NEW CTX CONTACTORS

Essential equipment
for all your
requirements

9 A TO 310 A THREE-POLE
INDUSTRIAL CONTACTORS

CTX three-pole
industrial
contactors,
a sense
of family

The new range of CTX


contactors provides safe
and effective control,
monitoring and protection
of circuits. It can be used
for electricity distribution
applications for both
commercial and industrial
buildings.
This robust range is
an addition that fits in
perfectly with the Legrand
circuit breaker offer (DPX
or DX-MA).

An entire range ....................................................................................................... p. 2

CTX-1 three-pole contactors ....................................................................... p. 4

CTX-2 three-pole contactors ....................................................................... p. 6

RTX-1 and RTX-2 thermal relays............................................................. p. 8

CTX-C three-pole contactors .................................................................... p. 10

Catalogue pages .................................................................................................. p. 12

CONTENTS

CTX industrial contactors,


a comprehensive range to choose from
The range of three-pole industrial contactors can be combined with additional
functions (thermal relays, auxiliary contact blocks and interlocking accessories)
that are specially designed to cover the most common applications. There are
also special CTX-C contactors for controlling capacitor banks for reactive energy
compensation.

CTX-1
Three-pole contactors
9 A to 105 A - AC 3

CTX-2
Three-pole contactors
150 A to 310 A - AC 3

Front-mounting
auxiliary
contact blocks

Side-mounting
auxiliary
contact blocks

CTX-1

310A

CTX-2

Control voltage and

250A

Control voltage 24 V , 110 V , 220 V , 400 V - 50/60 Hz


185A

205A

150A

9A

12A

18A

25A 32A

Up to 4 auxiliary contact
blocks per contactor

40A

50A

65A

80A

95A

105A

Up to 6 auxiliary contact
blocks per contactor

Up to 8 auxiliary contact
blocks per contactor

RTX-1, RTX-2
Thermal relays for CTX-1
and CTX-2 contactors

CTX -C
Three-pole contactors
12.5 kVAR to 70 kVAR

CTX-C
70 kVAR

Control voltage 110 V , 230 V , 440 V


55 kVAR
45 kVAR

30 kVAR
20 kVAR
16,7 kVAR
12,5 kVAR

Equipped with discharge resistors and auxiliary contact block (1 NO + 1 NC)

CTX-1: flexibility,
easy wiring and safety
Numerous combinations for a wide range of applications, from 9 A to 105 A.
Safety, with protected screw terminals, and flexibility for your configurations
with front or side-mounting auxiliary contact blocks
5

1
Side-mounting
auxiliary
contact block

4
6
4
Front-mounting
auxiliary
contact block

Front and side-mounting auxiliary


contact blocks
Up to 4 blocks for 40 A ratings
Up to 6 blocks for 50 to 60 A ratings

> Flexibility

9jVa[gZfjZcXnXd^ah!
24 VA to 400 VA
GZkZgh^WaZh^YZ"bdjci^c\
auxiliary contact
IZgb^cVahXdbeVi^WaZl^i]
all types of cable
Side-mounting auxiliary contact block:
reversible, with dual marking

> Time saving


:Vhnl^g^c\YjZidXaZVg
terminal marking
8d^al^i](iZgb^cVah[dg
easier wiring and tap-off
HcVe"dc[gdci"bdjci^c\
auxiliary contact
9>CgV^abdjci^c\jeid
65 A rating

Easy wiring due to


clear terminal marking

Screw or cage terminals depending on


rating of the contactor. Compatible with all
types of cable

Front-mounting auxiliary contact block:


quick, simple snap-on mounting

> Safety

I]ZhXgZliZgb^cVah
are protected against
accidental contact
>ciZgadX`^c\VXXZhhdg^Zh

Screw terminals protected against


accidental contact

Mechanical or electrical interlocking


for various configurations

CTX-2:
even greater adaptability
Safety, with protected screw terminals, and adaptability to specific applications
with AC or DC control circuits. Fits in perfectly with the CTX-1 family of contactors

1
Integrated auxiliary
contact block
(1N/O + 1 N/C)
for all ratings

Side-mounting auxiliary contact blocks


Up to 8 blocks per contactor

> Flexibility
9jVa[gZfjZcXnXd^ah!
230 VA and 400 VA
or electronic modules,
220 V to 440 VA /=
GZkZgh^WaZh^YZ"bdjci^c\
auxiliary contact
8dccZXi^dck^VXdccZXi^dc
plate suitable for the type
of cable

> Time saving

Side-mounting auxiliary contact block:


reversible, with dual marking

Connection via connection plate

:Vhnl^g^c\YjZidXaZVg
terminal marking

Easy wiring due to


clear terminal marking

> Safety

I]ZhXgZliZgb^cVah
are protected against
accidental contact
BZX]Vc^XVa^ciZgadX`^c\
accessories
Screw terminals protected against
accidental contact

Mechanical interlocking for


various configurations

RTX-1 & RTX-2 thermal relays


safe, effective protection
Safe and easy to use, these provide effective protection against normal,
balanced overloads and against long starting times. They are very reliable,
compensate the ambient temperature between -25 C and +60 C and operate
with no change in their characteristics up to an altitude of 3000 m

> Safe and easy to use

>ciZ\gViZYiZhiWjiidcVcY
indicator

Test pushbutton and trip indicator integrated


on the front panel of the unit

> Flexibility

;^mY^gZXiandcidi]Z
contactor or DIN rail

Relay easy to fix directly on the


contactor

or separately on DIN rail (depth 35 mm)


using a special base

> Adaptability to
different types of
application

KVg^djhdeZgVi^c\bdYZh

Function switch:
manual reset; manual reset with stop

Function switch:
automatic reset; automatic reset with stop

CTX-C: solution specially for


capacitor banks
Specially designed to reduce current peaks when capacitor banks are
XdccZXiZY!WnbZVchd[V[gdci"bdjci^c\WadX`Zfj^eeZYl^i]Y^hX]Vg\Z
resistors and auxiliary contacts
1
5
2

4
Front-mounting
auxiliary
contact block

10

> Flexibility

9jVa[gZfjZcXnXd^ah!
110 VA to 440 VA
IZgb^cVahXdbeVi^WaZl^i]
all types of cable

Integrated dual frequency control coils


Available in 110 VA , 230 VA , 440 VA

> Time saving


:Vhnl^g^c\YjZidXaZVg
terminal marking
8d^ahl^i](iZgb^cVah[dg
easier wiring and tap-off
HcVe"dc[gdci"bdjci^c\
auxiliary contact
C$D C$8egZ[VWg^XViZY
auxiliary contact

Discharge resistors.
Wired directly on the terminals

Screw or cage terminals depending on


rating of the contactor. Compatible with all
types of cable

Front-mounting auxiliary contact block:


quick, simple snap-on mounting

11

> Safety

I]ZhXgZliZgb^cVah
are protected against
accidental contact
BZX]Vc^XVa^ciZgadX`^c\
accessories
Screw terminals protected against
accidental contact

CTX-1 contactors

9 A to 105 A three-pole industrial contactors

293 04

293 74

294 04

294 34

Technical characteristics (p. 16)


Dimensions (p. 24)
Three-pole contactors equipped with control coil
Screw terminals protected against accidental contact in accordance with VDE 0106 T.100. VBG4
IP 20 for 9 A to 18 A ratings
IP 10 for 25 A to 105 A ratings
Can be fitted with auxiliary contact blocks for front or side mounting: up to 4 blocks for 9 A to 40 A ratings and up to 6 blocks for 50 A to 105 A
ratings
Conform to standards IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1
Pack

Cat.Nos

CTX-1 contactors

Pack

Three-pole contactors
Control circuit: 50/60 Hz AC
9A
With integrated auxiliary contact
Power terminals: screw terminals
Max. operating
current AC 3

12

1
1
1
1
1
1
1
1

293 00
293 02
293 04
293 05
293 10
293 12
293 14
293 15

1
1
1
1
1
1
1
1

293 20
293 22
293 24
293 25
293 30
293 32
293 34
293 35

1
1
1
1
1
1
1
1

293 50
293 52
293 54
293 55
293 60
293 62
293 64
293 65

1
1
1
1

293 70
293 72
293 74
293 75

Integrated
Control Voltage auxiliary contact

9A
1 NO
24 VA
9A
1 NO
110 VA
9A
1 NO
230 VA
9A
1 NO
400 VA
9A
1 NC
24 VA
9A
1 NC
110 VA
9A
1 NC
230 VA
9A
1 NC
400 VA
12 A
With integrated auxiliary contact
Power terminals: screw terminals
12 A
1 NO
24 VA
12 A
1 NO
110 VA
12 A
1 NO
230 VA
12 A
1 NO
400 VA
12 A
1 NC
24 VA
12 A
1 NC
110 VA
12 A
1 NC
230 VA
12 A
1 NC
400 VA
18 A
With integrated auxiliary contact
Power terminals: screw terminals
18 A
1 NO
24 VA
18 A
1 NO
110 VA
18 A
1 NO
230 VA
18 A
1 NO
400 VA
18 A
1 NC
24 VA
18 A
1 NC
110 VA
18 A
1 NC
230 VA
18 A
1 NC
400 VA
25 A
Power terminals: cage terminals
25 A
24 VA
25 A
110 VA
25 A
230 VA
25 A
400 VA

Cat.Nos

CTX-1 contactors (continued)


32 A
Power terminals: cage terminals

Dimensions

Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1

Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1

Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1

Size 2
Size 2
Size 2
Size 2

1
1
1
1

293 80
293 82
293 84
293 85

1
1
1
1

293 90
293 92
293 94
293 95

1
1
1
1

294 00
294 02
294 04
294 05

1
1
1
1

294 10
294 12
294 14
294 15

1
1
1
1

294 20
294 22
294 24
294 25

1
1
1
1

294 30
294 32
294 34
294 35

1
1
1
1

294 40
294 42
294 44
294 45

Max. operating
current AC 3

Control Voltage

Dimensions

32 A
32 A
32 A
32 A

24 VA
110 VA
230 VA
400 VA

Size 2
Size 2
Size 2
Size 2

40 A
Power terminals: cage terminals
40 A
24 VA
40 A
110 VA
40 A
230 VA
40 A
400 VA
50 A
Power terminals: cage terminals
50 A
24 VA
50 A
110 VA
50 A
230 VA
50 A
400 VA
65 A
Power terminals: cage terminals
65 A
24 VA
65 A
110 VA
65 A
230 VA
65 A
400 VA
80 A
Power terminals: cage terminals
80 A
24 VA
80 A
110 VA
80 A
230 VA
80 A
400 VA
95 A
Power terminals: cage terminals
95 A
24 VA
95 A
110 VA
95 A
230 VA
95 A
400 VA
105 A
Power terminals: cage terminals
105 A
24 VA
105 A
110 VA
105 A
230 VA
105 A
400 VA

Size 3
Size 3
Size 3
Size 3

Size 4
Size 4
Size 4
Size 4

Size 4
Size 4
Size 4
Size 4

Size 4
Size 4
Size 4
Size 4

Size 5
Size 5
Size 5
Size 5

Size 5
Size 5
Size 5
Size 5

CTX-1 contactors

auxiliary contacts, accessories, replacement coils

297 12

297 14

297 16

297 00

RTX-1 thermal relays


For CTX-1 industrial contactors

294 58

Technical characteristics (p. 16)


Dimensions (p. 24)
Pack

Cat.Nos

Auxiliary contact blocks


For CTX-1 contactors
Screw terminals
Front mounting

10
10
10
10

Type of contact

297 12 1 NO
297 13 1 NC
Side mounting
297 14 2 NO
297 15 1 NO + 1 NC

294 94

Technical characteristics (p. 20)


Dimensions (p. 26)
Thermal protection against normal overloads
Residual current protection against unbalanced overloads
Protection against long starting times
Ambient temperature compensation between -25 C and 60 C
Front test push-button
Trip indication
Independent double break auxiliary contacts (1 NO + 1 NC)
Function switch: manual reset; manual reset and stop; automatic reset
with stop; automatic reset without stop
Pack

Cat.Nos

For 9 A to 40 A CTX-1 contactors


Class 10 A

Interlocking accessories

5
5

For CTX-1 contactors


For 9 A to 105 A contactors
297 16 Mechanical interlock
297 17 Mechanical/electric interlock
2 x NC contacts

Terminal shields
1
1
1
1

For CTX-1 contactors


297 18 For 25 A and 32 A contactors (kits of 8 terminal
shields)
297 19 For 40 A contactors (kits of 6 terminal shields)
297 20 For 50 A and 80 A contactors (kits of 8 terminal
shields)
297 21 For 95 A and 105 A contactors (kits of 8 terminal
shields)

