DOC.CODE : DE.MS02
Sr. No. 1.0 1.1 1.2 1.3 1.4 1.5 2.0 2.1 2.2 2.3 2.4 2.5 2.6
Model * Compensation Current Capacity Input Requirements Nominal Input Voltage Nominal Input Frequency Phase / Wires Interrupting Capacity Max. Reactive Power @ 400 V Specifications Controller Control Type Response Time Power Device Overload Capacity 100 kA, fused 20 kVA 30 A 60 A
400 V (+10 % , - 15 %) 50 Hz ( 10 %) (60 Hz Optional) 3 Phase + N (4 Wire) 100 kA, fused 45 kVA 100 kA, fused 70 kVA 100 kA, fused 100 kVA 200 kA, fused 200 kVA
32 bit , DSP control Closed loop < 40 ms IGBT Limiting to nominal Current, Continuous limiting operation possible
Power Dissipation (in KW) @ nominal voltage 25 % Load 50 % Load 75 % Load 100 % Load 0.40 0.53 0.78 0.98
(1)
2.7
Harmonic Filtering
Non-zero Sequence 2 to 50 Harmonic compensation (Any 20 Harmonics individually selectable) Attenuation ratio up to 96 % Adjustable up to unity from 0.6 lag or 0.6 lead 4 units can be operated in Parallel
Remote monitoring through MODBUS, SNMP, HTTP Web Browser, Ethernet based monitoring through AHFMON, LIFENET
2.8 2.9 2.10 3.0 3.1 3.2 3.3 3.4 3.5 3.6
Power Factor Correction Parallel operation Communication Interface(optional) Environmental Acoustic Noise Level Operating Temperature Storage Temperature Relative Humidity Altitude Electrostatic discharge immunity
< 65 dBA @ 1 meter (Ref. ISO 3746) 0 to 40 Deg. C - 10 to 55 Deg. C Up to 95 % (Non-condensing) Up to 1000 m above sea level (without de-rating) 4 kV contact / 8 kV Air Discharge
(1) For zero sequence triplen harmonic compensation, consider Liebert AF3 model with neutral compensation (available upto 150 A). Please contact technical support group.
REV. NO. : 2*
REV.DATE : 18/05/2011
PAGE : 1
NEXT PAGE : 2
MR.QD.FR02.2
DOC.CODE : DE.MS02
30 A
60 A
100 A
150 A
300 A
500 A : 5 A
1000 A : 5 A
3000 A : 5 A
5000 A : 5 A
IP 40 (IP 41 optional) Forced Air Cooling RAL 7021 Bottom entry (Top entry optional) (For 300 A Top entry, Separate cable alley required) Front access Floor mounted
Mechanical Dimensions (in mm) - Width - Depth - Height + Plinth - Canopy (optional for IP41) Net Approximate Weight (in Kg) Floor area (m ) Floor loading (Kg/m ) Transport
2 2
REV. NO. : 2*
REV.DATE : 18/05/2011
PAGE : 2
NEXT PAGE : 3
MR.QD.FR02.2
DOC.CODE : DE.MS02
30 A
60 A
100 A
150 A
300 A
Corrugated Packing Dimension - Width (mm) - Depth (mm) - Height (mm) - Approx. Weight (Kg) 765 535 1070 140 810 610 1270 215 810 610 1850 330 810 610 1850 335 1210 910 1850 635
4.14
Wooden Packing Dimensions - Width (mm) - Depth (mm) - Height (mm) - Approx. Weight (Kg) 820 565 1100 170 915 760 1525 240 915 760 1930 390 915 760 1930 390 1375 1015 1930 745
4.15
Export Packing Dimensions - Width (mm) - Depth (mm) - Height (mm) - Approx. Weight (Kg) 890 640 1100 200 1040 890 1525 285 1040 890 2110 435 1040 890 2110 440 1500 1150 2110 795
REV. NO. : 2*
REV.DATE : 18/05/2011
PAGE : 3
NEXT PAGE : 4
MR.QD.FR02.2
DOC.CODE : DE.MS02
Safety Conducted and radiated emissions Immunity to electrostatic discharges (ESD) Immunity to Electrical fast transients (EFT) Immunity to Surges Immunity to Voltage dips & interruptions Guidelines for compensated harmonics
EN 50178 IEC 62040-2 IEC 61000-4-2 IEC 61000-4-4 IEC 61000-4-5 IEC 61000-4-11
IEEE 519
REV. NO. : 2*
REV.DATE : 18/05/2011
PAGE : 4
NEXT PAGE : --