SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - December 2005)

Rev 2 SAIC NUMBER

SAUDI ARAMCO INSPECTION CHECKLIST


Material Receiving Insp - Portable Fire Protection Equip
PROJECT TITLE

31-Dec-05 DATE APPROVED QR NUMBER

SAIC-B-2011
WBS / BI / JO NUMBER

1-Dec-06

MECH-

CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) LAYOUT DRAWING NUMBER SCHEDULED INSPECTION DATE & TIME SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO INSPECTION LEVEL

EQUIPMENT DESCRIPTION REV. NO. PURCHASE ORDER NUMBER

EQPT CODE

SYSTEM ID.

PLANT NO.

EC / PMCC / MCC NO. QUANTITY INSP. MH's SPENT TRAVEL TIME

ACTUAL INSPECTION DATE & TIME SAUDI ARAMCO ACTIVITY NUMBER CONTRACTOR INSPECTION LEVEL

SAUDI ARAMCO USE ONLY


WORK PERMIT REQUIRED?

ITEM No. A A1 A2 A3

ACCEPTANCE CRITERIA General Requirements Manufacturing & Testing Documentation has been submitted and conforms to the applicable SA-175 Form Final Material Disposition Report was submitted & verified complete. Outstanding punch list items (pre-shipment inspection) are identified for tracking & follow-up. NCRs detail final disposition and resolution. Portable Fire Extinguishing Equipment types are one of the following per SAES-B-019, Table 1 (See Excel Sh # 2 Attached): A) Portable hand held type extinguishers (4 types) Pressurized Water 9.5 L Class A (SAMS 21-104-550). CO2 with nonmetal horn 4.5 Kg Type BC (21-102-223). Dry Chemical 12.2 Kg Class BC (hydrocarbon plant) (21-102-820). Multi-purpose Dry Chemical Class ABC (21-102-775). B) Wheeled cart type extinguisher (2 types) Dry Chem 68 Kg Type BC for hydrocarbon plants (21-106-650). CO2 with dual 23 kg (50 lb) cylinders Type BC (21-106-690) C) Twin agent Extinguishers (Unit Skid or trailer) Portable Extinguishers must be one of the types listed above Exceptions to Class 21 SA stock numbers listed above must be reviewed & approved by Chief Fire Prevention Engineer. All portable fire extinguishers are "listed" as approved by a testing authority, either Underwriters Labs (UL) or Factory Mutual (FM). Dry Chem 12.2 Kg Class BC (SAMS-21-102-840) extinguishers use Purple K (potassium bicarbonate) as the extinguishing agent. Multi-purpose Dry Chemical Class ABC (SAMS-21-02-775) extinguishers use monoammonium phosphate (extinguishing agent). Extinguisher unit mounting components are supplied with extinguishers and meet manufacturer's recommended guidelines. Two-wheel cart-type Dry Chem 68 Kg Type BC extinguishers (specified in Table 1) come with a manufacturer's cover provided. Contractor can provide a cover OR a shelter must be built. NFPA 10 Requirements (Classification, Marking, etc) Instruction manuals are provided to detail instructions & cautions for extinguisher installation, operation, inspection, & maintenance. Extinguisher operating instructions are located on the front of the extinguisher & are clearly visible (with manufacturer's label). Extinguisher Classification Labels (on front) are as follows: A) Letters (A, B, C, D) show fire class extinguisher effectiveness. B) Class A & B are preceded by a rating number (effectiveness). Extinguisher Labels such as Hazardous material id system, six-year maintenance & hydrotest labels are attached, but not on front. Markings located on front of fire extinguisher shells are of adequate size & form to permit easy reading (legibility) at 1 meter. Pictorial concept markings combine extinguisher use & nonuse on a single label. Fire extinguishers suitable for more than one fire class are identified by multiple symbols in a horizontal sequence.

REFERENCE

PASS

FAIL

N/A

RE-INSP DATE

Sch Q, Att. III, Para. 3.14 Sch Q, Att. III, Para. 3.14 Sch Q, Att III, Para. 3.15

A4

SAES-B-019, Para. 4.1

A5 A6 A7 A8 A9

SAES-B-019 Para. 4.2 SAES-B-019 Para. 4.2 SAES-B-019 Para 4.2 SAES-B-019 Para 4.2 SAES-B-019 Para 4.5 SAES-B-019 Para 4.6

A10 B B1 B2 B3 B4 B5

NFPA 10, Para. 1.5.16 NFPA 10, Para. 1.5.11 NFPA 10, Para. 1.5.1 NFPA 10, Para. 1.5.11 NFPA 10, Annex B NFPA 10, Annex B

B6

Page 1 of 4

SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - December 2005)

Rev 2 SAIC NUMBER

SAUDI ARAMCO INSPECTION CHECKLIST


Material Receiving Insp - Portable Fire Protection Equip
PROJECT TITLE

31-Dec-05 DATE APPROVED QR NUMBER

SAIC-B-2011
WBS / BI / JO NUMBER

1-Dec-06

MECH-

CONTRACTOR / SUBCONTRACTOR

ITEM No.

