You are on page 1of 43

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Contents

Contents
1.1 Product Introduction 1.1.1 Denomination of Transmitter Model 1.1.2 Product Series 1.1.3 WT1151 WT2000 Series Smart Capacitive Pressure Transmitter 2 2 3 5 13 14 17 18 21 22 26 36 38 38 39 40 41

1 .2 Model Selection Guide 1.2.1 WT1151 1.2.2 WT1151 1.2.3 WT1151 1.2.4 WT1151 1.2.5 WT1151 1.2.6 WT1151 WT2000DP Differential Pressure Transmitter WT2000HP High Static Differential Pressure Transmitter WT2000GP Gage Pressure Transmitter WT 2000 AP Absolute Pressure Transmitter WT2000 LT Flanged Level Transmitter WT2000DP/GP Differential/Gage Pressure Transmitter with Remote Seal

1.2.7 WT2000TG Smart Directly Mounted Pressure Transmitter 1.3 Installation Accessories 1.3.1 Installation Bracket and Installation Type 1.3.2 Installation Bracket and Installation Type for Directly Mounted 1.3.3 Induced Pressure Connector 1.3.4 Connection Dimension for Process Flange

(The content of this catalog are subject to changes without notice.)

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

1.1

Product Introduction

WT1151 WT2000 series smart capacitive pressure transmitters have been self-developed and produced by Welltech through introducing overseas sophisticated equipment and benefiting from the advanced technology & successful experience of overseas similar products. WT1151 WT2000 adopt international high quality electronic components and key parts, and are supplied to domestic and overseas customers at most competitive price popularly. The guidebook only makes a general introduction of the common characteristics for the WT1151 WT2000 series transmitters, including the model denomination, product series, main features, working principles, function parameters. For the detailed information, please refer to the Operation Manual of WT1151 WT2000 series capacitive transmitters.

1.1.1 Denomination of Transmitter Model


Table 1 Denomination of Transmitter Model Necessary items

Optional items

WT1151

WT2000

Code DP HP AP GP

Model Code Differential pressure transmitter High static differential pressure transmitter Absolute pressure transmitter Gage pressure transmitter Code M1 M3 B01 22 23

Structual Material Flange connector Drain/vent valve Isolating diaphragm Filled liquid Silicon oil 316 stainless steel 316 stainless steel Hastelloy C-276

316 stainless steel 316 stainless steel 316L stainless steel

LT Flanged level transmitter Differential / gage pressure DP/GP transmitter with remote seal TG Directly mounted pressure transmitters

Accessories & Additional Functions 0-100% linear indicator (only for WT1151) LCD digital indicator Bending bracket mounted by pipe (carbon steel) Bending bracket mounted by panel (carbon steel) Flat bracket mounted by pipe (carbon steel) Bending bracket mounted by pipe (stainless steel) Bending bracket mounted by panel (stainless steel) Flat bracket mounted by pipe (stainless steel) Release valve located on upper of pressure chamber side Release valve located on lower of pressure chamber side Release valve located on opposite of process connecting port Vertically mounted pressure chamber (only for WT2000) Vertically mounted pressure chamber with side release (only for WT2000) NPT1/2 female thread oval flange NPT1/2 induced pressure connector with behind

Code 2 3 4 5 6 7 8 9 0 Code 2 3 4 5 6 7 8 9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

WT1151 Measuring Range(kPa) 0.125 0.75 3.74 18.668 68.9 206.8 689 2068 4137 1.5 7.5 37.4 186.8 689 2068 6890 20680 41370

B02 B03 B04 B05 B06 D1 D2 D3 V0 V1 C1 C12 C2 C21 d i

WT2000 Measuring Range(kPa) 0.1 0.188 0.935 4.67 17.24 51.7 172.25 517 1.5 7.5 37.4 186.8 690 2068 6890

14 induced pressure tube welded

M20*1.5 T-shaped male thread connecting block


M20*1.5 T-shaped male thread connecting block with tube welded behind 14 induced pressure

Flameproof Exd II BT4 Intrinsical safe Exia II CT6

Code S J Smart Smart

Output HART / 4~20 mA DC linear HART / 4~20 mA DC square root

20680 41370

1034.2

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

1.1.2
Table 2

Product Series(Table 2 3

4)

No .

Description

Model WT1151DP2S WT1151DP3S WT1151DP4S

Measuring Range (kPa) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.125 ~ 1.5 0.75 ~ 7.5 3.74 ~ 37.4 18.68 ~ 186.8 68.9 ~ 689 206.8 ~ 2068 689 ~ 6890 0.1 ~ 1.5 0.188 ~ 7.5 0.935 ~ 37.4 4.67 ~ 186.8 17.24 ~ 689 51.7 ~ 2068 172.25 ~ 6890 3.74 ~ 37.4 18.68 ~ 186.8 68.9 ~ 689 206.8 ~ 2068 0.935 ~ 37.4 4.67 ~ 186.8 17.24 ~ 689 51.7 ~ 2068 0.75 ~ 7.5 3.74 ~ 37.4 18.68 ~ 186.8 68.9 ~ 689

Max. Working Accuracy Grade Pressure (MPa)


4 0.25 7

2 3 4

WT1151DP5S 5 6 7 8 9 10 11 12 WT2000DP7S 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
Gage pressure transmitter High static differential pressure transmitter Differential pressure transmitter

WT1151DP6S WT1151DP7S WT1151DP8S WT2000DP2S WT2000DP3S WT2000DP4S WT2000DP5S WT2000DP6S

14 0.2

4 7

0.1 14

WT2000DP8S WT1151HP4S WT1151HP5S WT1151HP6S WT1151HP7S WT2000HP4S WT2000HP5S WT2000HP6S WT2000HP7S WT1151GP3S WT1151GP4S WT1151GP5S WT1151GP6S WT1151GP7S WT1151GP8S WT1151GP9S WT1151GP0S

0.2

32

0.1

0.25

0.2 /

206.8 ~ 2068 689 ~ 6890 2068 ~ 20680 4137 ~ 41370


3

0.5

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

Table 3

No . 30 31 32 33 34 35 36 37 38 39 40 41 42

Description

Model WT2000GP3S WT2000GP4S WT2000GP5S

Measuring Range (kPa) 0 0 0 0 0 0 0 0 0.188 ~ 7.5 0.935 ~ 37.4 4.67 ~ 186.8 17.24 ~ 689

Max. Working Accuracy Grade Pressure (MPa)

Gage pressure transmitter

WT2000GP6S WT2000GP7S WT2000GP8S WT2000GP9S WT2000GP0S WT1151AP4S WT1151AP5S WT1151AP6S WT1151AP7S

0.1 /

51.7 ~ 2068 172.25 ~ 6890 517 ~ 20680 1034.2 ~ 41370 0 10 ~ 37.4 18.68 ~ 186.8
0.2

0 0 0 0 0 0 0 0 0
0 0 0 0 0 0

68.9 ~ 689 206.8 ~ 2068 689~6890


/

0.2

43 44 45 46 47
48 49 50

Absolute pressure transmitter

WT1151AP8S WT2000AP4S WT2000AP5S WT2000AP6S WT2000AP7S WT2000AP8S


WT1151LT4S WT1151LT5S

10 ~ 37.4 10 ~ 186.8 17.24 ~ 689 51.7 ~ 2068 172.25 ~ 6890


3.74 ~ 37.4 18.68 ~ 186.8 68.9 ~ 689 0.935 ~ 37.4 4.67 ~ 186.8 17.24 ~ 689 Refer to flange pressure rating
0.2 0.2

0.1

Flanged level transmitter 51 52 53 54 55 56 57 58


4

WT1151LT6S WT2000LT4S WT2000LT5S WT2000LT6S

WT1151DP4S
Differential pressure transmitter with remote seal

0 0 0 0 0

6.2 ~ 37.4 31.1 ~ 186.8 117 ~ 689 345 ~ 2068 1170 ~ 6890
SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151DP5S WT1151DP6S WT1151DP7S WT1151DP8S

