Professional Documents
Culture Documents
Page 2
gases encourage the continuity of current flow across the contact wear. Conversely, for the lower power factor
contact air gap until either the current goes to zero, i.e. in switching duties of electrical equipment, test criteria call for
the zero cross over of the sine wave, or until the gap is fewer switching cycles. In endurance testing (high power
stretched so far that the density of conductive particles factor), switching cycles may number in the thousands; in
reduces to the point where the voltage will no longer overload testing (intermediate power factor), switching
sustain the arc. Figure 1 is a graphical representation of cycles will typically number in the tens; in short circuit
contact voltage and current at circuit interruption. The close on or interruption, (low power factor), switching
example depicts a circuit interruption at about 45o into cycles will number one or two.
the voltage wave. Because there is a current flowing at
the time of contact opening, the voltage across the Both the IEC and UL switchgear and controlgear standards
contacts increases to 100 volts ( the approximate value of are quite demanding with respect to product performance.
arc gap voltage in free air ). As long as the contact gap However, they permit a broad range of product ratings
has not stretched beyond that which will permit current because they recognize the diverse needs of electrical loads
flow and as long as there is current flow, the arc will throughout the world. Both are sound standards because
continue. (Opening speed of low voltage contacts is their qualification requirements are based on physics and
typically not fast enough to stretch the gap beyond a the effects of the generation, distribution and control of low
conducting distance within the first half cycle.) At the voltage electric power. Products qualified to either standard
higher power factor of 0,95, the left hand trace, note that should find ready qualification to the other standard. As will
the current goes to zero at 198,2o. At the lower power be seen throughout this discussion, this theme will repeat
factor of 0,2, the right hand trace, note that the current itself. A product qualified to an IEC standard will gain
goes to zero at 258,5o. qualification to the relevant UL product standard and
vice-versa. This does not say that they will carry the same
The traces assume that the interruption is successful at ratings in both standards, as will be seen when the standard
the first current zero crossover after contact opening. In applicable to circuit breakers is evaluated.
this example, the arcing time is 40% longer for the lower
power factor case.
150.00 150.00
100.00 100.00
50.00 50.00
0.00 0.00
Magnitude
Magnitude
0 50 100 150 200 250 300 350 400 0 50 100 150 200 250 300 350 400
E(C) I(.2)
-50.00 -50.00
I(.95) E(C)
-100.00 -100.00
-150.00 -150.00
-200.00
-200.00
-250.00
-250.00
Phase Angle
Phase Angle
The vaporized contact material created by arcing, It would make sense to evaluate the equipment in the order
produces a rapidly expanding pressure wave that can in which it appears in the power distribution system.
have explosive effects. As an indication of the ferocity of Accordingly, the first product to be discussed is switchgear
this pressure wave, when changed from a solid to a vapor, and controlgear assemblies.
copper expands to 6400 times its initial volume. From the
Ideal Gas Law, pV = nRT, it can be determined that the Switchgear and controlgear assemblies. The applicable
pressure associated with a 6400 times increase in volume standards for switchgear and controlgear assemblies are
would produce a substantial and explosive wave front. IEC 60439-1, UL 891 and UL 1558. Aside from the fact
For this reason, electrical equipment is tested in its that UL 1558 applies to the use of low voltage power air
intended enclosure. Given that the arcing time in the circuit breakers in switchgear assemblies only and UL 891
lower power factor case is longer, the material vaporized will allow molded case breakers, fused switches and low
from the contacts will be increased. Thus for the lower voltage air power circuit breakers, there is little difference
power factor case, one can expect significantly more in the qualification testing for similar current ratings of the
Page 3
final product. In UL 891, if the manufacturer uses a bus
design as shown in the standard, type testing is signifi- 1.5 MVA
2.17 kA
cantly reduced. In both IEC 60439-1 and UL 1558, full G1 G2 G3 G4 400 VAC
type testing is required. The type testing establishes that
the assembly is capable of serving the intended need.
