Professional Documents
Culture Documents
ELECTRO-PNEUMATICS
3.2 Theory
1
3.2.2 Components
Both pneumatic and electro-pneumatic controllers have a pneumatic power section. In
an electro-pneumatic control, the signal control section is made up of electrical
components, for example with electrical input buttons, proximity switches, relays, or a
programmable logic controller. The directional control valves form the interface
between the signal control section and the pneumatic power section in the controller
(refer figure 3.1).
Power components
- Cylinder
Command - Swivel cylinder Pneumatic
execution - Pneumatic motors power section
- Optical displays
Processing Elements
Signal - Relays
processing - Contactors
- Programmable logic
controllers (PLCs)
Electrical signal
Input Elements control section
Signal - Pushbuttons
input - Control switches
- Limit switches
- Reed switches
- Ind. proximity sensors
- Cap. proximity switches
- Light barriers
- Pressure-actuated
switches
2
3.2.2.1 Switch
There are three (3) types of electrical switches used in the design of electro-pneumatic
circuit. They are:
i) Opened contact switch
ii) Closed contact switch
iii) Multiple contact switches.
Figure 3.2(a), 3.2(b) and 3.2(c) shows the three types of contact switches at the
training box.
3 13 23 33 43
4 14 24 34 44
11 21 31 41
1
2
12 22 32 42
3
Single unit Multiple units
2 4 12 14 22 24 32 34 42 44
1 11 21 31 41
13 11
14 12
H1 H1
0V 0V
Figure 3.3(a): YES gate and NOT gate are the simplest electrical circuits
4
OR Gate (Disjunctive) AND Gate (Conjunctive)
24V 24V 13
13 23
14
14 24 13
H1 14
H1
0V 0V
Figure 3.3(b): OR Gate and AND Gate uses parallel and serial circuits with
opened contact switches.
12
11 12 22
12
H1
H1
0V 0V
Figure 3.3(c): NOR Gate and NAND Gate uses serial and parallel circuits with
closed contact switches.
3.2.2.3 Relay
Relay is an electrical device which contains a coil and a contactor switch. Relay also
can consist of a coil and multiple contactors. Figure 3.4 shows a coil (K) with 4
contactor switches at a training box.
5
Coil Changeover Contact
A1 12 14 22 24 32 34 42 44
A2 11 21 31 41
A1 12 14 12 14 12 14
A2 11 11 11
ordinary condition energized de-energized
(before energize)
Figure 3.5: The current flow in the coil will change the condition of
contactor switch
Figure 3.5 illustrates the changes of contactor switch. Once the current energizes the
coil, the contactor will switch from closed contact to be an opened contact. Inversely,
once the coil is de-energized, the contactor will return to it ordinary condition.
6
Figure 3.6(a) and 3.6(b) shows the electrical circuits with a relay and single output
(H1), and multiple outputs (H1, H2, H3, H4).
S1 S3 S1 S3
K1
S2 S2
H1 R1 H1
0V 0V
Figure 3.6(a): The electrical circuits WITHOUT and WITH relay (R1)
24V
13
S1
14 24 34 44
14 K1 K1 K1 K1
11 21 31 41
A1
K1 H1 H2 H3 H4
A2
0V
7
Solenoid valve is an electro-mechanical device that built-in with a coil (solenoid) and
a pneumatic/hydraulic directional control valve (DCV). There are three types of built-
in solenoid directional control valve. They are:
• 3/2 Way DCV single solenoid with spring return
• 5/2 Way DCV single solenoid with spring return
• 5/2 Way DCV double solenoid
The 3/2 way DCV single solenoid with spring return is used to control the actuation of
single acting cylinder, while the 5/2 way DCV single solenoid or double solenoid
respectively are used to control the actuation of double acting cylinder.
The 5/2 way DCV single solenoid and double solenoid can be distinguished by a built-
in spring instead of coil. DCV single solenoid or monostable valve consists of a built-
in solenoid at the left hand side and a built-in spring at the right hand side of the valve.
For the case of ‘normally closed DCV’, once the electrical current energizes the
solenoid, the valve is pushed to an ‘Opened’ position. Inversely, when the solenoid is
de-energized, the spring will push the valve back to the ‘Closed’ (original) position.
