You are on page 1of 48

Industrial Inverter for Fan and Pump

STARVERT iP5A
5.5~30kW(7.5~40HP) 3Phase 200~230Volts 5.5~450kW(7.5~600HP) 3Phase 380~480Volts

Drive Solution

STARVERT iP5A
LS Starvert iP5A is basically created for centrifugal fan and pump, so iP5A can help construct competitive system in your various applications.

Industrial Inverter for Fan and Pump STARVERT iP5A

Specialized Functions for Fan and Pump

Energy Saving and High Efficiency

STARVERT

iP5A
Contents
4 8 9 11 15 17 20 21 22 33 35 40 45

User-friendly Interface and Easy Maintenance

Intelligent Control Mechanism

Overview Model & Type Standard Specifications Wiring Terminal Configurations (Power Circuit Terminal) Terminal Configurations (Control Circuit Terminal) Programming Keypad Programming Keypad (Parameter Navigation) Parameter Description Trial Run Dimensions DB (Dynamic Braking) Unit External DB Resistor / Peripheral Device

iP5A

Specialized Functions for Fan and Pump


iP5A is designed for Fans and Centrifugal Pumps. So it can support system stability and cost effectiveness to meet customer needs.

PID Control
In the centrifugal fan and pump field, PID control is provided as a standard function in order to maintain a constant process control of pressure, flow and oil level. This function includes Pre-PID, Sleep and Wake up and output inverse sub-functions.

Dual PID
In case of an external PID control needed or cascade PID control, the built-in Dual PID function of iP5A can construct various systems.

Multi Motor Control (5.5~90kW)


With this Multi Motor Control function, a number of motors can be controlled simultaneously without having any extra controllers. MMC function surely provides energy savings and cost down effect.

Industrial Inverter for Fan and Pump STARVERT iP5A

Energy Saving and High Efficiency


iP5A, uniquely designed for fan and pump, guarantees a certain degree of energy saving by realizing system effectiveness optimization.

Sleep and Wake-up Function


Sleep and Wake-up function can stop inverters operation in extremely low weighted load situation. And if the load is restored to a normal situation, inverter will restart. This mechanism ultimately brings energy saving result of entire system.
Output frequency PID reference Wake-up mode Returning to normal state Run command
Sleep mode Adjusting output with detecting load
(Energy saving)

PID feedback

Pre Heating Function


When inverter is used in damp places such as green-house, this function can protect motor from damage and inverters failure from damp.

Flying Start Function


In case of more than 2 fans operated in one system or heavy fan spinning by inertia, iP5A detects motors speed and is able to control motor effectively.

Automatic Energy Saving


Load change may incur energy losses but the optimized flux control of iP5A results in more outstanding energy saving compared to previous models.
Reduction percentage
0.75

Damper control Conventional inverter control


0.50 0.40 0.25 0.20 0.10 0 10

600 RPM

V/F 30% manual energy saving Automatic energy saving

iP5A

20

30

40

50

60

70

Load %

iP5A

Intelligent Control
Regardless of outside alteration affecting inverters performance, iP5A generates constant performance with effectual functions and protection methods.

Constant and Stable Performance


Regardless of outside alteration such as input voltage variation by load change or weather effect, iP5A can handle motor and load with best performance.

Improved Management from Instant Power-off and Power Dip Generation


During the power Dip or instant power-off, which is generated by lightening, ground fault and power-failure, loads still keep the mechanical energy and this energy flows back to inverter by regeneration. The power-failure guarantee time is extended by using this electrical character of inverter.
Power failure for 1 second

Emitted energy

The mechanical energy stored during blackout can be used for inverters power.
Mechanical energy

Power failure for 3 seconds

Load
Consumed energy

Mecha -nical energy

Safety Stop
When unexpected power-failure blocks power supply, inverter stops motor by using inertia energy of load that prevents unexpected second accident (Parameter setting is required).

Current Leakage Reduction Algorithm


Damp condition is subject to cause system failure due to current leakage. And iP5A invents LS PWM algorithm to blow out this danger.

PWM

Zero vector

Zero vector

Valid vector

Valid vector

Flux Braking Algorithm


This can make the deceleration time shorter than the regular one, so it enhances system efficiency.

Automatic Carrier Frequency Change


Considering ambient temperature, iP5A can adjust the carrier frequency automatically.

Protection
iP5A has optimum optimal protection functions such as safety stop and prior motor operation.

Industrial Inverter for Fan and Pump STARVERT iP5A

User-friendly Keypad & Easy Maintenance


iP5A provides user-friendly keypad supporting simple parameter editing. And iP5As frame work is created for easy maintenance.

Easy Start
When pushingSTOPkey for 2~3 seconds in case inverter turns on, the inverter turns into Easy Start Modewith FWD, REV, and STOP command. SHIFT/ESCcan return it to previous mode. Control method: V/F Control frequency: Jog

1 4 2 6

7 9

NPN/PNP Input
iP5A has both NPN and PNP input, and you can select one of them easily.

Built-in 485 and Optional Communication


Built-in 485 of iP5A enables to set up communication system by itself without any additional device. And optional communication suggestion of iP5A can satisfy users who want to construct their own system.

Abundant I/O Suggestion


iP5A serves abundant I/O.
Digital Input/Output Analog Input (Voltage + Current)/Output Pulse Input NTC/PTC Input 8 points / 4 points (1+1) points /4 points 1 point 1 point

Long-life Condenser and Simple Framework


iP5A adopts long-life condenser and enables easy maintenance in simple framework.

6 3

Consumption Time Display


iP5A displays consumption time of components so that users can replace them in time.

Various Units of I/O Display


Various units of I/O display are supported in iP5A, so users can recognize operation status easily. 7

Others
Removable terminal board External fan available Cooling fan on/off control

iP5A

Model & Type

Motor Rating
5.5kW (7.5HP) 7.5kW (10HP) 11kW (15HP) 15kW (20HP) 18.5kW (25HP) 22kW (30HP) 30kW (40HP) 37kW (50HP) 45kW (60HP) 55kW (75HP) 75kW (100HP) 90kW (125HP) 110kW (150HP) 132kW (200HP) 160kW (250HP) 220kW (300HP) 280kW (350HP) 315kW (400HP) 375kW (500HP) 450kW (600HP)

200~230V Class
SV055iP5A-2NE SV075iP5A-2NE SV110iP5A-2NE SV150iP5A-2NO SV185iP5A-2NO SV220iP5A-2NO SV300iP5A-2NO

380~480V Class
SV055iP5A-4NE SV075iP5A-4NE SV110iP5A-4NE SV150iP5A-4NO SV185iP5A-4NO SV220iP5A-4NO SV300iP5A-4NO SV370iP5A-4O SV450iP5A-4O SV550iP5A-4O SV750iP5A-4O SV900iP5A-4O SV1100iP5A-4OL SV1320iP5A-4OL SV1600iP5A-4OL SV2200iP5A-4OL SV2800iP5A-4OL SV3150iP5A-4O SV3750iP5A-4O SV4500iP5A-4O

SV

055
Motor Rating 055 900 5.5 kW 90 kW

iP5A
Series Name iP5A

--

2
Input Voltage 2 4 200-230V 380-480V

NE
N: No Keypad O: UL Open Type E: UL Enclosed Type 1 L: Built-in DC Choke

SV055iP5A-2NE
INPUT 200-230 V 3 Phase 25A 50/60HZ OUTPUT 0-Input V 3 Phase 24A 0.01-120HZ 9.1KVA, Enclosed Type 1

Model Number Input Rating Output Rating Protection Degree Bar Cord Serial Number

Industrial Inverter for Fan and Pump STARVERT iP5A

Standard Specifications
200~230V Class (5.5~30kW / 7.5~40HP)
Model Number (SV iP5A-2)
Capacity [kVA]
Note1)

055
9.1 7.5 5.5 24 5.5 3.7 17

075
12.2 10 7.5 32 7.5 5.5 23

110
17.5 15 11 46

150

185

220

300
43.8 40 30 115 30 22 84

Fan or pump load Output ratings General load Frequency Voltage Input Voltage ratings Frequency Protection degree Weight [kg (lbs.)]

Motor rating

Note2)

(HP) (kW)

Current [A] (110% over current) (HP) Motor rating (kW) Current [A] (150% over current)

4.9 (10.8)

IP20 / UL Type1 6 (13.2)

22.9 28.2 33.5 20 25 30 15 18.5 22 60 74 88 110% 1 Minute (Normal Duty) 10 15 20 25 7.5 11 15 18.5 33 44 54 68 150% 1 Minute (Heavy Duty) 0.01~120 Hz 200~230V Note3) 3200~230V (-15%~+10%) 50/60 Hz ( 5%) IP00 / UL Open Note4) 6 (13.2) 13 (28.7) 13.5 (29.8) 20 (44.1)

20 (44,1)

380~480V Class (5.5~90kW / 7.5~125HP)


Model Number (SV iP5A-4)
Capacity [kVA]
Note1)

055
9.6 7.5 5.5 12

075
12.7 10 7.5 16

110
19.1 15 11 24

150
23.9 20 15 30

185

220

300

370

450

550

750

900

Fan or pump load Output ratings General load Frequency Voltage Input Voltage ratings Frequency Protection degree Weight [kg (lbs.)]

Motor rating

Note2)

(HP) (kW)

Current [A] (110% over current) (HP) Motor rating (kW) Current [A] (150% over current)

Standard Type Built-in DCL Type

31.1 35.9 48.6 59.8 72.5 87.6 121.1 145.8 25 30 40 50 60 75 100 125 18.5 22 30 37 45 55 75 90 39 45 61 75 91 110 152 183 110% 1 Minute (Normal Duty) 5.5 7.5 10 15 20 25 30 40 50 60 75 100 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 8.8 12 16 22/24 28/30 34/39 44/45 150% 1 Minute (Heavy Duty) 0.01~120 Hz 380~480V Note3) 3380~480V (-15%~+10%) 50/60 Hz ( 5%) IP20 / UL Type1 IP00 / UL Open Note4) 4.9 (10.8) 6 (13.2) 6 (13.2) 12.5 (27.6) 13 (28.7) 20 (44.1) 20 (44.1) 27 (59.5) 27 (59.5) 29 (64) 42 (92.6) 43 (94.8) 19.5 (43.9) 19.5 (42.9) 26.5 (58.3) 26.5 (58.3) 39 (86) 40 (88.2) 42 (92.6) 67 (147.4) 68 (149.9)

380~480V Class (110~450kW / 50~125HP)


Model Number (SV iP5A-4)
Capacity [kVA]
Note1) Note2)

1100
178 150 110 223 125 90 183

1320
210 200 132 264 150 10 223

1600
259 250 160 325 200 132 264

2200

2800

3150
488 400 315 613 350 280 547

3750
582 500 375 731 400 315 613

4500
699 600 450 877 500 375 731

Fan or pump load Output ratings General load Frequency Voltage Input Voltage ratings Frequency Protection degree DCL Weight [kg (lbs.)]

