You are on page 1of 12

s

4213

VAI60..

VBI60..L

VBI60..T

ACVATIXTM

Open/close ball valves 2-port VAI60.. and changeover ball valves VBI60..L VBI60..T 3-port, PN40
with internally threaded connections

Brass UNS C35330 (DZR) ball valve body DN 15...50 3 kvs 596 m /h Internally threaded connections Rp as per ISO 7-1 Angle of rotation 90 For use with rotary actuators GQD..9A, GMA..9E with spring-return and GSD..9A, GLB..9E without spring return

Use For use in heating, ventilating and air conditioning plants as open/close or changeover ball valve. For closed circuits (avoid cavitation, see page 5).

CE1N4213en 2013-02-12

Building Technologies

Type summary
Type Open/close ball valves 2-port VAI60.15-15 VAI60.20-22 VAI60.25-22 VAI60.32-35 VAI60.40-68 VAI60.50-96 DN kvs = = VBI60.20-9L VBI60.25-9L VBI60.32-13L VBI60.40-25L VBI60.50-37L Changeover ball valves 3-port (L) VBI60.15-5L VBI60.15-12T VBI60.20-16T VBI60.25-16T VBI60.32-25T VBI60.40-49T VBI60.50-73T 50 40 32 25 20 15 Changeover ball valves 3-port (T) DN kvs [m /h] 5 12 15 9 16 22 9 16 22 13 25 35 25 49 68 37 73 96
3

nominal size nominal flow rate of cold water (530 C) through the fully open ball valve at a differential pressure of 100 kPa (1 bar)

Equipment combinations
Type GSD..9A pmax Ball valves VAI60.15-15 VAI60.20-22 VAI60.25-22 VAI60.32-35 VAI60.40-68 VAI60.50-96 VBI60.15-5L VBI60.20-9L VBI60.25-9L VBI60.32-13L VBI60.40-25L VBI60.50-37L VBI60.15-12T VBI60.20-16T VBI60.25-16T VBI60.32-25T VBI60.40-49T VBI60.50-73T pmax = ps = maximum permissible differential pressure across ball valves control path, valid for the entire actuating range of the motorized ball valve; for low noise operation, we recommend a maximum permissible differential pressure of 200 kPa maximum permissible differential pressure at which the motorized ball valve will close securely against the pressure (close off pressure) 350 350 350 350 350 350 350 350 350 1400 350 1400 350 1400 1000 800 600 350 1400 1000 800 600 ps pmax Rotary actuators GQD..9A ps [kPa] GMA..9E pmax ps GLB..9E pmax ps

2 / 12 Siemens Building Technologies Open/close ball valves 2-port and changeover ball valves 3-port, PN40 CE1N4213en 2013-02-12

Rotary actuators for ball valves (overview)

Type / Stock no. GSD141.9A GSD341.9A GQD121.9A GQD321.9A GMA121.9E GMA321.9E GLB131.9E GLB331.9E
1) 2)

Actuator type Electromotoric Electromotoric Electromotoric Electromotoric

Operating voltage AC/DC 24 V AC 230 V AC/DC 24 V AC 230 V AC/DC 24 V AC 230 V AC 24 V AC 230 V

Positioning signal Open/Close


1)

Spring return function time

Data Sheet

time 30 s

N4655

2-position

30/15 s

2)

Yes

15 s

N4659

2-position

90/15 s

2)

Yes

15 s

N4658

(2) 3-position

150 s

N4657

2-wire SPDT (Single Pole Double Throw) open/close

Ordering

When ordering please give material, article type, purchase order text and quantity. Example:
Material VAI60.25-22 GLB131.9E Article Type VAI60.25-22 GLB131.9E Purchase Order (PO) text Open/Close Ball valve inside threaded, 2-Port Actuator for Ball valve, NSR Quantity 2 2

Spare parts, Rev. no. Delivery Applications with auxiliary functions

See overview, page 11. Ball valves and rotary actuators are supplied in separate packaging and not assembled prior to delivery. If a ball valve application requires a rotary actuator with auxiliary functions (for example switch or potentiometer), a standard actuator with a corresponding function can be used. In this case, a mounting set ASK77.. is required in addition to the rotary actuator. For assembly please consult mounting instructions accordingly. Rotary actuators GMA..1E (with spring-return) GLB..1E (without spring-return) GQD..1A (with spring-return) GSD..1A (without spring-return) Option Potentiometer, switches Potentiometer, switches Switches Switches Mounting set (order text) ASK77.2 Accessory Kit BV for GMAxx1.9E ASK77.3 Accessory Kit BV for GLBxx1.9E ASK77.4 Accessory Kit for BV GQDxx1.9A ASK77.4 Accessory Kit for BV GQDxx1.9A

Accessories

For thermal insulation, separate insulation covers are available.


