Pressure Relief Valve Sizing & Selection Report 19-sep-2013

Santa Cruz , Bolivia 591 (3) 355-9618 int 113 | www.prosertec-srl.com; Fax:591 (3) 311-7427 No Prpd. Chk. Appr. Quote Number:
Client: YPFB TRASPORTE SA Location: ESTACION SAMAIPATA Project: SISTEMA DE ALIVIOS Y VENTEOS VALVE ID Tag No. PSV-001 Service GLP PID No. SC-E02-PR-00-03-02 de 02 Line No. 6"-0.280-B-(V-3)-3001 End-User Ref. No.: Project Ref. No.:

Date

Revision

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

41 42 43 44 Quantity 45 1 46 GENERAL 47 Valve Type Pilot-Op, Modulating, Non-Flowing Pilot 48 Safety / Relief Safety Relief Balanced Yes 49 Nozzle Semi Bonnet Closed 50 CONNECTIONS 51 Inlet 3" Flngd. 600# RF Standard 52 Outlet 4" Flngd. 150# RF ASME B16.5 53 MATERIALS OF CONSTRUCTION 54 Body CS SA216-WCB/WCC 55 Cap CS SA516-70 56 MainValve Trim Stainless Steel 57 Seat Teflon 58 Seals Buna-N 59 Body SS A479-316 60 17-7 PH SST Trim Spring SST 61 PilotValve Seat Buna-N 62 Seals Buna-N 63 Diaphragm N/A 64 Tubing Fittings 304 SST CS CPI 65 Integral Sense NACE MR0175 (2002) No 66 67 68 69 70 SIZING / SELECTION SUMMARY 71 Valve Model No. 46312-34/S1 72 Brand Anderson Greenwood 73 Area Calculated Selected 6,308 6,733 74 (in) Data Set Orifice ASME FB, 3x4 75 Unit Required lb/hr 70010 76 Flow Rated Actual 74726,325 83029,250 77 78 Estimated Reaction Force 609,42 daN 79 Estimated Noise Level (db) 75,9 at 100-ft 80

SIZING DATA Design Code ASME Section VIII Sizing Std. API 520 Sizing Basis Blocked Discharge Fluid State at Inlet Gas / Vapor Relieving Case Pressure Relief Fluid Properties Fluid Name Propane Molecular Weight, M 47,88 Compressibility, Z 0,845 Ratio of Sp. Heats, k (Cp / Cv) 1,197 Gas Constant, C 336,9

Sizing Coefficients K, Gas Kb

Kd, Gas Kc

Unit 0,860 0,684

0,956 1,0

Required Capacity Total

Unit 70010

lb/hr

Accessories

Pressures Unit psig MAWP Operating 112 Set CDTP 150 Over Pressure 15,0 10% Constant Superimposed 0 Variable Superimposed 0 Back Pressure Built-Up 133 Total 133 Inlet Loss 4,500 3% Atmospheric (Barometric) 14,696 psia Relieving (Flowing) 175,196 psia Temperatures Unit F Operating Relieving 95 95 Design Min Design Max A 6,12 B 7,00 C 25,16 Weight 147 Valve Dimensions lb in Page : 1

Tag Notes Printed On: 25-sep-2013

Pentair PRVSIZE Software Version pr4.2_20121217.2

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2012 Pentair Valves & Controls.

