General Specications
GS 33L01A10-40E
GENERAL
This document provides the overall system specications of the CENTUM VP Systems with Vnet/IP.
SYSTEM CONFIGURATION
Vnet/IP domain Open Display Style Console HIS Enclosed Display Style Console HIS ProSafe-RS Safety Instrumented System SENG
SNTP Server
FCS (for FIO) ESB bus Other system Local node ER bus
V net router
Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5634 Fax.: 81-422-52-9802
GS 33L01A10-40E Copyright Feb. 2008 (YK) 9th Edition Jun. 2, 2010 (YK)
<<Contents>> <<Index>>
2
Generic Subsystem Gateway Station (GSGW)
A GSGW can collect and set data of various types of subsystems through OPC DA servers. No dedicated communication program is required. GSGW is a general-purpose PC with LFS1250 Generic Subsystem Gateway Package. For connections to the Vnet/IP, a VI702 Control Bus Interface Card is required. For more information, see GSGW Generic Subsystem Gateway Package (GS 33M20F10-40E).
SYSTEM COMPONENTS
Human Interface Station (HIS)
An HIS serves as a human machine interface for plant operators. Software packages are installed in a general-purpose personal computer (an IBM PC/AT compatible computer, hereinafter referred to as a general-purpose PC). The HIS PC can be assembled in the console box. For connections to the Vnet/IP, a VI702 Control Bus Interface Card is required. For more information on HIS hardware requirements, see the following General Specications: Enclosed Display Style Console Assembly (GS 33M50B40-40E) Open Display Style Console Assembly (GS 33M50B50-40E) Standard Operation and Monitoring Function (GS 33M05D10-40E) Vnet/IP Interface Card (GS 33L50C10-40E)
GS 33L01A10-40E
May 1, 2009-00
<<Contents>> <<Index>>
3
Layer 3 Switch
This is the COTS switch with the routing function, and can divide the Vnet/IP network into several domains.
Vnet/IP
Vnet/IP is the IEEE 802.3 compliant, dual-redundant high-speed (1Gbps) control network. All the components of the Vnet/IP network are connected to the Layer 2 switches. Layer 2 switches are required for each of the dual redundant networks. One of the dual-redundant networks (called Bus 1) is exclusively used for process control communication. The other (called Bus 2) is used not only for process control communication redundant with Bus 1, but also for the open communication with the generic Ethernet protocol. Using Layer 3 switches, the Vnet/IP can be divided into several domains. VI702 the NIC (Network Interface Card) for Vnet/IP is required for each PC, which is connected to the Vnet/IP. Commercially available products are used for all other network equipment such as switches, LAN cables, or repeaters.
V net Router
This is the equipment to connect a Vnet/IP system and a V net system. This router enables the HIS of both Vnet/IP and V net to operate the FCS of the other systems. The following product is available. AVR10D: Duplexed V net Router (for redundant use of communications and power supply modules) For information on the hardware specications, see Duplexed V net Router (GS 33L50D30-40E).
SNTP Server
The time of all the components connected to the Vnet/IP network is synchronized. By connecting the COTS SNTP server on the Vnet/IP network, the time of Vnet/IP components can be synchronized with UTC (Coordinated Universal Time).
Layer 2 Switch
This is the COTS (Commercial off-the-shelf) switch equipment. At least two switches are mandatory for one Vnet/IP system. The transmission speed for Vnet/IP has to be 1 Gbps.
Peripherals Device
Please use compatible models of the peripheral devices, such as printers, which support the designated Operation Systems. Consult with a Yokogawa sales department for more information about those compatible devices with HIS.
