Sepam series 20
PE50546a
Sepam series 20 is a family of current or voltage digital protection relays, for medium voltage public and industrial distribution networks.
Standard
2 3
Base unit, with various types of User Machine Interfaces (UMI): b basic UMI b advanced UMI with graphical LCD screen. Remote advanced UMI. 10 logic inputs and 8 output relays, 4 outputs on the base unit + 1 optional module providing 10 inputs and 4 outputs. 1 communication port: b connection to 1 or 2 S-LAN and/or E-LAN networks b Modbus, Modbus TCP/IP, IEC 60870-5-103, DNP3 and IEC 61850 communication protocols b RS 485 ( 2or 4 wire) or fiber optic network. Temperature data from 8 sensors, Pt100, Ni100, or Ni120. 1 analog output, 0-10 mA, 4-20 mA or 0-20 mA. Software tools: b Sepam parameter and protection setting b recovery and display of disturbance recording data b local or remote operation via an E-LAN.
IEC 61850
3 1 4
5 7 2
5 6 7
Characteristics
Conformity to standards
IEC 60255 - Protection relays IEC 60529 - Degree of protection IEC 60068 - Operating temperature IEC 61850-6, 7-1, 7-2, 7,3, 7-4 and 8-1 IP52 on front panel -25C to +70C (-13F to +158F) Communication networks and system in substation
Certifications
CE, UL508, CSA C22.2
Current applications
b S20, S24: substation incomers and feeders protection b T20, T24: transformer protection b M20: motor protection.
DE40546
Protections
Phase overcurrent Cold load pick-up with phase overcurrent protection Earth fault, sensitive earth fault Cold load pick-up with earth fault protection Breaker failure Unbalance/negative sequence Thermal overload Phase undercurrent Excessive starting , time locked rotor Starts per hour Recloser (4 cycles)
ANSI code
50/51
S20
4
S24
4
T20
4
T24
4 1 4 1 1 1 2
M20
4
1 4 4
1 1 1 1 2
1 2 1 1 1
49 RMS
37 48/51LR/14 66 79 v v b b b b v v b b b b v b b b b b b v v b b b b v b b b b b b
v b b b b v b b b b b b b b b b v v v v v b v b b
Metering
Phase current I1,I2,I3 RMS Residual current I0 Average current I1, I2, I3 Peak demand phase current IM1,IM2,IM3 b b b b
Temperature
Running hours counter/operating time Thermal capacity used Remaining operating time before overload tripping Waiting time after overload tripping
Starting current and time / overload Start inhibit time delay, number of starts before inhibition Disturbance recording b b v v v v v b v b b b b v v v v v b v b b b b v v v v v b v b b b b v v v v v b v b b
Switchgear diagnosis
Voltage applications
b B21: busbar protection b B22: loss of mains protection.
DE40547
Cumulative breaking current Trip circuit supervision Number of operations Operating time Charging time
Protections
Positive sequence undervoltage Remanent undervoltage Phase-to-phase undervoltage Phase-to-neutral undervoltage Phase-to-phase overvoltage Neutral voltage displacement Overfrequency Underfrequency Rate of change of frequency
ANSIcode
27D/47 27R 27 27S 59 59N 81H 81L
B21
2 1 2 1 2 2 1 2
B22
2 1 2 1 2 2 1 2 1 b b b b b v b
81R b b b b b b v b
Metering
Line voltage U21, U32, U13 Phase-to-neutral voltage V1, V2, V3 Residual voltage V0 Positive sequence voltage / rotation direction Frequency
Network diagnosis
Disturbance recording
Annunciation 30 b b b standard, v according to parameter settings and optional modules. Note: the figures (in the table) give the number of independant protection sets for each protection function.
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper. Design: Schneider Electric Photos: Schneider Electric Printed: