You are on page 1of 2

Through-Fault Current Calculator: A Resource for Selecting a Substation

Transformer Protective Device


One criterion in selecting a distribution substation transformer protective device is its ability to protect the transformer
from secondary-side limited faults . . . or “through-faults.” These faults are difficult to detect by the overcurrent relay of
the line-terminal circuit breaker, because the magnitude of the fault current is relatively low—being limited by the
impedance of the transformer. These faults are a challenge to clear as well, because of their high transient recovery
voltage.

That’s why a stand-alone protective device such as an S&C Circuit-Switcher is typically applied at each transformer.
S&C has tested each of its distribution transformer protective devices—Series 2000, Mark V, and Mark VI Circuit-
Switchers, and Trans-Rupter II® Transformer Protector—specifically for this duty, and assigned a secondary-fault
interrupting rating to each device.

This formula can be used to determine the secondary-fault interrupting rating required for the substation transformer
protective device, to properly protect a particular size and impedance of transformer:

I = (57.8P) / [(%Z)E]
The formula assumes an infinite (zero-impedance) source.

Through-Fault Current Calculator

Adobe Flash® Player Plug-in Required.

Where:

I = Inherent secondary-fault current, amperes

P = Transformer self-cooled three-phase base rating, kVA

E = System phase-to-phase voltage, kV

%Z = Percent transformer primary-to-secondary impedance, referred

A protective device is appropriate for the application if its secondary-fault interrupting rating is equal to or greater than
the value for “I” calculated above.

EXAMPLE:
The inherent secondary-fault current for a 20/40/50-MVA, 115-kV, 8%-impedance transformer would be:

I = [(57.8) (20 000 kVA)] / [(8) (115 kV)] = 1257 A


Check out these other resources for selecting a substation transformer protective device:

“Selection Guide for S&C Substation Transformer Protective Devices”


The selector table in this publication lets you compare the features and capabilities of S&C’s substation transformer
protective devices, so you can select the appropriate device for your application.

“Primary-Side Transformer Protection”.


This paper offers a complete overview of transformer protection, including typical protection schemes, a discussion of
transient recovery voltage and why secondary-side faults are difficult to interrupt, and criteria for selecting a device
appropriate to a particular application.

©2009 S&C Electric Company All rights reserved.

Site Map | Privacy Statement

You might also like