You are on page 1of 8

Selection guide

TeSys contactors
From 115 to 2750 A

Applications

Control of all types of motor for standard or severe duty applications Control of resistive, inductive and capacitive circuits: heating, lighting, cos rectification, transformers, normal-standby

Rated operational current

Ie max AC-3 (Ue y 440 V) Ie max AC-1 ( y 40 C)

115 A 200 A

150 A 250 A

185 A 275 A

225 A 315 A

265 A 350 A

330 A 400 A

Rated operational voltage

1000 V

1000 V

1000 V

1000 V

1000 V

1000 V

Number of poles

3 or 4

3 or 4

3 or 4

3 or 4

3 or 4

3 or 4

Rated operational power in category AC-3

220/240 V 380/400 V 415 V

30 kW 55 kW 59 kW 59 kW 75 kW 80 kW 65 kW

40 kW 75 kW 80 kW 80 kW 90 kW 100 kW 65 kW

55 kW 90 kW 100 kW 100 kW 110 kW 110 kW 100 kW

63 kW 110 kW 110 kW 110 kW 129 kW 129 kW 100 kW

75 kW 132 kW 140 kW 140 kW 160 kW 160 kW 147 kW

100 kW 160 kW 180 kW 200 kW 200 kW 220 kW 160 kW

440 V 500 V 660/690 V 1000 V

Add-on auxiliary contact blocks

Front mounting, identical to those used on LC1 D contactors (contacts: instantaneous LA1 DNpp, time delay LA2 DT or LA3 DR, dust and damp protected LA1 DX or DY or DZ)

Associated thermal overload relays

Manual-auto Electronic

LR9 F LT6

Interfaces

Specific Universal

LA4 FWB With or without, depending on the control circuit

Contactor type

LC1 F115

LC1 F150

LC1 F185

LC1 F225

LC1 F265

LC1 F330

Reversing contactor type

LC2 F115

LC2 F150

LC2 F185

LC2 F225

LC2 F265

For customer assembly 5/102 and 5/103 5/106 to 5/109

Pages

Contactors Reversing contactors

5/102 and 5/103 5/104 and 5/105

5/92

400 A 500 A

500 A 700 A

630 A 1000 A

780 A 1600 A

800 A 1000 A

750 A 800 A

1000 A 1250 A

1500 A 2000 A

1800 A 2750 A

1000 V

1000 V

1000 V

1000 V

1000 V

1000 V

1000 V

1000 V

1000 V

2, 3 or 4

2, 3 or 4

2, 3 or 4

3 or 4

1 to 4

1 to 4

1 to 4

1 to 4

110 kW 200 kW 220 kW 250 kW 257 kW 280 kW 185 kW

147 kW 250 kW 280 kW 295 kW 355 kW 335 kW 335 kW

200 KW 335 kW 375 kW 400 kW 400 kW 450 kW 450 kW

220 kW 400 kW 425 kW 425 kW 450 kW 475 kW 450 kW

250 kW 450 kW 450 kW 450 kW 450 kW 475 kW 450 kW

220 kW 400 kW 425 kW 450 kW 500 kW 560 kW 530 kW

280 kW 500 kW 530 kW 560 kW 600 kW 670 kW 530 kW

425 kW 750 kW 800 kW 800 kW 700 kW 750 kW 670 kW

500 kW 900 kW 900 kW 900 kW 900 kW 900 kW 750 kW

4 instantaneous contact compositions: 2 N/C + 2 N/O, 3 N/O + 1 N/C, 1 N/O + 3 N/C or 4 N/O

LR9 F LT6

LC1 F400

LC1 F500

LC1 F630

LC1 F780

LC1 F800

LC1 BL

LC1 BM

LC1 BP

LC1 BR

For customer assembly

5/146 and 5/147 5/148

5/93

Characteristics

TeSys contactors
TeSys LC1 F (115 to 800 A)
Control circuit: a.c. or d.c.

Environment
Contactor type Rated insulation voltage (Ui) Conforming to IEC 60947-4-1 Conforming to VDE 0110 gr C Rated impulse withstand voltage (Uimp) Conforming to standards Product certifications Degree of protection Conforming to IEC 60529 Conforming to VDE 0106 Standard version Storage Operation Permissible at Uc (1) Without derating Without derating C C C m Coil not connected to the power circuit V V kV LC1 F115 1000 1500 8 LC1 F150 1000 1500 8 LC1 F185 1000 1500 8

EN 60947-1, EN 60947-4-1, IEC 60947-1, IEC 60947-4-1, JEM 1038 CSA, UL, BV, GL, DNV, RINA, RMROS, LROS, CCC IP 2X front face with shrouds LA9 F Front face protected against direct finger contact with shrouds LA9 F TH - 60+ 80 - 5+ 55 - 40+ 70 3000