GS 33L01A10-40E
Jun. 1, 2010-00
<<Contents>> <<Index>>
4
Installing of Server PCs
Each number shown below includes the number of CS 3000 PCs. CENTUM VP achieves many functions using le sharing function of Windows. The number of PCs to share les simultaneously is restricted on the Windows Workstation OS. Therefore, when there are 9 or more stations (HIS, ENG, Exaopc) in one project, the PC with a server OS may be required. Please count the total station number in one project using the equations shown below in order to judge whether server PC is required or not. If the number is eight or smaller, a server PC is not required. If the number is larger than 8, consult with a Yokogawa sales representative for further examination. In case of PCs storing master Engineering database le When not using Engineering Tool for FOUNDATION eldbus (SSS5700) Total station number = HIS + ((ENG - 1) x 2) + Exaopc When using Engineering Tool for FOUNDATION eldbus (SSS5700) Total station number = HIS + ((ENG - 1) x 2) + Exaopc + 2 Number of PCs in which Standard Operation and Monitoring Function (LHS1100 or LHM1101) is installed ENG: Number of PCs in which Standard Builder Function (LHS5100 or LHM5100) is installed. Exaopc: Number of PCs with Exaopc Interface Package (NTPF100) When using Multiple Project Connection Package (LHS4450), see Multiple Project Connection Package (GS 33M05K20-40E). When using Expanded Test Function (LHS5425), a server PC is always required for storing master Engineering database. In case of PCs storing audit trail data When using LHS5170 Access Administrator Package, one PC which is dedicated for storing audit trail data must be prepared. When there are 9 or more stations (ENG, Recipe Management PC) in one project, the server PC may be required for storing audit trail data. Please count the total station number in one project using the equations shown below in order to judge whether server PC is required or not. If the number is eight or smaller, a server PC is not required. If the number is larger than 8, consult with a Yokogawa sales representative for further examination. Total station number = ENG + Recipe Management ENG: Number of PCs in which Standard Builder Function (LHS5100 or LHM5100) is installed. Recipe Management: Number of PCs in which CS Batch 3000 Recipe Management package (LHS5161) is installed HIS :
SYSTEM SPECIFICATIONS
Number of Tag
Up to 100,000 per system (when using LHS4000, up to 1,000,000 per system)
Minimum System
A minimum system consists of one HIS with engineering function and one FCS.
Maximum System
64 components/domain 16 domain/system 256 stations/system Components: Human Interface Station (HIS) Field Control Station (FCS) Advanced Process Control Station (APCS) Generic Subsystem Gateway (GSGW) System Integration OPC Station (SIOS) Safety Instrumented Systems (ProSafe-RS) OPC Interface Package (Exaopc) OPC server Field Communications Server for Plant Resource Manager (PRM) V net Router (AVR10D) On the bus 2, up to 124 general-use Ethernet devices (including intelligent network devices) other than listed above can be additionally connected.
Expanded System
The former systems than V net such as HF bus or RL bus can be connected on a Vnet/IP system through a bus converter on a V net. Vnet/IP domains and V net domains can be managed in the same project, or can be connected with a Multiple Project Connection Package. For more information, see Multiple Project Connection Package (GS 33M05K20-40E).
GS 33L01A10-40E
Jun. 1, 2010-00
<<Contents>> <<Index>>
The Vnet/IP is a real-time process control network used to connect system components. The Vnet/IP supports two types of communications: control-bus communications and open communications. The Vnet/IP is always dualredundant. Usually, control bus communications are carried out via bus 1. Open communications are carried out via bus 2. If a control communications error occurs on bus 1, control bus communications will be carried out via bus 2. The Vnet/IP uses general-purpose communications devices for network connection.
HIS ENG APCS GSGW Exaopc 1000BASE-T Max. 100 m
Vnet/IP domain
Vnet/IP domain
Layer 3 switch
HF-bus domain
FFCS-L
F03E.ai
GS 33L01A10-40E
Jul. 1, 2008-00
<<Contents>> <<Index>>
6
Required Network Equipment Specications
Layer 2 switch Connection Port: 1000BASE-T, full duplex Connection between switches: 1000BASE-T, 1000BASE-LX with speed, 1 Gbps (1.5 Mpps@64 byte) or faster, full duplex Auto-Negotiation: Mandatory Layer 3 switch Connection Port: 1000BASE-T, full duplex Connection between switches: 1000BASE-T, 1000BASE-LX with speed, 1 Gbps (1.5 Mpps@64 byte) or faster, full duplex Unicast dynamic routing protocol: RIPv2 (RIPv1 compatible mode is mandatory) Multicast Protocol: IGMP: Mandatory DVMRP or PIM-DM: Mandatory Management function SNMP
Communications Specications
Control communications Communication Method: Read/write communication, message communication, and intercontroller communication Inter-Controller Communication Period: 100 msec Open communications Open communications are executed via bus 2. Commercially available Ethernet communications devices can be connected. The total bandwidth that can be used for open communications on bus 2 is up to 300 Mbps. Transmission Path Specications Network Topology: Star Topology Transmission Path Redundancy: Available (control bus communications only) Transmission Cable: Unshielded twisted pair (UTP) at enhanced category 5 or better.