DCV double solenoid consists of two solenoids at the both sides of the valve. Both
solenoids are energized by electrical current to push the valve to an ‘Opened’ and
‘Closed’ positions. It is also called ‘bistable valve’ or ‘memory valve’.
8
Pneumatic
circuit
2 2
y1 y1
1 (P) 3 1 (P) 3
K1
Electrical
circuit
R1 y1
0V
Figure 3.7 shows the pneumatic and electrical circuits (electro-pneumatic circuits) for
actuating a single acting cylinder using 3/2 DCV single solenoid with spring return.
Then, Figure 3.8(a) and 3.8(b) shows the pneumatic and electrical circuits for
actuating a double cylinder using 5/2 DCV single solenoid and double solenoids
respectively.
Pneumatic
circuit
4 2 4 2
y1 y1
5 3
5 3
1 (P) 1 (P)
K1
Electrical
circuit
R1 y1
0V
9
Pneumatic
circuit
4 2 4 2
y1 y2 y1 y2
5 3 5 3
1 (P) 1 (P)
24V
5/2 way DCV double solenoid
S1 K1 S2
K2
Electrical
circuit
R2
R1 y1 y2
0V
10
Inductive Sensor Capacitive Sensor
24V 24V
R R
0V 0V 0V 0V
24V
Optical Sensor
0V 0V
PS a1
Pneumatic
circuit 4 2
y1 y2
5 3
1 (P)
24V
PS
S1 a1
Electrical K1 K2
circuit K3
R2 R3
R1 y1 y2
0V
11
Time delay ON timer delays the switching time upon an energizing. Let say a timer is
set to 5 seconds. When the timer coil T1 is energized, the timer will start compute the
time from zero second, thus the switches will change after 5 seconds. On the other
hand, when the timer coil T1 is de-energized, all switches will instantly return to it
original conditions.
Time delay OFF timer delays the switching time upon de-energizing. Let say a timer is
set to 10 seconds. When the timer coil T2 is energized, the timer will instantly change
the switching. Inversely, when the timer coil T2 is de-energized, the timer will start
compute the time until 10 seconds before the switches return to it original conditions.
Figure 3.11 shows the symbols for both types of delay timers.
A1 17 27 35 45
T1
A2 18 28 36 46
A1 17 27 35 45
T2
A2 18 28 36 46
Figure 3.11: Symbols of time delay ON and time delay OFF timers at a
controller box
Figure 3.12 shows the simple electrical circuit which consist of time delay OFF timer.
Once the switch S1 is pressed, the timer T2 is energized and the contactor K2 will
instantly changed to a closed contact condition. Then, if the switch S1 is released, the
timer will start computer the time to 5 seconds before the contactor K1 return to an
opened contact condition.
12
24V
S1
K1
Setting time
5 secs T1 Lamp
0V
4 2
A1 R1
C1
A2 1 R2
2 4 8 User setting
Set counter
Figure 3.13: Counter, switch and reset relay need to be connected in an electrical
circuit design
13
3.3 Practice
3.3.1 Practice 1
Task :
14
Name and sketch the related electro-pneumatic symbols :
a)
b)
c)
a)
b)
c)
15
3.3.2 Practice 2
Task :
16
Name and sketch the related pneumatic and electrical component symbols :
a)
b)
c)
a)
b)
c)
17
3.3.3 Practice 3
Task :
Design an electro-pneumatic control circuits using two pistons for the following
operation :
Press switch A to initiate extend of piston A and switch on a green LED. Fully extend
of piston A will initiate extend of piston B. Piston A will retract to an initial position if
piston B was fully extended. Once piston A was fully retracted, a red LED will be
switching ON while piston B start to retract.
• Use two 5/2 way DCV single solenoid with spring return
• Use two 5/2 way DCV double solenoid
18
Draw the Step Displacement Diagram for this operation :
19
3.3.4 Practice Case 4
a) (i) 24V
13 17
S1 T1
14 18
A1
5 seconds
T1 H1
A2
0V
(ii) 24V
15 17
S1 T1
16 18
A1
5 seconds
T1 H1
A2
0V
20
b) 24V
17 17 S2
S1 C1
18 18
A1 R1
5 seconds
C1 H1
A2
R2
0V
21
3.4 References
Prede, G., and Scholz, D. (1998). Electro-Pneumatic Basic Level TP201 Textbook.
Ed 12/1998. FESTO Didactic.
22