Transient Performance of Capacitor Voltage Transformers (CVT)

Introduction
In steady state, the secondary voltage of a capacitor voltage transformer mirrors the primary voltage. Because of the energy-storage elements used, the transient output, caused by sudden change in primary voltage, is no longer a replica of the primary. This distorted output may last for a few cycles of the supply frequency. These errors may be termed as the CVT linear transient since they would still occur in the event that all of the components of the CVT were linear. In addition to this, ferroresonance may occur resulting in voltage measurement error. Ferroresonance is caused by the saturation of the electromagnetic unit or inductive burden. Unlike the linear transient it does not occur with every change in primary voltage.

A CVT system can be represented by its Thevenin equivalent circuit. The analysis of a simplified L-C-R circuit for the case of a sudden collapse of the primary voltage (assuming a given set of initial conditions) produced the following conclusions: 1 If the equivalent capacitance Ce is larger and assuming a fixed value of the burden, the magnitude of the residual transient voltage becomes smaller. The intermediate voltage should also be maximized in order to achieve a high value of the equivalent capacitance. 2 The effect of the burden is so profound that it can dominate the CVT behavior. The burden configuration is insignificant since it determines the way in which energy can be stored and the path through which it can discharge. Pure resistive burden dissipates and does not store energy. Stored energy burdens (lagging or leading) create harmful effect on the transient response producing oscillations of low frequency nature. The oscillograms shown below illustrate the variation in the residual voltages as a function of burden at crest fault initiation. At zero fault initiation, the transient response worsens.

Linear Transient Error (Transient Response)


The linear transient error is mainly influenced by the following factors: 1 The Thevenin equivalent capacitance referred to the secondary voltage level, Ce. 2 The burden value and configuration. 3 The point of wave voltage interruption.

3 During the sudden application or sudden disappearance of primary voltage, the distribution of energy stored in the CVT is a major factor in understanding the effect of the point of wave voltage interruption. The transient performance in those cases is similar with the transients in the case of the primary short circuit. The amount of energy accumulated by the capacitor at zero initiation is equivalent to the energy stored by the series reactor at crest voltage initiation. The discharge time constant will vary depending upon where the maximum energy is stored. A typical example of transient response ( see below) indicates the worse case with the maximum energy on the capacitor at the time the primary voltage wave is going through the zero voltage interruption.

Trench Facilities
Trench Austria GmbH Paschinger Strasse 49 Postfach 13 A-4060 Linz-Leonding Austria Phone: 43-732-6793-0 Fax: 43-732-671341 Trench Brasil Ltda Via Expressa de Contagem, 2685 Contagem, Minas Gerais CEP 32370-485 Brazil Phone: 55-31-3391-5959 Fax: 55-31-3391-1828 Trench China MWB (Shanghai) Co., Ltd. No. 3658, Jiancheng Road Minhang, Shanghai Peoples Republic of China 200245 Phone: 86-21-54720088 Fax: 86-21-54723118 Trench High Voltage Products Ltd., Shenyang No. 2 Zhengliang Er. Road Jing Shen Xi San Street Dao Yi Economic Development Zone Shenyang 110136 P.R. China Phone: 86-24-89722688 Fax: 86-24-89737200 Trench Limited Bushing Division 432 Monarch Avenue Ajax, Ontario Canada L1S 2G7 Phone: 905-426-2665 Fax: 905-426-2671 Trench Limited Coil Product Division 71 Maybrook Drive Scarborough, Ontario Canada M1V 4B6 Phone: 416-298-8108 Fax: 416-298-2209 Trench Limited Instrument Transformer Division 390 Midwest Road Scarborough, Ontario Canada M1P 3B5 Phone: 416-751-8570 Fax: 416-751-6952 Trench Limited Power Line Carrier Division 815 Middlefield Road, Unit 6A Scarborough, Ontario Canada M1V 2P9 Phone: 416-291-8544 Fax: 416-291-5581 Trench France S.A. 16, Rue du Gnral Cassagnou B.P. 70 F-68 302 St. Louis, Cedex France Phone: 33-3 89-70-2323 Fax: 33-3 89-67-2663 Trench Germany GmbH Nrnberger Strasse 199 D-96050 Bamberg Germany Phone: 49-951-1803-0 Fax: 49-951-1803-224 Trench Switzerland AG Lehenmattstrasse 353 CH-4028 Basel Switzerland Phone: 41-61-315-51-11 Fax: 41-61-315-59-00 Trench (UK) Limited South Drive Hebburn Tyne & Wear NE 31 1 UW Phone: 44-191-483-4711 Fax: 44-191-430-0633

The Trench Group is your partner of choice for electrical power transmission and distribution solutions today; and for the development of your new technology solutions of tomorrow.

www.trenchgroup.com
E 214.60 Subject to change without notice (05.2006) Printed in Canada.

You might also like