Protective treatment Ambient air temperature around the device

Maximum operating altitude Operating positions

5
(not to be used for LC1 F780) With derating Apply the following derating coefficients: 0.75 on the pull-in voltage, 0.9 on the drop-out voltage and 0.8 on the operational current in AC-1. Apply the following derating coefficients: 1.15 on the pull-in voltage, 1.1 on the drop-out voltage and 0.8 on the operational current in AC-1. In either case: neither the making and breaking capacities nor the electrical and mechanical durabilities can be assured. Not to be used

Shock resistance (2) 1/2 sine wave = 11 ms

Contactor open Contactor closed

9 gn 15 gn 2 gn 6 gn

9 gn 15 gn 2 gn 6 gn

7 gn 15 gn 2 gn 5 gn

Vibration resistance (2) 5300 Hz

Contactor open Contactor closed

(1) In these conditions, it is recommended that LX9 F coils be used for contactor sizes F115 to F225. (2) In the least favourable direction, without change of contact state (coil at Uc). Where higher resistance to mechanical shock is required, select shock-proof contactors. Please consult your Regional Sales Office.

Selection : pages 5/160 to 5/183

References : pages 5/102 and 5/103

Dimensions : pages 5/128 and 5/129

Schemes : page 5/133

5/94

LC1 F225 1000 1500 8

LC1 F265 1000 1500 8

LC1 F330 1000 1500 8

LC1 F400 1000 1500 8

LC1 F500 1000 1500 8

LC1 F630 1000 1500 8

LC1 F780 1000 1500 8

LC1 F800 1000 1500 8

EN 60947-1, EN 60947-4-1, IEC 60947-1, IEC 60947-4-1, JEM 1038 CSA, UL, BV, GL, DNV, RINA, RMROS, LROS, CCC IP 2X front face with shrouds LA9 F Front face protected against direct finger contact with shrouds LA9 F TH - 60+ 80 - 5+ 55 - 40+ 70 3000 - 60+ 80 - 5+ 55 - 5+ 55 UL, CSA, GL, LROS

5
(not to be used for LC1 F780)

Apply the following derating coefficients: 0.75 on the pull-in voltage, 0.9 on the drop-out voltage and 0.8 on the operational current in AC-1.

Apply the following derating coefficients: 1.15 on the pull-in voltage, 1.1 on the drop-out voltage and 0.8 on the operational current in AC-1. In either case: neither the making and breaking capacities nor the electrical and mechanical durabilities can be assured.

7 gn 15 gn 2 gn 5 gn

6 gn 15 gn 2 gn 5 gn

6 gn 15 gn 2 gn 5 gn

6 gn 15 gn 1.5 gn 5 gn

9 gn 15 gn 2 gn 4 gn

6 gn 15 gn 2 gn 4 gn

5 gn 15 gn 2.5 gn 5.5 gn

6 gn 15 gn 2 gn 4 gn

(1) In these conditions, it is recommended that LX9 F coils be used for contactor sizes F115 to F225. (2) In the least favourable direction, without change of contact state (coil at Uc). Where higher resistance to mechanical shock is required, select shock-proof contactors. Please consult your Regional Sales Office.

5/95

Characteristics (continued)

TeSys contactors
TeSys LC1 F (115 to 800 A)
Control circuit: a.c. or d.c.

Pole characteristics
Contactor type Number of poles Rated operational current (le) In AC-3, y 55 C (Ue y 440 V) In AC-1, y 40 C Rated operational voltage (Ue) Frequency limits Conventional thermal current Rated making capacity Rated breaking capacity Up to Of the operational current (1) y 40 C A A V Hz A LC1 F115 3 or 4 115 200 1000 162/3200 200 LC1 F150 3 or 4 150 250 1000 162/3 200 250 LC1 F185 3 or 4 185 275 1000 162/3 200 275

I rms conforming to IEC 60947-4-1 A I rms conforming to IEC 60947-4-1 A A A A A A A A A m W W

Making current: 10 x I in AC-3 or 12 x I in AC-4 Making and breaking current: 8 x I in AC-3 or 10 x I in AC-4 1100 640 520 400 320 125 200 200 0.37 5 15 1200 700 600 450 350 160 200 250 0.35 8 22 1500 920 740 500 400 200 315 315 0.33 12 25

Maximum permissible current For 10 s No current flowing for preceding For 30 s 60 minutes with y 40 C For 1 min For 3 min For 10 min Short-circuit protection by fuses U y 440 V Motor circuit (type aM) With thermal overload relay (type gG) gG fuses At lth and 50 Hz AC-3 AC-1

Average impedance per pole Power dissipation per pole for the above operational currents Connection Bar

Number of bars Bar Cable with lug Cable with connector Bolt diameter Tightening torque Power circuit connections

Maximum c.s.a. 2 2 2 mm 20 x 3 25 x 3 25 x 3 mm2 95 120 150 mm2 95 120 150 mm 6 8 8 N.m 10 18 18 (1) Sine wave without interference. Above these values, please consult your Regional Sales Office.