Refer to flange pressure rating

0.2

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

Table 4

No.
59 60 61 62 63 64 65 66 67 68

Description

Model WT2000DP4S

Measuring Range (kPa) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6.2 ~ 37.4 31.1 ~ 186.8 117 ~ 689 345 ~ 2068 1170 ~ 6890 6.2 ~ 37.4 31.1 ~ 186.8 117 ~ 689 345 ~ 2068 1170 ~ 6890 6.2 ~ 37.4 31.1 ~ 186.8 117 ~ 689 345 ~ 2068 1170 ~ 6890 0.935 ~ 37.4 4.67 ~ 186.8 17.24 ~ 689 51.7 ~ 2068 172.25 ~ 6890 517 ~ 20680

Mas. Working Accuracy Grade Pressure (MPa)

Differential pressure transmitter with remote seal

WT2000DP5S WT2000DP6S WT2000DP7S WT2000DP8S WT1151GP4S WT1151GP5S WT1151GP6S WT1151GP7S

Refer to flange pressure rating

0.2

69 70 71 72 73 74 75 76 77 78 79 80

Gage pressure transmitter with remote seal

WT1151GP8S WT2000GP4S WT2000GP5S WT2000GP6S WT2000GP7S WT2000GP8S WT2000TG4S WT2000TG5S

Refer to flange pressure rating

0.2

Directly mounted pressure transmitter

WT2000TG6S WT2000TG7S WT2000TG8S WT2000TG9S WT2000TG0S

0.1

0.2

1034.2 ~ 35000

1.1.3

WT1151

WT2000 series smart capacitive pressure transmitter

WT1151

WT2000 series smart capacitive pressure transmitter (hereinafter called smart transmitter ) is

the pressure instrument adopting the microprocessor as its core, which extends the communication and other functions on the basis of the traditional 1151 capacitive transmitter. With the help of 275, 375 hand held communicator or other host computer adopting HART protocol, the bi-directional communication (data reading, writing and diagnosing) could be realized in the control room, transmitter field or any places connecting with control circuit. Note: The old version 275 hand held communicator will be valid only after being sent to Welltech to be amended to the new version one authorized by international HART Foundation.
SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

1.1.3.1

Main Features

WT1151 WT2000 series smart capacitive pressure transmitters not only have the inherent features of ordinary capacitive pressure transmitter, but also have following features: l Smart electronic part is constituted by one circuit board; l Turn down ratio: 15:1, recommended: 10:1 (WT1511); Turn down ratio: 40:1, recommended: 10:1 (WT2000); l Measuring range: 0-100Pa ~ 41370kPa; l Being able to adjust span and zero by local buttons; l Conforming to HART protocol, be able to carry out bi-directional communication with 275, 375 HART hand held communicator and the output signal will not be interrupted; l In DCS adopting HART protocol, being able to communicate bi-directionally with the host computer; l Having self-diagnosis and remote diagnosis functions; l Be equipped with EEPROM, which ensures no data loss due to the sudden electrical breaking; l Two-wire, 4-20mA output. WT2000 series smart capacitive transmitter is furnished additionally with the following features: l Elaborately designed in accordance with electro magnetic compatibility (EMC) requirement and passed the CE certification; l Adopting the digital temperature compensation technology, which greatly improves the temperature characteristic of the transmitter; l Modular compact structure, stable and reliable, with no need to open the cover and be able to adjust span and zero by local buttons.

1.1.3.2

Working Principle

The two pressures of the measured medium act upon the isolating diaphragms on both sides of element (see Fig. 1 for structure diagram) through high, low pressure chambers, and then transfer to the both sides of the pretensioned measuring diaphragm by the isolating diaphragm and the filled liquid inside the element. Either connection of the measuring diaphragm with the insulator electrodes of both sides composes a capacitor. In the case of unequal pressures for both sides, the displacement will take place with the replacement value being proportional to the differential pressure. Therefore the capacitance of both sides will be unequal, which will convert DC signal proportional to the pressure through the oscillation and modulation procedures. The work principle of gage pressure transmitter and absolute pressure transmitter is similar with that of differential pressure transmitter except that the pressure inside low-pressure chamber is atmosphere or vacuum.
Lead wire Lead wire

Fixed plate of capacitor Measuring diaphragm

Vaccum reference chamber

Fixed plate of capacitor Measuring diaphragm

Solid insulator

Solid insulator

Filled silicon oil

Filled silicon oil

Isolating diaphragm

Welding seal

Isolating diaphragm

Welding seal

a)

Element for Others

b)

Element for AP

Fig.1

Structure Drawing for

Element

1.1.3.3

Working Principle of Smart Pressure Transmitter

A/D convertor transforms the current of the modulator to the digital signal, which will be used by the microprocessor to judge the input pressure value. The microprocessor controls the work of transmitter. Besides,
6
SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

it is also engaged in such operations as the sensor linearization, resetting measuring range, engineering unit conversion, damping, square root and sensor trim, as well as diagnosis and digital communication.
4~20mA

Oscillation and modulation

A/D signal conversion

Sensitive element

Microprocessor sensor linearization measuring range transferring function engineering unit damp and communication diagnosis

D/A signal conversion

To control system

Digital communication Communication device

EEPROM Linear constant measuring range constant transmitter configuration

Zero

Span

Fig.2

Frame Diagram of Working Principle for WT1151

4~20mA

Oscillation and modulation

A/D signal conversion

Sensitive element

Microprocessor sensor linearization measuring range transferring function engineering unit damp and communication diagnosis

D/A signal conversion

To control system

Digital communication Communication device

EEPROM Linear constant measuring range constant transmitter configuration

TC

Zero

Span

Fig.3

Frame Diagram of Working Principle for WT2000

D/A convertor changes the digital signal, which have been calibrated by the microprocessor, into the 4 ~20mA analog signal and then transfers to the output loop. EEPROM stores all the configurations, characterization and digital trim data, which could be altered by the transmitter software. The data are stored in the EEPROM, which ensure it stored completely even if in case of outage. The digital communication circuit offers the transmitter with a connection interface to outside device (such as 275 smart hand held communicator or the control system adopting HART protocol). The circuit detects the digital signal overlapping upon 4 ~20mA signal, and transfers the needed information through the loop. The communication type adopts frequency shift keying technology FSK (Frequency Shift Keying) and conforms to Bell 202 standard.

1.1.3.4

Function Specification

Service: Liquid, gas and steam. Measuring range: see the attached table. Output signal: two-wire 4~20mA DC signal plus digital signal, the square root or linear output may be at the customer's options. Power supply: 12 ~45VDC, 15 ~45VDC for with LCD digital display, and 24VDC generally. Load feature: the maximum load resistance shall be RL = (Vs 12V) / 0.023A, RL -- the maximum load resistance, and Vs -- the voltage of power supply.
SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

Operation area

HART Communication area

Fig.4 Load Voltage Relation

Indicator: field output indication is furnished with current meter, 0 ~100% linear indicator, LCD digital indicator Span and zero: being able to adjust by local buttons or by HART communicator. Zero elevation and suppression: l Differential pressure transmitter: the maximum zero elevation is the difference between the upper range limit (URL hereinafter) and the span, and the maximum zero suppression is equal to URL. l Gage pressure transmitter: the maximum zero elevation is the difference between URL and the span, and the maximum zero suppression no more than the atmosphere pressure. l Absolute pressure transmitter: the maximum zero elevation is the difference between URL and the span, without zero suppression. Fault alarm: once the self-diagnosis program examines the faults, the analog output will be higher than 22mA or lower than 3.8mA to alarm, the high alarm or low alarm may be optional through the switch on the electronic part. Transmitter status and protection: switching the switch on the electronic part to prevent the transmitter configuration from being changed. Environmental temperature : 25 ~ +75 Storage temperature: 10 ~ +55 Damping: electrical damping is 0.2 ~ 16s, which can be adjusted per 0.1s, inherent time is 0.2s for sensor (silicon oil filled) , and 0.4s for range code 2.

