Professional Documents
Culture Documents
PROTECTIVE RELAY
Protective Relay:
It is a device that detects the faults in any system and initiates the operation of
the circuit breaker to isolate the defective element from the rest of the systems.
A protective relay does not anticipate or prevent the occurrence of a fault.
However, one exception in the Buchholz relay.
Nature and causes of faults:
In a power system the majority of faults occur due to failure of insulation which may
be caused due to:
1. Switching over voltages
2. Over voltage due to lightning
3. Insulators break down
4. Mechanical damage
5. Bridging of conductors by birds.
Function of Protective Relay:
Is to detect and locate a fault and issue / sends a command signal to the circuit
breaker to isolate the faulty element / parts.
Protective relays detects the normal and abnormal condition of the system by
constantly monitoring the electrical quantities, which are different under normal and
abnormal conditions.
The basic electrical quantities, which are likely to change during abnormal
conditions, are voltage, current, and phase angle, frequency. Protective relay utilizes
one or more of these quantities to detect abnormal conditions.
Relay coil
operating coil
S
CB
CT
NC
2
Essential qualities of a relay:
In order to perform its function satisfactorily it must posses the following qualities /
properties:
1. Selectivity / discrimination
2. Sensitivity
3. Speed
4. Reliability
Selectivity: It is the ability to discriminate between normal and abnormal
operating condition of the system.
Sensitivity: It is measured on the basis of least operating quantity in excess of
the set value to actuate the operating system of the relay.
Speed: To minimize the damage of the equipment due to fault a relay
should be able to communicate the abnormality as quickly as
possible.
Reliability: It must be reliable and function as and when calls for.
Certain operating terms of a relay:
Pick up value: Minimum operating quantity in excess of set value to
operate / actuate the operating mechanism.
Drop out value: The threshold value of the operating quantity below
which the relay fails to maintain its operated condition.
Operating time: The time which collapse between the instant when the
actuating quantities exceeds the pick-up value to the
instant when the relay contacts close.
Types of Protection: Normally two types of protection provided to the power system:
a. Primary protection and
b. Back up protection
Primary relays are the first line of defiance and operate as first as possible. Back
up relays operates only when primary relay fails. Back up relay normally have a large
time lag to allow sufficient time to the primary relay to operate.
R
3
R
2
R
1
A B
R
1
R
3
R
2
Fault Current
T
i
m
e
O
p
e
r
a
t
i
n
g
3
Classification of relays:
The relays are normally classified on the basis of the purpose for which it is being
installed.
1. Under voltage
2. Over voltage
3. Undercurrent
4. Over current
5. Under power
6. Over power
7. Direction or reverse current
8. Differential
9. Distance relay
They also sometimes classified on basis of time of operation:
1. Instantaneous
2. Definite time a lag
3. Inverse time lag
4. Inverse definite minimum time lag (IDMT)
Some times relays are also classified on the basis of construction and principle of
operation like
1. Electromagnetic attraction type
2. Electromagnetic induction type etc.
Depending upon the time of operation the relays are categorized as:
1. Instantaneous OCR
2. Inverse time OCR
3. Inverse definite minimum time (IDMT) OCR
4. Very inverse relay and
5. Extremely inverse relay
OVER CURRENT RELAY:
Induction type over current relay:
It consists of a metallic disc, which is free to rotate in between the poles of two
electromagnets. The upper electromagnet has a primary and secondary winding. The
primary is connected to the secondary of a CT in the line to be protected and is provided
with tappings. These tappings are connected to a plug setting bridge which usually
arrange to give seven section of tapping, over current range between 50% to 200% .
4
These values are percentages of the current rating of the relay. The secondary
winding is connected with the lower electromagnet. The torque-exerted on the disc is
due to the interaction of eddy currents produced there in by means of the leakage flux
from upper and lower electromagnet.
The spindle of the disc carries a moving contact which bridges the fixed contacts
when the disc rotates through an angle, which is adjustable between 0 and 360. By
adjusting the angle of traverse the relay can be given any desired time setting which
will be indicated in a dial calibration from 0 to 1. Actual time of operation to be
obtained from the relay nameplate.
IDMT
1.0
0.8
0.6
0.4
Operating
Time(S)
Operating current (PSM)
5
PSM =
Primary Current
Primary setting current
=
Primary Current
Relay Current setting x CT Ratio
Rated current of the relay is equal to the rated secondary current of the CT.