Connection Between component and a layer 2 switch Between layer 2 switches Between a layer 2 switch and a layer 3 switch *1: Cable Standard 100BASE-TX (IEEE802.3u) 1000BASE-T (IEEE802.3ab) 1000BASE-T (IEEE802.3ab) 1000BASE-LX (IEEE802.3z) 1000BASE-T (IEEE802.3ab) 1000BASE-LX (IEEE802.3z) Speed 100 Mbps (*1) 1 Gbps 1 Gbps 1 Gbps 1 Gbps 1 Gbps Maximum Distance 100 m
100 m 5 km 100 m 5 km
GS 33L01A10-40E
Jul. 1, 2008-00
<<Contents>> <<Index>>
If local nodes are connected to an AFV10S or AFV10D FCU, ESB Bus Coupler Modules (EC401) have to be installed in slots 7 and 8.
Transmission Path Specications Network Topology: Bus topology Transmission Path Redundancy: Available Transmission Speed: 128 Mbps Transmission Cable: Dedicated cable (YCB301) Transmission Distance: 10 m max.
ER Bus
Application An ER bus is a remote I/O communications bus to connect an FCU or local node unit to the I/O expansion nodes remotely. The nodes connected on the ER bus are named remote node. Communication Specications Connectable Devices: Remote node units (ANR10S, ANR10D) Number of ER buses: Max. 4 per FCU Number of Connectable Devices: The number of remote node units that can be connected to an ER bus varies according to the model and database selected.
Database Control Function for Standard Field Control Unit Control Function for Standard Field Control Unit plus Application Capacity Expansion Package (LFS1530) *1: Up to eight remote nodes per ER bus can be connected. Maximum Number of Remote Nodes 3 14 (*1) Total Number of Local and Remote Nodes 3 14
<<Contents>> <<Index>> Transmission Path Specications Network Topology: Bus topology Transmission Path Redundancy: Available Transmission Speed: 10 Mbps Transmission Cable: Coaxial cable (YCB141, YCB311). Use YCB147 ER-bus Adapter and YCB149 ER Bus Converter Unit for connecting YCB141 and YCB311 cables. One grounding unit (YCB117) per segment (*1) should be used when connecting YCB311 cable. Transmission Distance: YCB141: Max.185 m When mixing YCB141 and YCB311: Length of YCB141 + (185/500) x Length of YCB311 185 Number of Bus Adapter Units: Max. 4 per segment (*1) General-purpose Ethernet Repeater: The total transmission distance is limited by the number of repeaters. L 4 - 0.5 n L: total transmission distance (km) n: the number of the general-purpose Ethernet repeater (Max. 4 repeaters)
*1: If repeaters are used on ER bus, each part of the ER bus segregated by a repeater is referred to as a segment.
EB401
AFV10D (Node1)
AFV10D (Node1)
EB401
Repeater Optical Fiber Cable Repeater EB501 ANR10D (Node2) ER bus EB501
ANR10D (Node3)
Repeater
Repeater
Optical Fiber Optical Fiber Cable Cable Repeater EB501 Repeater ANR10D (Node4)
ANR10D (Node4)
ANR10D (Node3)
F04.ai
<<Contents>> <<Index>>
9
Standard FCS Software
LFS1500 Control Function for Standard Field Control Unit (for FIO, Vnet/IP) LFS1530 Application Capacity Expansion Package (for AFV10) For more information, see Control Function for Basic Field Control Unit, Application Capacity Expansion Package (GS 33L15C20-40E).
SOFTWARE
Operation and Monitoring Software
LHS1100 Standard Operation and Monitoring Function LHS1120 Console HIS Support Package for Enclosed Display Style LHS1130 Console HIS Support Package for Open Display Style LHS1150 Server for Remote Operation and Monitoring Function LHS2411 Exaopc OPC Interface Package (for HIS) LHS2412 CENTUM Data Access Library LHS4000 Million Tag Handling Package LHS4100 Congured Information Reference Package LHS4150 Recorder Output Package LHS4190 Line Printer Support Package LHS4200 Consolidated Historical Message Viewer (Meeting FDA) LHS4410 Control Drawing Status Display Package LHS4420 Logic Chart Status Display Package LHS4450 Multiple Project Connection Package LHS4600 Multiple-monitor Package LHS4700 Advanced Alarm Filter Package LHS6510 Long-term Data Archive Package LHS6530 Report Package LHS6600 CS Batch 3000 Process Management Package LHS6710 FCS Data Setting/Acquisition Package (PICOT) For more information on the above functions, see the respective GSs. The following operating systems can be used on HIS which supports operation, monitoring, and engineering. Windows Vista Business Edition Windows XP Professional Edition Windows Server 2003 Standard Edition Windows Server 2008 Standard Edition As for Windows OS and Service Pack, see Standard Operation and Monitoring Function (GS 33M05D1040E) and Standard Builder Function (GS 33M10D1040E). If it is necessary to run other third-party software on the HIS, consult with a Yokogawa sales department to conrm that it is supported.