Motor rating

(HP) (kW)

Current [A] (110% over current) (HP) Motor rating (kW) Current [A] (150% over current)

344 436 300 350 220 280 432 547 110% 1 Minute (Normal Duty) 250 300 160 220 325 432 150% 1 Minute (Heavy Duty) 0.01~120 Hz 380~480V Note3) 3380~480V (-15%~+10%) 50/60 Hz ( 5%) IP00 / UL Open Note4) 200 (441.9) 200 (441.9)

101 (222.7)

Built-in 101 (222.7) 114 (251.3)

External Option 243 (535.7) 380 (837.7)

380 (837.7)

Note 1) Rated capacity (v 3VI) is based on 220V for 200V class and 460V for 400V class. 2) Indicates the maximum applicable capacity when using a 4-Pole LS motor. 3) Maximum output voltage will not exceed the input voltage. An output voltage less than the input voltage may be programmed if necessary. 4) IP20/UL Type1 with optional conduit, it can be modified to UL Type1.

iP5A

Standard Specifications
Common Specifications (External)
Keypad Remote
32 character display LCD keypad Download and Upload available 2m, 3m and 5m long keypad cable enables users Remote cable to control the inverter from a distant area To enhance the regenerative braking performance, DB resistor Optional All units

Dynamic braking
DB unit Conduit for

it makes the inverter to accelerate/decelerate rapidly If it need a regenerative braking, it is used with DB resistor

According to inverter capacity

Conduit option

15~90kW Install it to fit for NEMA TYPE 1 Enclosure or IP20 (20~125HP) All series DEVICENET optional communication card (Above S/W V10) All series

NEMA TYPE 1 DEVICENET

PROFIBUS

PROFIBUS optional communication card (Above S/W V10) All series

LS485/MODBUS_RTU

LS485/MODBUS_RTU optional communication card (Above S/W V10) All series

LonWorks

Lonworks optional communication card (Above S/W V10) All series

Communication option card

BACNet

BACNet optional communication card (Above S/W V10) All series

MODBUS_TCP

MODBUS_TCP optional communication card (Above S/W V10) All series

Metasys_N2

Metasys_N2 optional communication card (Above S/W V10) All series

CCLink

CCLink optional communication card (Above S/W V10) All series

CANopen

CANopen optional communication card (Above S/W V10)

10

Industrial Inverter for Fan and Pump STARVERT iP5A

Wiring
For 5.5~30kW (7.5~40HP) Main Power Circuit

DC Bus Choke (Optional)


DC Bus Choke P1 (+) MCCB (Option) 3 AC Input 50/60 Hz R (L1) S (L2) T (L3) G

Dynamic Braking Unit (Optional) P N B1 B2

DB Unit (Optional) DB Resistor


DB Resistor

P2 (+) N (-)

U V W

Motor

Control Circuit
Programmable Digital Input 1 (Speed L) Programmable Digital Input 2 (Speed M) Programmable Digital Input 3 (Speed H) Fault Reset (RST) Inverter Disable (BX) Jog Frequency Reference (JOG) Forward Run Command (FX) Reverse Run Command (RX) Common Terminal

V+ M1 M2 M3 M4 M5 M6 M7 M8 CM A1 C1 A2 C2 A3 C3 A4 C4
RS485 Signal RS485 Common Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA

Analog Power Source (+12V) Frequency Reference (0~12V, V1S: -12~12V) Frequency Reference Common Terminal Frequency Reference (0~20mA or 4~20mA) Analog Power Source (-12V)

+ + -

V1 5G I V-

S0 S1 5G

Output Frequency Meter Output Voltage Meter Common for Output Meter Signal

Programmable Digital Output

3A 3C 3B

Fault Contact Output less than AC250V (DC30V), 1A

A0 B0 5G

Frequency Reference (Pulse: 0~100kHz) Common for Frequency Reference (Pulse)

CC+ CM

NT 5G

External Motor Thermal Detection

Note 1) 5G is Common Ground for Analog Input / Output. 2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input.

11

iP5A

Wiring
For 37~90kW (50~125HP) / 315~450kW (400~600HP) Main Power Circuit

DC Bus Choke (Optional )


DC Bus Choke P1 (+) MCCB (Option) 3 AC Input 50/60 Hz R (L1) S (L2) T (L3) G

Dynamic Braking Unit (Optional) P N B1 B2

DB Unit (Optional) DB Resistor


DB Resistor

P2 (+) N (-)

U V W

Motor

Control Circuit
Programmable Digital Input 1 (Speed L) Programmable Digital Input 2 (Speed M) Programmable Digital Input 3 (Speed H) Fault Reset (RST) Inverter Disable (BX) Jog Frequency Reference (JOG) Forward Run Command (FX) Reverse Run Command (RX) Common Terminal

V+ M1 M2 M3 M4 M5 M6 M7 M8 CM A1 C1 A2 C2 A3 C3 A4 C4
RS485 Signal RS485 Common Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA

Analog Power Source (+12V) Frequency Reference (0~12V, V1S: -12~12V) Frequency Reference Common Terminal Frequency Reference (0~20mA or 4~20mA) Analog Power Source (-12V)

+ + -

V1 CM I V-

S0 S1 5G

Output Frequency Meter Output Voltage Meter Common for Output Meter Signal

Programmable Digital Output

3A 3C 3B

Fault Contact Output less than AC250V (DC30V), 1A

A0 B0 CM
Frequency Reference (Pulse: 0~100kHz) Common for Frequency Reference (Pulse)

CC+ CM

ET 5G

External Motor Thermal Detection

Note 1) 5G is Common Ground for Analog Meter Output (SO, S1) and External motor thermal detection (ET). 2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input. 3) DC Reactor is built basically in inverters for 15~280kW.

12

Industrial Inverter for Fan and Pump STARVERT iP5A

For 110~280kW (150~350HP) Main Power Circuit


Dynamic Braking Unit (Optional) P N B1 B2 DB Resistor P2 (+) MCCB (Option) DC Reactor (Built-in) 3 AC Input 50/60 Hz R (L1) S (L2) T (L3) G U V W

DB Unit (Optional) DB Resistor

Motor

Control Circuit
Programmable Digital Input 1 (Speed L) Programmable Digital Input 2 (Speed M) Programmable Digital Input 3 (Speed H) Fault Reset (RST) Inverter Disable (BX) Jog Frequency Reference (JOG) Forward Run Command (FX) Reverse Run Command (RX) Common Terminal

V+ M1 M2 M3 M4 M5 M6 M7 M8 CM A1 C1 A2 C2 A3 C3 A4 C4
RS485 Signal RS485 Common Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA

Analog Power Source (+12V) Frequency Reference (0~12V,V1S: -12~12V) Frequency Reference Common Terminal Frequency Reference (0~20mA or 4~20mA) Analog Power Source (-12V)

+ + -

V1 CM I V-

S0 S1 5G

Output Frequency Meter Output Voltage Meter Common for Output Meter Signal

Programmable Digital Output

3A 3C 3B

Fault Contact Output less than AC250V (DC30V), 1A

A0 B0 CM
Frequency Reference (Pulse: 0~100kHz) Common for Frequency Reference (Pulse)

CC+ CM

ET 5G

External Motor Thermal Detection

Note 1) 5G is Common Ground for Analog Meter Output (SO, S1) and External motor thermal detection (ET). 2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input. 3) DC Reactor is built basically in inverters for 15~280kW.

13

iP5A

Wiring
For 15~30kW (20~40HP) Built-in DCL Type

P N B1 B2 DB Resistor P (+) N (-)

DC Reactor

3 AC Input 50/60 Hz

R (L1) S (L2) T (L3) G

U V W

Motor

For 37~90kW (50~125HP) Built-in DCL Type

P N B1 B2 DB Resistor P1 (+) P2 (+) N (-)

DC Reactor

3 AC Input 50/60 Hz

R (L1) S (L2) T (L3) G

U V W

Motor

Note) P1 (+) is not provided for wiring.

14

Industrial Inverter for Fan and Pump STARVERT iP5A

Terminal Configurations (Power Circuit Terminal)


5.5~30 kW (200V/400V Class)

(+)
R(L1) S(L2) T(L3) G P1
Jumper

(+)
P2

(--)
N U V W

37~90kW (50~125HP) / 315~450kW (400~600HP)400V Class

(+)
R(L1) S(L2) T(L3) P1
Jumper

(+)
P2

(--)
N U V W

15~18.5kW (20~25HP)Built-in DC Reactor Type, 400V Class

(+)
G R(L1) S(L2) T(L3) P

(--)
N U V W G

22~30kW (30~40HP)Built-in DC Reactor Type, 400V Class

(+)
R(L1) S(L2) T(L3) P

(-)
N U V W

37~90kW (50~125HP) / 110 ~280kW (150~350HP)Built-in DC Reactor Type, 400V Class

(+)
R(L1) S(L2) T(L3)
Note) P1 (+) is not provided for wiring.

(--)
N U V W

P2

Symbol
R, S, T (L1, L2, L3) G P1 (+), P2 (+) P2 (+), N (-) or P (+), N (-) U, V, W AC Line Voltage Input Earth Ground

Description

External DC Reactor [P1 (+)-P2 (+)] Connection Terminals (Jumper must be removed). DB Unit [P2 (+)-N (-)] Connection Terminals 3 Phase Power Output Terminals to Motor

15

iP5A

Terminal Configurations (Power Circuit Terminal)


Wires & Terminal lugs
Refer to below for wires, terminal lugs, and screws used to connect the inverter power input and output.
Terminal Screw Size 5.5kW (7.5HP) 7.5kW (10HP) 11kW (15HP) M4 M5 M5 M6 M6 M8 M8 M4 M5 M5 M6 M6 M8 M8 M10 M12 M12 M12 M12 M12 M12 M12 Screw Torque Kgfcm 17 35 35 57 57 135 135 17 35 35 57 57 135 135 269 474 474 474 474 474 474 474 Ibin 15.2 30.4 30.4 49.9 49.9 117.7 117.7 15.2 30.4 30.4 49.9 49.9 117.7 117.7 234.5 412.4 412.4 412.4 412.4 412.4 412.4 412.4 R, S, T 5.5 8 14 22 38 38 60 3.5 3.5 5.5 8 14 22 38 60 100 150 200 250 325 2200 2250 Wire mm
(L1, L2, L3)
2

Inverter Capacity

U, V, W 5.5 8 14 22 38 38 60 3.5 3.5 5.5 8 14 22 38 60 100 150 200 250 325 2200 2250

(L1, L2, L3)

AWG or kcmil R, S, T U, V, W 10 8 6 4 2 2 1/0 12 12 10 8 6 4 2 1/0 4/0 300 400 500 700 10 8 6 4 2 2 1/0 12 12 10 8 6 4 2 1/0 4/0 300 400 500 700 2400 2500

200V Class

15kW (20HP) 18.5kW (25HP) 22kW (30HP) 30kW (40HP) 5.5kW (7.5HP) 7.5Kw (10HP) 11 kW (15HP) 15 kW (20HP) 18.5kW (25HP) 22~30kW (30~40HP)

400V Class

37~55kW (50~75HP) 75~90kW (100~125HP) 110~132kW (150~200HP) 160kW (250HP) 220kW (300HP) 280kW (350HP) 315kW (400HP) 375kW (500HP) 450kW (600HP)

2400 2500

Note) Apply the rated torque to terminal screws. Loose screws can cause of short circuit or malfunction. Tightening the screw too much can damage the terminals and cause a short circuit or malfunction. Use copper wires only with 600V, 75 ratings. For 7.5~11kW 240V type inverters, R (L1), S (L2), T (L3) and U, V, W terminals are only for use with insulated ring type connector.

16

Industrial Inverter for Fan and Pump STARVERT iP5A

Terminal Configurations (Control Circuit Terminal)


5.5~30kW/7.5~40HP (200V/400V Class)

3A

3C

3B

A1

C1

A2

C2

A3

C3

A4

C4

C+ M1

CM CM

CM2

M6 M3

24 24

M7 M4

M8 M5

A0 V+

B0 V1

5G 5G

5P V-

S0 I

S1 NT

37~450 kW/50~600HP (400V Class)

3A

3C

3B

A1

C1

A2

C2

A3

C3

A4

C4

C+ M1

CM CM

CM2

M6 M3

24 24

M7 M4

M8 M5

CM V+

NC V1

5G CM

5G V-

ET I

S0 A0

S1 B0

17

iP5A

Terminal Configurations (Control Circuit Terminal)

Type

Symbol
M1, M2, M3 FX [M7] RX [M8] JOG [M6]

Name
Programmable Digital Input 1, 2, 3 Forward Run Command Reverse Run Command Jog Frequency Reference Defines programmable digital inputs.