Replacement coils
For CTX-1 contactors
For 9 A to 18 A contactors
Control Voltage
(50/60 Hz)

5
5
5
5

297 00
297 01
297 02
297 03

5
5
5
5

297 04
297 05
297 06
297 07

5
5
5
5

297 08
297 09
297 10
297 11

24 VA
110 VA
230 VA
400 VA
For 25 A to 40 A contactors
24 VA
110 VA
230 VA
400 VA
For 50 A to 105 A contactors
24 VA
110 VA
230 VA
400 VA

Thermal relays

1
1
1
1
1
1
1
1
1
1
1
1
1
1

294 58
294 59
294 60
294 61
294 62
294 63
294 64
294 65
294 66
294 67
294 68
294 69
294 70
294 71

1
1
1
1
1
1
1

294 72
294 73
294 74
294 75
294 76
294 77
294 78

Adjustment range
I min. (A)
I max. (A)

Integrated auxiliary
contacts

0.65
1.1
1 NO + 1 NC
1
1.5
1 NO + 1 NC
1.3
1.9
1 NO + 1 NC
1.8
2.7
1 NO + 1 NC
2.5
4
1 NO + 1 NC
4
6.3
1 NO + 1 NC
5.5
8.5
1 NO + 1 NC
8
12
1 NO + 1 NC
10
16
1 NO + 1 NC
14.5
18
1 NO + 1 NC
17.5
22
1 NO + 1 NC
21
26
1 NO + 1 NC
25
32
1 NO + 1 NC
30
40
1 NO + 1 NC
For 50 A to 105 A CTX-1 contactors
Class 10
24
32
1 NO + 1 NC
30
43
1 NO + 1 NC
42
55
1 NO + 1 NC
54
65
1 NO + 1 NC
64
82
1 NO + 1 NC
78
97
1 NO + 1 NC
90
110
1 NO + 1 NC

Dimensions

Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1
Size 1

Size 2
Size 2
Size 2
Size 2
Size 2
Size 2
Size 2

Fixing accessory

1
1

For RTX-1 thermal relays


Mounting on 35 mm DIN rail
294 94 Separate fixing base for Cat.Nos 294 58 to 294 71
294 95 Separate fixing base for Cat.Nos 294 72 to 294 78

13

CTX-2 contactors

CTX-2 contactors

150 A to 310 A three-pole industrial contactors

295 04

auxiliary contacts, accessories, replacement coils

295 24

Technical characteristics (p. 18)


Dimensions (p. 25)

Technical characteristics (p. 18)


Dimensions (p. 25)

Three-pole contactors equipped with control coil


Screw terminals protected against accidental contact in accordance with
VDE 0106 T.100. VBG4
Supplied with auxiliary contact block Cat.Nos 297 15 (1 NO + 1 NC)
Can be fitted with up to 8 auxiliary contact blocks for side mounting
Conform to standards IEC/EN 60947-1, IEC/EN 60947-4-1
Pack

Cat.Nos

1
1
1
1

295 00
295 02
295 04
295 05

295 10
295 12
295 14
295 15

Pack

Max. operating
current AC 3

150 A
150 A
150 A
150 A

Control Voltage

Integrated auxiliary
contact
Dimensions

1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC

Size 1
Size 1
Size 1
Size 1

185 A
Connect using connection plate
185 A
1 NO + 1 NC
24 VA
185 A
1 NO + 1 NC
110 VA
185 A
1 NO + 1 NC
230 VA
185 A
1 NO + 1 NC
400 VA

Size 1
Size 1
Size 1
Size 1

24 VA
110 VA
230 VA
400 VA

Cat.Nos

Auxiliary contact blocks


For CTX-2 contactors
For combination of max. 2 blocks
Side mounting
Screw terminals
Max. 1 additional block per contactor (in addition to
that supplied with the device)

CTX-2 contactors
Three-pole contactors
Control circuit: 50/60 Hz AC
150 A
Connect using connection plate

1
1
1
1

297 61

297 14

Type of contact

10
10

297 14 2 NO
297 15 1 NO + 1 NC

10
10
10

For combination of more than 2 blocks


Side mounting
Screw terminals
297 58 2 NO
297 59 1 NO + 1 NC
297 60 2 NC

Interlocking accessories

1
1

For CTX-2 contactors


For 150 A to 310 A contactors
297 61 Horizontal mechanical interlock
297 62 Vertical mechanical interlock (not UL)

Single pole terminal shield


CTX-2 contactors with electronic control
Three-pole contactors
Control circuit: 50/60 Hz AC or DC
205 A
Connect using connection plate
1
1
1
1

1
1
1
1

1
1

14

295 20
295 22
295 24
295 25

295 30
295 32
295 34
295 35

295 42
295 44

Max. operating
current
AC 3

205 A
205 A
205 A
205 A

Control Voltage

24 - 28 VA/ =
110 - 127 VA/ =
230 - 250 VA/ =
380 - 415 VA/ =

1
1

Integrated auxiliary
contact
Dimensions

1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC

250 A
Connect using connection plate
250 A
24 - 28 VA/ = 1 NO + 1 NC
250 A
110 - 127 VA/ = 1 NO + 1 NC
250 A
230 - 250 VA/ = 1 NO + 1 NC
250 A
380 - 415 VA/ = 1 NO + 1 NC
310 A
Connect using connection plate
310 A
110 - 127 VA/ = 1 NO + 1 NC
310 A 230 - 250 VA/ = 1 NO + 1 NC

Size 2
Size 2
Size 2
Size 2

Replacement coils for CTX-2 contactors


150 A to 185 A contactors
1
1

Control Voltage (50/60 Hz)

297 32 230 VA
297 33 400 VA

Control assembly for 205 to 310 A


contactors

Size 2
Size 2
Size 2
Size 2

Size 2
Size 2

For CTX-2 contactors


For 150 A and 185 A contactors
297 66 IPXXB terminal shield
For 205 A, 250 A and 310 A contactors
297 67 IPXXB terminal shield (kit of 3 terminal shields)

Comprises two elements: coil + module


Replacement coils
1
1
1
1

Control Voltage (50/60 Hz)

297 36 220 - 250 VA/ =


297 37 380 - 415 VA/ =
Electronic modules
297 47 220 - 250 VA/ =
297 48 380 - 415 VA/ =

