Type: Governing Class: Compression Ratio: Displacement: l (cu.in) Bore/Stroke: mm (in) Moment of Inertia: kg m (lb. in) Engine Electrical System: -Voltage/Ground: -Battery Charger Amps: Weight: kg (lb) - Dry: - Wet: 12/Negative 65 500 (1102) 520 (1146) Perkins 1104C-44TAG2 4 / In Line 4 Stroke Turbocharged Air To Air Charge Cooled Water Electronic ISO 8528 G2 18.3:1 4.4 (268.5) 105.0 (4.1)/127.0 (5.0) 1.51 (5160)

Lubrication system
Oil Filter Type: Total Oil Capacity l (US gal): Oil Pan l (US gal): Oil Type: Cooling Method: Spin-On, Full Flow 8.0 (2.1) 7.0 (1.8) API-CC/SE Water

Performance
Engine Speed: RPM Gross Engine Power: kW (hp) -Standby: -Prime: BMEP: kPa (psi) -Standby: -Prime: Regenerative Power: kW

50 Hz
1500 103.0 (138.0) 93.6 (126.0)

60 Hz
1800 117.5 (158.0) 106.8 (143.0)

1873.0 (271.7) 1781.0 (258.3) 1702.0 (246.9) 1619.0 (234.8) 8.2 13.8

Fuel System
Fuel Filter Type: Replaceable Element Recommended Fuel: 110% Load Prime 50 Hz 60 Hz Standby 50 Hz 60 Hz 24.1 (6.4) 29.3 (7.7) 18.2 (4.8) 21.9 (5.8) 12.6 (3.3) 15.4 (4.1) 24.1 (6.4) 29.3 (7.7) 21.9 (5.8) 26.3 (6.9) 16.6 (4.4) 19.9 (5.3) 11.7 (3.1) 14.2 (3.8) Class A2 Diesel Fuel Consumption: l/hr (US gal/hr) 100% Load 75% Load 50% Load

Air System
Air Filter Type: Combustion Air Flow: m/min (cfm) -Standby: -Prime: Max. Combustion Air Intake Restriction: kPa (in H2O) Radiator Cooling Air Flow: m/min (cfm) External Restriction to Cooling Air Flow: Pa (in H2O)

50 Hz
Replaceable Element 6.3 (221) 6.0 (212) 8.0 (32.1)

60 Hz

7.8 (275) 7.7 (273) 8.0 (32.1)

187.8 (6632) 244.2 (8624) 125 (0.5) 125 (0.5)

(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)

Cooling System
Cooling System Capacity: l (US gal) Water Pump Type: Heat Rejected to Water & Lube Oil: kW (Btu/min) -Standby: -Prime: Heat Radiation to Room: kW (Btu/min) -Standby: -Prime: Radiator Fan Load: kW (hp)

50 Hz
17.5 (4.6)

60 Hz
17.5 (4.6)

Exhaust System
Silencer Type: Silencer Noise Reduction Pressure Drop Across Silencer System: kPa (in Hg) Silencer Noise Reduction

50 Hz
Level 1

60 Hz

SD50 (1) 2.10 (0.620) 3.56 (1.051) 22 18.0 (5.3) 16.3 (576) 15.2 (537) 543 (1009) 514 (957) 17 15.0 (4.4) 20.4 (720) 18.4 (650) 574 (1065) 517 (963)

Centrifugal

50.7 (2883) 46.1 (2622) 7.5 (427) 6.8 (387) 2.8 (3.8)

62.5 (3554) 56.9 (3236) 9.2 (523) 8.4 (478) 4.8 (6.4)

Level: dB Max. Allowable Back Pressure: kPa (in. Hg) Exhaust Gas Flow: m/min (cfm) -Standby: -Prime: Exhaust Gas Temperature: C (F) m/min (cfm) -Standby: -Prime:

Cooling system designed to operate in ambient conditions up to 50C (122F). Contact your local Olympian dealer for power ratings at specific site conditions.