T1 2.5 MVA T2 2.5 MVA
3.6 kA 3.6 kA 9kA
400 VAC 400 VAC Bus
M2
TIE
Page 4
and support materials are evaluated to assure adequate 100,000 amps with a clearing time of up to two cycles.
performance at the operating temperatures. While not Bus short circuit testing can be done at this level as well.
absolutely demanding copper as the bus material, the
standards strongly suggest copper. In practice, copper is Most manufacturers of switchgear and controlgear
the bus material of choice. There are some products that assemblies serve broad market needs. Consequently, their
will use aluminum. However, the standards do emphasize bus designs will be placed into service with differing
careful consideration of electrolytic and galvanic actions configurations of breakers and fuses. For this reason, the
of dissimilar materials. The major concern for high standards permit testing without protective devices and
continuous current ratings on busses is to maintain require instead that the manufacturer stipulate a time
temperature within allowable limits without requiring duration and current level for the test. Since the test is
forced air cooling. If care is exercised in the design to done on the bus structure, if it survives a current level for
accommodate proximity and skin effects, a qualified cost a time that encompasses several protective devices, the
effective high current bus can be achieved. There are structure is more broadly applicable. One manufacturer
qualified low voltage busses rated to 10,000 amps and tested its switchgear design for 200,000 amps for 0,066
will probably take a step up to 12,000 amps in the near seconds, and 85,000 amps for 1 second. Since this test
future. was conducted on the smallest cross section bus structure,
2 kA, the product was qualified for the full range of the
The final major area of concern for the qualification of product.
switchgear and controlgear centers around the ability of
the bus structure to withstand the effects of short circuit The principle concern over high fault currents is centered
currents. Looking back at the two figures, one could around the mechanical ability of the bus structure and
expect an available fault current of 62,6 kA at the supports to withstand the magnetic forces accompanying
secondary side of the transformer with an unlimited the current peaks. These forces are a function of the
utility service on the primary. Given that most generators square of the current and the linear distance between the
of the 1,5 MVA rating today are permanent magnet parallel current paths. The closer the current paths are, the
generators, one could expect an available fault current stronger the accumulative force is. This force will cause
from the four generators of 86,6 kA. It becomes obvious the conductors to be pulled together if the current in both
that this level of short circuit current can cause consider- paths is flowing in the same direction. The force will push
able damage if the switchgear bus is not capable of the conductors apart for currents flowing in opposite
withstanding forces associated with the magnetic effects directions. At the conclusion of a test, the structure is
of currents of this magnitude. inspected to insure that the damage level does not reduce
the ability of the bus to continue to carry rated current. In
In both the IEC and UL standards, busses are rated to addition, a dielectric test is conducted to assure that none
withstand fault currents as determined by the protective of the insulators and mounts have deteriorated.
device. The tests conducted are based on the type of
clearing device, (fuse or breaker), the level of current the Where testing has been done on a switchgear or control-
device will let through and for how long that current will gear product to establish qualification to an IEC or UL
be allowed to flow. Fuses are typically rated to interrupt standard, and that testing has been witnessed by a third
higher current than breakers, but they do it in a shorter party, submission of the test results to the other approving
period. When operating in its current limiting range, a party for an equivalent approval to the remaining standard
fuse will clear a fault current typically in less than a half should suffice as evidence of qualification. It would seem
cycle. The breaker, depending on whether it has a short that prudent judgment would require an inspection of the
delay trip or instantaneous will clear a fault current in 2 to product proposed for qualification but if the test results
25 or 30 cycles. Only the larger breakers will have an are certified, they should be acceptable.
appreciable short time delay, up to 30 cycles, for the
higher currents, currents in excess of 20,000 amps. So the While the IEC standard discusses isolation and barriers
switchgear designer picks the protective device intended more thoroughly, the segregation requirements are quite
for use and states the current level and time for which the similar to those stipulated in UL 891 and 1558.
bus is to be evaluated. If the device is fused, testing will Construction of the assemblies is relatively similar with
be done at high currents, perhaps up to 200,000 amps, for allowance for differences in the accepted standard height
subcycle periods. If a power breaker is selected, the of these assemblies. UL products tend to be 90 in.
testing can be done at up to 85,000 amps for 0,5 seconds. (2,286 m) high. IEC products tend to be 2,0m (78,74 in)
Some breakers will have an ultimate interrupting rating of high. Cable terminations are quite similar. These products
Page 5
typically provide hole patterns in the bus landing pads to function as utilization category B. Only category B
accommodate cable lugs. A typical lug is a screw type that breakers are subject to short time withstand current tests.
