C.A. No.

DG MAP/PHASE-II/GPR/PKG-14 (R & C) OF 2012-13

PARTICULAR SPECIFICATIONS (Contd)

Serial Page No.300

Clause 20.7 (Contd) Cable entry for incoming cables shall be from bottom. Each feeder compartment shall be totally enclosed, self sufficient with MCCB/MCB unit, meters, interlocked door, pad locking facility, labelled terminal block, engraved anodised aluminium labels ( white letters in black background) for each feeder. Name plate details shall indicate designation of feeder. Indicating lamps shall be LED type with fuses. Non current carrying metal parts shall be connected to earth bar which shall be run through out the length of the panel and shall be provided with two independent earthing connections to external earthing leads. Feeder connections shall be by solid copper wires/aluminium strips with bimetallic clamps wherever required, through lugs, nuts, bolts and spring washers. All doors and covers shall be folded type with gasket. Insulating covers / barriers shall be on live terminals for protection against accidental touch. Vitreous enameled danger board with skull and indication of voltage shall be provided on panels. in The panel shall be provided with hinged door for access to equipment. The hinged door shall be interlocked so as to prevent opening of the door when the MCCB is ON & to prevent closing of the MCCB when the door is not fully closed. However, a device for by passing the door interlock shall be provided to enable operation of the MCCB during maintenance with the door open. External lighting distribution board located in substation building shall be of construction and general features as above but shall be wall mounting type. External lighting distribution board located outside shall be of outdoor feeder pillar type as per requirements of clause 17.6. Distribution Boards / Feeder Pillars on page 227 20.8 SINGLE PHASE ENERGY METERS Electronic type energy meters shall be single phase 240 V 10-40 Amp 50 Hz, LCD display with class 1.0 accuracy, Meter should be as per IS-13779 and with IS certification mark. Meters should be of S/S, Transparent Polycarbonate body with tamper Proof design & should give accuracy irrespective of mounting position. The accuracy should not get effected by external magnetic field. It should be with LED indication proportional to kWh for on spot calibration check. Meter should be suitable for : Frequency range: 50 Hz + 5% Starting Current: 0.4% of Basic Current Operating Ambient Temperature: 0 to 55 Deg. Cent. Power factor Range: 0.5 lag - UPF - 0.8 lead Meter should have following features : LED indication for Power on, Reverse Current, Display -_ 6 digit (1 decimal digit)

kWh Pulse output

Meter shall continue to operate satisfactorily under the following conditions :_ Phase/Neutral Reversed. _ Supply side-Load side interchanged _ Full Load/Partial Load terminated to Earth. _ Combination of any of the above. Contd...

C.A. No. DG MAP/PHASE-II/GPR/PKG-14 (R & C) OF 2012-13

Serial Page No.301

PARTICULAR SPECIFICATIONS (Contd) 20.9 THREE PHASE ENERGY METERS Electronic type energy meters shall be three phase, 4 wire 415 V, 10-40 Amp, 50 Hz , LCD display with class of accuracy 1.0 solidly earthed power supply system with balanced & unbalanced loads. Meter shall be as per IS -13779 with IS/BSI certificate mark. Meters should be of S/S, Transparent Polycarbonate body with tamper Proof design & should give accuracy irrespective of mounting position. The accuracy should not get effected by external magnetic field. It should be with LED indication proportional to kWh for on spot calibration check. Meter should be suitable for : Frequency range: 50 Hz + 5% Starting Current: 0.4% of Basic Current Operating Ambient Temperature: 0 to 55 Deg. Cent. Power factor Range: 0.5 lag - UPF - 0.8 lead Meter should have following features : LED indication for Power on, Reverse Current, Display -_ 6 digit (1 decimal digit)

kWh Pulse output

Meter shall continue to operate satisfactorily under the following conditions :_ Phase/Neutral Reversed. _ Supply side-Load side interchanged _ Full Load/Partial Load terminated to Earth. _ Combination of any of the above. 20.10 CFL light fittings LF-1, LF-2,, LF-3). The Fittings should be wired with multi-stranded twin core copper conductor PVC insulated cable for working voltage upto & including 1100 Volt, 50 Hz, AC supply. The surfaces of CRCA steel & Aluminium sheets used in the fittings shall be properly phosphatised & white powder coated. All wire leads to be adequately covered with sleeves for protection against accidental hardware parts used should be zinc coated or of brass so as to be corrosion resistant. contact. All

The guage / thickness is given in the technical specification should be followed strictly, the tolerance in thickness of sheet shall be as per IS-513/1994 with Amdt No.1 and IS-2676 / 1981 (Reaffirmed in 1996) The fittings shall be manufactured as per IS:1032 / Pt. V Sec. 1/1985 (Reaffirmed in 1995 1) for Fixed General Purposed Luminaries. with Amdt No.

