TECHNICAL INFORMATION

COMPANY PREFACE
ERSE KABLO, eutablished in 1996, has been growing rapidly by inreasing manufacturing capacity with as area of 12000 m2 which is 8000 m2 floor space. ERSE KABLO is manufacturer of mainly instrumentation cables, fre resistant cables shepbuilding and marine cables, signal control cables, coaxial cables, data transmission cables and telecommunication cables. ERSE KABLO exports more than 30% of her production to England, Germany, Austria, Hungary, Romania, Bulgaria, Latvia, Russia, Georgia, Kazakhistan, Egypt, Nigeria, Iraq, Jorolan, Qatar, Kuwait and Australia

QUALITY :
ISO 9001 Quality Assuarance program implemented by our company which pays great importance to quality and quality continuity in all organizations has been certified by NQA and VDE. ERSE KABLO products are supplied in conformity with international standards along with certificates of VDE, BV, GOST-R, Fire Certificate (Russia), Turkish Loyd, RINA, RohS, TSEK and TSE. This makes erse kablo reputable company in the cable industry. Quality control of the products is fastidiously performed at our QC laboratories equipped with the most advanced testing and inspection instruments at every stage of production, specially during the final tests. We can carry out routine tests as well as following type tests at our advanced labarotories. FIRE PERFORMANCE TESTS STANDARDS OF INSTRUMEN CABLES Circuit integrity and fire resistant (CI) a) IEC 60331-21/23 b) EN 50200 / BS EN 50200 / VDE 0482-200

Fire retardance test on cable bundles a) IEC 60332-3-24 (CATEGORY C) b) BS EN 50266-2-4 c) VDE 0482-266-2-4 d) EN 50266-2-4 Flame retardance test on single cables or single insulated cores a) IEC 60332-1-2 b) BS EN 60332-1-2 c) VDE 0482-332-1-2 d) EN 60332-1-2 Smoke density test a) IEC 61034-2 b) BS EN 61034-2 c) VDE 0482-1034-2 d) EN 61034-2 Corrosivitiy of combustion gases a) IEC 60754-2 b) BS EN 50267-2-3 c) VDE 0482-267-2-3 d) EN 50267-2-3 Halogen-free test a) IEC 60754-1 b) EN 50267-2-1 c) BS EN 50267-2-1 d) VDE 0482-267-2-1

www.ersekablo.com.tr

TECHNICAL INFORMATION
IEC 60331-21/23

EN 50200

IEC 60332-3-24 (CATEGORY C)

IEC 60332-1-2

IEC 61034-2
IEC 60754-1

www.ersekablo.com.tr

TECHNICAL INFORMATION

BASIC STANDARDS IN PRODUCTION OF INSTRUMENT CABLES - EN 50288-7 - BS 5308-1 - BS 5308-2 INSULATION AND SHEATH MATERIAL STANDARDS OF INSTRUMENT CABLES - EN 50290-2-21 - EN 50290-2-23 - EN 50290-2-29 - EN 50290-2-27 - EN 50363-1 PVC INSULATION / EN 50290-2-22 PVC SHEATH POLYETHLENE INSULATION / EN 50290-2-24 POLYETHLENE SHEATH XLPE INSULATION HFFR SHEATH SILICONE INSULATION

CONDUCTOR ACCORDING TO IEC 60228; VDE 0295; EN 60228 * SOLID (CLASS 1) * STRANDED (CLASS 2) * FLEXIBLE (CLASS 5) CONDUCTOR STRUCTURE SELECTION CRITERIA A) FLEXIBILITY B) CONNECTION TYPE

TYPICAL CONSTRUCTION (NOMINAL)


Conductor Size 0,50 mm 2 0,75 mm 2 1,00 mm 2 1,30 mm 2 1,50 mm 2 2,50 mm
2

Solid mm 1x0,80 1x0,98 1x1,13 1x1,38 1x1,76

Stranded (nominal) 7x0,30 7x0,37 7x0,43 7x0,49 7x0,52 7x0,67

Diam. mm 0,9 1,1 1,3 1,50 1,6 2,0

Flexible (nominal) 16x0,20 24x0,20 32x0,20 30x0,25 50x0,25

Diam. mm 0,9 1,1 1,3 1,6 2,0

INSULATION MATERIALS 2Y 2X Y Yw H HX 2G : : : : : : : Polyethylene (PE) Cross-Linked Polyethylene (XLPE) Polyvinylcloride PVC 105 oC-PVC Halogen-Free Insulation (HFFR) Cross-Linked Halogen-Free Insulation Silicone