1.1.3.5

Technical Specification

(Standard reference condition: under conditions of no shifting, silicon oil filled and 316L stainless steel for the isolating diaphragm) Accuracy: see table 2,3,4 Stability: being within the accuracy of the transmitter for 12 months Temperature effect: Please refer to Table 5 for the effect for each 10 under the max. span. For range code 2, 3 of WT1151, the temperature effect for each 10 is 0.60% . Static effect: Please refer to Table 6 for the effect under the max. Span.
Table 5

Accuracy Grade Range Code or Name 2 3 4 9 0 Remote seal, level


8

0.1 / 0.20% 0.10% / /

0.2 0.30% 0.30% 0.30% 0.30% /


SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

Table 6

Range Code or Name 0.1 2 3 4,5,6,7,8 High static 4,5,6,7 /

Accuracy Grade 0.2 0.5% / 7MPa 0.5% / 14MPa 0.30% / 14MPa 2% / 32MPa
2

0.30% / 14MPa 0.25% / 14MPa /

Vibration effect: 0.1% of max. span, 10 ~ 60Hz, S = 0.07mm, 60 ~ 150Hz, g = 9.8m/s ; in any direction. Power supply effect: less than 0.005% of output span/V. Electromagnetic radiation effect: 0.1% of max. span, radiation frequency 27~500MHz, test magnetic strength 3V/m. Electro magnetic compatibility (EMC): see Table 7 (for WT2000). Installation position impact: the working diaphragm not in vertical will result in a zero system error of zero of no more than 0.24kPa, which could be offset by adjusting zero and bring no impact to span. Structure material: for the material for such wetted parts as pressure chamber, connector, release valve, isolating diaphragm etc., please refer to the model and ordering code of different models. l the bolts is the galvanized carbon steel l The electrical housing is low copper aluminum alloy, with the epoxy sprayed coating on surface. Induced pressure connection: the connecting screws of the pressure chamber are NPT1/4, the connecting screws of the induced pressure connectors are NPT1/2, and the center distance can be altered by adjusting the connection block (51, 54, 57mm). Electrical connection: two screws of M20 1.5 or NPT 1/2 female screws are available on the transmitter housing to connect the cable duct. Inside the housing, there are cable terminals and measuring shims offered for testing. For connection with communicator, it could only be connected onto the measuring shims. Weight: about 5kg for WT1151 (excluding accessories, except flanged pressure transmitter), about 3.5kg for WT2000 (excluding accessories, except flanged pressure transmitter).
Table 7 EMC for WT2000 Pressure Transmitte

No. 1

Test Item

Test Standards

Test Method/ Condition

Performance Class See Clause 9

Test Result Pass

Emission enclosure

EN61326:1997+A1:1998 30MHz ~ 1000MHz Clause7.2 and Table 3

Emission (DC mains)

EN61326:1997+A1:1998 0.15MHz ~ 30MHz Clause7.2 and Table 3

See Clause 9

Pass

Electrostatic discharge

4kV(contact) 8kV(air) 80MHz ~ 1000MHz 10V / m 80% AM

Pass

EM field

Pass

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

Continued Table 7

No.
5

Test Item
Rated power frequency magnetic field

Test Standards

Test Method/ Performance Condition Class 30A/m Direction: transverse A longitudinal and vertical
2kV.5 / 50(Tr / Tn)ns 5kHz(+ / ) 1kV(differential mode) 2kV(common mode) 1.2s /50s 0.15MHz~80MHz 10V 80% AM B

Test Result
Pass

Burst

Pass

Surge

Pass

Conducted RF

Pass

Note: EMC authorized standard CE, EN61326: 1997+Al: 1998 Performance judging criterion A: with normal performance within the limit of technology specifications during the test. Performance judging criterion B: with a temporal reduction or loss in terms of the function or performance during the test, but can be restored itself. Performance judging criterion C: with a temporal reduction or loss in terms of the function or performance during the test, but can only be restored through operator's intervention or system resetting.

1.1.3.6

Smart Electronic Part

It adopts advanced integrated circuit and Surface Mount Technology (SMT), the electronic part of the transmitter is constituted by one circuit board. The microprocessor of the transmitter controls the conversion work of A/D and D/A, and can also implement the self-diagnosis and the digital communication. During the process of working, one digital pressure value is processed by the microprocessor, and stored as a digital to ensure the precise modification and the conversion of engineering units. In addition, the microprocessor can also realize such functions as linearization of the sensor, turn down ratio, damping time and other functions. EEPROM stores all the configurations, characterization and digital trim data. EEPROM is a nonvolatile memory device, which makes sure all the data could be completely stored in case of electrical breaking, thus realizing the real-time smart communication.

Software
One set of 275 or 375 hand held communicator could realize the testing and configuration for WT1151 WT2000 smart transmitter, or any upper level system in conformity with HART communication protocol could implement the communication. HART protocol adopts BELL202 frequency shift keying (FSK) of the industrial standard. The communication could be realized through the digital signal of 1200Hz or 2200Hz overlapped on the signal of 4~20mA. During the process of communication, the frequency signal would not exert any influence on the analog signal of 4~20mA.

Self-diagnosis
WT1151 WT2000 smart transmitter can implement the continuous self-diagnosis. Once any fault with the transmitter is detected, the client may make free choice for the transmitter output among 22mA or 3.8mA. Moreover, any HART upper level device can display the special signal code self-diagnosed by the transmitter.

Formatting
The formatting function is used for the initial setting of the transmitter or the maintenance of the digital electronic part. The standard formatting menu offers two functions: sensor adjusting and analog output adjusting.
10
SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

Sensor adjusting: including the characterization and sensor trim, this enables the electronic part to precisely reflect the pressure input. Meanwhile, the standard pressure source must be adopted. l Characterization: although WT1151 WT2000 smart transmitter has been characterized before leaving the factory, the client can still use this function, to make some simple update for WT1151 analog pressure transmitter to convert to smart type. Characterization function: adjusting the electronic part of WT1151 WT2000 smart transmitter to make sure it reflects the sensor output correctly. l Sensor trim: the function allows the characterized digital to be micro-adjusted. It affects originally characterized results. For the detailed information, please refer to the manual. Analog adjusting: make the digital current valu e of the transmitter be co nsistent with the 4~20mA analog current of the transmitter. Note: Please read the manual before implementing the adjusting.

Configuration
Standard configuration: the goods would be provided according to the following configurations, unless otherwise specified: engineering unit--kPa; 4mA--0kPa; 20mA--upper range limit (URL) ; output--linear Software tag: blank [software tag(8 characters), blank unless otherwise specified] Special configuration: in addition to the standard configuration data, the clients can also designate the following additional data(Table 8).
Table 8

Description symbol Information Date Damp

16 characters 32 characters Day/month/year Second Particular information Type code information Type code information

Insolating diaphragm material Sensor filled liquid Drain/vent Compact indicator

Type code information Type code information Type code information Installed or not installed

Remote seal device


Flange material O ring material

Fault alarm mode Parameter writing protection

High or low Off /on

1.1.3.7

Field Wiring Diagram


RL

Power supply Ammeter HART Communicator Smart transmitter Indicator gauge

Fig.5

Field Wiring Diagram for WT1151

WT2000 Smart Capacitive Transmitter

SHANGHAI WELLTECH AUTOMATION CO., LTD

11

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

1.1.3.8

Bus Communication
WT2000 series smart capacitive transmitter can adopt multi-station mode, that is, 15 sets of

WT1151

smart capacitive transmitter can be connected through one bus line (telephone line or twisted pair line) to realize the bi-directional communication with the host computer(adopting HART protocol). See Fig.6 for the working principle.