For open/close ball valves 2-port Ball valve VAI60.15.. VAI60.20.. VAI60.25.. VAI60.32.. VAI60.40.. VAI60.50.. Insulation cover ALI15VAI60/61 ALI20VAI60/61 ALI25VAI60/61 ALI32VAI60/61 ALI40VAI60/61 ALI50VAI60/61 For changeover ball valves 3-port Ball valve VBI60.15.. VBI60.20.. VBI60.25.. VBI60.32.. VBI60.40.. VBI60.50.. Insulation cover ALI15VBI60/61 ALI20VBI60 ALI25VBI60/61 ALI32VBI60/61 ALI40VBI60/61 ALI50VBI60/61

3 / 12

Siemens Building Technologies

Open/close ball valves 2-port and changeover ball valves 3-port, PN40

CE1N4213en 2013-02-12

Insulation covers for Open/close and changeover ball valves

ALI..VAI..

ALI..VBI..

Dimensions see page 10

Technical design Parts

1 Body 2 Connection with internal thread 3 Seat 4 O-ring 5 Ball 6 Stem 7 Slip clutch 8 O-ring

Sizing Flow diagram


400 300 200 111 83 55,6

96 73 68 49 37 25 35 16 2 2 3 15 1 12 9

----pmax

pmax for VAI60.. and VBI60.. see table equipment combinations for details = maximum permissible differential pressure across the ball valve, valid for the entire actuating range of the motorized ball valve; for low noise operation, we recommend a maximum permissible differential pressure of 200 kPa

4 / 12 Siemens Building Technologies Open/close ball valves 2-port and changeover ball valves 3-port, PN40 CE1N4213en 2013-02-12

Low noise operation

pv100

 100 = V 100 kPa = 3 1 m /h =

differential pressure across the fully open ball valve and the ball valves control path at a volumetric flow V100 volumetric flow through the fully open ball valve 1 bar 10 mWC 0.278 l/s water at 20 C

Cavitation

Cavitation accelerates wear on the ball and seat, and also results in undesirable noise. Cavitation can be avoided by not exceeding the differential pressure shown in the flow diagram on page 4, and by adhering to the static pressures shown below.
2500 25

2000

20

0 8
1

P1 [kPa]

1000

10

500

0 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300

0
4382D05

pmax [kPa]
pmax = p1 p3 M = = = = differential pressure with ball valve almost closed at which cavitation can largely be avoided static pressure at ball valve inlet static pressure at ball valve outlet pump water temperature

P1 [bar]
p1

1500

0 16

C C 0 C 14 0 C 12 0 C 1 0 80

15

p3
4382Z06

pmax

High temperature hot water example:

Pressure p1 at ball valve inlet: Water temperature:

500 kPa (5 bar) 120 C

From the diagram above, it will be seen that with the ball valve almost closed, the maximum permissible differential pressure pmax is 200 kPa (2 bar). Note on chilled water To avoid cavitation in chilled water circuits, ensure sufficient counter-pressure at the ball valves outlet, e.g. with an additional throttling ball valve downstream from the ball valve. Select the maximum differential pressure across the ball valve according to the 80 C curve in the flow diagram above.

5 / 12

Siemens Building Technologies

Open/close ball valves 2-port and changeover ball valves 3-port, PN40

CE1N4213en 2013-02-12

Operating pressure and temperature Fluids


Operating pressure [bar]

Operating temperature [C]

Operating pressure and medium temperature as per IS0 7005 Current local legislation must be observed. Notes Engineering Ensure cavitation-free flow (refer to page 5). Always use a strainer upstream of the ball valve to increase the ball valve's functional safety. Mounting Ball valve and rotary actuator can easily be assembled on site. Neither special tools nor adjustments are required. The ball valve VAI60.., VBI60.. is supplied with Mounting Instructions M4213 (74 319 0883 0. VAI60..
90 90

Orientation

VBI60..L VBI60..T

90

90

42 11Z03

6 / 12 Siemens Building Technologies Open/close ball valves 2-port and changeover ball valves 3-port, PN40 CE1N4213en 2013-02-12

4211Z04

Direction of flow

When mounting, pay attention to the ball valve's flow direction symbol. Ball valve VAI60.. Open/close ball valve 2-port VBI60..L Changeover ball valve 3-port (L-Type drill-hole) VBI60..T Changeover ball valves 3-port (T-Type drill-hole) Laser mark Delivery positon Turned 90 (Clockwise)

AB
4213Z01

AB
4213Z02

A AB = 100 %
A
A B AB
4213Z03

A AB = 0 %
A

AB B

A B

AB
4213Z04

4213Z12

B AB (AB B) = 100 % A B (B A) = 100 %


A
A B AB

AB
4213Z05

A B

AB
4213Z06

B
4213Z13

A AB = 100 % B AB = 0 % Commissioning

A AB = 0 % B AB = 100 %

Commission the ball valve only if the rotary actuator has been mounted correctly.