Description
(Factory setting: Multi-step frequency 1, 2, 3) Forward run when closed and stopped when open. Reverse run when closed and stopped when open. Runs at jog frequency when the jog signal is on. The direction is set by the FX (or RX) signal. When the BX signal is ON, the output of the inverter is turned off. When motor uses an electrical brake to stop, BX is used to turn off the output signal. Take caution when BX signal is off (Not turned off by latching) and FX signal (or RX signal) is on. If so, motor continues to run. Used for fault reset. Common terminal for NPN contact input and also common for the external 24V supply. Common 24V terminal for PNP contact input. Can be also used as a 24Vdc external power supply (Maximum output : +24V, 50mA) Power supply for analog frequency setting. Maximum output: +12V, 100mA, -12V, 100mA. Used by a DC 0~12V or -12~12V input to set the frequency reference. (Input impedance is 20 k) Used by a 0-20mA input to set the frequency reference. (Input impedance is 249) Used by a pulse input to set the frequency reference. Common terminal for analog frequency reference signal. Motor thermal sensor input. Used to prevent motor from overheating by using a NTC or PTC thermal sensor. Common terminal for external motor thermal detection. RS485 signal (See RS485 communication in manual for more details.) Common ground. Terminal for RS485 interface. Voltage output for one of the following: Output frequency, output current, output voltage, DC link voltage. Default is set to output frequency. (Maximum output voltage and output current are 0-12V and 1mA). Energizes when a fault is present. (AC250V, 1A: DC30V, 1A) Fault: 3A-3C closed (3B-3C Open) Normal: 3B-3C closed (3A-3C Open) Defined by programmable digital output terminal settings (AC250V, 1A: DC30V, 1A)

Starting Contact Function Select

BX [M5]

Inverter Disable

RST [M4] CM

Fault Reset Sequence Common (NPN) / 24V Com. Sequence Common (PNP) / Ext. +24Vdc supply Analog Power Source (+12V,-12V) Frequency Reference (Voltage) Frequency Reference (Current) Frequency Reference (Pulse) Frequency Reference Common Terminal External Motor Thermal Detection Common for NT (or ET) RS485 signal High, Low RS485 common Programmable Voltage Output Fault Contact Output Programmable Digital Output

Input Signal

24

V+, VV1 Analog Frequency Setting A0, B0 5G (~30kW) CM (37kW~) External Motor Thermal Detection RS485 Terminal NT (~30kW) ET (37kW~) 5G C+, CCM S0, S1,5G I

Voltage

Output Signal

3A, 3C, 3B Contact A1~4, C1~4

Note) M1~M8 terminals are User Programmable.

18

Industrial Inverter for Fan and Pump STARVERT iP5A

Terminal Configurations (Control Circuit Terminal)


iP5A provides Sink/Source (NPN/PNP) modes for sequence input terminal on the control circuit. The logic of the input terminal is settable to Sink mode (NPN mode)/Source mode (NPN mode) by using the J1 switch. Connection method is shown below.
Sink mode (NPN mode)
Put J1 switch down to set to Sink mode (NPN mode). CM terminal (24V GND) is common terminal for contact signal input. The factory default is Sink mode (NPN mode).

Source mode (PNP mode) Internal Power Supply Used


Put J1 switch up to set to Source mode (PNP mode). Terminal 24 (24V Power Supply) is common terminal for contact input signal.

Source mode (PNP mode) External Power Supply Used


Put J1 switch up to set to Source mode (PNP mode). To use external 24V Power Supply, make a sequence between external Power Supply (-) terminal and CM (24V GND) terminal.

19

iP5A

Programming Keypad
LCD Loader

32 character, background light, LCD display. Background tone is adjustable.

Program Button is used to go into programming mode to change data.

Mode Button moves you through seven program groups: DRV [Mode] FUN1 [ENT] DRV

Enter Button is used to enter changed data within a parameter. DRV [ENT] APP [MODE] DRV

[SHIFT] This button is used to move cursor across display in programming mode. [ESC] This button is used to move the program code to DRV 00 from any program code. Reverse Run Button Reverse Run LED blinks when drive Accels or Decels.

Forward Run Button Forward Run LED blinks when drive Accels or Decels.

20

Industrial Inverter for Fan and Pump STARVERT iP5A

Programming Keypad (Parameter Navigation)


Parameter group moves directly to DRV group by pressing [SHIFT] key in any parameter code.

Drive Group

FU1 Group

FU2 Group

I/O Group

Note) This figure shows group and code navigation through LCD display keypad. It can be different from actual display due to the group addition or code change.

21

iP5A

Parameter Description
DRV Group
CODE Comm. Addr Description
Command Frequency (Output Frequency during motor run, Reference Frequency during motor stop), Output Current(LCD) Acceleration 5.5~90kW (7.5~125HP) Time 110~450kW (150~600HP) Deceleration 5.5~90kW (7.5~125HP) Time 110~450kW (150~600HP)

LCD Keypad Display

Setting Range

Factory Default

Adj. During Run

DRV-00 Note1)

9100

Cmd. Freq

0 to FU1-30 [Hz]

0 [Hz]

DRV-01 DRV-02

9101 9102

Acc. Time Dec. Time

0 to 6000 [sec] 0 to 6000 [sec] 0 (Keypad) 1 (Fx/Rx-1) 2 (Fx/Rx-2) 3 (Int. 485) 0 (Keypad-1) 1 (Keypad-2) 2 (V1) 3 (V1S) 4 (I) 5 (V1+I) 6 (Pulse) 7 (Int. 485) 8 (Ext. PID) 0 to FU1-30 [Hz] * [A] * [rpm] * [V]

20 [sec] 60 [sec] 30 [sec] 90 [sec] 1 (Fx/Rx-1)

DRV-03

9103

Drive Mode (Run/Stop Method)

Drive Mode

DRV-04

9104

Frequency Mode (Frequency setting method)

Freq Mode

0 (Keypad-1)

DRV-05 DRV-06 DRV-07 DRV-08 DRV-09 DRV-10 DRV-11 DRV-12 DRV-13 DRV-14 Note2) DRV-15 Note2) DRV-16 DRV-18 Note2) DRV-19 DRV-20 Note3) DRV-91 Note4)

9105 9106 9107 9108 9109 910A 910B 910C 910D 910E 910F 9110 9112 9113 9114 915B

Step Frequency 1 Step Frequency 2 Step Frequency 3 Output Current Motor Speed DC link Voltage User Display Selection Current Trip Display Motor Direction Target/Output Frequency Display Reference/Feedback Frequency Display Speed Unit Selection PID Parameter AD Parameter EXT-PID Parameter Drive Mode 2

Step freq-1 Step freq-2 Step freq-3 Current Speed DC link Vtg User disp Fault Use Only 7-Segment Keypad Tar. Out. Freq. Ref. Fbk. Freq. Hz/Rpm Disp Pid Parameter AD Parameter Ext Pid Para Drive Mode2

* 0 (Forward)/1 (Reverse) * [Hz] * [Hz] Hz or Rpm * [Hz] AD [%] 0 (Keypad) 1 (Fx/Rx-1) 2 (Fx/Rx-2) 0 (Keypad-1) 1 (Keypad-2) 2 (V1) 3 (V1S) 4 (I) 5 (V1+I) 6 (Pulse)

10 [Hz] 20 [Hz] 30 [Hz] * [A] * [rpm] * [V] Output voltage [V] * 0 * [Hz] * [Hz] [Hz] * [Hz] AD % 1 (Fx/Rx-1)

* * * * * * *

DRV-92 Note4)

915C

Frequency Mode 2

Freq Mode2

0 (Keypad-1)

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 1) The speed unit is changed from [Hz] to [%] when DRV-16 is set to [Rpm]. Only User Unit will be displayed when APP-02 is set to [Yes] and when APP-06 is set to either I, V1 or Pulse and when one of I/O-86~ I/O-88 is set to either [Speed], [Percent], [Bar], [mBar], [kPa] or [Pa]. Output Frequency is displayed in DRV-00 during the Inverter is running. User Unit reference is displayed in DRV-00 during the Inverter is not running. 2) DRV-15, DRV-18 will appear when APP-02 [Process PI Mode] is set toYes . Also User Unit is displayed when one of I/O-86~I/O-88 is set to either [Speed], [Percent], [Bar], [mBar], [kPa] or [Pa]. 3) DRV-20 will appear when APP-80 [Ext Process PI Mode] is set toYes . 4) DRV-91/92 will appear only when one of I/O-20~27 is set to [Main drv] and DRV- 03/04 is set to [int485].

22

Industrial Inverter for Fan and Pump STARVERT iP5A

FU1 GROUP
CODE
FU1-00

Comm. Addr
9200

Description
Jump to Desired Code #

LCD Keypad Display


Jump Code 0

Setting Range
1 to 74 (Use Only LCD Keypad) (None) (Fwd prev) (Rev prev) (Linear) (S-curve) (U-curve) (Linear) (S-curve) (U-curve) 0 to 100 [%] 0 to 100 [%] 0 1 (No) (Yes) 1 to 50 [%] 1 to 100 [%] 0 (Accel) (Dc-start) (Flying-start) 0 to 60 [sec] 0 to 150 [%] 0 (Decel) (Dc-brake) (Free-run) (Flux-brake) 0.1 to 60 [sec] 0.1 to 60 [Hz] 0 to 60 [sec] 0 to 200 [%] 0 1 (No) (Yes) 40 to 120 [Hz] 40 to 120 [Hz] 30 to 120 [Hz] 0.1 to 10 [Hz] 0 1 (No) (Yes) 0 to FU1-35 FU1-34 to FU1-30 1 2 3 1 2

Factory Default
1

Adj. During Run

FU1-01

9201

Run Prevention

Run Prevention

1 2 0

0 (None)

FU1-02

9202

Acceleration Pattern

Acc. Pattern

1 2 0

0 (Linear)

FU1-03

9203

Deceleration Pattern Start Curve for S-Curve Accel/Decel Pattern End Curve for S-Curve Accel/Decel Pattern

Dec. Pattern

1 2

0 (Linear)

FU1-04 FU1-05 FU1-10 FU1-11 FU1-12 FU1-20 FU1-21 FU1-22


Note6) Note5)

9204 9205 920A 920B 920C 9214 9115 9116

Start Curve End Curve Pre-Heat Mode Pre Heat Level Pre Heat Perc Start Mode DcSt Time DcSt Value

50 [%] 50 [%] 0 (No) 30 [%] 100 [%] 0 (Accel) 0 [sec] 50 [%]

Pre-Heat Pre-Heat Value Pre-Heat Duty Start Mode Starting DC Injection Braking Time Starting DC Injection Braking Value

FU1-23

9217

Stop Mode

Stop Mode

0 (Decel)

FU1-24 FU1-25 FU1-26 FU1-27 FU1-28 FU1-29 FU1-30 FU1-31 FU1-32 FU1-33 FU1-34 FU1-35

Note7)

9218 9219 921A 921B 921C 921D 921E 921F 9220 9221

DC Injection Braking On-delay Time DC Injection Braking Frequency DC Injection Braking Time DC Injection Braking Value Safety Stop Power Source Freq Maximum Frequency Base Frequency Starting Frequency Frequency Limit Selection Low Limit Frequency High Limit Frequency

DcBlk Time DcBr Freq DcBr Fime DcBr Value Safety Stop Line Freq Max Treq Base Treq Start Treq Freq Limit F-limit Lo F-limit Hi

0.1 [sec] 5 [Hz] 1 [sec] 50 [%] 0 (No) 60 [Hz] 60 [Hz] 60 [Hz] 0.5 [Hz] 0 (No) 0.5 [Hz] 60 [Hz]

Note8)

9222 9223

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 5) Only displayed when FU1-02, FU1-03 is set to [S-Curve]. 6) Only displayed when FU1-20 is set to [DC-start]. 7) Only displayed when FU1-23 is set to [DC-break]. 8) Only displayed when FU1-33 is set toYes .