ACCEPTANCE CRITERIA Fire extinguisher markings (label, tag, stencil, etc) attached provide the following information: A) Contents product name as it appears on the MSDS. B) Listing of hazardous material identification per HMIS C) Listing of hazardous material in excess of 1 percent of contents. D) Listing of each chemical in excess of 5 percent of contents. E) Information (hazard of agents) per MSDS. F) Manufacturer's name, mailing address & phone number Decals applied are durable & resistant to color fading Color separation identification for markings is as follows: A) Picture symbol objects are white. B) Background borders are white. C) Background for "YES" symbols is blue. D) Background for symbols with slash mark ("NO") is black. E) Class of fire letters and wording are black. F) Slash mark for black background symbols are red.

REFERENCE

PASS

FAIL

N/A

RE-INSP DATE

B7

NFPA 10, Para. 1.6

B8

NFPA 10, Annex B

Specific Inspection Points for Portable hand type extinguishers (4) as applicable Pressurized Water 9.5L (2.5 gallon) Class A (21-104-550): A) Storage area is not exposed to direct sunlight or corrosive atmospheres or in environments exceeding 120F. B) Extinguisher mounting brackets or shelves are available. C) Gauge reading is 95-100 psi or indicates full. D) Gauge and glass is undamaged. E) Operating instructions are legible and facing outward. F) Safety pin and seal are intact. G) No sign of physical damage or corrosion exists. H) Hose is free from cracks and cuts. i) Nozzle is clear and not plugged. J) Hydrotest date from manufacturer is shown on label. K) Inspection tag exists showing last inspection date. CO2 4.5 Kg (10 lb) Class BC Extinguisher (SAMS 21-102-223): A) Storage area is not exposed to direct sunlight or corrosive atmospheres or in environments exceeding 120F. B) Extinguisher mounting brackets or shelves are available. C) Not sign of physical damage or corrosion exists. D) Operating instructions are legible and facing outward. E) Safety pin and seal are intact. F) Horn is nonmetallic, clear and unplugged. G) Hydrotest date from manufacturer is shown on label. H) Weigh cylinder(s) to determine if fully charged. i) Inspection tag exists showing last inspection date. Dry Chemical 12.2 Kg Class BC (SAMS-21-102-840) & the Multipurpose Dry Chemical Class ABC (21-102-775): A) Storage area is not exposed to direct sunlight or corrosive atmospheres or in environments exceeding 120F. B) Extinguisher mounting brackets or shelves are available. C) Not sign of physical damage or corrosion exists. D) Operating instructions are legible and facing outward. E) Safety pin and seal are intact. F) CO2 cartridge disc is intact, weigh cartridge to check for leaks. G) Cap gasket is in good condition. H) Puncture lever operates freely. i) Nozzle is clear and unplugged. J) Dry chemical level and type is correct with no caking. K) Hydrotest date from manufacturel is shown on label. L) Inspection tag exists showing last inspection date.

C1

GI-1781.001, Supplement Section 7.0

C2

GI-1781.001, Supplement Section 8.0

C3

GI-1781.001, Supplement Section 9.0

Page 2 of 4

SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - December 2005)

Rev 2 SAIC NUMBER

SAUDI ARAMCO INSPECTION CHECKLIST


Material Receiving Insp - Portable Fire Protection Equip
PROJECT TITLE

31-Dec-05 DATE APPROVED QR NUMBER

SAIC-B-2011
WBS / BI / JO NUMBER

1-Dec-06

MECH-

CONTRACTOR / SUBCONTRACTOR

ITEM No. C4 D

ACCEPTANCE CRITERIA Portable Halon Fire Extinguishers are no longer allowed (ozone depletion) & must be replaced with an approved type extinguisher. Wheeled cart type extinguisher (2 types) Dry Chem 68 Kg Type BC (SAMS-21-106-650): A) Storage area is not exposed to direct sunlight or corrosive atmospheres or in environments exceeding 120F. B) Manufacturer weather cover* (See 1G) is in good condition. C) Wheels turn freely & tires are inflated properly in good condition. E) Tamper seal and safety pin are intact. F) Nitrogen pressure gauge reads full (at least 1600 psi). G) Extinguisher has no obvious damage or corrosion. H) Rubber hose is coiled properly and in good condition. i) Nozzle moves freely, is in holder, unplugged & in good condition. J) Dry chemical level and type is correct with no caking. K) Cap gasket is in good condition L) Bursting disc is intact. M) Hydrotest date from manufacturel is shown on label. N) Inspection tag exists showing last inspection date. CO2 with dual 23 kg cylinders Type BC (SAMS-21-106-690): A) Storage area is not exposed to direct sunlight or corrosive atmospheres or in environments exceeding 120F. B) Hose is free from cracks & cuts. C) Hose is coiled properly. D) Tamper seal and safety pin are intact. E) Wheels rotate freely. F) Tires are properly inflated and in good condition G) Manufacturer's weather cover is in good condition. H) No obvious corrosion or physical damage exists. i) Hydrotest date from manufacturel is shown on label. J) Inspection tag exists showing last inspection date. Twin agent Extinguishers (Unit Skid or trailer) Inspect the Twin Agent Unit Skid or Trailer Extinguisher: A) Storage area is not exposed to direct sunlight or corrosive atmospheres or in environments exceeding 120F. B) Unit has a Mfg's cover (or will be housed in shed, sunshade). C) No obvious corrosion or physical damage. D) Tires are properly inflated and in good condition. E) Seal and safety pin are intact. F) Hoses are free from cracks, unplugged, & in good condition. G) Dry chemical level and type is correct with no caking. H) Nitrogen pressure gauge reads at least 2000 psi. i) CO2 cartridge disc is intact. J) Foam (light water) solution is used. K) Cap gasket in good condition. L) Hydrotest date from manufacturer is shown on label. M) Inspection tag exists showing last inspection date. GI-1781.001 General Requirements before Service All new fire extinguishers are delivered to Local Fire Control Unit to be inspected, commissioned, tagged, & numbered prior to service GI1781 Checklists above are used by SA Fire Control Unit. Contractor has checked all equipment before delivery to SA Extinguishers are kept packaged to prevent corrosion & fouling with corrosive dusts until such time for mixing extinguishing agents. SA Fire Control Unit is notified when Materials arrive.

REFERENCE GI-1781.001, Section 4.9

PASS

FAIL

N/A

RE-INSP DATE

D1

GI-1781.001, Supplement Section 11.0

D2

GI-1781.001, Supplement Section 12.0

E1

GI-1781.001, Supplement Section 12.0

F1

GI-1781.001, Section 5.10.1

F2

GI-1781.001, Supplement 1, 2

Page 3 of 4

SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - December 2005)

Rev 2 SAIC NUMBER

SAUDI ARAMCO INSPECTION CHECKLIST


Material Receiving Insp - Portable Fire Protection Equip
PROJECT TITLE

31-Dec-05 DATE APPROVED QR NUMBER

SAIC-B-2011
WBS / BI / JO NUMBER

1-Dec-06

MECH-

CONTRACTOR / SUBCONTRACTOR

ITEM No. F3

ACCEPTANCE CRITERIA All Extinguishing Agents (potassium bicarbonate, monoammonium phosphate & other approved chemicals) are checked during receipt. No damage to manufacturer's packaging (containers, bags) exists.

REFERENCE GI-1781.001, Section 5

PASS

FAIL

N/A

RE-INSP DATE

REMARKS: REFERENCE DOCUMENTS: 1- Saudi Aramco GI-1781.001 -- Inspection, Test, and Maintenance of Fire Protection Equipment, 25 May 2002 2- SAES-B-019 -- Portable, Mobile and Special Fixed Firefighting Equipment, (15 March 2006) 3- NFPA 10 -- Standard for Portable Fire Extinguishers, 2002 Edition

Contractor / Third-Party
Construction Representative*
Work is Complete and Ready for Inspection: Name, Initials and Date: Name, Initials and Date:

Saudi Aramco
PMT Representative
T&I Witnessed QC Record Reviewed Work Verified

QC Inspector
Performed Inspection Name, Initials and Date: Work / Rework May Proceed

PID Representative
T&I Witnessed Name, Initials and Date: QC Record Reviewed Work Verified

QC Supervisor
Quality Record Approved: Name, Sign and Date: *Person Responsible for Completion of Quality Work / Test

Proponent and Others


Name, Organization, Initials and Date: T&I Witnessed QC Record Reviewed Work Verified

Y = YES

N = NO F = FAILED