Professional Documents
Culture Documents
Reinforced Concrete Column Design Columns are vertical members loaded in compression and bending at the same time. Columns from structures must be designed to fail due to bending moments. If plastic hinges occur at the end of one column, the structure as a whole can still carry vertical loads and general failure appears. In case of failure due to compression, general failure occurs because all the members above the column fail. 5.3.1. Concrete Cover to reinforcement Eurocode 2 has special requirements for calculating of the minimum concrete cover. The minimum cover, Cmin should be provided in order to ensure: o the safe transmission of bond forces; o the protection of the steel against corrosion; o an adequate fire resistance. The nominal cover should be specified on the drawings, and it is defined as the minimum cover , plus an allowance in design for deviation .
The greater value of cmin satisfying both environmental and bond conditions should be used:
, where:
o o
- minimum cover due to bond requirement; - minimum cover due to environmental conditions; o - additive safety element;
o o 5.3.1.1.
- reduction of minimum cover for use of stainless steel; - reduction of minimum cover for use of additional protection Concrete cover of the transversal reinforcement
5.3.1.2.
5.3.2. Design compressive and tensile strengths The concrete class chosen for the girder, according to the exposure class of the element XC1 is C20/25. The value of the design compressive strength is defined as: fcd=cc*fck/c=1*20/1.5=13.33 N/mm2, where: o c - partial safety factor for concrete o cc - coefficient taking into account of long term effects on the compressive strength and of unfavorable effects resulting from the way the load is applied. This value is defined in the National Annex of each country. The recommended value is 1.0. The value of the design tensile strength is defined as: fctd=ct*fck,0.05/c=1*1.5/1.5=1 N/mm2, where: o c - partial safety factor for concrete o ct - coefficient taking into account of long term effects on the tensile strength and of unfavorable effects resulting from the way the load is applied. This value is defined in the National Annex of each country. The recommended value is 1.0.
5.3.3. PC52 (S345) Reinforcement properties The value of the design yield strength is defined as: fyd=fyk/s=345/1.15=300 N/mm2, where: o fyk characteristic yield strength; o fyd design yield strength; o s partial safety factor for steel.
5.3.5. Minimum and Maximum reinforcement areas The minimum area of longitudinal reinforcement in columns is given by: , where: o o Cross sectional area of concrete; Ultimate axial load; In Eurocode 2 the maximum nominal reinforcement area for columns is 4%. However, this area can be increased provided that the concrete can be placed and compacted sufficiently.
The diameter of the transverse reinforcement should not be less than 6 mm or 1/4 of the maximum diameter of the longitudinal bars. 5.3.6. Minimum spacing of reinforcement The minimum clear distance between bars should be the greater of: o Bar diameter; o Aggregate size(16 mm) plus 5mm; o 20 mm;
5.3.7. Critical length According to P100, in order to prevent plastic hinges that occur in the column, it is necessary to have a smaller spacing between stirrups near the nodes, on the critical length.
{ { {
At the first 2 stories, the critical length is increased with 50%: 5.3.8. Maximum spacing of transverse reinforcement The maximum spacing of the stirrups in columns, according to Eurocode 2, should not be greater than: o 12 times the minimum diameter of the longitudinal bars; o 60% of the lesser dimension of the column; o 240mm {
No longitudinal bar should be further than 150 mm from transverse reinforcement in the compression zone. According to P100/2006, the spacing between the stirrups should not exceed: o 33% of the lesser dimension of the column; o 125 mm o 7 times the minimum diameter of the longitudinal bars; {
At the first two levels of buildings with more than 5 stories and at the first story in case of smaller buildings, the spacing will be smaller besides the critical zone, with 50% of its length.