Selection : pages 5/160 to 5/183

References : pages 5/102 and 5/103

Dimensions : pages 5/128 and 5/129

Schemes : page 5/133

5/96

LC1 F225 3 or 4 225 315 1000 162/3200 315

LC1 F265 3 or 4 265 350 1000 162/3 200 350

LC1 F330 3 or 4 330 400 1000 16 2/3200 400

LC1 F400 2, 3 or 4 400 500 1000 162/3200 500

LC1 F500 2, 3 or 4 500 700 1000 162/3 200 700

LC1 F630 2, 3 or 4 630 1000 1000 16 2/3200 1000 1250

LC1 F780 3 or 4 780 1600 1000 162/3200 1600

LC1 F800 3 800 1000 1000 162/3 200 1000

1250

Making current: 10 x I in AC-3 or 12 x I in AC-4 Making and breaking current: 8 x I in AC-3 or 10 x I in AC-4 1800 1000 850 560 440 250 315 315 0.32 16 32 2200 1230 950 620 480 315 500 400 0.3 21 37 2650 1800 1300 900 750 400 500 500 0.28 31 44 3600 2400 1700 1200 1000 400 630 500 0.26 42 65 4200 3200 2400 1500 1200 500 800 800 0.18 45 88 5050 4400 3400 2200 1600 630 800 1000 0.12 48 120 6250 5600 4600 3000 2200 800 1000 2 x 800 (2) 0.10 60 250 5500 4600 3600 2600 1700 800 1000 1000 0.12 77 120

2 2 2 2 2 2 3 32 x 4 32 x 4 30 x 5 30 x 5 40 x 5 60 x 5 60 x 5 185 240 240 2 x 150 2 x 240 185 240 10 10 10 10 10 12 35 35 35 35 35 58 (2) Paralleling of poles must be carried out only in accordance with the fuse manufacturer's recommendations.

2 100 x 5 2 x 12 58

2 60 x 5 12 58

5/97

Characteristics

TeSys contactors
TeSys LC1 F (115 to 800 A)
Control circuit: a.c. supply

Control circuit characteristics with LX1 or LX9 coil


Contactor type Rated control circuit voltage (Uc) Control voltage limits ( y 55 C) 50 or 60 Hz coils 50 or 60 Hz V LC1 F115 241000 LC1 F150 LC1 F185

Operation Drop-out Operation Drop-out

0.851.1 Uc 0.350.55 Uc

40400 Hz coils

Average consumption at 20 C and at Uc a 50 Hz Inrush 50 Hz coil 40400 Hz coil Cos Sealed 50 Hz coil 40400 Hz coil Cos 60 Hz coil 40400 Hz coil Cos 60 Hz coil 40400 Hz coil Cos

VA VA

550 0.3 45 0.3 660 0.3 55 0.3 1216 2335 515 10 2400 Min/max c.s.a. 1/4 1/4 1/2.5 1/4 1.2

550 0.3 45 0.3 660 0.3 55 0.3 1216 2335 515 10 2400

805 0.3 55 0.3 970 0.3 66 0.3 1824 2035 715 10 2400

VA VA

a 60 Hz Inrush

VA VA

Sealed

VA VA

Heat dissipation

W Closing "C" Opening "O" In millions of operating cycles ms ms

Operating time (1) Mechanical durability at Uc

Maximum operating rate In operating cycles per hour at ambient temperature y 55 C Connection Flexible conductor 1 or 2 conductors without cable end Flexible conductor 1 conductor with cable end 2 conductors Solid cable without cable end Tightening torque Mechanical latching 1 or 2 conductors

mm2 mm2 mm2 mm2 N.m

1/4 1/4 1/2.5 1/4 1.2

1/4 1/4 1/2.5 1/4 1.2

Mechanical latch blocks LA6 DK must not be fitted on LC1 F contactors. For similar type of operation, use magnetic latching contactors CR1 F. See pages 5/208 to 5/235. (1) The closing time "C" is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time "O" is measured from the moment the coil supply is switched off to the moment the main poles separate.

Selection : pages 5/160 to 5/183

References : pages 5/102 and 5/103

Dimensions : pages 5/128 and 5/129

Schemes : page 5/133

5/98

Presentation

TeSys contactors
TeSys LC1 F
Auxiliary contact blocks

LAD N

LAD N, LAD C LAD N10, N01 LC1 F

LAD T, LAD S

LAD R

LA1 DX, DY, DZ

5/110

You might also like