Maintenance VAI60.. and VBI60.. ball valves are maintenance-free. Warning When doing service work on the ball valve / rotary actuator: Deactivate the pump and turn off the power supply Close the shutoff ball valves Fully reduce the pressure in the piping system and allow pipes to completely cool down If necessary, disconnect the electrical wires. Before putting the ball valve into operation again, make sure the rotary actuator is correctly fitted. Disposal Before disposal, the ball valve must be dismantled and separated into its various constituent materials. Legislation may demand special handling of certain components, or it may be sensible from an ecological point of view. Current local legislation must be observed. Warranty The technical data given for applications is valid only in conjunction with the Siemens rotary actuators listed under "Equipment combinations", page 2. All terms of the warranty will be invalidated if rotary actuators of other manufacture are used.
7 / 12

Siemens Building Technologies

Open/close ball valves 2-port and changeover ball valves 3-port, PN40

CE1N4213en 2013-02-12

Technical data VAI60.. VBI60..L VBI60..T PN 40 as per ISO 7268 To ISO 7005 within the permissible medium temperature range according to diagram on page 6 00.0001 of 00.0001 of kvs value kvs value < 0.01 of 00.0001 of kvs value kvs value Cold water, chilled water, low temperature hot water, high temperature hot water, water with anti-freeze. Recommendation: water treatment to VDI 2035 -10120 C 90 Dezincification resistant hot-pressed brass (DZR), CW602N Dezincification resistant hot-pressed brass (DZR), CW602N, chromium-plated Dezincification resistant hot-pressed brass (DZR), CW602N EPDM O-rings 00.0001 of kvs value

Functional data

PN class Operating pressure Leakage rate Through-port Bypass Permissible media

Materials

Medium temperature Angle of rotation Ball valve body Ball Stem Gland Refer to " Dimensions" page 9 Internally threaded connections Pressure Equipment Directive Pressure accessories Fluid group 2 Environmental compatibility

Dimensions / weight

Rp as per ISO 7-1 PED 97/23/EC As per article 1, section 2.1.4 Without CE marking as per article 3, section 3 (sound engineering practice) ISO 14001 (Environment) ISO 9001 (Quality) SN 36350 (Environmentally compatible products) RL 2002/95/EC (RoHS)

Standards

8 / 12 Siemens Building Technologies Open/close ball valves 2-port and changeover ball valves 3-port, PN40 CE1N4213en 2013-02-12

Dimensions

DN = H =

H1 =
4213M01

Nominal size Total actuator height plus minimum distance to the wall or the ceiling for mounting, connection, operation, service, etc. Dimension from the pipe centre to install the actuator (upper edge) H

Type VAI60.15-15 VAI60.20-22 VAI60.25-22 VAI60.32-35 VAI60.40-68 VAI60.50-96

DN 15 20 25 32 40 50

B [mm] 26 31 39 48 55 67

C [mm] 31 1) 38 42.5 52 61 74

D [mm] 42 42 42 42 42 42

Rp [Inch] Rp Rp Rp 1 Rp 1 Rp 1 Rp 2

L1 [mm] 30.8 33.5 38.4 44 50.9 58.1

L2 [mm] 61.6 67 76.8 88 101.8 116.2

H1 [mm] 27.6 30.5 30.5 34.3 39.8 52.8

H2 [mm] 37.6 40.5 40.5 44.3 49.8 62.8

GSD..9A [mm] > 300

GQD..9A [mm] > 300

GMA..9E [mm] >300 >310 >320 >335

GLB..9E [mm] >300 >310 >320 >335

kg

[kg] 0.28 0.36 0.46 0.7 1.1 1.74

DN = H =

H1 =
4213M02

Nominal size Total actuator height plus minimum distance to the wall or the ceiling for mounting, connection, operation, service, etc. Dimension from the pipe centre to install the actuator (upper edge) H

Type
VBI60.15-5L VBI60.20-9L VBI60.25-9L VBI60.32-13L VBI60.40-25L VBI60.50-37L VBI60.15-12T VBI60.20-16T VBI60.25-16T VBI60.32-25T VBI60.40-49T VBI60.50-73T

DN 15 20 25 32 40 50 15 20 25 32 40 50

B [mm] 26 39 39 48 55 67 26 39 39 48 55 67

C [mm] 49.5 61.05 66.5 78.6 87.6 105.9 49.5 61.05 66.5 78.6 87.6 105.9
1)