23

iP5A

Parameter Description
FU1 GROUP
CODE Comm. Addr
9228
Note9)

Description

LCD Keypad Display


0 V/F Pattern User Freq 1 User Volt 1 User Freq 2 User Volt 2 User Freq 3 User Volt 3 User Freq 4 User Volt 4 VAC 440.0V Motor Volt 0 Energy Save Manual Save % Kilo Watt Hour Inv. Temp. Motor Temp. No Motor Sel No Motor Level No Motor Time ETH Select ETH 1min ETH Cont Motor Type OL Level OL Time OLT Select OLT Level OLT Time Trip Select Stall Prev. Stall Level Acc/Dec Ch F Acc/Dec Freq Time Scale 0 1 0 0 1 0 1 0 1 0 1 1 2 1 2

Setting Range
(Linear) (Square) (User V/F) 0 to FU1-30 0 to 100 [%] 0 to FU1-30 0 to 100 [%] 0 to FU1-30 0 to 100 [%] 0 to FU1-30 0 to 100 [%] 73 to 115.0 [%] 0 to 600 [V] (None) (Manual) (Auto) 0 to 30 [%] M kWh 0 to 160 [Degree] 0 to 160 [Degree] (No) (Yes) 5 to 100 [%] 0.5 to 10.0 [sec] (No) (Yes) FU1-62 to 200 [%] 50 to FU1-61 (Maximum 150%) (Self-cool) (Forced-cool) 30 to 110 [%] 0 to 30 [sec] (No) (Yes) 30 to 150 [%] 0 to 60 [sec] 000 to 111 (Bit Set) 000 to 111 (Bit) 30 to 150 [%] 0 to FU1-30 (Max freq) (Delta freq) (0.01 sec)

Factory Default
0 (Linear) 15 [Hz] 25 [%] 30 [Hz] 50 [%] 45 [Hz] 75 [%] 60 [Hz] 100 [%] 100.0 [%] 0 [V] 0 (None) 0 [%] * * * 1 [Yes] 5 [%] 3.0 [sec] 1 (Yes) 150 [%] 120 [%] 0 (Selfcool) 110 [%] 10 [sec] 0 (No) 120 [%] 60 [sec] 100 000 (Bit) 100 [%] 0 [Hz] 0 (Max freq) 1 (0.1 sec)

Adj. During Run


FU1-40 FU1-41 FU1-42 FU1-43 FU1-44 FU1-45 FU1-46 FU1-47 FU1-48 FU1-49 FU1-50 FU1-51 FU1-52 Note10) FU1-54 FU1-55 FU1-56 FU1-57 FU1-58 FU1-59 FU1-60 FU1-61 FU1-62 FU1-63 FU1-64 FU1-65 FU1-66 FU1-67 Note11) FU1-68 FU1-69 FU1-70 FU1-71 FU1-72 FU1-73 FU1-74

Volts/Hz Pattern User V/FFrequency 1 User V/FVoltage 1 User V/FFrequency 2 User V/FVoltage 2 User V/FFrequency 3 User V/FVoltage 3 User V/FFrequency 4 User V/FVoltage 4 Input Voltage Adjustment Motor Rated Voltage Energy Save Energy Save % Integrating Wattmeter Inverter Temperature Motor Temperature No Motor Selection Trip Current Level Trip Time Setting Electronic Thermal Selection Electronic Thermal Level for 1 Minute Electronic Thermal Level for Continuous Characteristic Selection (Motor Type) Overload Warning Level Overload Warning Time Overload Trip Selection Overload Trip Level Overload Trip Delay Time Input/Output Phase Loss Protection Stall Prevention Mode Selection Stall Prevention Level Accel/Decel Change Frequency Reference Frequency for Accel and Decel Accel/Decel Time Scale

9229 922A 922B 922C 922D 922E 922F 9230 9231 9232 9233 9234 9236 9237 9238 9239 923A 923B 923C 923D 923E 923F 9240 9241 9242 9243 9244 9245 9246 9247 9248 9249 924A

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 9) FU1-41~48 only displayed when FU1-40 is set toUser V/F. 10) Only displayed when FU1-51 is set toManual . 11) Only displayed when FU1-66 is set toYes .

24

Industrial Inverter for Fan and Pump STARVERT iP5A

FU2 GROUP
CODE
FU2-00 FU2-01 FU2-02 FU2-03 FU2-04 FU2-05 FU2-06 FU2-07 FU2-08 Note12) FU2-10 FU2-11 FU2-12 FU2-13 FU2-14 FU2-15 FU2-16 FU2-20 FU2-21 FU2-22 FU2-23 Note14) FU2-24 FU2-25 FU2-26 Note15)
Note13)

Comm. Addr
9300 9301 9302 9303 9304 9305 9306 9307 9308 930A 930B 930C 930D 930E 930F 9310 9314 9315 9316 9317 9318 9319 931A

Description
Jump to Desired Code # Last Trip 1 Last Trip 2 Last Trip 3 Last Trip 4 Last Trip 5 Erase Trips Dwell Frequency Dwell Frequency Frequency Jump Selection Jump Frequency 1 Jump Frequency 1 Jump Frequency 2 Jump Frequency 2 Jump Frequency 3 Jump Frequency 3 Power ON Start Selection Restart after Fault Reset Speed Search Selection P Gain During Speed Search I Gain During Speed Search Number of Auto Retry Delay Time before Auto Retry

LCD Keypad Display


Jump Code Last Trip-1 Last Trip-2 Last Trip-3 Last Trip-4 Last Trip-5 Erase Trips Dwell Time Dwell Freq Jump Freq Low Jump Lo 1 High Jump Hi 1 Low Jump Lo 2 High Jump Hi 2 Low Jump Lo 3 High Jump Hi 3 Power-ON Run RST Restart Speed Search SS P-Gain SS I-Gain Retry Number Retry Delay 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 18 20 21 22 23 0 1 0 1 0 1 0 1

Setting Range
1 to 95 (Use Only LCD Keypad) By pressing [PROG] and [] key, the frequency, current, and operational status at the time of fault can be seen. (No) (Yes) 0 to 10 [sec] FU1-32 to FU1-30 (No) (Yes) 0 to FU2-12 FU2-11 to FU1-30 0 to FU2-14 FU2-13 to FU1-30 0 to FU2-16 FU2-15 to FU1-30 (No) (Yes) (No) (Yes) 0000 to 1111 (Bit Set) 0 to 9999 0 to 9999 0 to 10 0 to 60 [sec] (0.75kW) (1.5kW) (2.2kW) (3.7kW) (5.5kW) (7.5kW) (11.0kW) (15.0kW) (18.5kW) (22.0kW) (30.0kW) (37.0kW) (45.0kW) (55.0kW) (75.0kW) (90.0kW) (110.0kW) (132.0kW) (160.0kW) (220.0kW) (280.0kW) (315.0kW) (375.0kW) (450.0kW) 2 to 12 0 to 10 [Hz] 1 to 200 [A] 0.5 to 200 [A] 70 to 100 [%]

Factory Default
40 0 (None) 0 (None) 0 (None) 0 (None) 0 (None) 0 (No) 0 [sec] 5 [Hz] 0 (No) 10 [Hz] 15 [Hz] 20 [Hz] 25 [Hz] 30 [Hz] 35 [Hz] 0 (No) 0 (No) 0000 200 500 0 1 [sec]

Adj. During Run


* * * * *

FU2-40

9328

Rated Motor Selection for 5.5~450kW Inverter

Motor Select

*Depending on the inverter capacity

FU2-41 FU2-42 FU2-43 FU2-44 FU2-45

9329 932A 932B 932C 932D

Number of Motor Poles Rated Motor Slip Rated Motor Current (RMS) No Load Motor Current (RMS) Motor Efficiency

Pole Number Rated-Slip Rated-Curr Noload-Curr Efficiency

4 *Depending on FU2-40

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 12) Only displayed when FU2-07 is set to [1~10 sec]. 13) Only displayed when FU2-10 is set toYes . 14) Only displayed when FU1-23 is set to [DC-break]. 15) Only displayed when FU1-33 is set toYes .

25

iP5A

Parameter Description
FU2 GROUP
CODE
FU2-46 FU2-47 FU2-48

Comm. Addr
932E 932F

Description
Load Inertia Gain for Motor Speed Display

LCD Keypad Display


Inertia Rate RPM Factor

Setting Range

Factory Default
0 100 [%] 5 [kHz] 4 [kHz] 3 [kHz] 0 (Normal 1)

Adj. During Run


FU2-49

FU2-60 FU2-61 Note16) FU2-62 FU2-63 FU2-64 FU2-65 FU2-66 FU2-67 FU2-68 FU2-69 FU2-80 FU2-81 FU2-82 FU2-83 FU2-84 FU2-85 FU2-87 FU2-90 FU2-91 FU2-92

FU2-93

FU2-94 FU2-95

0 to 8 1 to 1000 [%] 5.5~22kW 0.7~15 [kHz] 30kW 0.7~10 [kHz] 9330 Carrier Frequency Carrier Freq 37~75kW 0.7~4 [kHz] 90~450kW 0.7~3 [kHz] 0 (Normal 1) 9331 PWM Type Selection PWM Mode 1 (Normal 2) 2 (Low leakage) 0 (V/F) 933C Control Mode Selection Control Mode 1 (Slip compen) 2 (Sensorless) 0 (No) 933D Auto Tuning Selection Auto Tuning 1 (Yes) 0 to (depending on FU2-40) 933E Stator Resistance of Motor Rs [ohm] 0 to (depending on FU2-40) 933F Leakage Inductance of Motor Lsigma [mH] * Automatically set corresponding to motor rating. If different, check motor rating setting. 9340 Pre-excitation Time Pre Ex Time 0 to 60 [sec] 9341 P Gain for Sensorless Control SL P-Gain 0 to 9999 9342 I Gain for Sensorless Control SL I-Gain 0 to 9999 0 (Manual) 9343 Manual/Auto Torque Boost Selection Torque Boost 1 (Auto) 9344 Torque Boost in Forward Direction Fwd Boost 0 to 15 [%] 9345 Torque Boost in Reverse Direction Rev Boost 0 to 15 [%] 9350 Power On Display Power On Disp 0 to 12 1 (Watt) 9351 User Display Selection User Disp 0 (Voltage) 9352 Software Version S/W Version Ver X.XX 9353 Last Trip Time Last Trip Time X:XX:XX:XX:XX:X 9354 Power On Time On-Time X:XX:XX:XX:XX:X 9355 Run-time Run-Time X:XX:XX:XX:XX:X 9357 Power Set Power Set 0.1~400 [%] 0 (Default) 935A Parameter Display Para. Disp 1 (All Para) 2 (Diff Para) 0 (No) 935B Read Parameter Para. Read 1 (Yes) 0 (No) 935C Write Parameter Para. Write 1 (Yes) 0 (No) 1 (All Groups) 2 (DRV) 3 (FU1) 935D Initialize Parameter Para. Init 4 (FU2) 5 (I/O) 6 (EXT) 7 (COM) 8 (APP) 935E Parameter Write Protection Para. Lock 0 to 9999 0 (No) 935F Parameter Save Para. Save 1 (Yes)

0 (V/F) 0 (No) *Depending on FU2-40 *Depending on FU2-40 1 [sec] 1000 100 0 (Manual) 2 [%] 2 [%] 0 0 (Voltage) Ver X.XX

100 0 (Default) 0 (No) 0 (No)

0 (No)

0 0 (No)

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 16) Only FU2-61~66 displayed when FU2-60 is set to [Sensorless].

26

Industrial Inverter for Fan and Pump STARVERT iP5A

I/O GROUP
CODE
I/O-00 I/O-01 Note17) I/O-02 I/O-03 I/O-04 I/O-05 I/O-06 I/O-07 I/O-08 I/O-09 I/O-10 I/O-11 I/O-12 I/O-13 I/O-14 I/O-15 I/O-16

Comm. Addr
9400 9401 9402 9403 9404 9405 9406 9407 9408 9409 940A 940B 940C 940D 940E 940F 9410

Description
Jump to Desired Code # Filtering Time Constant for V1 Signal Input V1 Input Minimum Voltage Frequency Corresponding to V1 Input Minimum Voltage V1 Input Minimum Voltage V1 Input Maximum Voltage Filtering Time Constant for I Signal Input I Input Minimum Current Frequency Corresponding to I Input Minimum Current Filtering Time Constant for I Signal Input Frequency Corresponding to I Input Maximum Current Pulse Input Method Pulse Input Filter Pulse input Minimum Frequency Frequency Corresponding to I/O-13 Pulse Input Maximum Frequency Frequency Corresponding to I/O-15 Pulse input Minimum Frequency

LCD Keypad Display


Jump Code V1 Filter V1 Volt x1 V1 Freq y1 V1 Volt x2 V1 Freq y2 I Filter I Curr x1 I Freq y1 I Curr x2 I Freq y2 P Pulse Set P Filter P Pulse x1 P Freq y1 0 1

Setting Range
1 to 98 (LCD Keypad Only) 0 to 9999 [msec] 0 to 12 [V] 0 to FU1-30 [Hz] 0 to 100.00 [**] 0 to 12 [V] 0 to FU1-30 [Hz] 0 to 100.00 [**] 0 to 9999 [msec] 0 to 20 [mA] 0 to FU1-30 [Hz] 0 to 100.00 [**] 0 to 20 [mA] 0 to FU1-30 [Hz] 0 to 100.00 [**] (A+B) (A) 0 to 9999 [msec] 0 to 10 [kHz] 0 to FU1-30 [Hz] 0 to 100.00 [**]
Note18) Note18) Note18) Note18) Note18)

Factory Default
1 10 [msec] 0 [V] 0 [Hz] 10 [V] 60 [Hz] 10 [msec] 4 [mA] 0 [Hz] 20 [mA] 60 [Hz] 1 (A) 10 [msec] 0 [kHz] 0 [Hz] 10 [kHz]

Adj. During Run


P Pulse x2 P Freq y2 0

0 to 100 [kHz] 0 to FU1-30 [Hz] 0 to 100.00 [**] (None) (Half of x1) (Below x1) (None) (FreeRun) (Stop) 0.1 to 120 [sec] 0 1 2 (Speed-L) (Speed-M) (Speed-H) (XCEL-L) (XCEL-M) (XCEL-H) (Dc-Brake) (2nd Func) 1 2 0
Note18)

60 [Hz]

I/O-17

9411

Criteria for Analog Input Signal Loss

Wire Broken

0 (None)

I/O-18

9412

Operating Selection at Loss of Freq. Reference Waiting Time after Loss of Freq. Reference

Lost Command

1 2

0 (None)

I/O-19

9413

Time Out

1.0 [sec]

I/O-20

9414

Programmable Digital Input TerminalM1 Define

M1 Define

3 4 5 6 7

0 (Speed-L)

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 17) When DRV-04 is set to either V1, V1S, I or V1+I or Pulse, only selected item codes are displayed in I/O-1~I/O-19. 18) Only user unit displayed when APP-02 or APP-80 is set to [Yes], after APP-06 is set to one of I, V, Pulse, after then when one of I/O-86~I/O-88 is set to either speed, percent, Bar, mBar, kPa, Pa.

27

iP5A

Parameter Description
I/O GROUP
CODE Comm. Addr Description LCD Keypad Display
8 9 10 11 12 13 14 15 16 17 18 19 I/O-20 9414 Programmable Digital Input TerminalM1 Define 20 M1 Define 21 22 23 24 25 26 27 28 29 30 31 32 33 34 I/O-21 I/O-22 I/O-23 I/O-24 I/O-25 I/O-26 I/O-27 9415 9416 9417 9418 9419 941A 941B Programmable Digital Input TerminalM2 Define Programmable Digital Input TerminalM3 Define Programmable Digital Input TerminalM4 Define Programmable Digital Input TerminalM5 Define Programmable Digital Input TerminalM6 Define Programmable Digital Input TerminalM7 Define Programmable Digital Input TerminalM8 Define M2 Define M3 Define M4 Define M5 Define M6 Define M7 Define M8 Define

Setting Range
(Exchange) (-Reserved-) (Up) (Down) (3-Wire) (Ext Trip) (Pre-Heat) (iTerm Clear) (Open-loop) (Main-drive) (Analog hold) (XCEL stop) (P Gain2) (-Reserved-) (Interlock1) (Interlock2) (Interlock3) (Interlock4) (Speed_X) (RST) (BX) (JOG) (FX) (RX) (ANA_CHG) (Pre-Excite) (Ext PID Run) Same as I/O-20 Same as I/O-20 Same as I/O-20 Same as I/O-20 Same as I/O-20 Same as I/O-20 Same as I/O-20

Factory Default

Adj. During Run

0 (Speed-L)

1 (Speed-M) 2 (Speed-H) 27 (RST) 28 (BX) 29 (JOG) 30 (FX) 31 (RX)

28

Industrial Inverter for Fan and Pump STARVERT iP5A

CODE
I/O-28 I/O-29 I/O-30 Note19) I/O-31 I/O-32 I/O-33 I/O-34 I/O-35 I/O-36 I/O-37 I/O-38 I/O-39 I/O-40 I/O-41 I/O-42 I/O-50 I/O-51 I/O-52 Note20) I/O-53 I/O-54 I/O-55 I/O-56 I/O-57 I/O-58 I/O-59 I/O-60 I/O-61 I/O-62 I/O-63

Comm. Addr
941C 941D 941E 941F 9420 9421 9422 9423 9424 9425 9426 9427 9428 9429 942A 9432 9433 9434 9435 9436 9437 9438 9439 943A 943B 943C 943D 943E 943F

Description
Terminal Input Status Filtering Time Constant for Programmable Digital Input Terminals Jog Frequency Setting Step Frequency 4 Step Frequency 5 Step Frequency 6 Step Frequency 7 Step Frequency 8 Step Frequency 9 Step Frequency 10 Step Frequency 11 Step Frequency 12 Step Frequency 13 Step Frequency 14 Step Frequency 15 Acceleration Time 1 (for Step speed) Deceleration Time 1 (for Step speed) Acceleration Time 1 (for Step speed) Deceleration Time 2 Acceleration Time 3 Deceleration Time 3 Acceleration Time 4 Deceleration Time 4 Acceleration Time 5 Deceleration Time 5 Acceleration Time 6 Deceleration Time 6 Acceleration Time 7 Deceleration Time 7

LCD Keypad Display


In Status Ti Filt Num Jog Freq Step Freq-4 Step Freq-5 Step Freq-6 Step Freq-7 Step Freq-8 Step Freq-9 Step Freq-10 Step Freq-11 Step Freq-12 Step Freq-13 Step Freq-14 Step Freq-15 Acc Time-1 Dec Time-1 Acc Time-2 Dec Time-2 Acc Time-3 Dec Time-3 Acc Time-4 Dec Time-4 Acc Time-5 Dec Time-5 Acc Time-6 Dec Time-6 Acc Time-7 Dec Time-7 0 1 2 3 4

Setting Range
00000000000/11111111111 2 to 1000 [msec]

Factory Default
00000000000 15 10 [Hz] 40 [Hz] 50 [Hz] 40 [Hz] 30 [Hz] 20 [Hz] 10 [Hz] 20 [Hz] 30 [Hz] 40 [Hz] 50 [Hz] 40 [Hz] 30 [Hz] 20 [sec] 20 [sec] 30 [sec] 30 [sec] 40 [sec] 40 [sec] 50 [sec] 50 [sec] 40 [sec] 40 [sec] 30 [sec] 30 [sec] 20 [sec] 20 [sec]

Adj. During Run


*

0 to FU1-30

I/O-70

9446

S0 Output Selection

S0 Mode

I/O-71 I/O-72 I/O-73 I/O-74 Note21) I/O-75

9447 9448 9449 944A 944B

S0 Output Adjustment S1 Output Selection S1 Output Adjustment Frequency Detection Level Frequency Detection Bandwidth

S0 Adjust S1 Mode S1 Adjust FDT Freq FDT Band 0 1 2 3 4 5 6 7

I/O-76

944C

Programmable Digital Output Terminal Define (Aux terminal)

Aux Mode1

0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] (Frequency) (Current) (Voltage) (DC link Vtg) (Ext PID Out) 10 to 200 [%] Same as I/O-70 10 to 200 [%] 0 to FU1-30 [Hz] 0 to FU1-30 [Hz] (None) (FDT-1) (FDT-2) (FDT-3) (FDT-4) (FDT-5) (OL) (IOL)

0 (Frequency)

100 [%] 2 (Voltage) 100 [%] 30 [Hz] 10 [Hz]

0 (None)

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 19) I/O-30~I/O-34 displayed only when one of I/O-20~I/O-27 is set to either JOG, Speed_L, Speed_M, Speed_H. I/O-35~I/O-42 displayed only when one of I/O-20~I/O-27 is set to Speed_X. 20) I/O-52~I/O-63 displayed only when one of I/O-20~I/O-27 is set to either XCEL_L, XCEL_M, XCEL_H. 21) I/O-74~I/O-75 displayed only when one of I/O-76~I/O-79 is set to either FDT-1~FDT5.

29

iP5A

Parameter Description
I/O GROUP
CODE Comm. Addr Description LCD Keypad Display
8 9 10 11 12 13 14 15 16 17 18 19 20

Setting Range
(Stall) (OV) (LV) (OH) (Lost Command) (Run) (Stop) (Steady) (INV line) (COMM line) (SSearch) (Ready) (MMC) Same as I/O-76 Same as I/O-76 Same as I/O-76 000 to 111 [bit] 00000000/11111111 0 to 9999 0 to 9999 0 (Power On Fan) 1 (Run Fan) 2 (Temper-Fan) 0 to 70 [] 0 (Speed) 1 (Percent) 2 (Bar) 3 (mBar) 4 (kPa) 5 (Pa) Same as I/O-86 Same as I/O-86 1 to 250 0 (1200 bps) 1 (2400 bps) 2 (4800 bps) 3 (9600 bps) 4 (19200 bps) 0 (None) 1 (FreeRun) 2 (Stop) 0.1 to 120 [sec] 2 to 1000 [msec] 00000000000/11111111111 1 to 1000 000 to 111 [bit] 0 to 255 [8C]

Factory Default

Adj. During Run

I/O-76

944C

Programmable Digital Output Terminal Define (Aux terminal)

Aux Mode1

0 (None)

I/O-77 I/O-78 I/O-79 I/O-80 I/O-81 I/O-82 I/O-83 I/O-84 I/O-85

944D 944E 944F 9450 9451 9452 9453 9454 9455

Programmable Digital Output Terminal Define Programmable Digital Output Terminal Define Programmable Digital Output Terminal Define Fault Output Relay Setting (3A, 3B, 3C) Terminal Output Status Waiting time after Fault Output Relay On Waiting time after Fault Output Relay Off Fan Con Sel (37~90kW) Fan Temp (37~90kW)

Aux Mode2 Aux Mode3 Aux Mode4 Relay Mode Out Status Relay On Relay Off Fan Mode Fan Temper

0 (None) 0 (None) 0 (None) 010 [bit] 00000000 0 0 0 70 []

I/O-86

9456

Voltage Input User Unit Selection

V1 Unit Sel

0 (Speed)

I/O-87 I/O-88 I/O-90

9457 9458 945A

Current Input User Unit Selection Pulse Input User Unit Selection Inverter Number

I Unit Sel Pulse Unit Sel Inv No.

0 (Speed) 0 (Speed) 1

I/O-91 Note22)

945B

Baud Rate Selection

Baud Rate

3 (9600 bps)

I/O-92 I/O-93 Note23) I/O-94 I/O-95 I/O-96 I/O-97 I/O-98

945C 945D 945E 945F 9460 9461 9462

Operating Methodat Loss of Freq. Reference Waiting Time after Loss of Freq. Reference Communication Response Delay Time A or B Contact Input Time Overheat Trip Selection Motor Overheat Trip Temperature

COM Lost Cmd COM Time Out Delay Time In No/Nc Set In Check Time OH Trip Sel MO Trip Temp

0 (None) 1.0 [sec] 5 [msec] 00000000000 1 [msec] 010 [bit] 110 [8C]

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 22) 38400 bps can be set only when the external communication option card is installed. 23) Only I/O-92 ~ I/O-93 displayed when DRV-03/04 is set to [int485].