For frosted/ground glass, one face of the glass is made rough by grinding or chemically. The idea is to render it translucent so that it transmits light but provides privacy by obstruction vision. The lamp light also does not react directly to the eyes. Contd...

C.A. No. DG MAP/PHASE-II/GPR/PKG-14 (R & C) OF 2012-13

Serial Page No.302

Clause 20.10 (Contd)

PARTICULAR SPECIFICATIONS (Contd)

All openings should be provided with insulated busing /sleeves wherever the electric wire is drawn in order to avoid the damage to insulation. The different components shall be manufactured as per detailed technical specification and dimensional sketches. The fittings will be free from burrs, sharp edges etc. For dimensions of the fittings, refer to sketches. Metal shades shall be well finished in white powder coated paint outside and inside. Glass shades shall be heat resistant frosted / opaque type and shall be true in shape free from flaws, specks or bubbles and shall be uniform in thickness, free from sharp edges and uniform in colour. 20.10.1 Sketch No LF-1: connections. Finish: Circular Base: Wall mounted type fitting made out of CRCA sheet steel, pre wired upto main

White powder coated. 0.80 mm thick 110 mm dia.

Circular front canopy 0.80 mm thick 95 mm dia 65 mm deep (check nut attachment To couple the back plate and front canopy.) Holder: Glass Bi-pin brass lamp holder used in the fittings should be ISI marked as per IS/1258/1987 with Amdt No 1,2 & 3. Dome shaped frosted glass 160 mm dia to be fixed with 4 Nos. brass screw. 0.70 mm

20.10.2 Sketch No LF-2: Wall Mounted Type Fittings made out of CRCA sheet steel of thickness, pre wired upto main connection. Finish: Black Plate Dimensions Square top: Clear Glass panels: Overall size: Holder: : : White powder coated. 0.70 mm thick. 170 mm x 70 mm 140 mm x 140 mm 02 Nos in sides + 1 No. glass panel in front, to be made translucent 400 mm x 145 mm.

Bi-pin brass lamp holder used in the fittings should be ISI marked as per IS:1258 / 1987 with Amdt No 1, 2 & 3. Contd...

C.A. No. DG MAP/PHASE-II/GPR/PKG-14 (R & C) OF 2012-13

Serial Page No.303

PARTICULAR SPECIFICATIONS (Contd) 20.10.3 Sketch No LF-3: Ceiling Mounted Type fitting suitable for 11 Watt (3U) CFL made out of 0.70 mm thick CRCA sheet, pre wired upto maint connection. Finish: Circular Base: Holder White powder coated. Dia 240 mm x 40 mm deep. Bi-pin brass lamp holder used in the fittings should be ISI marked as per IS:1258/1987 with Amdt No 1,2 & 3. Frosted glass of 200 mm dia, screwed on the fittings.

Glass

Samples of all above light fittings should be submitted for approval. 20.10.4 BULK HEAD FITTINGS These shall be roubust in construction, made from case iron, pressed steel on case aluminium and fitted with porcelain lamp holder, vitreous enameled reflectors and hinged water tight front with key and wire or pressed metal guards. Samples of light fittings should be submitted for approval. 20.11 CEILING FANS ISI marked electric ceiling fan capacitor type with double ball bearing complete with capacitor, 300 mm down rod, canopies, three number blades made of aluminum alloy, electronic stepped speed regulator suitable for single phase AC, 230 volt, 50 Hz supply and confirming to class I of IS:374/1979 with amendment number 1 to 6 :(a) Blade thickness without paint shall be as follows:Sweep size Minimum blade thickness 900 mm & 1200 mm 1.0 mm 1400 mm & 1500 mm 1.1 mm The material of the blade shall be H3 Grade Aluminium Alloy sheet conforming to IS:737/1976. The load bearing bolt shall be of min. 6 mm dia with aluminium clamp, Spring Washer, Nut and Check nut and spilt pin. Down rod shall be of 1.5 to 1.6 mm nominal thick ERW pipe of appropriate length. Shackle made from 2 mm nominal thick CRCA sheet. Bolts (2 Nos) shall be 6 mm with Spring washer Nut and Check nut and spilt pin. Shank shall be made of CRCA Sheet of thickness 1.6 mm minimum without paint for all size. Contd...