Engineering Software
Standard Builder Function Access Control Package Graphic Builder CS Batch 3000 Builder CS Batch 3000 Recipe Management Package LHS5170 Access Administrator Package (FDA: 21 CFR Part 11 compliant) LHS5420 Test Function LHS5425 Expanded Test Functions LHS5426 FCS Simulator Package LHS5427 HIS Simulator Package LHS5450 Multiple Project Connection Builder LHS5490 Self-documentation Package LHS5800 Turbomachinery I/O Module Logic Builder Package For more information on the above functions, see the respective GSs.
All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation
GS 33L01A10-40E
Jun. 2, 2010-00
<<Contents>> <<Index>>
10
INSTALLATION AND ENVIRONMENTAL CONDITIONS
Documents
LHS5495 Electronic Document For more information, see Electronic Instruction Manual (GS 33M01W10-40E).
The installation and environmental conditions for Yokogawas components (not including the generalpurpose PCs, General-Purpose Network Device, console HISs, node units for FIO and I/O modules) are shown below. For a general-purpose PC and Network equipment, see their specications. For an Enclosed display style console HIS, an Open display style console HIS, a node unit for FIO, or an I/O module, see the general specications for each device (GS 33M50B40-40E, GS 33M50B50-40E or GS 33M50F10-40E). Ambient Temperature: 5 to 40 C (YAX101, YAX801) 0 to 50 C (FCS) Ambient Humidity: 20 to 80 %RH 10 to 90 %RH (FCS) Non-condensation Temperature Change Rate: 10 C per hour Power Requirements: 100 to 120 V AC 10 %, 50 or 60 Hz 3 Hz 220 to 240 V AC 10 %, 50 or 60 Hz 3 Hz 24 V DC 10 % Withstanding Voltage: 1500 V AC for 1 minute (for 100-120 and 220-240 V AC model) 500 V AC for 1 minute (for 24 V DC model) Insulation Resistance: 20 M at 500 V DC 10 M at 500 V DC (YAX101, YAX801) Grounding: Independent ground of up to 100 Noise: Electric Field: Up to 3 V/m (26 MHz to 1.0 GHz) Up to 3 V/m (1.4 to 2.0 GHz) Up to 1 V/m (2.0 to 2.7 GHz) Magnetic Field: Up to 30 A/m (AC), up to 400 A/m (DC) Static: Up to 4 kV (direct discharge), up to 8 kV (aerial discharge) Continuous Vibration: Displacement amplitude: Up to 0.25 mm (1 to 14 Hz) Acceleration: Up to 2 m/s2 (14 to 100 Hz)
<<Contents>> <<Index>>
11
The CENTUM VP Entry Class is available for small-scale systems. Up to 8,000 tag names can be used in a CENTUM VP Entry Class system.
The CENTUM VP Entry Class uses specic Entry Class packages such as built-in HIS packages. There is no restriction on FCS models.
Engineering Software
Entry Class Model LHM5100 LHM5150 LHM5490 Product Standard Builder Function Test Function Self-documentation Package Remarks
Restrictions
For CENTUM VP Entry Class, the following restrictions apply. Only one domain per system The HIS in a CENTUM VP Entry Class project cannot access the FCSs in other projects of CENTUM VP, CENTUM VP Entry Class, CENTUM CS 3000 and CENTUM CS 3000 Entry Class. The HIS in a CENTUM VP Entry Class project can access the FCSs in the Micro-XL system ,but not other former CENTUM systems.