Prosertec Srl. 4to Anillo #3880 y Av. Roca y Coronado

Pressure Relief Valve Calculation Report 19-sep-2013

Date Revision Client: YPFB TRASPORTE SA Location: ESTACION SAMAIPATA End-User Ref. No.: Project: SISTEMA DE ALIVIOS Y VENTEOS Project Ref. No.: VALVE ID CALCULATION NOTES 1 11 Tag No. PSV-001 2 12 Valve Model No. 46312-34/S1 Qty. 1 3 13 SIZING DATA 4 14 Design Code ASME Section VIII Sizing Std. API 520 15 5 Gas / Vapor 6 Fluid State at Inlet 16 CALCULATION SUMMARY 7 Required 70010 lb/hr Required 6,308 in 8 18 Flow Area Rated 74726,325 lb/hr Selected 6,733 in 9 19 Estimated Reaction Force 609,42 daN Estimated Noise Level (db) 75,9 at 100 ft 10 20 Variable Type Variable Name Symbol Input Value Equation Value Fluid Properties Molecular Weight M 47,88 47,88 Ratio of Specific Heats k 1,197 1,197 Compressibility Z 0,845 0,845 Process Cond. Required Mass Flow Wreq 70010 lb/hr 70010 lb/hr Set Pressure Pset 150 psig 150 psig Over Pressure Pover 15,0 psig 15,0 psig Inlet Line Loss Ploss 4,500 psig 4,500 psig Back Pressure Pback 133 psig 133 psig Atmospheric Pressure Patm 14,696 psia 14,696 psia Relieving Temperature T 95 F 554,670 R Distance from Valve (noise) r 100 ft 100 ft Rupture Disc CCF Kc 1,0 1,0 Valve Data Discharge Coefficient (actual) Kd 0,956 0,956 Discharge Coefficient (derated) K 0,860 0,860 Orifice Area A 6,733 in 6,733 in Back Pressure Correction Factor Kb 0,684 0,684 Outlet Diameter Do 4,06 in 4,06 in Calculate Inlet Relieving Pressure, Outlet Pressure, Absolute Pressure Ratio P1 = Pset + Pover - Ploss + Patm P1 175,196 psia P2 = Pback + Patm P2 147,696 psia PR = P2 / P1 PR 0,843 Calculate Gas Constant C = 520 * {k * [2 / (k + 1)]^[(k + 1) / (k - 1)] }^0.5 Calculate Mass Critical Flow W = A * C * K * P1 * Kb * Kc * [M / (T * Z)]^0.5 Calculate Required Orifice Area Areq = A * Wreq / W Calculate Mass Critical Flow (for Noise Calc) W = A * C * Kd * P1 * Kb * Kc * [M / (T * Z)]^0.5 C 336,9

Santa Cruz , Bolivia 591 (3) 355-9618 int 113 | www.prosertec-srl.com; Fax:591 (3) 311-7427 No Prpd. Chk. Appr. Quote Number:

74726,325 lb/hr

74726,325 lb/hr

Areq

6,308 in

6,308 in

83029,25 lb/hr

Calculate Noise Level at 100-ft (30-m) L100 L100 = [87.75 * log( 1/PR ) + 14.09] + [10 * log(0.29354 * W * k * T / M)]

75,9 db

Printed On: 25-sep-2013

Pentair PRVSIZE Software Version pr4.2_20121217.2

Page : 2

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2012 Pentair Valves & Controls.

Prosertec Srl. 4to Anillo #3880 y Av. Roca y Coronado

Pressure Relief Valve Calculation Report 19-sep-2013

Santa Cruz , Bolivia 591 (3) 355-9618 int 113 | www.prosertec-srl.com; Fax:591 (3) 311-7427 No Prpd. Chk. Appr. Quote Number:
Client: YPFB TRASPORTE SA Location: ESTACION SAMAIPATA Project: SISTEMA DE ALIVIOS Y VENTEOS VALVE ID 1 Tag No. PSV-001 2 Valve Model No. 46312-34/S1 Qty. 1 3 SIZING DATA 4 Design Code ASME Section VIII Sizing Std. API 520 5 Gas / Vapor 6 Fluid State at Inlet CALCULATION SUMMARY 7 Required 70010 lb/hr 8 Flow Rated 74726,325 lb/hr 9 Estimated Reaction Force 609,42 daN 10 Calculate Noise Level at Distance, r Lp Lp = L100 - 20 * log(r / 100) Calculate Outlet Static Pressure Po Po = [(0.00245 * A * C * Kd * P1 * Kc) / (Do^2 * (k * Z)^0.5)] - Patm Calculate Reaction Force for Open Discharge Fr Ao = ( * Do^2) / 4 Fr = (A * C * Kd * P1 * Kc / 366) * {k / [(k + 1) * Z]}^0.5 + (Ao * Po) Printed On: 25-sep-2013 609,42 daN End-User Ref. No.: Project Ref. No.: 11 12 13 14 15 16 18 19 20

Date

Revision

CALCULATION NOTES

Area

Required Selected Estimated Noise Level (db)

6,308 in 6,733 in 75,9 at 100 ft 75,9 db

41,447 psig

1370,0 lbf

Pentair PRVSIZE Software Version pr4.2_20121217.2

Page : 3

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2012 Pentair Valves & Controls.