HART serial interface

24V power supply Hart smart capacitive pressure transmitter Addr1 Addr2 Addr3

Fig.6

Multi-station Communication Sketch Drawing for WT1151

WT2000 Smart Capacitive Transmitter

12

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Product Introduction

1 .2
different types WT1151

Model Selection Guides

This section lists the outline diagram, outline dimensions, installation types , model and ordering code of WT2000 capacitive transmitter.

There are two kinds of material, buna and viton for the wetted O ring. Unless otherwise specified in the ordering, buna is usually adopted. Viton is used for high static differential pressure transmitter and pressure transmitter of range code 9 and 0. Buna is used for wetted O ring of oval flange.
If the customer needs to order the transmitter of special model, special specification or special structure and material, which is not listed in this catalog, please contact with our sales department, and we will do our best to meet the needs of the customers. As to measuring dangerous gas; or working pressure is over 10MPa; or temperature of medium is >200 < 25 , ; or very corrosive medium such as vitriol, hydrochloric acid etc., please make sure to designate name

of medium, pressure, temperature, consistency, density etc. The buyer shall be responsible for the model selection, anti-corrosion, installation and operation.

Warranty
With respect to the failed transmitter due to the inherent quality problem, our company promises to repair or replace the product free of charge within 18 months after the delivery of the goods on the premise that the failed transmitter should be sent back to our company. In the case of repairing and replacing the products out of the warranty period, our company will charge the due cost.

SHANGHAI WELLTECH AUTOMATION CO., LTD

13

WT1151

WT2000DP Differential Pressure Transmitter

Model Selection Guides

1.2.1

WT1151

WT2000DP Differential Pressure Transmitter

Adopting the differential capacitor as the detecting element to constitute the capacitive transmitter, with the input pressure being 0~1.5kPa, 0~7.5kPa, 0~37.4kPa and 0~1865kPa etc. Service: liquid, gas and steam. Output: 4~20mA DC, in conformity with HART communication protocol.

Fig.7

WT1151DP/HP Differential Pressure Transmitter Outline

177 (with field indicator)

1. Nameplate (remove it when adjusting span and zero); 2. Oval flange, induced pressure connection screw is NPT1/2. Note: Oval flange can be turned; 3. While without oval flange, NPT1/4 screw on the pressure chamber for induced pressure connection; 4. NPT1/4 screw for connecting with the release valve (on upper or on lower); 5. Release valve; 6. Pressure chamber, turnable.

Fig.8
14

Outline Dimension for WT1151DP/HP Differential Pressure Transmitter


SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000DP Differential Pressure Transmitter

Model Selection

Fig.9

WT2000DP/HP Differential Pressure Transmitter Outline


133.5 (with field indicator)

92

Vertically Mounted Pressure Chamber


1. Nameplate; 2. NPT1/4 screw for connecting with the release valve (on upper or on lower); 3. Pressure chambe, turnable; 4. Release valve; 5. NPT1/4 screw on the pressure chamber for induced pressure connection.

198

Fig.10 Table 9

Outline Dimension for WT2000DP/HP Differential Pressure Transmitter

Range Code A (mm)

2~5 54.0

6 55.6 3mm

7 55.6

8 56.8

Note: Dimension A changed while the oval flange is turned, i.e. A


SHANGHAI WELLTECH AUTOMATION CO., LTD

15

WT1151

WT2000DP Differential Pressure Transmitter

Model Selection

Model and Ordering Code for DP Differential Pressure Transmitter Table 10


WT1151DP Smart Differential Pressure Transmitter WT2000DP Smart Differential Pressure Transmitte Code 2 3 4 5 6 7 8 WT2000DP Measuring range(kPa) WT1151DP Measuring range(kPa) 0-0.1~1.5(Max.working pressure 4MPa) 0-0.125~1.5(Max.working pressure 4MPa) 0-0.188~7.5(Max.working pressure 7MPa) 0-0.75~7.5(Max.working pressure 7MPa) 0-0.935~37.4 0-3.74~37.4 0-4.67~186.8 0-18.68~186.8 0-17.24~690 0-68.9~689 0-51.7~2068 0-206.8~2068 0-172.25~6890 0-689~6890 Code Output S Smart 4 ~ 20mA DC in conformity with HART communication protocol J Smart 4 ~ 20mA DC square root output in conformity with HART communication protocol Structual material Code Flange connector Isolating diaphragm Vent/drain valve Filled liquid 316 stainless steel 316 stainless steel 316 stainless steel 22 Silicon oil 316 stainless steel 316 stainless steel Hastelloy C-276 23 Code Max.working pressure MPa No marking 10(only for measuring range code 4 5 6 7 8) 14 (only for measuring range code 4 5 6 7 8) DCode Indicator M1 0~100% linear indicator(only for WT1151) M3 LCD digital indicator Code B01 B02 B03 B04 B05 B06 Installation bracket Bending bracket mounted by pipe(carbon steel) Bending bracket mounted by panel(carbon steel) Flat bracket mounted by pipe(carbon steel) Bending bracket mounted by pipe(stainless steel) Bending bracket mounted by panel(stainless steel) Flat bracket mounted by pipe(stainless steel) Code D1 D2 D3 V0 V1 Pressure chamber Release valve located on upper of pressure chamber side Release valve located on lower of pressure chamber side Release valve located on the opposite of the process connecting port Vertically mounted pressurechamber (only for WT2000) Vertically mounted pressure chamber with side release(only for WT2000) Code Connector C1 NPT1/2 female thread oval flange NPT1/2 induced pressure connector with 14 C12 induced pressure tube welded behind C2 C21 M20 1.5 T-shaped male thread connecting block M20 1.5 T-shaped male thread connecting block with 14 induced pressure tube welded behind Code Safe grade Flameproof Exd II BT4(WT1151)/CT3~T6(WT2000) d Intrinsical safe Exia II CT6(WT1151)/CT3~T6(WT2000) i Code Cleaning 1 Degreasing on surface (only for WT2000) WT1151DP 5 WT2000DP 5 S S 22 22 DM1 M3 B01 B01 D2 D2 C12 C12 d i 1 WT1151DP model selection example WT2000DP model selection example

16

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000HP High Static Differential PressureTransmitter

Model Selection

1.2.2 WT1151

WT2000HP High Static Differential Pressure Transmitter

The high static pressure transmitter can measure the differential pressure under working pressure of 32MPa. Withstanding working pressure of 32MPa and the overload protection ensure the transmitter can be used reliably in high static pressure system. Output 4~20mA DC, in conformity with HART communication protocol. Model and Ordering Code for HP High Static Differential Pressure Transmitter
Table 11
WT1151HP Smart High Static Differential Pressure Transmitter WT2000HP Smart High Static Differential Pressure Transmitte WT1151HP Measuring range(kPa) WT2000HP Measuring range(kPa) Code 4 0-3.74 37.4 0-0.935 37.4 5 0-18.68 186.8 0-4.67 186.8 6 0-68.9 689 0-17.24 690 7 0-206.8 2068 0-51.7 2068 Output Code Smart 4 20mA DC in conformity with HART communication protocol S Smart 4 20mA DC square root output in conformity with HART communication protocol J Code 22 Flange connector Structual Material Isolating diaphragm Vent/drain valve 316 stainless steel Filled liquid Silicon oil

316 stainless steel 316 stainless steel Code Max.Working pressure MPa No marking 25 F-