will accommodate a range of conductor diameters. When Comparable in UL, short time withstand current tests are
crimp lugs are required, the hole pattern is punched to conducted on breakers furnished without instantaneous
match the specified lug. trips. Typical duration for the short time withstand test is
from 0,3 to 0,5 seconds. Before the solid state and
Circuit Breakers The standards applicable to circuit microprocessor trip era, short time trip functions were not
breakers are IEC 60947-2, UL 489 and 1066. UL 1066 available in molded case breakers. The introduction of this
pertains to low voltage air power circuit breakers. UL 489 new trip function sensing technology has enabled more
pertains to molded case and insulated case breakers. IEC flexible coordination and multifunction trips in molded
60947-2 states in its scope,”... It (60947-2) applies what- case breakers. However, short time trip functions in
ever the rated currents, the method of construction or the molded case breakers are typically quite short in time 4 to
proposed applications of the circuit breaker may be. ...”. 6 cycles and relatively low currents in the 10 k A to 15 kA
The UL standards present a list of continuous and short range.
circuit ratings from which the manufacturer is encouraged
to choose when specifying the performance of the circuit The overload and operational performance capability tests
breaker. The IEC standard, with the exception of the ICS are found in the general performance qualification
rating, permits the manufacturer to specify the regimen. Overload testing is conducted at 6 X rated
performance ratings. In either case, the manufacturer continuous current and 0,5 power factor in both standards.
assigns a continuous and interrupting rating to the circuit IEC testing differs in that it does not require the overload
breaker. These assigned ratings determine which, and the test for breakers rated higher than 630 amps continuous.
severity of the tests to be conducted for qualification. The number of cycles of operation differ between the
standards with the UL standard requiring more operations.
To determine suitability for service at the selected Endurance, operational performance capability, test
utilization voltage, Ue, a dielectric test is conducted requirements in switching cycles both with and without
typically at 2500 volts or 2 X rated + 1000 volts current, are comparable between IEC and UL for breakers
depending on if the test is conducted before or after rated over 250 amps.
current performance tests. A dielectric test is conducted
FI LE:
after each regimen of current tests to determine success. A DATE: CONTINUOUS CURRENT
temperature rise test is conducted on a new sample at full STD. MFG. 250 400 RATING
600 630 800 1200 1250 1600
IEC 947-2 A 22 25 25 25 25 25
rating prior to other tests to determine suitability of the 690 VAC G 18 18 18
product for continuous current. The temperature rise at M 10 12 12 40 40
S 18 25 25 35
various points throughout the product are compared with UL 489 C 25 35 35 35 50
the allowable rises for those points in the standard. If the 600 VAC D 25 25 25 65 65
G 25 65 65
actual rise at all points is below the allowable, the product S 25 35 35 50 50 50
passes the test. UL 1066 C 42 50
600 VAC G 42 65
S 42 65
The next series of tests confirm the ability of the breaker
to trip at the calibrated currents in the specified time. NOTES: 630 and 1250 A continuous rating is an IEC rating only
Page 7
This is directly related to the physics of the controlled tests are essentially the same. Confirmation of conformity
devices. Motors will have high inrush currents, lasting to the test requirements is achieved if there is no
seconds, on turn on. This is due to the locked rotor state of permanent arcing, contact welding, arcing to ground and
the motor at turn on. Because this starting current can be the device passes a dielectric test of 2X rated + 1000 Volts
6 X full load running current, designers must make for 1 minute.
allowance for it in the design of the power distribution
system to the motor. In some cases, a designer may choose Power Ic/Ie Cycles
to place the motor close to the service entrance to mini- IEC UL Factor IEC UL IEC UL
mize the impact of voltage drop in the distribution system AC-1 AC general use 0.75-0.8 1.0 6000
resulting from this inrush. Where that is not practical, a AC-3 AC across the line motor starting1 0.4-0.5 2.0 6000 1000
designer will either specify larger conductors than other- AC-5a AC electric discharge lamps 0.4-0.5 2.0 6000 6000
wise required to carry the full load running current or use AC-5b AC incandescent lamps, Tungsten 0.75-0.8 1.0 6000 6000
one of several reduced voltage starting techniques. Such
starting schemes as Y-∆ and autotransformer will apply Table 4. Endurance performance criteria for
less than line voltage to the motor for initial start. When electromagnetic contactors.
the motor has achieved breakaway and is rotating at some
speed less that synchronous, the starter switches to full The IEC standard departs from the UL standard for short
line voltage mode to accelerate the motor to and maintain circuit product type testing. UL 508 requires short circuit
synchronous speed. Motor starting torque and operating testing for motor control, starters, overload relays and
horse power requirements will also dictate the starting controls incorporating overload relays only. The IEC
scheme to be used. (An aside, as of October 1997, only standard requires short circuit testing for all magnetically
high efficiency motors can be installed in the US market. operated devices within the scope of IEC 60947-4-1.