30

Industrial Inverter for Fan and Pump STARVERT iP5A

APP GROUP
CODE
APP-00 APP-01 APP-02 APP-03 Note25) APP-04 Note26)
Note24)

Comm. Addr
9700 9701 9702 9703 9704

Description
Jump to Desired Code # Application Mode Selection PID Operation Selection PID F Gain Selection PID Auxiliary Reference Mode Selection

LCD Keypad Display


Jump Code App Mode Proc PI Mode PID F-gain Aux Ref Mode 0 1 0 1 2 3 4 5 6 7 8 0 1 2 0 1 0 1

Setting Range
1 to 99 (LCD Keypad Only) (None) (MMC) (No) (Yes) 0 to 999.9[%] (No) (Yes) (Keypad-1) (Keypad-2) (V1) (V1S) (I) (V1+I) (Pulse) (Int. 485) (Ext. PID) (I) (V1) (Pulse) 0 to 999.9 [%] 0 to 32.0 [sec] 0 to100 [msec] 0.00 to FU1-30 FU1-32 to APP-10 0.0 to 999.9 [%] 0.0 to 999.9 [%] 0.0 to 100.0 [%] (No) (Yes) (No) (Yes) 0 to 6000 [sec] 0 to 6000 [sec] 30 to FU1-30 [Hz] (Linear) (Square) (User V/F) 0 to 15 [%] 0 to 15 [%] 30 to 150 [%] FU2-28 to 200 [%] 50 to FU2-27 (Max 150%) 1 to 200 [A] * 1 to 4 * 0 to 7 0 to FU1-30

Factory Default
1 0 (None) 0 (No) 0.0 [%] 0 (No)

Adj. During Run


APP-05 Note27)

9705

PID Auxiliary Reference Signal Selection

Aux Ref Sel

2 (V1)

APP-06 APP-07 APP-08 APP-09 APP-10 APP-11 APP-12 APP-13 APP-14 APP-15 APP-17 APP-20 Note28) APP-21 APP-22 APP-23 APP-24 APP-25 APP-26 APP-27 APP-28 APP-29 APP-40 Note29) APP-41 APP-42 APP-43 APP-44

9706 9707 9708 9709 970A 970B 970C 970D 970E 960F 9711 9714 9715 9716 9717 9718 9719 971A 971B 971C 971D 9728 9729 972A 972B 972C

PID Feedback Signal Selection P Gain for PID Control I Gain for PID Control D Gain for PID Control High Limit Frequency for PID Control Low Limit Frequency for PID Control PID Output Scale PID P2 Gain P Gain Scale PID Output Inverse PID U Curve Feedback Select 2nd Acceleration Time 2nd Deceleration Time 2nd Base Frequency 2nd V/F Pattern 2nd Forward Torque Boost 2nd Reverse Torque Boost 2nd Stall Prevention Level 2nd Electronic Thermal Level for 1 minute 2nd Electronic Thermal Level for Continuous 2nd Rated Motor Current Number of Auxiliary Motor Run Display Aux. Motor Start Selection Operation Time Display on Auto Change The Number of Aux Motor Start Frequency of Aux. Motor 1

PID F/B PID P Gain PID I Time PID D Time PID Limit-H PID Limit-L PID Out Scale PID P2-Gain P Gain Scale Out Inverse PID U Fbk 2nd Acc Time 2nd Dec Time 2nd Base Freq 2nd V/F 2nd F-Boost 2nd R-Boost 2nd Stall 2nd ETH 1min 2nd ETH Cont 2nd R-Curr Aux Mot Run Starting Aux Auto Op Time Nbr Aux s Start Freq 1

0 (I) 1.0 [%] 10.0 [sec] 0.0 [msec] 60 .00 [Hz] 0.5 [Hz] 100.0 [%] 100.0 [%] 100.0 [%] 0 (No) 0 (No) 5 [sec] 10 [sec] 60 [Hz] 0 (Linear) 2 [%] 2 [%] 100 [%] 130 [%] 120 [%] 3.6 [A] * 1 * 4 49.99 [Hz]

0 1 0 1

0 1 2

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 24) MMC (Multi Motor Control) function is applied to inverters only for 5.5~90kW (7.5~125HP). 25) Only APP-03~APP-17 displayed when APP-02 is set to [Yes] (5.5~90kW/7.5~125HP). Only APP-03~APP-17 and APP-63~APP-65 displayed when APP-2 is set to [Yes] (110~450kW/150~600HP). 26) If APP-04 is set to no, DRV-04 setting will be reference of process PID. And APP-05 setting will be ignored. 27) If APP-04 is set, APP-04 will appear. And APP-05 setting value will be reference of process PID, DRV-04 setting will be ignored. 28) Only APP-20~APP-29 displayed only when one of I/O-20~I/O-27 is set to either 2nd Func . 29) Only APP-40~APP-71 displayed when APP-01 is set to [MMC].

31

iP5A

Parameter Description
APP GROUP
CODE
APP-45 APP-46 APP-47 APP-48 APP-49 APP-50 APP-51 APP-52 APP-53 APP-54 APP-55 APP-56 APP-57 APP-58 APP-59 APP-60 APP-61 APP-62 APP-63 APP-64 APP-65 APP-66 APP-67 APP-68 APP-69 APP-71 APP-74 APP-75 APP-76 APP-80

Comm. Addr
972D 972E 972F 9730 9731 9732 9733 9734 9735 9736 9737 9738 9739 973A 973B 973C 973D 973E 973F 9740 9741 9742 9743 9744 9745 9747 974A 974B 974C 9750

Description
Start Frequency of Aux. Motor 2 Start Frequency of Aux. Motor 3 Start Frequency of Aux. Motor 4 Start Frequency of Aux. Motor 5 Start Frequency of Aux. Motor 6 Start Frequency of Aux. Motor 7 Stop Frequency of Aux. Motor 1 Stop Frequency of Aux. Motor 2 Stop Frequency of Aux. Motor 3 Stop Frequency of Aux. Motor 4 Stop Frequency of Aux. Motor 5 Stop Frequency of Aux. Motor 6 Stop Frequency of Aux. Motor 7 Delay Time before Operating Aux Motor Delay Time before Stopping Aux Motor Accel Time when Number of Pump Decreases Decel Time when Number of Pump Increases PID Bypass Selection Sleep Delay Time Sleep Frequency Wake-Up Level Auto Change Mode Selection Auto Change Time Auto Change Level Inter-Lock Selection Pressure Difference for Aux Motor Stop PrePID Reference Frequency PrePID Exit Level PrePID Stop Delay Ext PID Operation Selection

LCD Keypad Display


Start Freq 2 Start Freq 3 Start Freq 4 Start Freq 5 Start Freq 6 Start Freq 7 Stop Freq 1 Stop Freq 2 Stop Freq 3 Stop Freq 4 Stop Freq 5 Stop Freq 6 Stop Freq 7 Aux Start DT Aux Stop DT PID Acc Time PID Dec Time Regul Bypass Sleep Delay Sleep Freq Wake Up Level Auto Ch_Mode Auto Ex-Intv Auto Ex-Level Inter-Lock Actual Pr Diff PrePID Freq PrePID Exit PrePID Dly Ext PI Mode 0 1 0 1 2 3 0 1 2 0 1 0 1

Setting Range

Factory Default
49.99 [Hz] 49.99 [Hz] 49.99 [Hz] 49.99 [Hz] 49.99 [Hz] 49.99 [Hz] 20.00 [Hz] 20.00 [Hz] 20.00 [Hz] 20.00 [Hz] 15.00 [Hz] 15.00 [Hz] 15.00 [Hz] 5.0 [sec] 5.0 [sec] 2.0 [sec] 2.0 [sec] 0 (No) 60.0 [sec] 0.00 [Hz] 35.0 [%] 0 72:00 20.0 [Hz] 0 (No) 2 [%] 0 0 600 0 (No)

Adj. During Run

0 to FU1-30

APP-81 Note30) APP-82 APP-83 APP-85 APP-86 APP-87 APP-88 APP-89 APP-90 APP-91 APP-92 APP-93 APP-95 APP-97

9751 9752 9753 9755 9756 9757 9758 9759 975A 975B 975C 975D 975F 9761

Ext PID Reference Signal Selection Ext PID Reference Level Ext PID Feedback Signal Selection P Gain for ExtPID I Time for ExtPID D Time for ExtPID High Limit Frequency for ExtPID Control Low Limit Frequency for ExtPID Control ExtPID Output Scale ExtPID P2 Gain ExtPID P Gain Scale ExtPID F Gain ExtPID Output Inverse ExtPID Loop Time

Ext Ref Sel Ext Ref Perc Ext Fbk Sel ExtPID P Gain ExtPID I Time ExtPID D Time ExtPID lmt-H ExtPID lmt-L ExtPID Scale Ext P2 Gain Ext P Scale ExtPID F Gain ExtOut Inverse Ext Loop Time

0 1

0.0 to 999.9 [sec] 0.0 to 999.9 [sec] 0 to 600.0 [sec] 0 to 600.0 [sec] (No) (Yes) 0.0 to 9999 [sec] 0 to FU1-30 [Hz] 0.0 to 100.0 [%] 0, 1 (Aux), 2 (Main) 00:00 to 99:00 FU1-32 to FU1-30 [Hz] (No) (Yes) 0 to100 [%] 0 to FU1-30 0 to 100.0 [%] 0 to 9999 (No) (Yes) (I) (V1) (Pulse) (Key-Pad) 0 to 100.00 [%] (I) (V1) (Pulse) 0 to 999.9 [%] 0 to 32.0 [sec] 0 to 2000 [msec] 0 to 100.00 [%] 0 to 30.00 [%] 0 to 999.9 [%] 0 to 999.9 [%] 0 to 100.0 [%] 0 to 999.9 [%] (No) (Yes) 50 to 200 [msec]

3 (Key-Pad) 50.00 [%] 0 (I) 1.0 [%] 10.0 [sec] 0 [msec] 100.00 [%] 0 [%] 100.0 [%] 100.0 [%] 100.0 [%] 0.0 [%] 0 (No) 100 [msec]

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 30) Only APP-81~APP-97 displayed when APP-80 is set to [Yes].

32

Industrial Inverter for Fan and Pump STARVERT iP5A

Trial Run
Operation Example (1)
V/F Control + Analog Voltage Input (V1) + Operation via Terminal (FX/RX) Operation condition Control mode: V/F control Frequency command: 50 [Hz] analog input via V1 terminal Accel/Decel time: Accel15 [sec], Decel25 [sec] Drive mode: Run/Stop via FX/RX terminal, Control terminal: NPN mode
3P AC INPUT R (L1) S (L2) T (L3) G S0 M8 (RX) M7 (FX) M6 M5 M4 M3 M2 M1 CM Potentiometer 2 [kohm], 1/2W V+ V1 5G 3A 3C 3B 5G S1 U V W

Wiring

IM

S/W

Step
1 2 3 4 5

Parameter setting
Control Mode Selection Drive Mode Frequency Mode 50 [Hz] Freq Command Setting Accel/Decel Time

Code
FU2-60 DRV-3 DRV-4 DRV-0 DRV-1 DRV-2 Set it to 0 (V/F). Set it to Fx/Rx-1.

Description

Set V1 Analog input value in frequency mode. Set freq command 50 [Hz] via V1 (Potentiometer). Set Accel time to 15 [sec] in DRV-2. Set Decel time to 25 [sec] in DRV-3. Motor starts to rotate in forward direction at 50Hz with Accel time 15 [sec] when

Terminal FX

I/O-26

FX terminal is turned ON. Motor decelerates to stop with Decel time 25 [sec] when FX terminal is turned OFF. When RX terminal is turned ON motor starts to rotate in Reverse direction

Terminal RX

I/O-27

at 50 [Hz] with Accel time 15 [sec]. When it is OFF, motor decelerates to stop with Decel time 25 [sec].