32 Code Indicator M1 0~100% linear indicator (only for WT1151) M3 LCD digital indicator Code Installation bracket B01 Bending bracket mounted by pipe(carbon steel) B02 Bending bracket mounted by panel(carbon steel) B03 Flat bracket mounted by pipe(carbon steel) B04 Bending bracket mounted by pipe(stainless steel) B05 Bending bracket mounted by panel(stainless steel) B06 Flat bracket mounted by pipe(stainless steel) Code D1 D2 D3 V0 V1 Pressure chamber Release valve located on upper of pressure chamber side Release valve located on lower of pressure chamber side Release valve located on the opposite of the process connecting port Vertically mounted pressure chamber (only for WT2000) Vertically mounted pressure chamber with side release(only for WT2000) Code Connector C1 NPT1/2 female thread oval flange C12 NPT1/2 induced pressure connector with 14 induced pressure tube welded behind Code Safe Grade d Flameproof Exd II BT4(WT1151)/CT3~T6(WT2000) i Intrinsical safe Exia II CT6(WT1151)/CT3~T6(WT2000) Code Cleaning Degreasing on surface(only for WT2000) 1

WT1151HP 5 WT2000HP 5

S S

22 22

M1 M3

B01 B01

D2 D2

C12 C12

d i 1

WT1151HP model selection example WT2000HP model selection example

SHANGHAI WELLTECH AUTOMATION CO., LTD

17

WT1151

WT2000GP Gage Pressure Transmitter

Model Selection

1.2.3

WT1151

WT2000GP Gage Pressure Transmitter

WT1151 WT2000GP capacitive pressure transmitter (gage pressure) can measure the pressure within a range from 0.188kPa to 41370kPa. Service: liquid, gas and steam. Output: 4~20mA DC, in conformity with HART communication protocol.

Fig.11

WT1151GP/AP Pressure Transmitter Outline

177 (with field indicator)

1. Nameplate (remove it when adjusting span and zero); 2. Oval flange, induced pressure connection screw is NPT1/2. Note: oval flange can be turned; 3. While without oval flange, NPT1/4 screw on the pressure chamber for induced pressure connection; 4. NPT1/4 screw for connecting with the release valve (on upper or on lower); 5. Release valve; 6. Pressure chamber, turnable.

Fig.12
18

Outline Dimension for WT1151GP/AP Pressure Transmitter


SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000GP Gage Pressure Transmitter

Model Selection

Fig.13

WT2000GP/AP Pressure Transmitter Outline


133.5 (with field indicator)

92

1. Nameplate; 2. NPT1/4 screw for connecting with the release valve (on upper or on lower); 3. Pressure chamber, turnabl; 4. Release valve; 5. NPT1/4 screw on the pressure chamber for induced pressure connection.

198

Vertically Mounted

Pressure Chamber

Fig.14 Table 12

Outline Dimension for WT2000GP/AP Pressure Transmitter

Range Code A (mm)

3~5 54.0

6~7 55.6

8 56.8
3mm

9 57.9

0 59.1

Note: Dimension A changed while the oval flange is turned, i.e. A

SHANGHAI WELLTECH AUTOMATION CO., LTD

19

WT1151

WT2000GP Gage Pressure Transmitter

Model Selection

Model and Ordering Code for GP Gage Pressure Transmitter


Table 13
WT1151GP Smart Gage Pressure Transmitter WT2000GP Smart Gage Pressure Transmitte Code WT1151GP Measuring range(kPa) 0-0.75~7.5 3 0-3.74~37.4 4 0-18.68~186.8 5 0-68.9~689 6 0-206.8~2068 7 0-689~6890 8 0-2068~20680 9 0-4137~41370 0 Output Code S Smart Code 22 23

WT2000GP Measuring range(kPa) 0-0.188~7.5 0-0.935~37.4 0-4.67~186.8 0-17.24~690 0-51.7~2068 0-172.25~6890 0-517~20680 0-1034.2~41370

4~20mA DC in conformity with HART communication protocol Structual material Isolating diaphragm Flange connector Filled liquid Vent/drain valve 316 stainless steel 316 stainless steel 316 stainless steel Silicon oil Hastelloy C-276 316 stainless steel 316 stainless steel Code Indicator M1 0~100% linear indicator(only for WT1151) M3 LCD digital indicator Code Installation bracket B01 Bending bracket mounted by pipe(carbon steel) B02 Bending bracket mounted by panel(carbon steel) B03 Flat bracket mounted bypipe(carbon steel) B04 Bending bracket mounted by pipe(stainless steel) B05 Bending bracket mounted by panel(stainless steel) B06 Flat bracket mounted by pipe(stainless steel) Code Pressure chamber D1 Release valve located on upper of pressure chamber side D2 Release valve located on lower of pressure chamber side D3 Release valve located on the opposite of the process connecting port V0 Vertically mounted pressure chamber (only for WT2000) V1 Vertically mounted pressure chamber with side release (only for WT2000) Code Connector C1 NPT1/2 female thread oval flange C12 C2 C21 NPT1/2 induced pressure connector with 14 induced pressure tube welded behind M20 1.5 T-shaped male thread connecting block M20 1.5 T-shaped male thread connecting block with 14 induced pressure tube welded behind Code Safe grade Flameproof Exd II BT4(WT1151)/CT3~T6(WT2000) d Intrinsical safe Exia II CT6(WT1151)/CT3~T6(WT2000) i Code Cleaning Degreasing on surface(only for WT2000) 1

WT1151GP 0 WT2000GP 9

S S

22 22

M1 M3

B01 B01

D2 D2

C1 C1

d i 1

WT1151GP WT2000GP

model selection example model selection example

20

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000AP Absolute Pressure Transmitter

Model Selection

1.2.4

WT1151

WT 2000AP Absolute Pressure Transmitter

WT1151 WT2000AP absolute pressure transmitter may measure absolute pressure of the deaerating system, the distillation tower, the evaporator and the crystallizer etc., and can withstand 10MPa overpressure. Service: liquid, gas and steam. Output: 4~20mA DC in conformity with HART communication protocol. Model and Ordering Code for AP Absolute Pressure Transmitter
Table 13
WT1151AP Smart Absolute Pressure Transmitte WT2000AP Smart Absolute Pressure Transmitte WT1151AP Measuring range kPa WT2000AP Measuring range kPa Code 4 0 10 37.4 0 10 37.4 5 0 18.68 186.8 0 10 186.8 6 0 68.9 689 0 17.24 690 7 0 206.8 2068 0 51.7 2068 8 0 689 6890 0 172.25 6890 Output Code S Smart 4-20mA DC in conformity with HART communication protocol Structual material Code Vent/drain valve Isolating diaphragm Filled liquid Flange connector 316 stainless steel 316 stainless steel 316 stainless steel 22 Silicon oil Hastelloy C-276 316 stainless steel 316 stainless steel 23 Code Indicator M1 0~100% linear indicator(only for WT1151) M3 LCD digital indicator Code Installation bracket B01 Bending bracket mounted by pipe(carbon steel) B02 Bending bracket mounted by panel(carbon steel) B03 Flat bracket mounted bypipe(carbon steel) B04 Bending bracket mounted by pipe(stainless steel) B05 Bending bracket mounted by panel(stainless steel) B06 Flatbracketmountedby pipe(stainless steel) Code Pressure chamber D1 Release valve located on upper of pressure chamber side D2 Release valve located on lower of pressure chamber side D3 Release valve located on the opposite of the process connecting port V0 Vertically mounted pressure chamber (only for WT2000) V1 Vertically mounted pressure chamber with side release (only for WT2000)
Code C1 C12 C2 C21

Connector NPT1/2 female thread oval flange NPT1/2 induced pressure connector with 14 induced pressure tube welded behind M20 1.5 T-shaped male thread connecting block M20 1.5 T-shaped male thread connecting block with 14 induced pressure tube welded behind
Code Safe Grade d Flameproof Exd II BT4(WT1151)/CT3~T6(WT2000) Intrinsical safe Exia II CT6(WT1151)/CT3~T6(WT2000) i Code Cleaning Degreasing on surface(only for WT2000) 1