These motors have higher starting inrush current ranging When a fault occurs in a circuit, the voltage goes to zero
from 8 to 13 times their full load running current.) at the point of fault, therefore, for short circuit testing, the
Contactors serving transformers and ballast lighting loads coils of the magnetically held devices are powered from a
will also experience high inrush currents to meet the separate source in the product qualification regimen. This
magnetizing needs of the load. However, these currents is a provision of both the IEC and UL standards. This
will reduce to normal levels within the first 10 cycles of assures that the magnetic coil maintains its strength for
operation. Consequently, the switching burden is not as closing and withstanding the effects of fault currents on
severe as that of motor loads. the contact assemblies.
There are two operations for qualification of the device for
The overload test regimen of both standards requires 50
short circuits. The first operation is conducted with the
cycles of operation for the conditions stated. The IEC
contacts of the device and its protective device closed. The
standard requires either an additional 50 closing
second operation is done by closing the device, (contactor,
operations at 10 X rated current or as an alternative, the
etc.). The test sequence is identified as O - t - CO. It is read
overload make and break test can be conducted at 10 X
as, Open, time, Close Open. The criteria for passing
making and 8 X beaking for 50 cycles for AC-3 contac-
allows destruction of the contactor contacts and to varying
tors. Upon completion of the overload regimen, an
degrees, contact welding.
endurance regimen is conducted. Table 4 summarizes the
requirements of the endurance test for both standards.
Except for across the line motor starting contactors, the
2000 85 kA
1125 42 kA
750 30 kA
UL 500 18 kA
250 10 kA
65 5 kA
2.6 1 kA 3 kA
16 63 125 315 630 1000 1600
Figure 4. Short circuit test currents, IEC vs. UL
Page 8
The test values of fault current for IEC qualification are Unlike the other products covered by IEC 947, ATSE is as
generally lower than those for UL qualification. This much a control system as it is a switching device. Both the
discrepancy arises from the fact the IEC standard specifies UL and IEC recognize this. The tests therefore include
short circuit test currents based on continuous current verification of voltage sensing for over and under voltage
ratings of the device under test. The UL standard specifies conditions, frequency sensing, intentional time delays and
the short circuit test current based on the horsepower or significant operating times. Additionally, where a unique
kW rating of the device under test. As an example, if a con- switching arrangement is provided, the standards allow for
tactor for a 20 hp motor is to be qualified to UL at 480 evaluation of it as well. Such product provisions as closed
VAC, 3Ø, its continuous current rating would be 27 A transition transfer, delayed transition transfer and bypass
(table 42.2, UL 508). The required short circuit test current isolation automatic transfer switch products are
is 5,000 Amps rms Sym. The IEC short circuit test current accommodated by these standards. Each of these product
for a contactor continuously rated 27 amps is 3000 amps derivatives must be evaluated to assure that it complies
rms Sym. This observation is substantiated by figure 4. with the intent of these standards in addition to providing
the enhanced features.
Criteria for passing the short circuit test allows both
The making and breaking, overload, and operational
contact welding and contact destruction in the UL verifica-
performance, endurance, tests are the same for both
tion test. In the IEC test, type “1” coordination for all
standards. The tests are summarized in table 5. In each
devices permits damage to both the contactor and overload
standard, both of these regimens are conducted on the same
relay; type “2” coordination permits contact welding but
sample. In the UL standard, a temperature rise test is
no damage to the overload relay.
required after the overload test. In each standard, a dielec-
tric withstand is required after the endurance test. The data
Automatic Transfer Switching Equipment The
given in table 5 is for qualification to utilization category
applicable standards covering low voltage automatic
AC-33A. Utilization category AC-33A in the IEC standard
transfer switching equipment, ATSE, are UL 1008 and IEC
is the equivalent of the total system load category of UL
947-6-1. While there is no designated difference in class in
1008. There are other less stringent test criteria for the
the UL standard, the IEC standard identifies the circuit
ATSE in overload and endurance qualification when the
breaker scheme ATSE as a Class CB. It designates the
ATSE is intended for infrequent operation or restrictive
double throw type as the Class PC.