From the fig. Operating time when the current setting multiplier is 10 and the
time multiplier setting is 1, is 3 seconds. This is sometimes called as basic 3/10 curve.
For getting the time of operation for 0.8 curve [ 3 x 0.8 = 2.4 Sec ]. The above
characteristic is known as IDMT. For DMT curve the upper electromagnet is allowed
to saturate for a particular value of current. This results in flattering of the time
current curve.
Directional Over current relay:
The upper magnet of the directional element carries a winding connected
through PT. The lower magnet carries another winding connected through CT and by
the fault current. This winding is carried over to the upper electromagnet of the non
directional element. The contacts of the directional elements are connected in series
with the lower electromagnet of the non-directional element.
It is seen the
movement of the non
directional element is
controlled by the directional
element. When the power
flows in a particular
direction only the relay will
operate.
A TYPICAL CONNECTION
(Phasor Diagram)
Max Torq.
I
V
I
u
o
Op. Region
Non Op. Region
Zero Torq. Line
V
AC
V
BA
V
CA
I
A
I
B
I
C
30
0
I
A
I
B
I
C
V
B
C
V
C
A
V
A
B
(a)
(b)
(c)
I
Directional
Unit
Trip
110 V
DC
V
OC Unit
6
The relay current I leads the relay voltage.
T
v
I
sin ( + u ) KVI sin ( + u )
T
max
occurs when + u = 90
And T = O when + u = 0 or 180
The directional element will operate only when I lies within 90. If its is more than
90 the relay will restrain.
There are two types of connection to get the relay current leading as shown in (b) and
(c)
OVER CURRENT PROTECTIVE SCHEME
(a) Definite time
(b) IDMT
(c) Very Inverse
(d) Extremely Inverse
O
p
e
r
a
t
i
n
g
T
i
m
e
PSM
1.5 S
1 S
0.5 S
Time graded
80%
Current graded
7
DRAW BACK:
1. If the fault occurs near the power source the time of operation of the relay is large.
In this the relay takes longest time with heavy fault current.
In the current graded scheme:
1. The relay fails to differentiate between fault very close to B which may be of either
side.
2. Consequently relays are set to protect only a part of the feeder.
Distance Relay:
Distance relays are used to protect the transmission lines. This relay measures the
impedance or some components of the line impedance. As the measured quantity is
proportional to the distance along the line, the measuring relay is called a distance relay.
The most important and versatile family in these groups of relays are:
a. Impedance relay
b. Reactance relay
c. MHO relay
IMPEDANCE RELAY:
In an impedance relay operating torque produced by square of the current and the
restraining torque produced by the square of the voltage.
T = K
1
I
2
K
2
V
2
K
3
(Torque of control Spring)
= K
1
I
2
K
2
V
2
(Neglecting K
3
of the balance)
Combined instantenious factors and IDMT
IDMT
instant
A B C
CB
CB
PT
CT CB
F
1
F
2
B
A Z
L
8
For the operation of the relay K
1
I
2
> K
2
V
2
(operating torque > restraining torque)
Or V
2
< K
1
I
2
K
2
Z = \ ( K
1
) < constant impedence)
K
2
The operating characteristics of the relay may be explained through R X
diagram.
The locus of Z is a circle. Depending on the phasor relationship of current with
voltage the Z vector may coincide with R on (X , R ) zone. Since the operation of
the relay is independent of phase relation between voltage and current hance it gives a
non directional relay characteristic. As and when impedence falls below Z the relay
operates. A directional feature normally used to protect against fault behind the zone to
be protected in an impedence relay.
By providing a directional element in series with the relay the characteristic may
be expressed as
T VICos( o) > 0 when = ZVI
COS ( o) > 0
or ( o) < 90
o
o
To Trip Circuit
F
A
P.T
C.T
B
C
u
Z
X
R
V
I
-X
OP Zone
Non-OP Zone
R
Directional features
X
Operating
Non-operating
o
9
MHO RELAY : (Admittance Relay )
The mho relay is similar in principle to an impedance relay but is made
inherently directional by the addition of a voltage winding known as polarising winding.
In such connection operating torque is obtained by the V-I element and the restraining
torque by the voltage element. This gives the mho relay a voltage restrained directional
relay whose torque equation may be written as
T = KVIcos (u-o)-K
1
V
2
-K
2
At balance, T=0,
K
1
V
2
= KVIcos (u-o)-K
2
I
V
=
1 K
K
cos (u-o) -
1
2
K
K
Z= K