WT1151AP 5 WT2000AP 4

S S

22 22

M1 M3

B01 B01

D2 D2

C1 C1

d i 1

WT1151AP WT2000AP

model selection example model selection example

SHANGHAI WELLTECH AUTOMATION CO., LTD

21

WT1151

WT2000LT Flanged Level Transmitter

Model Selection

1.2.5

WT1151 WT2000LT Flanged Level Transmitter

The mounting flange of WT1151 WT2000LT capacitive level transmitter adopts ANSI3 , 4 (with the flange rating Class 150, Class 300, Class 600) or DN80 (with the flange rating 1.6/4.0MPa, 6.4MPa, 10MPa). The installation dimensions are shown in the following Table 15. If customer follows GB9116-88 standard, DN shall be equal to 80 or 100, and PN to 2MPa. There are 316L, Hastelloy C-276, tantalum etc. for material of the wetted diaphragm. Our company can also offer other special mounting flange according to the requirement of customer. Unless otherwise specified, our company will supply the mounting flange of 3 , Class 150.
Fig. 15 WT1151LT Flanged Level Transmitter Outline

NPT 1 / 4 while without connector

Sealing face

Inserted depth 50,100,150mm

n-d Hole distributed diameter Nameplate Release valve

Fig.16
22

Outline Dimension for WT1151LT Flanged Level Transmitter


SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000LT Flanged Level Transmitter

Model Selection

Fig.17

WT2000LT Flanged Level Transmitter Outline


n-d Hole distributed diameter Release valve

NPT 1 / 4 while without connector

Sealing face

Inserted depth 50,100,150mm

Fig.18

Outline Dimension for WT2000LT Flanged Level Transmitter

SHANGHAI WELLTECH AUTOMATION CO., LTD

23

WT1151

WT2000LT Flanged Level Transmitter

Model Selection

Table 15 Dimension for Flange in Fig.16 18

Nominal Diameter
DN50 (Sealing face DIN 2526 E) (Flange DIN 2501) DN80 (Sealing face DIN 2526 E) (flange DIN 2501 DN2'' (ANSI B 16.5 R F )

Rated Pressure

D 165 200 215

D1 125 160 170 120.6 152.4 168.3 191 200

B 48.3 76 76 48.3 76 76 89 89

C 102 127 127 92.1 127 127 157 157

A 20 24 28 17.4 22.2 27.0 30 32

Thread Required Thread Qty.

4 8 8 4 4 8 8 8

M16 M16 M20 M16 M16 M20 M18 M20

Class 150 Class 150 Class 300 Class 150 Class 300

152.4 190.5 209.5 229 255

DN 3 (ANSI B 16.5 R F ) DN 4 (ANSI B 16.5 R F )

Model and Ordering Code for LT Flanged Level Transmitter


Tabel 16
WT1151LT Smart Level Transmitter WT2000LT Smart Level Transmitter WT1151LT Measuring range kPa WT2000LT Measuring range kPa Code 4 0-3.74 37.4 0-0.935 37.4 5 0-18.68 186.8 0-4.67 186.8 6 0-68.9 689 0-17.24 690 Output Code Smart 4 20mA DC in conformity with HART communication protocol S Code Nominal diameter Inserted cylinder length mm Diaphragm material on high pressure side DN80/DN3 316L Flat flange A0 DN80/DN3 316L 50 A2 DN80/DN3 316L 100 A4 DN80/DN3 316L 150 A6 316L DN100/DN4 Flat flange B0 316L DN100/DN4 50 B2 316L DN100/DN4 100 B4 316L DN100/DN4 150 B6 316L DN2 Flat flange G0 316L DN2 50 G2 316L DN2 100 G4 316L DN2 150 G6 316L DN50 Flat flange J0 316L DN50 50 J2 316L DN50 100 J4 316L DN50 150 J6 Hastelloy C-276 DN80/DN3 Flat flange C0 Hastelloy C-276 50 DN80/DN3 C2 Hastelloy C-276 100 DN80/DN3 C4 Hastelloy C-276 150 C6 DN80/DN3 Hastelloy C-276 Flat flange D0 DN100/DN4 Hastelloy C-276 50 D2 DN100/DN4 Hastelloy C-276 100 D4 DN100/DN4 DN100/DN4 Hastelloy C-276 150 D6

24

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000LT Flanged Level Transmitter

Model Selection

H0 H2 H4 H6 K0 K2 K4 K6 E0 F0 I0 L0

Flat flange Hastelloy C-276 DN2 Hastelloy C-276 DN2 50 Hastelloy C-276 DN2 100 Hastelloy C-276 150 DN2 Flat flange Hastelloy C-276 DN50 Hastelloy C-276 50 DN50 Hastelloy C-276 100 DN50 Hastelloy C-276 150 DN50 Flat flange Tantalum DN80/DN3 Flat flange Tantalum DN100/DN4 Flat flange Tantalum DN2 Flat flange Tantalum DN50 Code Installation flange DN3'' Class150 stainless steel A DN4'' Class150 stainless steel B DN2'' Class150 stainless steel G DN3'' Class300 stainless steel C DN4'' Class300 stainless steel D DN80 PN1.6MPa/4MPa stainless steel E DN50 PN1.6MPa/4MPa stainless steel J DN80 PN6.4MPa stainless steel F Structual material of sensor part Code Flange connector Vent/drain valve Isolatingv diaphragm Filled liquid 22 316 stainless steel 316 stainless steel 316 stainles ssteel Silicon oil 23 316 stainless steel 316 stainless steel Hastelloy C-276 Code Indicator M1 0~100% linear indicator (only for WT1151) M3 LCD digital indicator Code Pressure chamber D1 Release valve located on upper of pressure chamber side D2 Release valve located on lower of pressure chamber side D3 Release valve located on the opposite of the process connecting port Code Connector C1 NPT1/2 female thread oval flange
C12 C2 C21

NPT1/2 induced pressure connector with 14 induced pressure tube welded behind M20 1.5 T-shaped male thread connecting block M20 1.5 T-shaped male thread connecting block with 14 induced pressure tube welded behind Code Safe grade Flameproof Exd II BT4(WT1151)/CT3~T6(WT2000) d Intrinsical safe Exia II CT6(WT1151)/CT3~T6(WT2000) i Code Cleaning Degreasing on surface(only for WT2000) 1

WT1151LT 4 WT2000LT 5

S S

A0 B6

C B

22 22

M1 M3

D2 D2

C12 C12

d i 1

WT1151LT model selection example WT2000LT model selection example

SHANGHAI WELLTECH AUTOMATION CO., LTD

25

WT1151

WT2000DP/GP Differential /Gage Pressure Transmitter with Remote Seal

Model Selection

1.2.6

WT1151

WT2000DP/GP Differential/Gage Pressure Transmitter with Remote Seal

When WT1151 WT2000DP/GP transmitter is equipped with the remote seal it will become WT1151 WT2000DP/GP differential/gage pressure transmitter with remote seal. WT1151 WT2000DP/GP differential/gage pressure transmitter with remote seal can prevent the isolating diaphragm of the transmitter from being directly touched with the measured medium. It is applicable to the following situations: 1. The measured medium will bring corrosion to the transmitter connector and the sensitive element; 2. The high temperature medium is necessary to be isolated from the transmitter; 3. There are suspended solid particles in the measured medium or high-viscous, which will easily result in plugging of transmitter connector and pressure chamber; 4. The measured medium is easy to solidify or crystallize when being induced out by induced pressure tube; 5.Water flush is needed before the measured medium is changed while the measured medium not allow of mixing. 6. It is required to maintain the sanitary condition and prevent from pollution. WT1151 WT2000DP/GP differential/gage pressure transmitter with remote seal combines WT1151 WT2000DP/GP differential/gage pressure transmitter with the remote seal, so it still owns all the characteristics of WT1151 WT2000DP/GP differential/gage pressure transmitter. Measuring range is 0~6kPa to 0~7MPa. Various structual materials are available. The remote seal device adopts the welding structure, which ensures high reliability. The filled liquid chamber adopts low volume design to reduce the temperature influence. According to the requirement of the customer, the application temperature for ordinary filled silicon oil is 40~149 , and for high temperature silicon oil 15~315 . For the details, please refer to Table 26. The upper limit of working pressure for the remote seal is the rated pressure of the remote seal chosen by the customer. The working pressure shall not be less than 35kPa (absolute pressure).
26
SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000DP/GP Differential /Gage Pressure Transmitter with Remote Seal