load application. However, given the nature of emergency
loads, the total system load rating, AC-33A, is the pre-
To this point in this summary, the equipment discussed has
ferred rating.
been single throw. By nature of the application, switching
a designated load between two power sources, ATSE is
Short circuit tests are conducted on a separate sample.
either double throw equipment or two single throw devices
There are two of these tests for PC class ATSE and three
arranged in a double throw scheme. When conducting
for CB class ATSE. CB class ATSE must make, break and
switching test regimens, they are conducted on each set of
withstand short circuit current. PC class ATSE does not
contacts. For example, a switching cycle for ATSE is
have to break short circuit current. The UL regimen
comprised of the normal source contacts making and
requires the withstand test to be conducted first. The IEC
breaking and the alternate source contacts making and
standard requires the withstand after the making and
breaking. For the short circuit and withstand current tests,
breaking tests. Criteria for success in the IEC standard
they are conducted on one set of contacts only if both sets
adds a temperature rise test after the test regimen, over and
of contacts have the same design. Where the contact design
above the success criteria defined in the UL standard. Each
differs between the normal and alternate main contacts,
of the standards allow conducting the tests with and
these tests are conducted on the set of contacts likely to
without an overcurrent protective device ahead of the
produce the worst case.
sample to be qualified. Where the test is conducted without
an overcurrent protective device ahead of the sample, the
The test regimen for the qualification of ATSE begins with
short circuit current is interrupted by a test station
evaluation of operating controls. Tests include temperature
disconnect after a minimum specified time. For samples
rise, dielectric, making and breaking, operational
having continuous current ratings of 400 A or less, the on
performance, short circuit making, short circuit breaking,
time of the current is 25 ms minimum. For switches rated
short time withstand and conditional short circuit current.
above 400 A, the minimum on time is 50 ms. Where a short
The short circuit testing varies depending on the type of
circuit protective device is used ahead of the ATSE sample
product, class PC or CB.
Page 9
0 < Ie = < 300 < Ie 400 < Ie 600 < Ie 800 < Ie 1600 < Ie 2500 <
300 = < 400 = < 600 = < 800 = < 1600 = < 2500 Ie
Overload
# Cycles 50 50 50 50 50 25 3
I / Ie 6 6 6 6 6 6 6
Endurance
# Cycles w/current 6000 4000 2000 2000 1500 1000 1000
# Cycles w/o current 1000 1000 1500 2000 2000
I / Ie (1) (1) (1) (1) (1) (1) (1)
(1) Half of the cycles are at I / Ie = 1.
(2) The power factor for the overload test is 0, 5; for the endurance test it is 0, 75 to 0, 8.
under test, it must be identified in the appropriate reports makes it mandatory that equipment performance be eval-
and markings. For UL, appropriate identification is the uated in higher available current circuits. Not having such
SCPD label information. For the IEC, one can identify the stiff power systems, equipment judged for service in
SCPD but must provide the Ipk and I2t data as well. In Europe is judged at lower current levels. For example, a
the withstand test, for magnetically held devices, UL circuit breaker is deemed to qualify to UL 489 at a current
requires the contactor to be held closed electrically; IEC of 35 kA. That same breaker might qualify to IEC 947-2
imposes the same requirement but allows a separate at only 25 kA because the operating voltage is 690 VAC
power source to be used for the operating coil. The as opposed to 600 VAC. An astute observation is that the
required test values of short circuit current are the same in MVA interrupting ratings of the IEC and UL rated break-
both standards. ers is about the same. This is as physics would suggest.
Summary It is physics that determines the behavior elec- The question is more “..at what level..” than “..if..” a
tric power. Regardless of where in the world electricity device qualified to the one standard can be used where the
flows, it is independent of local and national laws. other standard predominates. The answer to this question
However, the environments in which electricity flows dif- is one for the engineer. Given knowledge of the applica-
fers around the world. For this reason, codes and stan- tion and performance characteristics of the equipment per
dards will vary. These will take into account the environ- their respective standards, the engineer would be quite
ment in which electrical equipment operate. The breadth comfortable in making the necessary design decisions.
of the electric power distribution system in North America
Page 10