RTX-2 thermal relays

CTX-C CONTACTORS

For CTX-2 thermal contactors

Our solution
for connecting
capacitor banks
installations

294 86

294 82

>>>

Technical characteristics (p. 20)


Dimensions (p. 26)
Thermal protection against normal overloads
Residual current protection against unbalanced overloads
Protection against long starting times
Ambient temperature compensation between -25 C and 60 C
Front test push-button
Trip indication
Independent double break auxiliary contacts (1 NO + 1 NC)
Function switch: manual reset; manual reset and stop; automatic reset
with stop; automatic reset without stop

Pack

Cat.Nos

Thermal relays
For 150 A to 185 A CTX-2 contactors
Class 10

1
1
1
1

1
1
1

294 82
294 83
294 84
294 85

Adjustment range
I min. (A)
I max. (A)

Integrated auxiliary
contact

63
90
1 NO + 1 NC
90
120
1 NO + 1 NC
110
140
1 NO + 1 NC
140
190
1 NO + 1 NC
For 205 A to 310 A CTX-2 contactors
Class 10
294 86
120
190
1 NO + 1 NC
294 87
175
280
1 NO + 1 NC
294 88
200
310
1 NO + 1 NC

Dimensions

Size 1
Size 1
Size 1
Size 1

Size 2
Size 2
Size 2

> Three-pole contactors from 12.5 kVAR


to 70 kVAR for capacitors banks installations
> Equipped with auxiliary contact and discharge
resistors for connecting three-phase capacitors
banks
> Control voltage: 110 VA, 230 VA et 440 VA

p. 27

15

CTX-1 contactors
technical characteristics

NStandards

NAmbient conditions

Conform to standards:

Storage temperature: - 55 C to 80 C
Operating temperature - 40 C to 60 C
Working altitude
up to 3000 m: Nominal Value
between 3000 and 4000 m: 90%Ie 80%Ue
between 4000 and 5000 m: 80%Ie 75%Ue

- IEC/EN 60947-1
- IEC/EN 60947-4-1
- IEC/EN 60947-5-1
- UL 508

NMounting position
30

30
No Variation of nominal powers
No Variation of holding and drop-out Voltage

NPower circuit characteristics


9A

12 A

18 A

25 A

32 A

40 A

50 A

65 A

80 A

95 A

Nominal thermal rating Ith Q 55C

(A)

25

25

32

45

60

60

90

110

110

140

105 A
140

Nominal operating current Ie

(A)

12

18

25

32

40

50

65

80

95

105

Nominal operating Voltage Ue

(V)

690

690

690

690

690

690

690

690

690

690

690

Nominal insulation Voltage (Ui)

(V)

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

Maximum permanent current in AC1


Frequency range
Making capacity (rms) (IEC 947)
Breaking capacity
(rms) (IEC 947)

Short-time current

25

25

32

45

60

60

90

110

110

140

140

25...400

25...400

25...400

25...400

25...400

25...400

25...400

25...400

25...400

25...400

25...400

(A)

450

450

450

550

550

550

1000

1000

1000

1280

1280

(A)

250

250

250

450

450

450

920

920

920

1050

1050

Ue = 500 V

(A)

250

250

250

450

450

450

920

920

920

1050

1050

Ue = 690 V

(A)

130

130

130

205

205

205

780

780

780

950

950

1 sec.

(A)

455

455

570

1010

1010

1265

1580

2530

2530

3300

3300

5 sec.

(A)

205

205

254

450

450

450

710

1130

1130

1485

1485

10 sec.

(A)

144

144

180

320

320

400

500

800

800

1050

1050

Ue 400 V

30 sec.

(A)

85

85

104

185

185

230

290

460

460

600

600

1 min.

(A)

60

60

74

130

130

165

205

325

325

430

430

3 min.

(A)

35

35

46

90

90

100

120

185

185

250

250

(min.)

10

10

10

10

10

10

10

10

10

10

10

Type "1" coordination


gL/gG

(A)

50

50

63

100

100

125

200

200

200

250

250

Type "2" coordination


gL-gG

(A)

25

35

35

63

63

80

100

125

125

160

200

gL-gG without welding

(A)

Recovery time

Protection against
short-circuits
Without thermal relay

(A)
(Hz)

Impedance per pole (m )


Dissipation per pole

Insulation resistance

16

10

10

25

35

35

50

80

100

100

140

160

2.35

2.35

2.41

1.28

1.28

0.95

0.85

0.86

0.86

0.76

0.76

AC-1

(W)

1.47

1.47

2.46

2.59

4.6

3.42

6.86

10.40

10.40

14.89

14.89

AC-3

(W)

0.19

0.34

0.78

0.80

1.31

1.52

2.12

3.63

5.5

6.86

8.37

Between adjacent poles (m )

>10

>10

>10

>10

>10

>10

>10

>10

>10

>10

>10

Between poles and


exposed conductive part (m )

>10

>10

>10

>10

>10

>10

>10

>10

>10

>10

>10

Between input and output (m )

>10

>10

>10

>10

>10

>10

>10

>10

>10

>10

>10

NControl circuit characteristics


AC

9 A to 18 A

25 A to 40 A

50 A to 80 A

Nominal insulation Voltage Ui

(V)

1000

1000

1000

1000

Standard Voltages Us 50 Hz

(V)

24...690

24...690

24...690

24...690
24...600

Standard Voltages Us 60 Hz

50/60 Hz coil limit Voltage

Dual frequency coil consumption

(V)

24...600

24...600

24...600

50 Hz service

xUs

0.8...1.1

0.8...1.1

0.8...1.1

0.8...1.1

60 Hz service

xUs

0.85...1.1

0.85...1.1

0.85...1.1

0.85...1.1

50 Hz closing

xUs

0.5...0.8

0.6...0.8

0.6...0.8

0.6...0.8

60 Hz closing

xUs

0.65...0.85

0.7...0.85

0.7...0.85

0.7...0.85

50 Hz opening

xUs

0.3...0.55

0.35...0.60

0.35...0.60

0.35...0.60

60 Hz opening

xUs

0.35...0.35

0.4...0.6

0.4...0.6

0.4...0.6

Holding (50 Hz/60 Hz)

(VA)

6.8/5.6

11.4/9.5

20/16.6

20/16.6

Inrush (50 Hz/60 Hz)

(VA)