Prosertec Srl. 4to Anillo #3880 y Av. Roca y Coronado

Pressure Relief Valve Dimensional Drawing 19-sep-2013

Santa Cruz , Bolivia 591 (3) 355-9618 int 113 | www.prosertec-srl.com; Fax:591 (3) 311-7427 No Prpd. Chk. Appr. Quote Number:
Client: YPFB TRASPORTE SA Location: ESTACION SAMAIPATA Project: SISTEMA DE ALIVIOS Y VENTEOS VALVE ID Tag No. PSV-001 Service GLP PID No. SC-E02-PR-00-03-02 de 02 Line No. 6"-0.280-B-(V-3)-3001 End-User Ref. No.: Project Ref. No.: 7 8 9 10 11 12

Date

Revision

1 2 3 4 5 6

SELECTION SUMMARY
Valve Model No. Brand Inlet Outlet 3" 4" Flngd. Flngd. 46312-34/S1 Anderson Greenwood

CONNECTIONS
600# 150# RF RF Standard ASME B16.5

Quantity 1

Wt.= A= B= C= D= E= F= G= H=

147 lb 6,12 in 7,00 in 25,16 in

= = = = = = = = =

66,68 kg 155,45 mm 177,80 mm 639,06 mm

Dimension Notes

Accessories not shown. Weight and dimensions shown are approximate. Actual valve may vary from. image.

Tag Notes
Printed On: 25-sep-2013

Pentair PRVSIZE Software Version pr4.2_20121217.2

Page : 4

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2012 Pentair Valves & Controls.

Summary Report
Project Information
Company: Location: My Company Project: Project Ref. No.: My Project

Tag Information
Tag Number: Revision: Prepared By: PSV-001 Last Modified: Checked By: 20/09/2013 06:32:08 p.m. Approved By:

Specific Tank Data


Sized Using User Defined Flow Pressure Fluid: Propane Pressure Set Point: 150 psig Allowed Over Pressure: 15,0 psig Pressure Flow Rate: 70010

Valve Sizing Information


Valve Type: 463, FB, 3x4 Part Number: 46312-34/S1 Max Pressure Flow Capacity: Quantity to Order: 74726,325 lb/hr 1

Selected Valve Description


Code XA XE XJ KE LW XC XH XD XH XF XI XG 4 AC AE KT DA AH AZ CH BZ BK AP AM DN DJ DJ FE 1 Category Option Lift Lever Remote Sense Spike Snubber Pilot Spring Set Pressure Range Field Test Connection Isodome Backflow Preventer Close Tee Supply Filter Remote Unloader Manual Blowdown Model Main Valve Lift Main Valve Piston Type Service Orifice Main Valve Materials Valve Size Inlet Connection Inlet Connection Face Style Outlet Connection Main Valve Body Type Nace Main Valve Seat Main Valve Soft Goods Pilot Soft Goods Fitting Type Code Case 2203 Description No Lift Lever Integral Sense No Spike Snubber 150-300 psig 500 psig and below No Field Test No Isodome No Backflow Preventer No Close Tee No Supply Filter No PH7 Remote Unloader No Manual Blowdown 400 Series - Modulating Pilot-Operated Full Lift, Full Bore Orifice Soft Seat/Seals Gas Service other than "Air" Full Bore (Largest practical orfice area for a given valve inlet size) CS Body & SST Trim (STD Valve) 3x4 inch 600# Raised Face - RF 150# RF Single Slip-on Inlet and Integral Outlet Standard (Nace not required) Teflon Buna-N Buna-N CS CPI Fittings No code case

Printed On: 25-sep-2013

Pentair PRVSIZE Software Version pr4.2_20121217.2

Page : 5

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2012 Pentair Valves & Controls.

You might also like