Model Selection

Outline Dimension for WT1151DP/GP Differential/Gage Pressure Transmitter with Remote Seal

177 (with field indicator)

177 (with field indicator)

Fig.19

Outline Dimension for WT1151DP/GP Differential /Gage Pressure Transmitter with Remote Seal

SHANGHAI WELLTECH AUTOMATION CO., LTD

27

WT1151

WT2000DP/GP Differential /Gage Pressure Transmitter with Remote Seal

Model Selection

Outline Dimension for WT2000DP/GP Differential/Gage Pressure Transmitter with Remote Seal

Fig.20

Outline Dimension for WT2000DP/GP Differential/Gage Pressure Transmitter with Remote Seal
SHANGHAI WELLTECH AUTOMATION CO., LTD

28

WT1151

WT2000DP/GP Differential /Gage Pressure Transmitter with Remote Seal

Model Selection

Customer's process connecting flange

Remote seal flange

Customer's flange

Fig.21

Outline Dimension for 1199PFW Flat Remote Seal ( DN 3'', Working Pressure 2.5MPa)

Fig.22

Outline Dimension for 1199PFW-1 Flat Remote Seal

Inserted depth 50,100,150

Fig.23 Outline Dimension for 1199EFW Inserted Cylinder Remote Seal


SHANGHAI WELLTECH AUTOMATION CO., LTD

29

WT1151

WT2000DP/GP Differential /Gage Pressure Transmitter with Remote Seal

Model Selection

Table 17 Dimension for 1199PFW-1/1199EFW Remote Seal

Nominal Diameter
DN50 (Sealing face DIN 2526 E) (Flange DIN 2501) DN80 (Sealing face DIN 2526 E) (Flange DIN 2501)

Rated Pressure

D 165 180 200 215

D1 125 135 160 170 120.6 127.0 152.4 168.3 191 200

B 57 57 75 75 57 57 75 75 89 89

C 102 102 138 138 92.1 92.1 127 127 157 157

A 20 26 24 28 17.4 20.6 22.2 27.0 30 32

Thread Required Qty. Thread

4 4 8 8 4 8 4 8 8 8

M16 M20 M16 M20 M16 M16 M16 M20 M18 M20

DN 2 (ANSI B 16.5 R F ) DN 3 (ANSI B 16.5 R F ) DN 4 (ANSI B 16.5 R F )

Class 150 Class 300 Class 150 Class 300 Class 150 Class 300

152.4 165.1 190.5 209.5 229 255

Upper sleeve flange

Upper sleeve flange Sealing ring

Lower sleeve Lower sleeve Flush hole NPT 1/4 Sealing ring Flush hole NPT 1/4

Fig.24

Outline Dimension for 1199RFW Flanged Remote Seal

Fig.25

Outline Dimension for 1199RTW Threaded Remote Seal (Max. Working Pressure 10MPa)

Table 18 Dimension for1199RFW Flanged Remote Seal


Dimension for upper sleeve flange Nominal Diameter (inch) 1 1 1/2 2 3 Nominal Thickness Outside Pressure of Bolt Diameter A (Class/MPa) Hole D 150/2 300/5 150/2 300/5 150/2 300/5 150/2 300/5 110 125 127 156 152 165 191 210 14.3 17.2 17.2 20.7 19.1 22.2 23.8 25.5 Center Distance B 79.5 89 98.4 114.5 120.6 127 152.4 168.3 Bolt Hole Quantity n 4 4 4 4 4 8 4 8 Dimension for lower sleeve flange Bolt Hole d 16 20 16 23 20 20 20 23 Diameter E(mm) Diameter F(mm)

26.9 41.9 52.5 79

66.5 78.7 95.2 127

30

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000DP/GP Differential /Gage Pressure Transmitter with Remote Seal

Model Selection

Model and Ordering Code for DP/GP Differential/Gage Pressure Transmitter with Remote Seal
Table 19
WT1151DPYC/GPYC Smart Differential /Gage transmitter with remote seal WT2000DPYC/GPYC Smart Differential /Gage transmitter with remote seal Code WT1151 Measuring range(kPa) 0 6.2 37.4 4 0 31.1 186.8 5 6 0 117 690 7 0 345 2068 8 0 1170 6890 Code Output Smart 4-20mA DC in conformity with HART communication protocol S Code 22 Flange connector Isolating diaphragm 316LSST 316LSST One remote seal device(mating with GPYC) According to Table 20 21 22 23 S1 24 25 to place ordering Two remote seal devices(mating with DPYC) S2 Indicator Code M1 0~100% linear display(only for WT1151) M3 LCD digital display Code Installation bracket B01 Bending bracket mounted by pipe(carbon steel) B02 Bending bracket mounted by panel(carbon steel) B03 Flat bracket mounted by pipe(carbon steel) B04 Bending bracket mounted by pipe(stainless steel) B05 Bending bracket mounted by panel(stainless steel) B06 Flat bracket mounted by pipe(stainless steel) Code Safe grade Flameproof Exd II BT4(WT1151)/CT3~T6(WT2000) d Intrinsical safe Exia II CT6(WT1151)/CT3~T6(WT2000) i Code Cleaning Degreasing on surface(only for WT2000) 1 Type of remote seal device Code Flat 1199PFW 1199PFW-1 Flat Screwed 1199RTW Inserted cylinder 1199EFW Flanged 1199RFW

WT1151DPYC 4 1199PFW11A11-755

22

S2

M1

B01

1199PFW

Model Selection example Refer toTable 20-25

SHANGHAI WELLTECH AUTOMATION CO., LTD

31

WT1151

WT2000DP/GP Differential /Gage Pressure Transmitter with Remote Seal

Model Selection

Ordering Code for Flat Remote Seal Device


Table 20
1199PFW Flat Remote Seal Device Code Measuring range (kPa) DN3 Class 150 11 DN2 Class 150 13 23 DN50 PN1.6MPa/4MPa 24 DN80 PN1.6MPa/4MPa Code Diaphragm material of remote seal device 316LSST A HastelloyC-276 B Tantalum C Code Housing material 316SST 11

1199PFW

11

11

Model selection example for flat remote seal device

Table 21
1199PFW-1

Code 11 12 13 15 16 17 23 24 25 26

Flat Remote Seal Device Measuring range (kPa) DN3 Class 150 DN4 Class 150 DN2 Class 150 DN3 Class 300 DN4 Class 300 DN2 Class 300 DN50 PN1.6MPa/4MPa DN80 PN1.6MPa/4MPa DN50 PN6.4MPa DN80 PN6.4MPa Diaphragm material of remote seal device Code 316LSST A HastelloyC-276 B Tantalum C

1199PFW-1 11

Model selection example for flat remote seal device

32

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000DP/GP Differential /Gage Pressure Transmitter with Remote Seal

Model Selection

Ordering Code for Threaded Remote Seal Device


Table 22

Structual material Upper sleeve is 316SST, installation ring is galvanized carbon steel, and gasket is asbestos or viton, buna Upper sleeve is 316SST, installation ring is 316SST, and gasket is asbestos or viton, buna