53/44

120/100

245/204

245/204

(W)

2.2/1.8

3.2/2.6

5.2/4.3

5.2/4.3

Heat dissipation (50 Hz/60 Hz)


Magnetic circuit
closed

cos

0.33

0.28

0.26

0.26

Magnetic circuit open

cos

0.84

0.73

0.54

0.54

NO closing time at
energisation

(ms)

6...20

7...25

9...35

9...35

NO opening time at
de-energisation

(ms)

6...13

5...25

9...15

9...15

NO closing time at
energisation

(ms)

8...20

10...19

15...30

15...30

NO opening time at
de-energisation

(ms)

6...13

5...25

9...15

9...15

Dual frequency coil (at 50 Hz)

106 operations

Power factor

Values between + 10% Us


and - 20% Us
Holding and drop-out
times
Values at Us

Mechanical endurance

Maximum rate

95 A and 105 A

10

10

AC1 at nominal power operations/hour

1200

1200

1200

1200

AC2 at nominal power operations/hour

1000

1000

1000

750

AC3 at nominal power operations/hour

1200

1200

1200

600

AC4 at nominal power operations/hour

360

360

200

200

Dual frequency coil with no load operations/hour

3600

3600

3600

3600

17

CTX-2 contactors
technical characteristics

NStandards

NAmbient conditions

Conform to standards:

Storage temperature: - 55 C to 80 C
Operating temperature - 40 C to 60 C
Working altitude
up to 3000 m: Nominal Value
between 3000 and 4000 m: 90%Ie 80%Ue
between 4000 and 5000 m: 80%Ie 75%Ue

- IEC/EN 60947-1
- IEC/EN 60947-4-1

NMounting position
30

30
With no variation of nominal powers
With no variation of holding and dropout voltage

NPower circuit characteristics


150 A

185 A

205 A

250 A

310 A
450

Nominal thermal rating Ith 40C

(A)

250

250

315

315

Nominal operating current Ie in AC3

(A)

150

185

205

250

309

Nominal operating Voltage Ue

(V)

1000

1000

1000

1000

1000

Nominal insulation Voltage Ui

(V)

1000

1000

1000

1000

1000

Maximum permanent current in AC1

(A)

250

250

315

315

450

Frequency limits

(Hz)

25...400

25...400

25...400

25...400

25...400

Making capacity (rms)

(A)

1850

2200

2500

2500

3700

Ue 400V

(A)

1600

1850

2000

3500

3500

Ue = 500 V

(A)

1600

1850

2000

3500

3500

Ue = 690 V

(A)

1000

1200

1660

2200

2200

Ue = 1000 V

(A)

350

350

850

1100

1100

1 sec.

(A)

2500

2500

4000

5500

5500

5 sec.

(A)

2500

2500

3200

3500

3500

10 sec.

(A)

2300

2300

2400

2500

2500

30 sec.

(A)

1250

1250

1400

1600

1600

1 min.

(A)

900

900

1000

1200

1200

3 min.

(A)

600

600

750

900

900

(min.)

10

10

10

10

10

Type "1" coordination gL/gG

(A)

355

355

500

500

630

Type "2" coordination gL/gG

(A)

250

250

315

400

500

Without welding

(A)

200

200

250

315

425

(m)

0.30

0.30

0.28

0.28

0.28
56.7

Breaking capacity (rms)

Short-time current

Recovery time
Short-circuit protection by fuse
Without welding
Impedance per pole
Dissipated power

AC-1

(W)

19

19

27.7

27.7

per pole

AC-3

(W)

6.8

10.3

11.7

17.5

26.7

between adjacent poles

(m)

> 10

> 10

> 10

> 10

> 10

between poles and exposed


conductive part

(m)

> 10

> 10

> 10

> 10

> 10

between input and output

(m)

> 10

> 10

> 10

> 10

> 10

Insulation resistance

18

NControl circuit characteristics


AC

150 A

185 A

205 A

250 A

Nominal insulation Voltage Ui

(V)

1000

1000

1000

1000

1000

Standard Voltages Us (50/60 Hz)

(V)

24...690

24...690

24...690

24...690

24...690

Operating Voltage

xUs

0.8...1.1

0.8...1.1

0.8...1.1

0.8...1.1

0.8...1.1

Trip Voltage

xUs

0.4...0.6

0.4...0.6

0.4...0.6

0.4...0.6

0.4...0.6
-

Voltage limits

Dual frequency coil


consumption

Power factor

Holding and drop-out times


at Us

Held closed
(CTX-2 150 to 185 A)

50 Hz

(VA)

46

46

60

60 Hz

(VA)

38.3

38.3

50

Held open
(CTX-2 150 to 185 A)

50 Hz

(VA)

568

568

1082

60 Hz

(VA)

473

473

901

Dissipated power
(CTX-2 150 to 185 A)

50 Hz

(W)

23

23

22.2

60 Hz
CTX-2
150 to
185 A
Held closed
CTX-2
205 to
310 A
CTX-2
150 to
185 A
Held open
CTX-2
205 to
310 A
NO closing time at
energisation
NO opening time at
de-energisation

(W)

19.1

19.1

18.5

cos

0.4

0.4

0.37

cos

cos

0.6

0.6

0.6

cos

(ms)

20...25

20...25

36...40

60...70

60...70
13...17

(ms)

10...13

10...13

10...15

13...17

106 operations

10

10

10

10

10

No-load

operations/hour

2400

2400

2400

1200

1200

AC1/AC3 at nominal power

operations/hour

600

600

600

600

60

AC2 at nominal power

operations/hour

250

250

250

250

250

AC4 at nominal power

operations/hour

150

150

150

150

150

Mechanical endurance

Maximum rate

DC

205 A

250 A

Nominal insulation Voltage Ui

(V)

1000

1000

1000

Standard Voltages Us

(V)

24...500

24...500

24...500

Voltage limits
Consumption

Holding and drop-out


times at U
Mechanical endurance

Maximum rate

310 A

310 A

Operating Voltage

xUs

0.8...1.1

0.8...1.1

0.8...1.1

Trip Voltage

xUs

0.35...0.5

0.4...0.6

0.4...0.6

Holding

(W)

3.5

3.5

3.5

Inrush

(W)

350

350

350

NO closing time at
energisation

(ms)

60,..70

60,..70

60,..70

(ms)