Insulation Materials Selection Criteria a) Electrical features b) Thermal resistance c) Inflammability d) Connection method

www.ersekablo.com.tr

TECHNICAL INFORMATION
WALL THICKNESS AND ELECTRICAL FEATURES OF INSULATION Wall thickness of insulation is selected in accordance with the following parameters: * Operation voltage (300/500 V) * Mutual Capacity (wires) (nF/km) - PVC insulation : With Overall Screened Max. 130 nF/km With Individual and Overall Screened Max. 170 nF/km - PE and XLPE insulation : With Overall Screened With Individual and Overall Screened Max. 75 nF/km Max. 100 nF/km

* Insulation resistance of insulated cores (MXKm) - PVC insulation : 100 MXKm - SILICONE insulation : 300 MXKm - PE/XLPE insulation : 5000 MXKm CORE COLOUR ENCODING a) Individually unscreened and overall screened cables CORE PAIR TRIPLE : WHITE - Each core is numbered in order : BLACK / WHITE - Each core has same number : BLACK / WHITE / RED - Each core has same number

b) Individually and overall screened cables PAIR TRIPLE : In BLACK / WHITE pairs, numbered band : In BLACK / WHITE / RED triples, numbered band

Note : Core colour encoding is also made in accordance with BS 5308 CABLE STRUCTURE DEFINITIONS CORE PAIR TRIPLE : Consists of an insulated conductor : Consists of a stranded of two cores : Consists of a stranded of three cores

SCREENING Screen is used for decreasing or preventing electrical interferences described below * Preventing intermal electrical interferences caused by adjacent line crcuits inside the cable * Preventing electrical interferences in the cable caused by external power sources (motors, energy cables, machines running on HF power, HF radio waves.) Methods of decreasing internal electrical mixing and interference *Stranding of cable pairs and triples with different steps *Individual screening of cable pairs and triples The general structure of individual screening is in the following (ISCR) -Tinned copper earth core with polyester laminated aluminum tape Types of individual screening are as follows:
PiMF TiMF : Pair In Metal Foil (PSCR) : Triple In Metal Foil (TSCR)

Methods of decreasing external electrical mixing and interference (OSCR) * Braid copper wire, polyester laminated Al tape or overall screening made of copper braid is a good option for preventing external electrical interferences. * In overall screening, materials with high conductivity should be used.

www.ersekablo.com.tr

TECHNICAL INFORMATION
GENERAL SCREENS TYPE (OSCR) (St) (C) (St)C (Cu B) ARMOURINGS a) b) c) Double Steel Band Armour (SWB) Galvanized Steel Wire Braid (Q/GSWB) Galvanized Steel Wire Armour (SWA) : : : : Polyester laminated aluminium tape + tinned copper drain wire Copper wire braid Aluminium tape + tinned copper wire braid Copper tape

Cables usually need an additional protection against mechanic effects hat may occur during laying and other works. In addition, these armours serve as earthing and screen protectors. OUTER SHEATH MATERIAL 2Y Y Y Yv Yw YY FRLS H HX : : : : : : : : : Polyethylene outer sheath PVC outer sheath Hydrocarbon resistant Polyvinylchloride Reinforced outer sheath o 105 C resistant PVC sheath Double PVC sheath Low smoke PVC sheath (LSF) Halogen-free outer sheath (HFFR/LSZH/LSOH/FRNC) HFFR cross-linked sheath (HFFR/LSZH/LSOH/FRNC/Resistant to oils and hydrocarbons)

COLOURS PREFERRED FOR OUTER SHEATHS


BLACK BLUE GREY ORANGE : : : : The best UV resistance In EX-PROOF connections Indoor applications Fire resistant applications

OTHER PROFERTIES CI : Fire resistand -fI : Flame retardant (IEC 60332-3-24) RE : Instrument cable