33

iP5A

Trial Run
Operation Example (2)
V/F control + Analog input (V1S) + Operation via terminal FX/RX Operation condition Control mode: V/F control Frequency command: Setting 50 [Hz] via Analog input (V1S) Accel/Decel time: Accel time 15 [sec], Decel time 25 [sec] Drive mode: Run/Stop via FX/RX, Control terminal: NPN mode
3P AC INPUT R (L1) S (L2) T (L3) G S0 M8 (RX) M7 (FX) M6 M5 M4 M3 M2 M1 CM Potentiometer 2 [kohm], 1/2W V+ V1 V3A 3C 3B 5G S1 U V W

Wiring

IM

S/W

Step
1 2 3 4 5

Parameter setting
Control Mode Selection Drive Mode Frequency Mode Operating Frequency Command 50 [Hz] Setting Accel/Decel Time Setting

Code
FU2-60 DRV-3 DRV-4 DRV-0 DRV-1 DRV-2 Set it to 0 (V/F).

Description
Set it to 1 (Fx/Rx-1). Set it to 3 (V1S). Set 50 [Hz] via potentiometer (V1S). Set accel time to 15 [sec] in DRV-1 with decal time to 25 [sec] in DRV-2. When FX terminal is turned ON, motor rotating in forward direction starts

FX Terminal (M7)

IO-26

running at 50 [Hz] for 15 [sec]. When FX terminal is turned OFF, motor decelerates to stop for 25 [sec]. When RX terminal is turned ON, motor rotating in reverse direction starts

RX Terminal (M8)

IO-27

running at 50 [Hz] for 15 [sec]. When RX terminal is turned OFF, motor decelerates to stop for 25 [sec].

34

Industrial Inverter for Fan and Pump STARVERT iP5A

Dimensions
SV055iP5A (200/400V Class)

DRV

FU1

FU2

I/O

EXT

LC-200
MODE PROG ENTER

LE-200
RUN SHIFT

ESC SHIFT

STOP REV
RESET

FWD

PROG ENT

C1
STOP
RESET

RUN

C2

C3

7.5

W2 W1

H2 H1

D1

mm (inches)

Model
SV055iP5A-2/4

W1
150 (5.91)

W2
130 (5.12)

H1
284 (11.18)

H2
269 (10.69)

D1
156.5 (6.16)

C1
24 (0.98)

C2
24 (0.98)

C3
24 (0.98)

Enclosure Type
IP20 UL Type 1

SV075~300iP5A (200/400V Class)

DRV

FU1

FU2

I/O

EXT

LE-200
LC-200
MODE PROG ENTER

RUN SHIFT

ESC SHIFT

STOP REV
RESET

FWD

PROG ENT

STOP
RESET

RUN

SV150~300 iP5A-2/4
C1 C2 C3

H1 H2

7.5

W3 W2 W1

W3

D1

SV075~110 iP5A-2/4 mm (inches)

Model
SV075iP5A-2/4 SV110iP5A-2/4 SV150iP5A-2/4 SV185iP5A-2/4 SV220iP5A-2/4 SV300iP5A-2/4

W1

W2

W3
6 (0.23) 6 (0.23) 9 (0.35) 9 (0.35) 9 (0.35) 9 (0.35)

H1

H2

D1

C1

C2

C3

Enclosure Type
IP20 UL Type 1 IP20 UL Type 1 IP00 UL Open IP00 UL Open IP00 UL Open IP00 UL Open

200 (7.87) 180 (7.09) 200 (7.87) 180 (7.09) 250 (9.84) 230 (9.06) 250 (9.84) 230 (9.06) 304 (11.97)284 (11.18) 304 (11.97)284 (11.18)

284 (11.18)269 (10.69) 182 (7.16) 35 (1.37) 24 (0.98) 35 (1.37) 284 (11.18)269 (10.69) 182 (7.16) 35 (1.37) 24 (0.98) 35 (1.37) 385 (15.16)370 (14.57) 201 (7.91) 385 (15.16)370 (14.57) 201 (7.91) 460 (18.11)445 (17.52) 234 (9.21) 460 (18.11)445 (17.52) 234 (9.21) -

35

iP5A

Dimensions
SV150~300iP5A (UL Type 1 or UL Open Type with Conduit Option used, 200V/400V Class)
W1 W2 Note) Mounting NEMA 1 conduit option to the 15~90kW (20~125HP) Open Type meets NEMA 1 but does not comply with UL Enclosed Type 1. To that end, please purchase UL Type 1 product.

LC-200
MODE PROG ENTER

ESC SHIFT

STOP REV
RESET

FWD

H2 H1 H3

9 7.5

W3

Model
SV150iP5A-2/4 SV185iP5A-2/4 SV220iP5A-2/4 SV300iP5A-2/4

W1
250 (9.84) 250 (9.84) 304 (11.97) 304 (11.97)

W2
230 (9.06) 230 (9.06) 284 (11.18) 284 (11.18)

H1
200.8 (7.9) 200.8 (7.9) 236 (9.29) 236 (9.29)

H2
385 (15.16) 385 (15.16) 460 (18.11) 460 (18.11)

H3
370 (14.57) 370 (14.57) 445 (17.52) 445 (17.52)

D1
454.2 (17.88) 454.2 (17.88) 599.2 (23.59) 599.2 (23.59)

D2
201 (7.91) 201 (7.91) 234 (9.21) 234 (9.21)

C3
146 (5.74) 146 (5.74) 177.5 (6.98) 177.5 (6.98)

IP20 UL Type 1 IP20 UL Type 1 IP20 UL Type 1 IP20 UL Type 1

SV150~SV300 iP5A (400V Class)-Built-in DCL Type

W1 W2

D1

LC-200
MODE PROG ENTER

ESC SHIFT

STOP REV
RESET

FWD

H1 H2

W3

Model
SV150, 185iP5A-4L SV220, 300iP5A-4L

W1
250 (9.84) 260 (10.23)

W2
186 (7.32) 220 (8.66)

W3
7 (0.28) 7 (0.28)

H1
403.5 (15.88) 480 (18.89)

H2
392 (15.43) 468.5 (18.44)

D1
261.2 (10.28) 268.6 (10.57)

IP00 UL Type 1 IP20 UL Type 1

36

D2

mm (inches) Enclosure Type

mm (inches) Enclosure Type

D1

Industrial Inverter for Fan and Pump STARVERT iP5A

SV150~SV300 iP5A (Built-in DCL Type, UL Type 1 or UL Open Type with Conduit Option used, 400V Class)
W1 W2

LC-200
MODE PROG ENTER

ESC SHIFT

STOP REV
RESET

FWD

H1

H2

W3

Model
SV150, 185iP5A-4L SV220, 300iP5A-4L

W1
250 (9.84) 260 (10.23)

W2
186 (7.32) 220 (8.66)

W3
7 (0.28) 7 (0.28)

H1

H2

D1

D2
188.4 (7.42) 188.8 (7.43)

475.5 (18.72) 392 (15.43) 261.2 (10.28) 552 (21.73) 468.5 (18.44) 268.6 (10.57)

IP20 UL Type 1 IP20 UL Type 1

SV370~SV550iP5A (400V Class)

LC-200
MODE PROG ENTER

ESC SHIFT

STOP REV
RESET

FWD

H1 H2

D1 W3 W2 W1 W3

Model
SV370, 450iP5A-4 SV550iP5A-4 SV370, 450iP5A-4L (Built-in DCLType) SV550iP5A-4L (Built-in DCL Type)

W1
300 (11.81) 300 (11.81) 300 (11.81) 300 (11.81)

W2
190 (7.48) 190 (7.48) 190 (7.48) 190 (7.48)

W3
9 (0.35) 9 (0.35) 9 (0.35) 9 (0.35)

H1
534 (21.02) 534 (21.02) 684 (26.92) 684 (26.92)

H2

D1

515 (20.28) 265.6 (10.46) 515 (20.28) 292.6 (11.52) 665 (26.18) 265.6 (10.46) 665 (26.18) 292.6 (11.52)

D2

mm (inches) Enclosure Type

mm (inches) Enclosure Type


IP00 UL Open IP00 UL Open IP00 UL Open IP00 UL Open

D1

37

iP5A

Dimensions
SV370~550iP5A (UL Type 1 or UL Open Type with Conduit Option Used, 400V Class)
W1 W2 Note) Mounting NEMA 1 conduit option to the 15~90kW (20~125HP) Open Type meets NEMA 1 but does not comply with UL Enclosed Type 1. To that end, please purchase UL Type 1 product.

LC-200
MODE PROG ENTER

ESC SHIFT

STOP REV
RESET

FWD

H1

H2

W3

Model
SV370, 450iP5A-4 SV550iP5A-4 SV370, 450iP5A-4L SV550iP5A-4L

W1
300 (11.81) 300 (11.81) 300 (11.81) 300 (11.81)

W2
190 (7.48) 190 (7.48) 190 (7.48) 190 (7.48)

W3
9 (0.35) 9 (0.35) 9 (0.35) 9 (0.35)

H1
642 (25.28) 642 (25.28) 792 (31.18) 792 (31.18)

H2
515 (20.28) 515 (20.28) 665 (26.18) 665 (26.18)

D1

D2

265.6 (10.46) 163.4 (6.43) 292.6 (11.52) 190.4 (7.5) 265.6 (10.46) 163.4 (6.43) 292.6 (11.52) 190.4 (7.5)

IP20 UL Type 1 IP20 UL Type 1 IP20 UL Type 1 IP20 UL Type 1

SV750, 900iP5A (400V Class)

LC-200
MODE PROG ENTER

ESC SHIFT

STOP REV
RESET

FWD

H1 H2

W3

W2 W1

W3

D1

Model
SV750, 900iP5A-4 SV750, 900iP5A-4L (Built-in DCL Type)

W1
370 (14.57) 370 (14.57)

W2
220 (8.66) 220 (8.66)

W3
9 (0.35) 9 (0.35)

H1
610 (24.02) 760 (29.92)

H2
586.5 (23.09) 736.6 (28.99)

D1
337.6 (13.29) 337.6 (13.29)

IP00 UL Open IP00 UL Open

38

D2

mm (inches) Enclosure Type

mm (inches) Enclosure Type

D1

Industrial Inverter for Fan and Pump STARVERT iP5A

SV750, 900iP5A (UL Type 1 or UL Open Type with Conduit Option used, 400V Class)
W1 W2 Note) Mounting NEMA 1 conduit option to the 15~90kW (20~125HP) Open Type meets NEMA 1 but does not comply with UL Enclosed Type 1. To that end, please purchase UL Type 1 product.