13...17

13...17

13...17

10 6 operations

10

10

10

No-load operations/hour

1200

1200

1200

AC3 at nominal power operations/hour

600

600

600

AC4 at nominal power operations/hour

150

150

150

NO opening time at
de-energisation

19

RTX-1 and RTX-2 thermal relays


technical characteristics

NStandards

NAmbient conditions

Conform to standards:

Storage temperature: - 40 C to 70 C
Operating temperature - 25 C to 60 C
Working altitude
up to 3000 m: with no change in characteristics
Relative humidity: 98%
Protective treatment: Tropicalised

- IEC/EN 60947-4-1
- IEC/EN 60947-5-1

NMounting position
-30
-90

-9
0

+9
0

NPower circuit and control circuit characteristics


RTX-1
For CTX contactors:

RTX-2

9 to 40 A

50 to 105 A

150 to 185 A

205 to 310 A

10 A
0.65...40
CTX 1, 9 to 40 A

10 A
24...110
CTX 1, 50 to 105 A

10 A
63...190
CTX 2, 150 to 185 A

10 A
120...400
CTX 2, 205 to 310 A

GENERAL
Class
Adjustment range
Suitable for

(A)

POWER CIRCUIT
Nominal insulation Voltage
(IEC 947-4) U
Frequency limits

Cabling capacity

(V)

690

1000

1000

1000

(Hz)

0...400

0...400

0...400

50...60

Flange - solid wire

(mm2)

16

50

120

Flange - flexible wire

(mm2)

10

50

120

With flat terminal

(mm)

25 x 5

Loop (solid)

(mm)
(Nm)

2.5

4.5

6.5

30 x 10
23

Tightening torque
CONTROL CIRCUIT
Nominal insulation Voltage
(IEC 947-4) Ui
Nominal thermal rating Ith
AC-15 - Ue-Ie
Nominal Voltage
and current
DC-13 - Ue-Ie
Use according to Ul and CSA
gL fuse
Cabling capacity
Tightening torque

20

(V)

690

(A)
(V - A)
(V - A)

10
110/120 - 3; 220/240 - 2; 380/415 - 1; 480/500 - 0.8; 660/690 - 0.3
24 - 2; 48 - 1.4; 110 - 0.6; 250 - 0.3; 440 - 0.1
B600 - Q600
10
2.5
0.8

(A)
(mm2)
(Nm)

+30

RTX-1 thermal relays

RTX-2 thermal relays

NTripping curves

NTripping curves

tripping curves

tripping curves

RTX-1 Class 10 for 9 A to 40 A CTX-1 contactors

RTX-2 Class 10 for 150 A to 185 A CTX-2 contactors


Tripping time (s)

Tripping time (s)


10000
8000
6000

10000
8000
6000

4000

4000

2000
1500

2000
1500

1000
800
600

1000
800
600

Single phase
Cold state

400
200

200
Three-phase
Cold state

100
80
60

40

20

20

10
8
6

10
8
6

Three-phase
Hot state

2
1.5

1.2

Three-phase
Hot state

2
1.5
I/Ir

Three-phase
Cold state

100
80
60

40

Single phase
Cold state

400

10 12

1.05

I/Ir
1

1.2

1.05

Multiples of the current setting

10 12

Multiples of the current setting

RTX-1 Class 10 for 50 A to 105 A CTX-1 contactors

RTX-2 Class 10 for 205 A to 310 A CTX-2 contactors

Tripping time (s)

Tripping time (s)

10000
8000
6000

10000
8000
6000

4000

4000

2000
1500

2000
1500

1000
800
600

1000
800
600

Single phase
Cold state

400
200

400
200

Three-phase
Cold state

100
80
60

Three-phase
Cold state

100
80
60

40

40

20

20

10
8
6

10
8
6
4

4
Three-phase
Hot state

2
1.5
1

Single phase
Cold state

I/Ir
1

1.2

1.05

Three-phase
Hot state

2
1.5
3

Multiples of the current setting

10 12

I/Ir
1

1.2

1.05

10 12

Multiples of the current setting

21

CTX-1 and CTX-2 contactors

NCoordination of contactors / circuit breakers


According to IEC 60947-2
Type 2 coordination
Three-pole combination

Motor

Circuit breaker

Thermal relay

Test

Nominal
power
(kW)

Nominal
current
(A)

Type

Nominal
current
(A)

Magnetic
threshold
(A)

Cat.Nos

Type

Type

Adjustment
range
(A)

Cat.Nos

Conditional
short-circuit
current
Iq (kA)

0.75
1.1
1.5
2.2
2.5
3
3.7
4
5.5
6.3
7.5
10
11
12.5
15
16
18.5
20
22
25
30
31.5

1.9
2.7
3.5
5
5.7
6.7
8
8.5
11
13
15
20
22
25
29
31
35
38
41
47
57
59

DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA
DX-MA

2.5
4
4
6.3
6.3
10
10
10
12.5
16
16
25
25
25
40
40
40
40
63
63
63
63

32
50
50
80
80
125
125
125
160
200
200
320
320
320
500
500
500
500
880
880
880
880

071 62
071 63
071 63
071 64
071 64
071 52
071 52
071 52
071 53
071 54
071 54
071 55
071 55
071 55
071 56
071 56
071 56
071 56
071 60
071 60
071 60
071 60

CTX-1 9 A
CTX-1 9 A
CTX-1 9 A
CTX-1 9 A
CTX-1 9 A
CTX-1 12 A
CTX-1 12 A
CTX-1 12 A
CTX-1 25 A
CTX-1 25 A
CTX-1 25 A
CTX-1 25 A
CTX-1 25 A
CTX-1 25 A
CTX-1 32 A
CTX-1 32 A
CTX-1 40 A
CTX-1 40 A
CTX-1 50 A
CTX-1 50 A
CTX-1 65 A
CTX-1 65 A

RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1

1.8 - 2.7
2.5 - 4
2.5 - 4
4 - 6.3
4 - 6.3
5.5 - 8.5
5.5 - 8.5
8 - 12
8 - 12
10 - 16
10 - 16
17.5 - 22
17.5 - 22
21 - 26
25 - 32
25 - 32
30 - 40
30 - 40
30 - 43
42 - 55
54 - 65
54 - 65

294 61
294 62
294 62
294 63
294 63
294 64
294 64
294 65
294 65
294 66
294 66
294 68
294 68
294 69
294 70
294 70
294 71
294 71
294 73
294 74
294 75
294 75