Consult your Olympian representative for more information

Alternator Performance Data


50 Hz Data Item
415/240V 400/230V 230/115V 200/115V 380/220V 220/110V 220/127V 480/277V 240/139V 380/220V 220/110V

60 Hz
240/120V 208/120V 230/115V 440/254V 220/127V

Motor Starting Capability* kVA

187

176

160

208

206

136

160

149

177

Short Circuit Capacity** %

300

300

300

300

300

300

300

300

300

Reactances: Per Unit

Xd X'd X''d

3.200 0.120 0.074

3.440 0.130 0.080

3.810 0.150 0.089

2.840 0.110 0.066

3.240 0.130 0.075

5.080 0.200 0.118

4.310 0.170 0.100

4.660 0.180 0.108

3.850 0.150 0.090

Reactances shown are applicable to standby ratings. * Based on 30% voltage dip. Improved motor starting capability is available with optional Permanent Magnet generator or AREP excitation. ** With optional Permanent Magnet generator or AREP excitation.

Alternator Technical Data


Physical Data
Manufacturer: Model: No. of Bearings: Insulation Class: Winding Pitch - Code: Wires: Ingress Protection Rating: Excitation System: AVR Model: OLYMPIAN LL3014B 1 H 2/3 - 6 12 IP23 SHUNT R250

Operating Data
Overspeed: RPM Voltage Regulation (steady state) (% ): Wave Form NEMA = TIF: Wave Form IEC = THF: Total Harmonic Content LL/LN: Radio Interference: 2250 +/- 0.5 50 2.0% 4.0%

Supression is in line with European Standard EN61000-6

Radiant Heat: kW (Btu/min) -50 Hz: -60 Hz: 9.0 (512) 11.0 (626)

Consult your Olympian representative for more information

3 Phase Ratings and Performance at 50 Hz, 1500 RPM

Technical Data
Voltage
kVA
415/240V 400/230V 380/220V 230/115V 220/127V 220/110V 200/115V

3 Phase Ratings and Performance at 60 Hz, 1800 RPM

Prime
kW
80.0 80.0 80.0 80.0 80.0 80.0 80.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0

Standby
kVA
110.0 110.0 110.0 110.0 110.0 110.0 110.0

Voltage
kW
88.0 88.0 88.0 88.0 88.0 88.0 88.0 480/277V 220/127V 380/220V 240/120V 230/115V 440/254V 220/110V 208/120V 240/139V

Prime
kVA
113.0 113.0 111.0 113.0 113.0 113.0 111.0 113.0 113.0

Standby
kW
90.4 90.4 88.8 90.4 90.4 90.4 88.8 90.4 90.4

kVA
125.0 125.0 122.0 125.0 125.0 125.0 122.0 125.0 125.0

kW
100.0 100.0 97.6 100.0 100.0 100.0 97.6 100.0 100.0

Weights & Dimensions


Weights: kg (lb)
Net (+ lube oil) Wet (+ lube oil & coolant) Fuel, lube oil & coolant 1167 (2573) 1180 (2601) 1372 (3024)

Dimensions: mm (in)
Length Width Height 2370 (93.3) 735 (28.9) 1381 (54.4)

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Definitions
Standby Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

General Data
Documents
Operation and maintenance manuals provided. Wiring diagrams included.

Quality Standards
BS4999, BS5000, BSEN60034, BSEN61000, IEC60034.

Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Warranty
All equipment carried full manufacturer's warranty.

Standard Reference Conditions


Note: Standard reference conditions 27C (80F) air Inlet Temp, 152.4m (500ft) A.S.L. 60% relative humidity. Fuel consumption data at full laod with diesel fuel with spedcific gravity of 0.85 and conforming to Bs2869: 1998, Class A2.

Market: International LEHF7036-01

Information contained in this publication may be considered confidential. Discretion is recommended when distributing. Materials and specifications are subject to change without notice. CAT, CATERPILLAR, OLYMPIAN, their respective logos and ''Caterpillar Yellow'', as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.

www.CAT-ElectricPower.com 2008 Caterpillar All rights reserved. Printed in the U.S.A.