D [mm] 42 42 42 42 42 42 42 42 42 42 42 42

Rp [Inch] Rp Rp Rp 1 Rp 1 Rp 1 Rp 2 Rp Rp Rp 1 Rp 1 Rp 1 Rp 2

L1 [mm] 33.3 40.2 42.7 49.6 54.8 65.7 33.3 40.2 42.7 49.6 54.8 65.7

L2 [mm] 66.6 80.4 85.4 99.2 109.6 131.4 66.6 80.4 85.4 99.2 109.6 131.4

H1 [mm] 27.6 30.5 30.5 34.3 39.8 52.8 27.6 30.5 30.5 34.3 39.8 52.8

H2 [mm] 37.6 40.5 40.5 44.3 49.8 62.8 37.6 40.5 40.5 44.3 49.8 62.8

GSD..9A [mm] > 300

GQD..9A [mm] > 300

GMA..9E [mm] >300

GLB..9E [mm] >300

kg

[kg] 0.32 0.73 0.62 0.97 1.43 2.36 0.31

>310 >320

>310 >320

> 300

> 300

>300

>300

0.74 0.63 0.69 1.38 2.26

>310 >320

>310 >320

Body larger than union nut

9 / 12

Siemens Building Technologies

Open/close ball valves 2-port and changeover ball valves 3-port, PN40

CE1N4213en 2013-02-12

Dimensions with insulation covers for open/close ball valves 2-port


C 67
4213M03

D1

DN = H =

E L
Type Insulation cover ALI15VAI60/61 ALI20VAI60 ALI25VAI60/61 ALI32VAI60/61 ALI40VAI60/61 ALI50VAI60/61 to ball valve VAI60.15-15 15 VAI60.20-22 20 VAI60.25-22 25 VAI60.32-35 32 VAI60.40-68 40 VAI60.50-96 50 DN B 56 56 56 86 95 105 C 95 95 95 100 102 96 D 65 66 80 95 98 110 D1 27 32 37 47 50 56 E 21 27 34 43 48 61 L 100 105 108 130 140 160 > 300 > 300 GSD..9A [mm] GQD..9A [mm] [mm] [mm] [mm] [mm] [mm] [mm]

B
H GMA..9E [mm] >300 >310 >320 >335

Nominal size Total actuator height plus minimum distance to the wall or the ceiling for mounting, connection, operation, service, etc.

GLB..9E [mm] >300 >310 >320 >335

kg

[g] 15 16 20 28 32 36

Dimensions with insulation covers for changeover ball valves 3-port


67

E
DN = H =
4213M04

C1 C

Nominal size Total actuator height plus minimum distance to the wall or the ceiling for mounting, connection, operation, service, etc.

Type Insulation cover


ALI15VBI60/61 ALI20VBI60 ALI25VBI60/61 ALI32VBI60/61 ALI40VBI60/61 ALI50VBI60/61

D1

H DN 15 20 25 32 40 50 C 100 115 115 125 125 145 C1 50 55 55 55 55 60 D 70 80 80 95 95 110 D1 34 40 40 45 45 54 E 21 27 34 43 48 61 L 100 120 120 150 150 170 >310 >320 >310 >320 > 300 > 300 >300 >300 GSD..9A [mm] GQD..9A [mm] GMA..9E [mm] GLB..9E [mm]
kg

to ball valve
VBI60.15.. VBI60.20.. VBI60.25.. VBI60.32.. VBI60.40.. VBI60.50..

[mm] [mm] [mm] [mm] [mm] [mm]

[g] 21 30 30 41 43 51

10 / 12 Siemens Building Technologies Open/close ball valves 2-port and changeover ball valves 3-port, PN40 CE1N4213en 2013-02-12

Revision numbers
Type Open/close ball valves 2-port VAI60.15-15 VAI60.20-22 VAI60.25-22 VAI60.32-35 VAI60.40-68 VAI60.50-96 Changeover ball valves 3-port (L) VBI60.15-5L VBI60.20-9L VBI60.25-9L VBI60.32-13L VBI60.40-25L VBI60.50-37L VBI60.15-12T VBI60.20-16T VBI60.25-16T VBI60.32-25T VBI60.40-49T VBI60.50-73T Changeover ball valves 3-port (T) ..A ..A ..A ..A ..A ..A ..A ..A ..A ..A ..A ..A ..A ..A ..A ..A ..A ..A Valid from rev. no.

11 / 12

Siemens Building Technologies

Open/close ball valves 2-port and changeover ball valves 3-port, PN40

CE1N4213en 2013-02-12

12 / 12 Siemens Building Technologies

2010-2013 Siemens Switzerland Ltd. Open/close ball valves 2-port and changeover ball valves 3-port, PN40

Subject to change CE1N4213en 2013-02-12