15
15
15
15
15
15
15
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10

Voltage
(V)
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400

Motor

22

Contactor

Circuit breaker

Contactor

Thermal relay

Voltage
(V)
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400

Test

Nominal
power (kW)

Nominal
current
(A)

Type

Nominal
current
(A)

Magnetic
threshold
(A)

Cat.Nos

Type

Type

Adjustment
range
(A)

Cat.Nos

Conditional
short-circuit
current
Iq (kA)

12.5
15
16
18.5
20
22
25
30
31.5
37
40
45
50
55
63

25
29
31
35
38
41
47
57
59
68
74
82
92
102
115

DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125
DPX-H 125

25
40
40
40
40
63
63
63
63
100
100
100
100
125
125

250
400
400
400
400
630
630
630
630
1000
1000
1000
1000
1250
1250

250 51
250 52
250 52
250 52
250 52
250 53
250 53
250 53
250 53
250 54
250 54
250 54
250 54
250 55
250 55

CTX-1 50 A
CTX-1 95 A
CTX-1 95 A
CTX-1 95 A
CTX-1 95 A
CTX-1 95 A
CTX-1 95 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-2 150 A
CTX-2 150 A

RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-2
RTX-2

24 - 32
24 - 32
24 - 32
30 - 43
30 - 43
30 - 43
42 - 55
54 - 65
54 - 65
64 - 82
64 - 82
78 - 97
78 - 97
90 - 120
90 - 120

294 72
294 72
294 72
294 73
294 73
294 73
294 74
294 75
294 75
294 76
294 76
294 77
294 77
294 83
294 83

36
36
36
36
36
36
36
36
36
36
36
36
36
36
36

Motor

Circuit breaker

Nominal
power (kW)

Nominal
current
(A)

15
16
18.5
20
22
25
30
31.5
37
40
45
50
55
63
75
90
110
132
150
160

29
31
35
38
41
47
57
59
68
74
82
92
102
115
137
164
204
238
262
282

Type

Nominal
current
(A)

Magnetic
threshold
(A)

DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 630
DPX-H 630

40
40
40
40
63
63
63
63
100
100
100
100
100
160
160
250
250
250
320
320

140 - 400
140 - 400
140 - 400
140 - 400
220 - 630
220 - 630
220 - 630
220 - 630
350 - 1000
350 - 1000
350 - 1000
350 - 1000
350 - 1000
560 - 1600
560 - 1600
900 - 2500
900 - 2500
900 - 2500
1600 - 3200
1600 - 3200

Motor

Contactor

Thermal relay

Cat.Nos

Type

Type

Adjustment
range
(A)

253 52
253 52
253 52
253 52
253 53
253 53
253 53
253 53
253 54
253 54
253 54
253 54
253 54
253 55
253 55
253 56
253 56
253 56
255 42
255 42

CTX-1 50 A
CTX-1 50 A
CTX-1 50 A
CTX-1 50 A
CTX-1 50 A
CTX-1 95 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 95 A
CTX-2 150 A
CTX-2 185 A
CTX-2 185 A
CTX-2 250 A
CTX-2 250 A
CTX-2 250 A
CTX-2 250 A

RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-2
RTX-2
RTX-2
RTX-2
RTX-2
RTX-2
RTX-2
RTX-2

24 - 32
24 - 32
30 - 43
30 - 43
30 - 43
42 - 55
54 - 65
54 - 65
64 - 82
64 - 82
78 - 97
78 - 97
90 - 120
90 - 120
110 - 140
140 - 190
175 - 280
175 - 280
175 - 280
200 - 310

Circuit breaker

Nominal
power (kW)

Nominal
current
(A)

15
16
18.5
20
22
25
30
31.5
37
40
45
50
55
63
75
90
110
132
150

27
29
34
37
40
45
53
56
65
71
78
88
98
110
129
157
188
218
244

Contactor

Type

Nominal
current
(A)

Magnetic
threshold
(A)

Cat.Nos

Type

DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 250
DPX-H 630

40
40
40
40
40
63
63
63
100
100
100
100
100
160
160
160
250
250
250

140 - 400
140 - 400
140 - 400
140 - 400
140 - 400
220 - 630
220 - 630
220 - 630
350 - 1000
350 - 1000
350 - 1000
350 - 1000
350 - 1000
560 - 1600
560 - 1600
560 - 1600
900 - 2500
900 - 2500
900 - 2500

253 52
253 52
253 52
253 52
253 52
253 53
253 53
253 53
253 54
253 54
253 54
253 54
253 54
253 55
253 55
253 55
253 56
253 56
253 56

CTX-1 50 A
CTX-1 50 A
CTX-1 50 A
CTX-1 50 A
CTX-1 50 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-1 105 A
CTX-2 150 A
CTX-2 150 A
CTX-2 185 A
CTX-2 250 A
CTX-2 250 A
CTX-2 310 A

Test
Cat.Nos

Conditional
short-circuit
current
Iq (kA)

Voltage
(V)

294 72
294 72
294 73
294 73
294 73
294 74
294 75
294 75
294 76
294 76
294 77
294 77
294 83
294 83
294 84
294 85
294 87
294 87
294 87
294 88

50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400

Thermal relay
Type

Adjustment
range
(A)

RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-1
RTX-2
RTX-2
RTX-2
RTX-2
RTX-2

24 - 32
24 - 32
24 - 32
30 - 43
30 - 43
42 - 55
42 - 55
54 - 65
64 - 82
64 - 82
64 - 82
78 - 97
90 - 110
90 - 110
110 - 140
140 - 190
175 - 280
175 - 280
175 - 280

Test
Cat.Nos

Conditional
short-circuit
current
Iq (kA)

Voltage
(V)

294 72
294 72
294 73
294 73
294 73
294 74
294 74
294 75
294 76
294 76
294 76
294 77
294 78
294 78
294 84
294 85
294 87
294 87
294 87