(b) (c)

(d) (e) (f) (g)

C.A. No. DG MAP/PHASE-II/GPR/PKG-14 (R & C) OF 2012-13

Serial Page No.304

PARTICULAR SPECIFICATIONS (Contd) Clause 20.11 (Contd) (h) (j) Powder coated Super Enamel paint with Primer Coating, white colour. Electronic stepped speed regulator as per IS: 11037 shall be capable of reducing the speed of the fan at least 50% of the full speed at the test voltage. Fans shall be capable of running at all the running position of the regulator at the rated voltage. Capacitor of size ranging from 1.70 to 2.50 mfd to be put and fixed for easily replacement and placed at sufficient distance from the windings, comply with IS:1709-1984 and shall be suitable for working at full load under ambient air temp up to 700 C.

(k)

20.12

EXHAUST FANS 300 MM 6 POLES Exhaust fan 300 mm sweep as per IS:2312-1967 with amendment No 1 to 8 suitable for single phase AC 230 Volts, 50 c/s Capacitor run complete with mounting ring four Nos fixing holes with louver shutters. (a) (b) (c) (d) (e) (f) (g) (h) (j) (k) (l) (m) (n) (o) (p) (q) (r) (s) (t) (u) (v) (w) Sweep Number of poles Air deliver at rated voltage (cubic meter per hour) Power input Current at rated voltage Rated Voltage with frequency Power factor Rated speed in RRM Fan casting material Mounting ring frame material its thickness Type and Grade Class of insulation of Motor Type of bearing Type of lubricant system Number of blades Material and thickness of blade Material and thickness of shaft Capacitor rating in Micro-farad Method of Mounting Capacitor Type and grade of primer and finishing Thickness of bracket Louver shatters Flexible rubber pads (Heavy duty) 300 mm 6 poles 1145 55 watt 0.26 A 230 volts 50 Hz Single Phase 0.9 900+5% Aluminum Frame MS Sheet, 0.8 mm Class E Double ball bearing & made of steel Suitable grease cup shall be provided per bearing separately Four 0.8 to 1.0 mm 450 mm mild steel Comply with IS 1709-1960 (1.70 to 2 mfd) Capacitor should be mounted on fan Motor back over with suitable clamp. Grey enameled paint with primer coats. 3 mm Frame MS Sheet 0.7 mm Louvers Aluminum Sheet 0.40 mm To reduce fan motor vibrations. Contd...

C.A. No. DG MAP/PHASE-II/GPR/PKG-14 (R & C) OF 2012-13

PARTICULAR SPECIFICATIONS (Contd) 20.13 ELECTRIC WATER HEATER CAPACITY 25 LTRS

Serial Page No.305

Storage type Electric Water Heater of 240 Volts single phase AC 50 Hz supply (ISI Marked to IS : 2082 / 1993 with latest amendment). Stainless Steel inner container shall conform to material grade 07 Cr 18 Ni of IS : 1570 (Part-5) / 85 Outer container shall be made of CRCA sheet duly pretreated and finished in either white stove enamel paint or powder coated in white colour. In coastal areas/heavy rainfall area the outer cover shall be of Poly Carbonate moulded min 2 mm thickness. Storage Electric Water Heater shall be complete in all respect with fittings as listed in below:(a) (b) (c) (d) (e) (f) (g) (h) (a) (b) (c) (d) (e) (f) (g) (h) (j) (k) Heating Unit Thermostat Indicating Lamp Thermal cutout Drain Plug Two meter three flexible cable with 3-pin plug of 16 A capacity. Provision for vent pipe pressure relief valve/device. Fusible plug fitted on the crown of water heater with operating temperature between 90 degree C to 100 degree C. Rated Capacity Material and thickness of outer shell (with tolerance). Material and thickness of inner shell (with tolerance) Material & Grade of insulation between inner & outer shell. Thickness of Insulation between inner & outer shell Hot Water out put in litres (min) Operating Temperature of Thermal cut out Thermostat setting Standing losses Details of Mounting of Heating Elements in the water Heater. Heating Element 25 Ltr 0.56 to 0.70 mm CRCA Sheet 0.56 to 0.62 mm Stainless Steel sheet Resin bonded Glass Wool Insulation 35 to 40 mm Approximate 45 Degree/Centigrade 90 +/- 6 Degree/Centigrade 70 Degree/Centigrade 1.386 Kwh/Per 24 hrs Cup Type with pocket for the Thermal cut out fixed by means of 3 clamps/triangular type fixed with 3 nut bolt. As per IS 302-2-21(1992)

(l)

20.14 Approved make of components All electrical material shall be used from the list of approved makes enclosed as Appendix E. Contd...