Induced pressure port

Ordering Code for Inserted Cylinder Remote Seal Device


Table 23
1199EFW Inserted Cylinder Remote Seal Device Type Code DN3 Class 150 11 DN4 Class 150 12 DN2 Class 150 13 DN3 Class 300 15 DN4 Class 300 16 17 DN2 Class 300 23 DN50 PN1.6MPa/4MPa 24 DN80 PN1.6MPa/4MPa 25 DN50 PN6.4MPa 26 DN80 PN6.4MPa Code Diaphragm material of remote seal device 316LSST A Hastelloy C-276 B Code Length of inserted cylinder ( 2 ) 50mm 20 ( 4 ) 100mm 40 60 ( 6 ) 150mm

1199EFW

11

60

Model selection example for flatremote seal

SHANGHAI WELLTECH AUTOMATION CO., LTD

33

WT1151

WT2000DP/GP Differential /Gage Pressure Transmitter with Remote Seal

Model Selection

Ordering Code for Flanged Remote Seal Device


Table 24

Structual material Upper sleeve is 316SST, uppel sleeve flange is galvanized carbon steel, and gasket is asbestos or viton Upper sleeve is 316SST, uppel sleeve flange is 316SST, and gasket is asbestos or viton

34

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000DP/GP Differential /Gage Pressure Transmitter with Remote Seal

Model Selection

Ordering Code for Capillary


Table 25
1199CAP Material 304 dimension 3 1

Code 755 757 759 760 761 764

Length of capillary 1.0m 2.0m 4.0m 6.0m 8.0m Special Code Protection sleeve No marking Armoured 304 PVC protection sleeve, armoured304 A

1199CAP

755

Model selection example

755A

Simplified model seection example

Characteristic of Filled Liquid


Table 26

Note:

The temperature limit is reduced under vacuum circumstance (<50kPa absolute pressure), which should be specified in ordering. If pressure exceeds 590kPa, the temperature can be up to 315 ; otherwise, the temperature is below 315 . Ordering code should be written after the code of capillary. For example: WT1151DP4S22S2M1B01 1199RFW21A11A21-S

Covered Film of Remote Flange


F46 Note: Cover F46 film to isolating diaphragm F46 only applicable to situation of positive pressure and remote flange filled with ordinary silicon oil; Ordering code F46 only applicable to level transmitter, PFW-1 and PFW remote seal device; F46 will be covered by user self while installing flange. For example: WT1151DP4S22S2M1B01 1199PFW-1 11A-F46
35

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT2000TG Smart Directly Mounted Pressure Transmitter

Model Selection

1.2.7

WT2000TG Smart Directly Mounted Pressure Transmitter

WT2000TG smart directly mounted pressure transmitter adopts the mature metal capacitive sensor and advanced sensor from America as sensitive element, and with high performance and price ratio. Since it is featured with stability and reliability, compact and strong structure etc., It is widely used in petrochemical, power station, water treatment, food making and other industries which needs a high requirement for pressure measuring, and enjoys a rather good reputation in the field. WT2000TG directly mounted pressure transmitter (gage pressure) Measuring range: 0-0.935kPa~35000kPa. Service: liquid, gas and steam. Output: smart, 4~20mA DC, in conformity with HART communication protocol.

133.5 (with field indicator)

For range code 4 5 6 7 A = 170mm For range code 8 9 0 A = 185mm


Fig.26 Outline Dimension for WT2000TG Smart Directly Mounted Pressure Transmitter

36

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT2000TG Smart Directly mounted Pressure Transmitter

Installation Accessories

Model and Ordering Code for WT2000TG Smart Directly Mounted Pressure Transmitter
Table 27
WT2000TG Smart Directly Mounted Pressure Transmitter Measuring range kPa Code 0 0.935 37.4 4 0 4.67 186.8 5 0 17.24 690 6 7 0 51.7 2068 8 0 172.25 6890 9 0 517 20680 0 0 1034.2 35000 Code Output Smart 4-20mA DC in conformity with HART communication protocol S Connection type Code
A B C D E M20 1.5 male thread NPT1/2 male thread G1/2 male thread NPT1/2 female thread NPT1/4 female thread Indicator Code M3 LCD digital indicator Code Installation bracket Bracket mounted on wall CS for range code B11 Flat bracket mounted by pipe CS for range code B12 Bracket mounted on wall SS for range code B13 Flat bracket mounted by pipe SS for range code B14 Flat bracket mounted by pipe CS for range code B15 Bracket mounted on wall CS for range code B16 Flat bracket mounted by pipe SS for range code B17 Bracket mounted on wall SS for range code B18 Code Safe grade Flameproof Exd CT3 T6 d i Intrinsical safe Exia CT3 T6 Code Cleaning Degreasing on suface 1

4 4 4 4 8 8 8 8

5 5 5 5 9 9 9 9

6 6 6 6 0 0 0 0

7 7 7 7

WT2000TG

M3

B11

WT2000TG model selection example

SHANGHAI WELLTECH AUTOMATION CO., LTD

37

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Installation Accessories

1.3
1.3.1

Installation Accessories

Installation Bracket and Installation Type

Fig.27

Bending Bracket Mounted by Pipe

Ordering Code B01/B04

Installation hole

Fig.28

Bending Bracket Mounted by Panel

Ordering Code B02/B05

38

SHANGHAI WELLTECH AUTOMATION CO., LTD

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Installation Accessories

Fig.29

Flat Bracket Mounted by Pipe

Ordering Code B03/B06

1.3.2

Installation Bracket and Installation Type for Directly Mounted


133.5 (with 133.5 field indicator) 133.5 (with 133.5 field indicator)

Gap for opening the cover 20mm

Gap for opening the cover 20mm

Installation bracket

Installation bracket
Flat bracket mounted by 2 pipe (Code B12/B14/B15/B17)

Bracket mounted on wall


(Code B11/B13/B16/B18)

SHANGHAI WELLTECH AUTOMATION CO., LTD

Installation bracket

Hoop

Hoop

39

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Installation Accessories

1.3.3

Induced Pressure Connector

1. Pressure chamber flange 2. O ring 3. NPT1/2 oval flange 4. Bolt M10 40 NPT1/2 Thread Connector(Code C1)

1. NPT1/2 transitional connector 2. Nut M20 1.5 3. Sealing ring 4. 14 induced pressure tube NPT1/2 Thread Transitional Induced Pressure Connector (Code C12)

1. Pressure chamber flange 2. M20 1.5 T-shaped male thread connector 3. Bolt 4. O ring M20 1.5 T-shaped Male Thread Connection Block(Code C2)

1. Pressure chamber flange 2. Bolt 3. M20 1.5 T-shaped male thread connector 4. O ring; 5. Nut M20 1.5 6. 14 induced pressure tube M20 1.5 Thread Connector (Code C21)

Fig.30

Induced Pressure Connector


SHANGHAI WELLTECH AUTOMATION CO., LTD

40

WT1151

WT2000 Series Smart Capacitive Pressure Transmitter

Installation Accessories

1.3.4

Connection Dimension for Process Flange If customer orders WT1151 WT2000LT flanged level transmitter or WT1151 WT 2000DP/GP differential/gage pressure transmitter with remote seal device of EFW RFW , the following drawing is for reference for dimensions of 3'', 4'' Class 150 process connection flange(used for installing the flange, and offered by customer self) and the sealing gasket.

Evenly distributed

Fig.31 Customer's Process Connection Flange for 3'' Class 150 Flange(D Determined by Customer) (for Reference)

Evenly distributed

Fig.32

Customer's Process Connection Flange for 4'' Class 150 Flange (D Determined by Customer) (for Reference)

Table 28 Dimension for Sealing Gasket of Flange

Mating flange 3 4

D 127 157

d 80 95
Fig.33 Sealing Gasket of Flange

The customer may select the material of the sealing gasket of flange at his own option according to the characteristic of the measured medium. Our company recommends using such material as asbestos rubber, buna, viton, nylon, or PTFE etc.

SHANGHAI WELLTECH AUTOMATION CO., LTD

41

You might also like