50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440

23

CTX-1 contactors
dimensions

NDimensions
Size 5 contactors

Size 1 contactors

126

85
7.5

75

90

117.5

73

50

81

45

4.5
5.5

35
56

Size 2 contactors

Auxiliary contacts
Cat.Nos 297 12/13

55

98

10.3

29

7.5

79

60

50

87

44.5

4.5

40

Cat.Nos 297 14/15

45

1.4

11

85

55

98

79

60

7.5

50

87

4.5

78

Size 3 contactors

Interlocking accessories
11

40
45

Size 4 contactors
116
9

90

117.5

66

5.5
56
60

24

85

CTX-2 contactors
dimensions

NDimensions
Interlocking accessories
Cat.No 297 61

Size 1 contactors
3.5

164

55

61

15.5

160

96

148.5

112
38 38

178

11.5

112

165.5

6.8
M8

45

18

10

102

Cat.No 297 62

Size 2 contactors
11.5

150
48

208

48

12

350

307

212

187

200

165

180

150

60
105

M10

120

25

51

Auxiliary contacts
Cat.Nos 297 14/15
29

44.5

10.3

25

RTX-1 thermal relays

RTX-2 thermal relays

NDimensions

NDimensions

dimensions

Size 1 thermal relays

Size 1 thermal relays


5.7

108
38 38
18

137
82.7

86

40.5

13.5

104

34.5

92.5

64

8.85

dimensions

15

M8

8.85

70

Size 2 thermal relays

36.5

42

109.7

40

57

79.7

M6
40

Size 2 thermal relays


130
48

235
48

55

135

177

130

7
22.5

26

22.5

10

M10

CTX-C contactors

12.5 kVar to 70 kVar three-pole contactors for connecting


capacitor banks

CTX-C contactors
replacement coils

297 02

Technical characteristics (p. 28)


296 04

296 64
Pack

Technical characteristics (p. 28)


Dimensions (p. 29)

Cat.Nos

CTX-C contactors
Three-pole contactors
Max. reactive power calculated for an ambient
temperature 55 C
12.5 kVAR/25 A

1
1
1

296 02
296 04
296 05

1
1
1

296 12
296 14
296 15

1
1
1

296 22
296 24
296 25

1
1
1

296 32
296 34
296 35

1
1
1

296 42
296 44
296 45

1
1
1

296 52
296 54
296 55

1
1
1

296 62
296 64
296 65

Max. reactive
power kVAR

12.5
12.5
12.5

Control Voltage

110 VA
230 VA
440 VA
16.7 kVAR/32 A
16.7
110 VA
16.7
230 VA
16.7
440 VA
20 kVAR/45 A
20
110 VA
20
230 VA
20
440 VA
30 kVAR/60 A
30
110 VA
30
230 VA
30
440 VA
45 kVAR/90 A
45
110 VA
45
230 VA
45
440 VA
55 kVAR/110 A
55
110 VA
55
230 VA
55
440 VA
70 kVAR/140 A
70
110 VA
70
230 VA
70
440 VA

Replacement coils for CTX-C contactors


For contactors 12.5 kVAR to 20 kVAR

Three-pole contactors equipped with prefabricated auxiliary contacts


and discharge resistors for connecting three-phase capacitor banks
Conform to standards: IEC/EN 60947-1, IEC/EN 60947-4-1,
IEC/EN 60947-5-1
Pack

Cat.Nos

Integrated
auxiliary contact

Dimensions

1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC

Size 1
Size 1
Size 1

1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC

Size 2
Size 2
Size 2

1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC

Size 3
Size 3
Size 3

1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC

Size 4
Size 4
Size 4

1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC

Size 4
Size 4
Size 4

1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC

Size 5
Size 5
Size 5

1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC

Size 1
Size 1
Size 1

Control Voltage
(50/60 Hz)

5
5
5
5
5
5
5
5
5

297 01 110 VA
297 02 230 VA
297 80 440 VA
For contactors 30 kVAR
297 05 110 VA
297 06 230 VA
297 81 440 VA
For contactors 45 kVAR to 70 kVAR
297 09 110 VA
297 10 230 VA
297 82 440 VA

27

CTX-C contactors
technical characteristics

NStandards

NAmbient conditions

Conform to standards:

Storage temperature: - 50 C to 80 C
Operating temperature - 25 C to 55 C (with no reduction)
Working altitude up to 3000 m: with no change in characteristics

- IEC/EN 60947-4-1
- IEC/EN 60947-5-1

NMounting position
Vertical mounting +/- 30

NPower circuit and control circuit characteristics


25 A

32 A

45 A

60 A

90 A

110 A

140 A

POWER CIRCUIT (POLES)


Nominal Voltage

(V)

690

690

690

690

690

690

690

Nominal insulation Voltages


according to IEC 947

(V)

1000

1000

1000

1000

1000

1000

1000

Thermal current

Max. operating power at 55C

(A)

25

32

45

60

90

110

140

230/240V

(kVar)

7.5

10

12.5

20

25

35

45

380/400V

(kVar)

12.5

16.7

20

30

45

55

70

660/690V

(kVar)

15

20

25

35

55

65

85

280.000

280.000

200.000

150.000

120.000

90.000

Electrical endurance

(operations) 280.000

Max. operations/hour

(operations/
hour)

350

350

350

240

150

150

150

50 Hz

(V)

24-690

24-690

24-690

24-690

24-690

24-690

24-690

60 Hz

(V)

24-600

24-600

24-600

24-600

24-600

24-600

24-600

circuit open

(VA)

45

45

48

88

191

191

198

circuit closed

(VA)

15.5

15.5

17

circuit open

(VA)

54

54

58

125

245

245

250

circuit closed

(VA)

11.5

20

20

23

circuit open

(VA)

35

35

39

110

215

215

220

circuit closed

(VA)

11

15

15

19

CONTROL CIRCUIT
Standard Voltages

Frequency

Consumption

Dual frequency 50 Hz

Dual frequency 60 Hz
INSTANTANEOUS AUXILIARY CONTACT BLOCKS
Nominal insulation Voltage Ui

(V)

100

Thermal current Ith

(A)

10

28

CTX-C contactors
dimensions

NDimensions
Size 4 contactors

Size 1 contactors

90

73

4.5

118.5

66

7.5

82.5

45

50

35

131

5.5

137.5

56

77

162

60

Size 2 contactors

Size 5 contactors
7.5

75

128.5

90

73

85.5

45

50

35

168.5

4.5

56

133
5.5

139.5
56

86

172
178.5

Size 3 contactors

60

79

40
45

7.5

90.5

55

50

4.5

66

144
150.5

EX210016 - January 2010

World Headquarters and


International Department
28, av. du Marchal-de-Lattre-de-Tassigny
87045 Limoges Cedex - France
 : + 33 5 55 06 87 87
Fax : + 33 5 55 06 74 55
www.legrandgroup.com