<<Contents>> <<Index>>
12
*3: A Class A hardware device is designed for use in the industrial environment. Please use this device in the industrial environment only. A lightning arrestor or its equivalent is required to meet this surge immunity standard. The length of the cable to feed the external power supply for AGS813 AO channels should not exceed 30 meters. An external device such as a power unit with harmonic current neutralizer and an active harmonics conditioner must be connected to meet this harmonic current emission standard. The specied limits of voltage drops across wiring must be satised to meet this standard. To meet the standard for hazardous location equipment, 19-inch rack-mounted devices must be installed in a keyed metallic cabinet approved by CSA or non-incendive regulator in your area. To meet the standard for hazardous location equipment, 19-inch rack-mounted devices must be installed in a keyed metallic cabinet approved by FM or non-incendive regulator in your area. To be compatible with Type n, the specication requirements of EN 61010-1 and EN 60079-15 must be met, and a keyed metallic cabinet, whose degree of protection is IP 54 or above, prescribed by IEC 60529 must be used for housing.
REGULATORY COMPLIANCE
CENTUM VP hardware components conform to the following standards. See the applicable general specications to ensure each devices compliance. Safety Standards (*1) [CSA] CSA C22.2 No. 61010-1 [CE Marking] Low Voltage Directive EN 61010-1 (*2) EMC Conformity Standards (*1) [CE Marking] EMC Directive EN 55011 Class A Group 1 (*3) EN 61000-6-2 (*4) EN 61000-3-2 (*5) EN 61000-3-3 (*6) [C-Tick Marking] EN 55011 Class A Group 1 (*3) Standards for Hazardous Location Equipment [CSA Non-Incendive] (*7) Class I, Division 2, Groups A, B, C and D Temperature code T4 CSA Standard C22.2 No. 157-92 CSA Standard C22.2 No. 213-M1987 ISA Standard ISA-S12.12 1994 (for 100-120 V AC and 24 V DC power supply) [FM Non-Incendive] (*8) Class I, Division 2, Groups A, B, C and D Temperature code T4 FM Class Number 3600: 1998 FM Class Number 3611: 2004 FM Class Number 3810: 2005 (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) [Type n] (*9) II 3G Ex nC [nL] II C T4 EN 60079-15: 2005 IEC 60079-0: 2004 IEC 60079-11: 1999 (for 24 V DC power supply) II 3G EEx nA II T4 EN 50021: 1999 (I/O Module with built-in barrier, for 24 V DC power supply) [Type i (Intrinsic Safety)] II (1) G D [EEx ia] II C EN 50014: 1997 +A1 +A2 EN 50020: 1994 [FM Intrinsic Safety] Associated intrinsically safe apparatus for connection to Class I, II and III, Division 1, Groups A, B, C, D, E, F and G or Class I, Zone 0, Group II C FM Class Number 3600: 1998 FM Class Number 3610: 1999 ANSI/ISA-12.12.02: 2003
*1: *2: To conform to safety standards and EMC conformity standards, install 19-inch rackmounted devices in a keyed metallic cabinet. The analog input side of this equipment is measurement category 1. For details, see CENTUM VP Installation Guidance (TI 33L01J10-40E).
*4:
*5:
*6: *7:
*8:
*9:
Note: According to the New Approach Directive, the manufacturer and the representative ofce in EU are indicated below: Manufacturer: Yokogawa Electric Corporation (29-32 Nakacho, Musashino-shi, Tokyo 180-8750, Japan). Representative ofce in EU Community: Yokogawa Europe B.V. (Euroweg 2, 3825 HD Amersfoort, The Netherlands).
TRADEMARKS
CENTUM, Vnet/IP, DARWIN, DAQSTATION ProSafe and Exaopc are registered trademarks of Yokogawa Electric Corporation. Exaplog and Exapilot are trademarks of Yokogawa Electric Corporation. Windows is a registered trademark of Microsoft Corporation in the United States and/or other countries. Ethernet is a registered trademark of XEROX Corporation. Modbus is a registered trademark of Schneider Electric and/or such related companies. PLC, PLC-5 and SLC500 are trademarks or registered trademarks of Rockwell Automation, Inc. MELSEC and MELSEC-A are registered trademarks of Mitsubishi Electric Corporation. SYSMAC is a registered trademark of Omron Corporation. FOUNDATION of FOUNDATION eldbus is a registered trademark of Fieldbus Foundation. Other product and company names appearing in this document are trademarks or registered trademarks of their respective holders.
All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation Subject to change without notice.