LC-200
MODE PROG ENTER

ESC SHIFT

STOP REV
RESET

FWD

H1

H2

W3

D2

D1

mm (inches)

Model
SV750, 900iP5A-4 SV750, 900iP5A-4L (Built-in DCL Type)

W1
370 (14.57) 370 (14.57)

W2
220 (8.66) 220 (8.66)

W3
9 (0.35) 9 (0.35)

H1
767.5 (30.22) 917.5 (36.12)

H2
586.5 (23.09) 736.5 (28.99)

D1
337.6 (13.29) 337.6 (13.29)

D2
223.4 (8.8) 223.4 (8.8)

Enclosure Type
IP20 UL Type 1 IP20 UL Type 1

mm (inches)

SV1100, 1600iP5A (400V Class)

Model
SV1100, 1320iP5A-4L SV1600iP5A-4L

W1
510 (20.08) 510 (20.08)

W2
381 (15.00) 381 (15.00)

W3
11 (0.43) 11 (0.43)

H1

H2

D1

Enclosure Type
IP00 UL Open IP00 UL Open

768.5 (30.26) 744 (29.29) 422.6 (16.64) 844 (33.23) 819.5 (32.26) 422.6 (16.64)

mm (inches)

SV2200, 2800iP5A (400V Class)

Model
SV2200, 2800iP5A-4L

W1
690 (27.17)

W2
581 (22.87)

W3
14 (0.55)

H1

H2

D1

Enclosure Type
IP00 UL Open

1063 (41.85) 1028 (40.49) 449.6 (17.70)

mm (inches)

SV3150, 4500iP5A (400V Class)

Model
SV3150, iP5A-4L SV3750, 4500iP5A-4L

W1
772 (30.39) 922 (36.30)

W2
500 (19.69) 580 (22.83)

W3
13 (0.51) 14 (0.55)

H1

H2

D1

Enclosure Type
IP00 UL Open IP00 UL Open

1140.5 (44.90) 1110 (43.70) 442 (17.40) 1302.5 (51.28)1271.5 (50.06) 495 (19.49)

39

iP5A

DB (Dynamic Braking) Unit


DBU Models
UL Inverter Applicable motor rating
11~15 kW (15~20 HP) 200V class 18.5~22 KW (25~30 HP) 30~37 kW (40~50 HP) 45~55 kW (60~75 HP) Non UL type 400V class 11~15 kW (15~20 HP) 18.5~22 kW (25~30 HP) 30~37 kW (40~50 HP) 45~55 kW (60~75 HP) 75 kW (100 HP) 11~15 kW (15~20 HP) 200V class 18.5~22 kW (25~30 HP) 30~37 kW (40~50 HP) 45~55 kW (60~75 HP) 11~15 kW (15~20 HP) 18.5~22 kW (25~30 HP) UL type 30~37 kW (40~50 HP) 45~55 kW (60~75 HP) 400V class 75 kW (100 HP) 90~110 kW (125~150 HP) 132~160 kW (200~250 HP) 220 kW (300 HP) 280~315 kW (350~400 HP) 375~450 kW (500~600 HP) SV075DBH-4 SV150DBU-2U SV220DBU-2U SV370DBU-2U SV550DBU-2U SV150DBU-4U SV220DBU-4U SV370DBU-4U SV550DBU-4U SV750DBU-4U SV550DBU-4, 2set SV750DBU-4, 2set SV750DBU-4, 3set Group 3.

DB Unit
SV150DBU-2 SV220DBU-2 SV037DBH-2 SV037DBH-2, 2set SV150DBU-4 SV220DBU-4 SV037DBH-4

Dimension
Group 1. Group 2. Group 1.

Group 2.

Terminal Configuration Group 1 -

CM G P

OH N N B2 G
Description
Ground terminal

G P/B1 B1

B2

B1

Group 2 -

Group 3 -

B2
Terminals
N P CM OH*

Terminals
G B2 B1 N P

Description
Connect to inverter terminal N Connect to inverter terminal P1 OH common Over Heat Trip output terminal (Open Collector output: 20mA, 27V DC)

Connect to DB Resistors B2 Connect to DB Resistors B1 Connect to inverter terminal N Connect to inverter terminal P1

40

Industrial Inverter for Fan and Pump STARVERT iP5A

Wiring for DB unit and DB resistor (For 5.5~90kW/7.5~125HP inverters)

DB Resistor
TH2 TH1

DB Unit
B2 B1 P
Short

B2 B1

G N

Max distance between P & P2: 5m

P1 (+)

P2 (+)

N (-)

MCCB (Option) 3 AC Input 50/60 Hz R (L1) S (L2) T (L3) G U V W

Motor

Programmable Digital Input: Ext Trip

M1 M2 M3 M4 M5 M6 M7 M8 CM

Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA

S0 S1 5G

Output Frequency Meter Output Voltage Meter Common for output meter signal

3A 3C 3B

Fault Contact Output less than AC250V (DC30V), 1A

Common Terminal

DB resistor terminal
B1, B2

Description
Wire terminal properly based on wiring block diagram. Connect a DB resistor to the DB Unit s B1, B2 terminals. Thermal sensor terminal of DB resistor. Normal temperature (Ambient): Contact ON (TH1-TH2 closed) DB resistor overheated: Contact OFF (TH1-TH2 Open). Wire it to the inverter terminal defined as External Trip.

TH1, TH2

41

iP5A

DB (Dynamic Braking) Unit


Group 1
(Unit: mm)

4-M5 Mounting

Dynamic Braking Unit


WIRING
U R V S (P2) T W P N

IM

B1 B2 G B2 B1 N P

185

192

OHT

POWER

RUN

12.5

125 150

12.5

3.5

172

68.5

42

Industrial Inverter for Fan and Pump STARVERT iP5A

Group 2
(Unit: mm)

80

Dynamic Braking Unit

RESET POWER 245 OHT OCT 258 RUN 231.5 12 5.5 80 123 130 5

15 27

75

43

iP5A

DB (Dynamic Braking) Unit


Group 3
(Unit: mm)

44

Industrial Inverter for Fan and Pump STARVERT iP5A

External DB Resistor
iP5A do not have built-in DB resistor on power stack as factory installation. External DB Unit and Resistor (Optional) should be installed. See the following table for more details (ED: 5%, Continuous Braking Time: 15 sec). If Enable duty (%ED) is increased to 10%, use external DB resistor having twice Wattage rating.
Applied motor capacity (kW/HP)
5.5/7.5 7.5/10 11/15 15/20 18.5/25 22/30 30/40 5.5/7.5 7.5/10 11/15 15/20 18.5/25 22/30 30/40 37/50 45/60 55/75 75/100 90/125

Operating rate (ED/Continuous Braking Time)


5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 10%/6 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 10%/6 sec 10%/6 sec 10%/6 sec 10%/6 sec 10%/6 sec 10%/6 sec

100 % Braking Torque [ohm]


30 20 15 11 9 8 4.2 120 90 60 45 35 30 16.9 16.9 11.4 11.4 8.4 8.4

150% Braking Torque [ohm]


20 15 10 8 5 5 85 60 40 30 20 20 -

[W]
700 1000 1400 2000 2400 2800 6400 700 1000 1400 2000 2400 2800 6400 6400 9600 9600 12800 12800

Type
Type3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 -

[W]
800 1200 2400 2400 3600 3600 1000 1200 2000 2400 3600 3600 -

Type
Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 -

200V

400V

Peripheral Device
MCCB (Molded Case Circuit Breaker) and MC (Magnetic Contactor)
Voltage Motor [kW]
5.5 7.5 11 15 18.5 22 30

Inverter Model
SV055iP5A-2 SV075iP5A-2 SV110iP5A-2 SV150iP5A-2 SV185iP5A-2 SV220iP5A-2 SV300iP5A-2

MCCB (LS Industrial Systems)


ABS53b/50A ABS63b/60A ABS103b/100A ABS103b/100A ABS203b/125A ABS203b/150A ABS203b/175A

MC (LS Industrial Systems)


GMC-40 GMC-40 GMC-50 GMC-85 GMC-100 GMC-100 GMC-150

200V Class

45

iP5A

Peripheral Device
MCCB (Molded Case Circuit Breaker) and MC (Magnetic Contactor)
Voltage Motor [kW]
5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 220 280 315 375 450

Inverter Model
SV055iP5A-4 SV075iP5A-4 SV110iP5A-4 SV150iP5A-4 SV185iP5A-4 SV220iP5A-4 SV300IP5A-4 SV370iP5A-4 SV450iP5A-4 SV550iP5A-4 SV750iP5A-4 SV900iP5A-4 SV1100iP5A-4 SV1300iP5A-4 SV1600iP5A-4 SV2200iP5A-4 SV2800iP5A-4 SV3150iP5A-4 SV3750iP5A-4 SV4500iP5A-4

MCCB (LS Industrial Systems)


ABS33b/30A ABS33b/30A ABS53b/50A ABS63b/60A ABS63b/60A ABS103b/100A ABS103b/100A ABS203b/125A ABS203b/150A ABS203b/175A ABS203b/225A ABS403b/300A ABS403b/400A ABS603b/500A ABS603b/600A ABS803b/700A ABS803b/800A ABS1003/1000A ABS1203/1200A ABS1203/1200A

MC (LS Industrial Systems)


GMC-22 GMC-22 GMC-40 GMC-50 GMC-50 GMC-65 GMC-75 GMC-100 GMC-125 GMC-150 GMC-180 GMC-220 GMC-300 GMC-300 GMC-400 GMC-600 GMC-600 GMC-800 900A 1000A

400V Class

AC Input Fuse
Voltage Motor [kW]
5.5 7.5 11 15 18.5 22 30 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 220 280 315 375 450

Inverter Model
SV055iP5A-2 SV075iP5A-2 SV110iP5A-2 SV150iP5A-2 SV185iP5A-2 SV220iP5A-2 SV300iP5A-2 SV055iP5A-4 SV075iP5A-4 SV110iP5A-4 SV150iP5A-4 SV185iP5A-4 SV220iP5A-4 SV300IP5A-4 SV370iP5A-4 SV450iP5A-4 SV550iP5A-4 SV750iP5A-4 SV900iP5A-4 SV1100iP5A-4 SV1300iP5A-4 SV1600iP5A-4 SV2200iP5A-4 SV2800iP5A-4 SV3150iP5A-4 SV3750iP5A-4 SV4500iP5A-4

AC Input Fuse [A]


40 60 80 100 125 150 200 20 30 40 60 70 80 100 125 150 175 250 300 350 400 450 700 800 900 1000 1200

AC Reactor [mH]
0.39 0.28 0.20 0.15 0.12 0.10 0.07 1.22 1.14 0.81 0.61 0.45 0.39 0.287 0.232 0.195 0.157 0.122 0.096 0.081 0.069 0.057 0.042 0.029 0.029 0.024 0.024

DC Reactor [A]
30 40 59 75 96 112 160 15 20 30 38 50 58 80 98 118 142 196 237 289 341 420 558 799 799 952 952

[mH]
1.37 1.05 0.74 0.57 0.49 0.42 0.34 5.34 4.04 2.76 2.18 1.79 1.54 1.191 0.975 0.886 0.753 0.436 0.352 Built-in Built-in Built-in Built-in Built-in 0.090 0.076 0.064

[A]
29 38 56 71 91 107 152 14 19 29 36 48 55 76 93 112 135 187 225

200V Class

400V Class

836 996 1195

46

For your safety, please read user's manual thoroughly before operating. Contact the nearest authorized service facility for examination, repair, or adjustment. Please contact qualified service technician when you need maintenance. Do not disassemble or repair by yourself!

Safety Instructions

Any maintenance and inspection shall be performed by the personnel having expertise concerned.

2006.8 LS Industrial Systems Co.,Ltd. All rights reserved.

www.lsis.biz HEAD OFFICE


LS Tower 1026-6, Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do 431-848, Korea

Global Network LS Industrial Systems (Middle East) FZE Dubai, U.A.E.


Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: jungyongl@lsis.biz

Dalian LS Industrial Systems Co., Ltd. Dalian, China

Europe Middle East South West Asia South East Asia CIS America

+82-2-2034-4376 / ywsohn@lsis.biz +82-2-2034-4901 / bonseongk@lsis.biz +82-2-2034-4645 / sungkyup@lsis.biz +82-2-2034-4707 / ohpark@lsis.biz +82-2-2034-4913 / jinhkang@lsis.biz +82-2-2034-4377 / younsupl@lsis.biz

Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn

LS Industrial Systems (Wuxi) Co., Ltd. Wuxi, China


Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn

LS-VINA Industrial Systems Co., Ltd. Hanoi, Vietnam


Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com

LS-VINA Industrial Systems Co., Ltd. Hochiminh , Vietnam


Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com

LS Industrial Systems Tokyo Office Tokyo, Japan


Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz

LS Industrial Systems Shanghai Office Shanghai, China


Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn

LS Industrial Systems Beijing Office Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn

LS Industrial Systems Guangzhou Office Guangzhou, China


Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz

LS Industrial Systems Chengdu Office Chengdu, China


Address: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. China Tel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn

Specifications in this catalog are subject to change without notice due to continuous product development and improvement.

LS Industrial Systems Qingdao Office Qingdao, China


Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn

2010. 03

Starvert iP5A(E) 2006. 08/(06) 2010. 03 Printed in Korea STAFF