5.3.9. Design of the Column B1 The maximum bending moments in the columns and design bending moments in the girders reduced at the column`s edge were extracted from ETABS. Frame structures are more safety if the plastic hinges appear first at the ends of the girders. To assure this requirement, weaker columns must be avoided and transversal reinforcement must be assured on the column to prevent the failure in the node . 5.3.9.1. Maximum Bending Moments
The bending moments MULS and axial forces NED were determined using ETABS.
5.3.9.2.
Frame structures are more safety if the plastic hinges appear first at the ends of the girders. To assure this requirement, the design bending moment are computed with the formula: , for Marginal Columns;
o o o o
maximum bending moment on the column in ULS; capable moment of the girder in the node i; - design bending moment of the girder in the node i.
5.3.9.3.
additional eccentricity
If
, the
Because of the small eccentricity of the axial force, the concrete does not crack and can support alone the eccentric compression. Therefore, the minimum reinforcement percentage is placed from constructive reason. The capable bending moment of the column is computed using the formula:
5.3.9.4.
Biaxial bending
The effects of biaxial bending may be checked using the expression: , where: o - Design moment in the respective direction including second order effects in a column o o o o - Moment of resistance in the respective direction the capable axial force; the design axial force;
,
a1.098
5.3.9.5.
Eurocode 2 introduces the strut inclination method for shear capacity checks. In this method the shear is resisted by concrete struts acting in compression and shear reinforcement acting in tension.
Having the capable moments, in the bearing and in the field, we determine the shear force corresponding to the capable bending moments, from static equilibrium on the girder. , where: o o {
5.3.9.6.
, where:
( o ( )
The capable shear force of stirrups reinforced elements is the minimum value given by:
, where: o transversal reinforcement area (for n=4 branches of the stirrup and d=10mm); o design strength of the transversal reinforcement; o o .9*d=0.9*655=589.5 mm; strength reduction factor of cracked concrete due to shear;
We impose: s=100mm
o For Story 1-8: On the critical length stirrups with 4 branches. On the rest of the column, we provide 10/125 mm stirrups with 4 branches. o For Ground Floor: We provide 10/75 mm stirrups with 4 branches. 5.3.9.7. Horizontal design shear force in the nodes , we provide 10/100 mm
The design shear force in the nodes is computed using the following formula: for Edge nodes; for Central nodes, where: o o the girders; o design shear force from the column under the node; { - overstrength factor; the real areas of reinforcement from the superior and inferior part of
Table.5.3.6. Horizontal capable shear forces in the nodes (on X and Y direction)
Story STORY1 STORY2 STORY3 STORY4 STORY5 STORY6 STORY7 STORY8 kN 1531.74 1348.22 1181.15 1013.88 846.67 679.68 512.99 346.62 0.2345 0.2064 0.1808 0.1552 0.1296 0.1040 0.0785 0.0531 kN 3735.1 3668.5 3606.8 3543.9 3479.9 3414.8 3348.6 3281.1 kN 2988.1 2934.8 2885.4 2835.1 2783.9 2731.8 2624.9 2624.9 kN -14.379 35.304 35.304 35.304 35.304 35.304 35.304 35.304 kN -411.36 -331.14 -331.14 -331.14 -331.14 -331.14 -331.14 -331.14
For Edge nodes: , where: o o the girders; o stirrups in the node; o o o area of a branch of a stirrup; number of horizontal stirrups in the node; - number of bars - total area of horizontal normalized axial force of the inferior column; the real areas of reinforcement from the superior and inferior part of
The condition is checked for the nodes at all levels. 5.3.9.10. Longitudinal reinforcement checking in the node , where: o vertical longitudinal reinforcement passing through the node, including the longitudinal reinforcement of the column; o o edge reinforcements of the columns; o - interaxial distance between the reinforcement from the superior and inferior part of the girders; total area of horizontal stirrups in the node - interaxial distance between the
5.3.9.11.
- coefficients considering the bars shape, the concrete cover and confinement
o o o o o o o o o 5.3.9.12. Overlapping Lengths { - minimum anchorage length for compressed bars , We impose {